Conext Core XC Series Grid Tie Photovoltaic Inverter

Planning and Installation Manual

www.schneider-electric.com

Conext Core XC Series Grid Tie Photovoltaic Inverter

Planning and Installation Manual

www.schneider-electric.com

Copyright 2013 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.

Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY, OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS, OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL, OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK; AND (C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITHIN THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM. Document Number: 990-4613B Contact Information Revision: Revision C Date: February 2013

www.schneider-electric.com

For other country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page Information About Your System As soon as you open your product, record the following information and be sure to keep your proof of purchase. Serial Number Product Number Purchased From Purchase Date
_________________________________ _________________________________ _________________________________ _________________________________

About This Manual


Audience
This manual is intended for use by qualified personnel installing a system involving Schneider Electric Conext Core XC Series Grid Tie Photovoltaic Inverters. Qualified personnel have training, knowledge, and experience in: Installing electrical equipment and PV power systems (up to 1000 V). Applying all applicable installation codes. Analyzing and reducing the hazards involved in performing electrical work. Selecting and using Personal Protective Equipment (PPE).

Configuration, servicing, and maintenance must be performed by authorized service personnel only. Authorized service personnel meet the requirements for a qualified installer, plus they have received specific training from the manufacturer on servicing the Conext Core XC Series. This manual does not contain information regarding servicing or de-energization for servicing. Authorized service personnel should refer to the Service Bulletin for Conext Core XC Series Inverter Lock-Out and Tag-Out Procedures (document number 993-0438) and the Conext Core XC Series Grid Tie Photovoltaic Inverter Commissioning and Configuration Manual (document number 990-9283).

Conventions Used
The following conventions are used in this manual.

DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.

WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death or serious injury.

CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in moderate or minor injury.

NOTICE
NOTICE indicates a potentially hazardous situation, which, if not avoided, can result in equipment damage.

990-4613B Revision C

iii

Conext Core XC Series Planning and Installation Manual

Abbreviations and Acronyms


AMCA ANSI BDEW CE CENELEC DIN GFDI HVAC IEC NFPA PE PPE PV RMS SELV VAC VDC VDE Air Movement and Control Association International, Inc. American National Standards Institute Bundesverband der Energie- und Wasserwirtschaft German Association of Energy and Water Industries European Conformity mark (European Union standards compliance) European committee for electrotechnical standardization Deutsches Institut fr Normung (German national standards organization) Ground fault detection interrupter Heating, ventilation, and air-conditioning International Electrotechnical Commission National Fire Protection Association Protective earth (ground) Personal Protective Equipment Photovoltaic Root mean square Safety Extra Low Voltage Volts (alternating current) Volts (direct current) Verband der Elektrotechnik, Elektronik und Informationstechnik German Association for Electrical, Electronic, and Information Technologies

Related Information
You can find more information about Schneider Electric and its products and services at www.schneider-electric.com.

iv

990-4613B Revision C

Important Safety Instructions


READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD
This manual contains important safety instructions for the Conext Core XC Series Grid Tie Photovoltaic Inverter (Conext Core XC Series) that must be followed during installation procedures.

DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Read all instructions, cautionary markings, and all other appropriate sections of this manual before installing or maintaining the Conext Core XC Series. To be installed and serviced only by qualified/authorized personnel equipped with appropriate personal protective equipment and following safe electrical work practices. This inverter is energized from multiple sources: the PV array, the AC grid, and the external auxiliary AC source (if used). Before opening doorsa or covers: Consult system diagram to identify all sources. De-energize, lock out, and tag out all sources following the procedure beginning on page ix. Wait at least 15 minutes for internal capacitors to discharge to safe voltages. Operation of the switches in or on the inverter does not remove all power from this inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC source have been disconnected externally. Before servicing, test using a meter rated at least 1000 V AC and DC, to ensure all circuits are de-energized. For proper circuit isolation, connect a suitably rated isolating transformer between the output of the inverter and the utility power line connections. The transformer must be selected and installed in accordance with this manual. The transformer must be an isolation type having separate primary and secondary windings. This inverter must be mounted on a non-flammable surface. See Anchoring the Inverter on page 24 for details.

Failure to follow these instructions will result in death or serious injury.


a. A maintenance feature is available for equipped inverters that will allow the DC cabinet door to be opened without interrupting inverter operation (opening any other doors will interrupt inverter operation). Check with your country sales organization to determine whether your inverter is equipped with this feature.

990-4613B Revision C

Conext Core XC Series Planning and Installation Manual

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH HAZARD OF EQUIPMENT DAMAGE
Obey the manuals instructions plus all physical, electrical, and environmental specifications shipped with the inverter.

Failure to follow these instructions can result in death or serious injury and/or damage to equipment.

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH
In all installations, the installer must provide external disconnecting means for the PV input, AC output, and external auxiliary AC source input wiring. The overcurrent protection devices within the inverter are intended to provide adequate protection for inverter circuitry only. It is the installer's responsibility to determine whether additional external overcurrent protection is required for the PV input, AC output, and external auxiliary AC source wiring, in accordance with the applicable installation codes.

Failure to follow these instructions can result in death or serious injury.

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH
Do not install or attempt to operate the inverter if it has been dropped or has received more than cosmetic damage during transport or shipping. If the inverter is damaged, or suspected to be damaged, contact customer service.

Failure to follow these instructions can result in death or serious injury.

WARNING
LIMITATIONS ON USE
The inverter is not intended for use in connection with life support systems or other medical equipment or devices. The inverter can only be used in grid-interconnected PV systems. It is not suitable for any other application areas.

Failure to follow these instructions can result in death or serious injury.

WARNING
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
Use caution and follow the instructions in this manual for correct lifting, moving, and mounting of the inverter. The inverter can easily fall over if it is moved without caution. The inverter must be securely attached to the mounting surface after positioning.

Failure to follow these instructions can result in death or serious injury and/or damage to equipment.

vi

990-4613B Revision C

Safety

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Do not defeat or change the settings of the heaters located inside the inverter as these heaters are installed to help prevent condensation inside the inverter.

Failure to follow these instructions can result in death or serious injury and/or damage to equipment.

CAUTION
HAZARD OF BURNS
Components become hot during normal operation. Surfaces inside of the inverter may continue to be hot after the 15 minute duration required to discharge the internal capacitors. After opening the cabinet doors, follow all posted warnings and use caution before touching conductive surfaces.

Failure to follow these instructions can result in moderate or minor injury.

CAUTION
HAZARD OF OVERHEATING AND EQUIPMENT DAMAGE
Keep the supply air and exhaust air areas unobstructed. Follow the installation, ventilation, and clearance instructions.

Failure to follow these instructions can result in moderate or minor injury and damage to equipment.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Inverter electronics can be destroyed by electrostatic charge. Wear electrostatic protection gear, and use anti-static tools and procedures when installing the inverter. Failure to follow these instructions can result in damage to equipment.

990-4613B Revision C

vii

Conext Core XC Series Planning and Installation Manual

Personal Protection
Follow these instructions to help protect yourself while working with the Conext Core XC Series.

WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Never work alone when installing this inverter. A team of two is required until external sources are properly de-energized, locked out and tagged out, and verified de-energized with a meter, according to the procedure beginning on page ix. Thoroughly inspect the inverter prior to energizing. Verify that no tools or materials have inadvertently been left inside the inverter and that all guards and barriers are properly replaced and secured.

Failure to follow these instructions will result in death or serious injury. Installation personnel must be equipped with adequately rated, standard personal protective equipment including the following: Electrically rated protective gloves Protective glasses Fire resistant clothing Ear protection Electrically rated protection shoes or boots Electrical protection hard hat and face shield Padlocks and tags (for lock out and tag out of disconnects) Appropriately rated meter for verifying the inverter is de-energized

Check local safety regulations and applicable workplace safety procedures for additional requirements.

viii

990-4613B Revision C

Safety

Installation Lock-out and Tag-out Procedure


Lock out refers to the practice of preventing de-energized circuits from being reenergized by putting locks on the disconnecting devices, holding them open. Tag out refers to the practice of attaching a tag to the disconnect-device locks warning others not to operate the disconnect device and containing information relating to the lock out, such as the person responsible, the reason, and the date and time. Combined these two practices are called the lock-out and tag-out (LOTO) procedure. The installation LOTO procedure can only be used if the inverter is being energized for the first time, during installation. This procedure cannot be used once the inverter has been installed and energized for the first time. If the inverter has been previously energized, additional steps are required to correctly LOTO the inverter for troubleshooting and service. These steps are detailed in the Service Bulletin for Conext Core XC Series Inverter Lock-Out and Tag-Out Procedures (document number 993-0438) and must be performed by authorized service personnel. Follow all steps of this procedure to de-energize all sources of supply external to the inverter. This allows access to all parts of all cabinets, including behind internal barriers, during installation. See Figure i and Figure iii for the locations of the parts of the inverter referred to in the following procedure.

DANGER
MULTIPLE SOURCES WITH HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
The Conext Core XC Series inverter is energized from the PV array, the AC grid, and the external auxiliary AC source (if used). Before installing the inverter: Consult system diagram to identify all sources. De-energize, lock out, and tag out all sources following the procedure beginning on page ix. Test using a meter rated at least 1000 V AC and DC to ensure all circuits are deenergized. The following procedure only applies to installation of an inverter, not to servicing. If the inverter is already installed, additional steps are needed to de-energize, LOTO, and verify internal voltages, and these steps must only be performed by authorized service personnel. Operation of the switches in or on the inverter does not remove all power from this inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC source have been disconnected externally. Additional external disconnecting means for the PV, AC, and external auxiliary AC source (if used), capable of being locked out and tagged out, must be provided as part of the installation to help facilitate safe installation and for certain servicing operations.

Failure to follow these instructions will result in death or serious injury.

990-4613B Revision C

ix

Conext Core XC Series Planning and Installation Manual Follow these lock-out and tag-out steps: 1. Turn the ENABLE STATE/DISABLE STATE switch to the DISABLE STATE position. See Figure i. 2. Turn the inverter ON/OFF switch to OFF. See Figure i. 3. Open, lock out, and tag out the AC output (grid) circuit at its external disconnecting means provided as part of the installation. 4. Open, lock out, and tag out all incoming PV input circuits at the external disconnecting means provided as part of the installation. 5. Open, lock out, and tag out the external auxiliary AC source (if used) at its external disconnecting means provided as part of the installation. 6. Wearing appropriate PPE and using a voltmeter with minimum ratings of 1000 V AC and DC that has been tested on a known AC voltage source and a known DC voltage source before use, verify that all external circuits are deenergized by checking for zero voltage at all of the following locations: a) AC output (grid): Measure the voltage from each phase to ground and each phase to the other phases at the inverter side of the external disconnecting means provided as part of the installation. b) PV input: Measure the voltage from DC+ and DC- to ground and from DC+ to DC- at the inverter side of the external disconnecting means provided as part of the installation. c) External auxiliary AC source (if used): Measure the voltage from each phase to ground and from phase to phase at the inverter side of the external disconnecting means provided as part of the installation. 7. Open, lock out, and tag out the AC circuit breaker (QF1) on the AC cabinet door. See Figure i. 8. Open, lock out, and tag out the PV disconnect (QF11) on the DC cabinet door. See Figure i.

990-4613B Revision C

Safety

Front panel user interface Power stage cabinet AC cabinet DC cabinet

ENABLE STATE/ DISABLE STATE

switch Inverter ON/OFF switch

AC circuit breaker

PV disconnect

Figure i Lock-out and tag-out components 9. Open the AC cabinet, and then lock out and tag out the inverter ON/OFF switch (QF2) (see Figure iii): a) Lock the metal bracket in place. b) Tag the lock. 10. Open the DC cabinet, and then lock out and tag out the PV auxiliary circuit breaker (see Figure ii and Figure iii): a) Remove the small plastic barrier over the PV auxiliary circuit breaker (QF12). b) Open the breaker. c) Remove the large plastic barrier from over the upper portion of the DC cabinet. d) Replace the small plastic barrier over the PV auxiliary circuit breaker. e) Lock the barrier in place, and then tag it.

990-4613B Revision C

xi

Conext Core XC Series Planning and Installation Manual

Remove these two screws to access the PV auxiliary circuit breaker.

Do not remove this screw. Do not remove the small plastic barrier over the surge arrestors. This barrier is only removed during maintenance to replace the surge protection devices.

Figure ii Location of DC plastic barriers When steps 1-10 have been completed: The external sources are verified de-energized, locked out, and tagged out. The inverter switches have all been opened, locked out, and tagged out.

This completes the LOTO procedure for the external sources and the inverter for first-time installation of the inverter.
Note: inverter shown with barriers removed

Internal inverter ON/OFF switch

PV auxiliary circuit breaker

Figure iii Internal lock-out and tag-out components xii 990-4613B Revision C

Contents
Important Safety Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - v Installation Lock-out and Tag-out Procedure - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ix

Introduction
Operator Interface Controls - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 12 ENABLE STATE/DISABLE STATE Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -13 Inverter ON/OFF Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -13 Front Panel User Interface - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -15 Local vs. Remote Monitoring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16 Setting the Communication Method - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -16 AC Circuit Breaker and PV Disconnect Switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 18

Planning
Inverter Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 22 Site Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -22 Conduit Entry - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -23 Anchoring the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24 Grounding the Inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24 Installation at High Elevation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -24 Ventilation Outside a PV Shelter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -25 Exhaust Duct Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -25 Venting Recommendations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -26 PV Array Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 27 Number of PV Panels - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -27 Grounding the Array - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -27 Utility Side Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 28 Transformer Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -28 General Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -28 Medium Voltage Winding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -29 Low Voltage Winding Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -29 Electrical Diagram - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 210

Installation
Unloading - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 32 Removing the Conext Core XC Series from a Truck - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -33 Removing the Conext Core XC Series from the Pallet - - - - - - - - - - - - - - - - - - - - - - - - - - - - -34 Mounting and Anchoring the Inverter- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 35 Opening Access Doors - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 35 General Wiring Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 36 Conductor Termination - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -36 Grounding - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -39 Specific Wiring Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 310 AC Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -310

990-4613B Revision C

xiii

Conext Core XC Series Planning and Installation Manual PV Array Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Auxiliary AC Source Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - External AC Auxiliary Power Source - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Internal AC Auxiliary Power Source - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Remote Communication and Control Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Modbus/RS-485 Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Connecting the Remote Communication and Control Devices - - - - - - - - - - - - - - - - - Completing the Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 313 316 317 319 321 322 323 326

Inspection
Visual Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 42 Re-installing AC and DC Barriers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43 Arranging for Commissioning and Configuration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43

Specifications
System Specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Electrical Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Physical and Environmental Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Regulatory Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Bolt Sizes and Torque Requirements - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A2 A2 A3 A4 A4 A5

B Site Evaluation Checklist

xiv

990-4613B Revision C

Figures
Figure i Figure ii Figure iii Figure 1-1 Figure 1-2 Figure 1-3 Figure 1-4 Figure 1-5 Figure 2-1 Figure 2-2 Figure 2-3 Figure 2-4 Figure 2-5 Figure 2-6 Figure 2-7 Figure 3-1 Figure 3-2 Figure 3-3 Figure 3-4 Figure 3-5 Figure 3-6 Figure 3-7 Figure 3-8 Figure 3-9 Figure 3-10 Figure 3-11 Figure 3-12 Figure 3-13 Figure 3-14 Figure 3-15 Figure 3-16 Figure 3-17 Figure 3-18 Figure 3-19 Figure 3-20 Figure 3-21 Figure 3-22 Figure 3-23 Figure 3-24 Figure 3-25 Figure 3-26 Figure A-1 Lock-out and tag-out components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - xi Location of DC plastic barriers- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -xii Internal lock-out and tag-out components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -xii Conext Core XC Series main external components - - - - - - - - - - - - - - - - - - - - - - - - - - 12 ENABLE STATE/DISABLE STATE switch and inverter ON/OFF switch - - - - - - - - - - - - - 14 Front panel user interface - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15 Setting parameter control - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17 AC circuit breaker and PV disconnect switch - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 19 Cabinet conduit entries, viewed from the top- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 23 Main inverter anchor bolt pattern - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 24 Mounting locations: exhaust routing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 26 PV shelter airflow with shroud (side venting) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 26 Pulsed inverter operation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 29 Setup to determine impedance Z - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 210 Conext Core XC Series electrical diagram (sample only) - - - - - - - - - - - - - - - - - - - - - 210 Fork-lifting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 33 Removing bolts without lifting the inverter - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 34 Removing bolts by lifting the inverter with a forklift - - - - - - - - - - - - - - - - - - - - - - - - - - - 35 AC terminal lug connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 37 DC terminal lug connections - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 38 Single point ground (PE); ground bar - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 39 Removing the external auxiliary AC source barrier- - - - - - - - - - - - - - - - - - - - - - - - - - 310 Removing the main AC barrier - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 310 Removing the AC floor plates- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 311 Removing the metal guard- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 311 AC terminal connections from the external transformer - - - - - - - - - - - - - - - - - - - - - - 312 Location of small DC plastic barriers - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 313 Removing the large plastic barrier - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 314 Removing the DC barrier - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 314 Removing the DC floor plates - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 315 PV array cable routing and terminations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 315 Connecting XT4:1 and XT4:2 - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 318 XT2 location in AC cabinet- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 318 Moving the voltage tap wire (original Conext Core XC Series)- - - - - - - - - - - - - - - - - - 319 Moving the voltage tap wire (newer Conext Core XC Series) - - - - - - - - - - - - - - - - - - 319 XT2 terminal block settings for internal auxiliary AC source - - - - - - - - - - - - - - - - - - - 320 Routing the communication cable - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 323 XT14 terminal block - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 324 Connecting the communication cable- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 325 Modbus/RJ-45 pinouts - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 325 XT14 terminal identification - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 326 Conext Core XC Series dimensions (XC680 model shown)- - - - - - - - - - - - - - - - - - - - - A5

990-4613B Revision C

xv

xvi

Tables
Table 1-1 Table 3-1 Table 3-2 Table 3-3 Table 3-4 Table 3-5 Table A-1 Table A-2 Table A-3 Table A-4 Communication features - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16 Voltage ranges and transformer taps for external auxiliary AC source (original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -317 Voltage ranges and transformer taps for external auxiliary AC source (newer Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -317 XT2:21 cable location for transformer tap (original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -319 Tap selection for internal auxiliary AC source connection (original Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -320 Tap selection for internal auxiliary AC source connection (newer Conext Core XC Series) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -320 Electrical specifications- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A2 Physical and environmental specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A3 AC terminal bolt size and torque values - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A4 PV terminal bolt size and torque values - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A4

990-4613B Revision C

xvii

xviii

Introduction

Chapter 1 contains information about the features and functions of the Conext Core XC Series.

990-4613B Revision C

11

Conext Core XC Series Planning and Installation Manual

Operator Interface Controls


Figure 1-1 shows the main external components of the Conext Core XC Series.
Exhaust Front panel user interface Power stage cabinet AC cabinet DC cabinet Exhaust Exhaust Exhaust

ENABLE STATE/ DISABLE STATE

switch Inverter ON/OFF switch

AC circuit breaker

PV disconnect

Air intake

Air intake

Air intake

Air intake

Figure 1-1 Conext Core XC Series main external components All Conext Core XC Series cabinet doors must be closed and locked during normal operation. For specific maintenance operations, some inverters have a feature that will allow the DC cabinet door to be opened without interrupting inverter operation (opening any other doors will interrupt inverter operation). This feature is intended only to allow the DC cabinet door to be opened to read the display of the isolation monitor, such as a Vigilohm insulation monitoring device, and must be closed again immediately after reading the display. Check with your country sales organization to determine whether your inverter is equipped with this feature.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Close the DC cabinet door as soon as you have read the display of the isolation monitor. Avoid longer than necessary operation with the DC cabinet door open.

Failure to follow these instructions can result in damage to equipment, can compromise the environmental protection of the inverter, and can void your warranty.

12

990-4613B Revision C

Introduction: Operator Interface Controls

ENABLE STATE/DISABLE STATE Switch


The Conext Core XC Series has an ENABLE STATE/DISABLE STATE switch located on the AC cabinet door beside the front panel user interface, see Figure 1-2 on page 14. Under normal conditions, the ENABLE STATE/DISABLE STATE switch is in the ENABLE STATE position. The main AC circuit breaker and PV disconnect switch will not close unless the switch is in the ENABLE STATE position. The inverter will not operate unless the switch is in the ENABLE STATE position. To change any grid settings, the switch must be turned to the DISABLE STATE position. Turning the switch to the DISABLE STATE position initiates an immediate controlled shutdown of the inverter, and it opens both the main AC circuit breaker and PV disconnect switch within the inverter.

DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Turning the switch to the DISABLE STATE position will not de-energize the inverter; it only stops power production. Externally disconnect the PV, AC, and external auxiliary AC source to de-energize the switch terminals.

Failure to follow these instructions will result in death or serious injury.

Inverter ON/OFF Switch


The Conext Core XC Series has an inverter ON/OFF switch located on the AC cabinet door, see Figure 1-2. The inverter ON/OFF switch is also the auxiliary power breaker. Under normal conditions, the inverter ON/OFF switch is in the ON position, providing the auxiliary power necessary for power production and for maintenance functions such as viewing and extracting data from the front panel user interface or performing software updates. The main AC circuit breaker and PV disconnect switch cannot be closed unless the switch is in the ON position. The inverter will not restart unless the switch is in the ON position. To initiate a power cycle, the switch must be turned to the OFF position and then back to the ON position. Turning the switch to the OFF position initiates an immediate controlled shutdown of the inverter and opens both the main AC circuit breaker and PV disconnect switch within the inverter.

DANGER
HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Turning the switch to the OFF position will not de-energize the inverter; it only stops power production. Externally disconnect the PV, AC, and external auxiliary AC source to de-energize the switch terminals.

Failure to follow these instructions will result in death or serious injury.

990-4613B Revision C

13

Conext Core XC Series Planning and Installation Manual

ENABLE STATE/ DISABLE STATE

switch

Inverter ON/OFF switch

Figure 1-2 ENABLE STATE/DISABLE STATE switch and inverter ON/OFF switch

14

990-4613B Revision C

Introduction: Operator Interface Controls

Front Panel User Interface


The Conext Core XC Series has a display and keypad with scroll wheel on the front panel for local monitoring and configuration (see Figure 1-3 on page 15). Extensive status information and Offline state or Service state events are reported to the front panel user interface. Use the scroll wheel to navigate through menu or value options, and press the center of the scroll wheel to select the menu or value. The keypad has four F function keys, RUN (remote enable) and STOP/RESET (remote disable) keys, and an ESC escape key. See the Conext Core XC Series Grid Tie Photovoltaic Inverter Operation and Maintenance Manual (document number 990-4612) for additional details on how to operate the front panel user interface.
Inverter operating mode Periodic servicing reminder

Access level Event ID Inverter status line Inverter state Parameter value F2, F3, and F4 function keys (context-specific) Exit current menu Unused Scroll wheel

Inverter activity or state description Parameter description

PV

LVL2

6341

Active Power Point Tracking

Online
Active power

463.5 kW

F1 return to default parameter display

Disable via software command Enable via software command

Figure 1-3 Front panel user interface

990-4613B Revision C

15

Conext Core XC Series Planning and Installation Manual

Local vs. Remote Monitoring


The Conext Core XC Series provides information to users about the systems current state and recent events, as described in Table 1-1. Table 1-1 Communication features
Information Type System status Description The system states are: Offline state event Disable Online Offline Service Front panel user interface: event ID and a brief text description Optional remote monitoring system: event ID and an extensive text description Front panel user interface: event ID and a brief text description Optional remote monitoring system: event ID and an extensive text description Communication Method Front panel user interface Optional remote monitoring system

The time and details are stored in non-volatile memory.

Service state event

The time and details are stored in non-volatile memory.

Data logging

Optional remote monitoring system

Setting the Communication Method


The Parameter Control menu on the front panel user interface sets whether the inverter is controlled locally on the front panel user interface or remotely. To change the communication method: 1. Ensure you are at the home screen. 2. Press the center of the scroll wheel. 3. Scroll to Language, Time, Interface, and then press the center of the scroll wheel. 4. Scroll to Parameter Control Station, and then press the center of the scroll wheel. 5. Scroll to highlight either Panel Control or Modbus, and then press the center of the scroll wheel to apply the change. Select Panel Control to use the front panel user interface for communication. Select Modbus to communicate through an optional remote monitoring interface.

16

990-4613B Revision C

Introduction: Local vs. Remote Monitoring

Language, Time Interface

Parameter Control Station Panel Control Modbus

Figure 1-4 Setting parameter control 6. Press F4 to return to the home screen. When the parameter control is set to Modbus, you can still access the Parameter Control Station menu on the front panel interface to change back to panel control.

990-4613B Revision C

17

Conext Core XC Series Planning and Installation Manual

AC Circuit Breaker and PV Disconnect Switch


DANGER
MULTIPLE SOURCES WITH HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
Operation of the switches in or on the inverter does not remove all power from this inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC source have been disconnected externally. All service and maintenance must be performed by authorized service personnel only, as defined on page iii, following the instructions in Service Bulletin for Conext Core XC Series Inverter Lock-Out and Tag-Out Procedures (document number 9930438).

Failure to follow these instructions will result in death or serious injury. The main AC circuit breaker is located on the AC cabinet door and the PV disconnect switch is located on the DC cabinet door as shown in Figure 1-5 on page 19. Additional external AC and PV disconnecting means, capable of being locked out and tagged out, must be provided as part of the installation to help facilitate safe installation of the inverter and for certain service operations. The main AC circuit breaker and PV disconnect switch are each load-break rated disconnects. During an Offline state or Service state eventor if the inverter is shut off for any reasonthe AC circuit breaker and PV disconnect switch automatically open. Each is capable of breaking its full load current.

18

990-4613B Revision C

Introduction: AC Circuit Breaker and PV Disconnect Switch

AC cabinet

DC cabinet

AC circuit breaker (QF1)

PV disconnect switch (QF11)

AC circuit breaker

PV disconnect switch

Figure 1-5 AC circuit breaker and PV disconnect switch

990-4613B Revision C

19

Conext Core XC Series Planning and Installation Manual

110

990-4613B Revision C

Planning

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, ARC FLASH, AND FIRE
Installation of this inverter must only be planned and performed by qualified personnel in accordance with all applicable installation codes. See page iii for the definition of qualified personnel. The Conext Core XC Series must be mounted over a non-flammable surface in accordance with the instructions in Inverter Requirements below.

Failure to follow these instructions will result in death or serious injury.

990-4613B Revision C

21

Conext Core XC Series Planning and Installation Manual

Inverter Requirements
Site Requirements
The Conext Core XC Series is designed to be installed indoors only. Establish and maintain the following site conditions to help facilitate safe and efficient installation, operation, and servicing of the Conext Core XC Series. Ventilation The inverter has open sections in the bottom of the AC and DC cabinets and ventilation openings in the front of all cabinets. Additionally, there are exhaust openings at the top of all cabinets. Overall pressure drop across combined intake and exhaust must not exceed 60 Pa. To help reduce the risk of fire, the inverter must be mounted over non-flammable surfaces below the inverter and extending in front of the inverter for 1 m (39 in.). That area under and in front of the inverter must also be kept clear of flammable materials during operation of the inverter. The inverter must be mounted flush to the mounting surface, without openings around the bottom perimeter of the inverter. Openings for wire entry must be filled or closed to maintain a non-flammable barrier under the inverter. Maintain a minimum clearance of 1 m (39 in.) in front of the inverteror more if required by local codes for service clearancefor air intake, maintenance, and serviceability. Maintain a minimum of 300 mm (11 in.) clearance above the inverter. Exhaust ducting must be installed in accordance with these requirements. Make sure the site is fork-lift accessible. A customer-supplied fork-lift and licensed fork-lift operator are required to perform many maintenance tasks. External cabling enters the inverter from the bottom into the wiring compartments of the AC and DC cabinets. Appropriate conduits and fittings must be used based on local electrical codes. The inverter has an ingress protection rating of IP20. The installation location must meet the physical and environmental specifications listed in Table A-2 on page A3. The heat load of the inverter is approximately 17 kW (58,000 BTU/hour) at full load. External ventilation or air conditioning must be designed to keep the ambient air outside of the inverter cabinets to a maximum of 45 C (113 F) to allow for full-rated inverter output power. Above 45 C (113 F), the inverter will derate its power output up to 50 C (122 F). Consult with Schneider Electric on derating charts for power output depending on ambient temperature. The total cooling air flow required for the inverter is 4000 m/h (3000 m/h from the power stage cabinet and 500 m/h each from the AC and DC cabinets). Air intake quality The intake for the inverter is located on the front (see Figure 2-4). The intake airflow should meet the requirements of the environmental specifications listed in Table A-2 on page A3. If these conditions cannot be met, filtration must be implemented external to the intake to ensure contaminants do not enter the inverter.

Flammability

Clearance

Accessibility Cabling

IP rating

Heat load

22

990-4613B Revision C

Planning: Inverter Requirements

Conduit Entry
Conduit and cable entry is from the bottom of the inverter. Figure 2-1 shows a top view of the maximum allowable area and location in which electrical conduits can penetrate the cabinets of the Conext Core XC Series. Conductor size must be pre-determined when the conduit is installed and must be based on local code requirements.

DANGER
HAZARD OF ELECTRIC SHOCK
The circuits provided for use with external communications and control equipment are designed to provide safety isolation from neighboring hazardous circuits within the inverter. Separate conduit entries must be provided for the communications and control circuits and the PV circuits and all AC circuits. See Remote Communication and Control Wiring in the Conext Core XC Series Planning and Installation Manual for proper maintenance of safety isolation for wiring related to these circuits. The Conext Core XC Series is not provided with a conduit mounting surface to interface with the chassis. As such, no bonding to ground is provided for external metal conduits and this bonding must be provided elsewhere in the installation.

Failure to follow these instructions will result in death or serious injury.

Dimensions in mm (not to scale)

Figure 2-1 Cabinet conduit entries, viewed from the top

990-4613B Revision C

23

Conext Core XC Series Planning and Installation Manual

Anchoring the Inverter WARNING


HAZARD OF FIRE
The Conext Core XC Series must be mounted on, and anchored to, a level, nonflammable surface.

Failure to follow these instructions can result in death or serious injury. The mounting surface upon which the inverter is anchored must be structurally designed to meet any applicable local codes for weight bearing and seismic requirements. Twelve 13 mm holes are provided on the bottom of the cabinets for anchoring to the mounting surface. Figure 2-2 depicts the layout pattern of the anchoring holes for the inverter. The mounting surface must either be pre-drilled to accept masonry anchors or have pre-installed anchoring bolts.

Dimensions in mm (not to scale)

Figure 2-2 Main inverter anchor bolt pattern

Grounding the Inverter


The safety ground or protective earth connection point for grounding the inverter is the AC ground bus bar in the AC cabinet and is marked with . That point must be connected to ground (earth) in the installation in accordance with applicable installation codes. Ground connection points are also provided in the DC cabinet for the bonding wires that ground the PV array frames and these points are also marked with .

Installation at High Elevation


Conext Core XC Series inverters that are installed at elevations greater than 1000 meters may produce slightly less power than inverters that are installed at lower elevations. Depending on ambient temperature at altitude, the output power may automatically derate above 1000 m. The installer must derate the PV and AC voltages above 2000 m. For more information about PV generator specifications at altitude, see the Application Note: Altitude Derating for Conext Core XC Series.

24

990-4613B Revision C

Planning: Inverter Requirements

Ventilation Outside a PV Shelter


Conext Core XC Series inverters can be installed in a PV shelter designed typically to house inverters, distribution boxes, transformers, and monitoring equipment. Schneider Electric sells PV shelters, under the product name PV Boxes. The ventilation required when using a PV shelter must meet the following criteria: Wind, including lateral wind, must not be allowed to stop outgoing air flow while the inverter is operating. Predict any way that wind, including lateral wind, may compromise the venting method used, such as partially closing vents, or closing all of the vents on one side of the PV shelter. The result of this compromise must not exceed the allowable overall pressure drop (see Ventilation on page 22) and must maintain the minimum airflow requirements of the inverter (see Heat load on page 22). Wind, including lateral wind, must not be allowed to create a back-flow of air (carrying humidity, snow, rain, or dust) into the inverter at any time.

You may use a single component, such as an actuated damper, or a combination of components, such as a duct, shroud, and louvers, to meet the criteria.

Exhaust Duct Requirements


A standard HVAC sheet metal duct can be integrated and sealed to the interior wall of the PV shelter to make sure exhaust airflow cannot recirculate within the PV shelter. One 90 bend with a smooth transition is permitted as shown in Figure 2-4 on page 26. The duct must be designed to accommodate the following: Minimum duct area: 445 x 2250 mm (17.5 x 88.5 in.). Overall pressure drop across combined intake and exhaust for the PV shelter must not exceed 60 Pa.

Figure 2-3 shows the mounting locations on top of the inverter to accommodate an exhaust duct (if one is planned to route the exhaust to the exterior of the PV shelter). If the inverter exhaust is to be routed to the exterior of a PV shelter, mount the exhaust duct on top of the inverter in the locations shown in Figure 2-3.

DANGER
HAZARD OF SHOCK AND AMPUTATION
Do not modify the roof panels of the inverter as doing so could expose live and moving parts. It can also cause contamination inside the inverter and compromise the functional design.

Failure to follow these instructions will result in death or serious injury.

990-4613B Revision C

25

Conext Core XC Series Planning and Installation Manual


The minimum duct area to prevent airflow restriction is 445 x 2250 mm (17 x 88 in.).

Figure 2-3 Mounting locations: exhaust routing

Venting Recommendations
You can use any configuration that meets the requirements in Ventilation Outside a PV Shelter on page 25. One recommended venting configuration is: Side venting with fixed and gravity louvers and a shroud (see Figure 2-4).
Shroud Duct

Fixed louvers

Gravity louvers

Intake airflow

Grey arrows show exhaust airflow

Figure 2-4 PV shelter airflow with shroud (side venting)

26

990-4613B Revision C

Planning: PV Array Requirements

PV Array Requirements
In all installations, the installer must provide disconnecting means for the PV input. The installer is also responsible for determining any external overcurrent protection required for these circuits, in accordance with the applicable installation codes, the currents involved (see Appendix A, Specifications), the wiring size used, and any other system parameters required by the installation codes.

Number of PV Panels
To determine the number of photovoltaic panels required for the PV power plant, use the PV planning tool or sizing tool on the Schneider Electric website (www.schneider-electric.com).

Grounding the Array


The PV input can be floating, positive grounded, or negative grounded, depending on the options ordered. For positive grounded or negative grounded arrays, a factory-installed PV grounding option provides positive or negative grounding of the array, depending on the version ordered, and it includes a 10 A ground fault detector/ interrupter (GFDI). This circuit breaker will open the array grounding path to interrupt ground fault currents exceeding the trip levels of the breaker. At the same time, it will shut down the inverter, open the AC breaker and PV disconnect, and report an event with the appropriate event ID to the front panel user interface and to any optional remote monitoring system. For floating arrays, an optional factory-installed PV isolation monitoring relay is available that will monitor the array insulation resistance to ground. If the array insulation resistance falls below the setpoint, the isolation monitor will shut down the inverter, open the AC breaker and PV disconnect, and report an event with the appropriate event ID to the front panel user interface and to any optional remote monitoring system. The qualified installer is responsible for determining the type and settings of ground fault protection that will provide adequate protection for the array and its wiring and that are acceptable according to applicable local codes and standards.

990-4613B Revision C

27

Conext Core XC Series Planning and Installation Manual

Utility Side Requirements


In all installations, the installer must provide disconnecting means for the AC input and external auxiliary AC source input wiring. The installer is also responsible for determining any external overcurrent protection required for these circuits, in accordance with the applicable installation codes, the currents involved (see Appendix A, Specifications), the wiring size used, and any other system parameters required by the installation codes.

Transformer Requirements
A custom, high-efficiency, line-frequency isolation transformer must be placed between the inverter and the grid. This transformer is not provided and must be supplied as a separate component.

NOTICE
EQUIPMENT DAMAGE
You must select a transformer appropriate for the overall system design. Medium voltage (MV) isolation transformers that are connected to Conext Core XC Series inverters must meet the technical requirements described in Transformer Requirements. If an overvoltage protection is required (for example, a Schneider Electric Cardewtype limiter) refer toTransformer Requirements for sizing information. For simplicity, do not connect the overvoltage protection device to the neutral; connect it between any one line (L1, L2, or L3) and ground. Multiple overvoltage protection devices may be used, but are restricted to one overvoltage protection device per line. Do not connect any point on the inverter-side winding of the isolation transformer to ground.

Failure to follow these instructions will result in damage to the inverter.

General Requirements
The MV transformer must be capable of handling non-sinusoidal voltages up to 450 V of ground. These voltages may occur due to pulsed inverter operation as illustrated in Figure 2-5 on page 29. The rms (root mean square) value of the voltages in relation to ground is a maximum of 900 V. A shield winding is recommended as a dU/dt filter between the low voltage and high voltage windings. Impedance Z (%) for the transformer must be 6%, with tolerance limits between 4.5% and 6.5%. The MV transformer must manage nominal current loading up to 55 C ambient (still air). The configuration of the MV transformer should take into account the local grid frequency and should meet local and regional standards.

28

990-4613B Revision C

Planning: Utility Side Requirements

The Conext Core XC Series inverter bridge switching frequency is 3.2 kHz. This graph is provided for informational purposes only. This should not be interpreted as typical operation. The voltage numbers on the y-axis are for reference only.

Figure 2-5 Pulsed inverter operation

Medium Voltage Winding Requirements


The medium voltage (utility-side) windings of the MV transformer may be configured Wye or Delta and must match the voltage at the utility interconnection point. If the medium voltage windings of the transformer are configured Wye, the resulting neutral connection of this Wye combination may be connected to the neutral connection at the utility interconnection point. Connection of this utility-side neutral does not affect the operation of the inverter. The medium voltage windings should have a voltage level that matches the medium-voltage grid in the region. A tap changer should be installed on the medium voltage side to align the output voltage with the voltage level of the medium voltage grid.

Low Voltage Winding Requirements


The low voltage (inverter-side) windings of the MV transformer can only be configured as a Delta or floating Wye.

NOTICE
INVERTER DAMAGE
Do not connect any point on the inverter-side winding of the MV transformer to ground. Failure to follow this instruction will result in equipment damage. 990-4613B Revision C One galvanically isolated low voltage three-phase winding combination should be available for each inverter. Each low voltage winding must match the rated AC voltage of the inverter. 29

Conext Core XC Series Planning and Installation Manual Each low voltage winding must be capable of handling non-sinusoidal
Vvoltages with a voltage gradient (dU/dt) of up to 500 ----of ground. s

The neutral point (if present) must not be connected or grounded. Impedance Z (%) between the low voltage windings should be 10%, with tolerance limits between 7% and 11%. To determine Z between the low voltage winding, short-circuit one of the windings and increase the voltage on the other winding until the nominal current flows, as shown in Figure 2-6. The medium voltage windings should be idle.

IN Uk

Figure 2-6 Setup to determine impedance Z

Electrical Diagram
Since installations vary widely, a sample electrical diagram of the Conext Core XC Series is provided in Figure 2-7. Use this diagram for system planning purposes only.

Example only. Details such as external disconnects, overcurrent protection, and grounding are not shown.

Figure 2-7 Conext Core XC Series electrical diagram (sample only)

210

990-4613B Revision C

Installation
DANGER
MULTIPLE SOURCES WITH HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH
The Conext Core XC Series inverter is energized from the PV array, the AC grid, and the external auxiliary AC source (if used). Before installing the inverter: Consult system diagram to identify all sources. De-energize, lock out, and tag out all sources following the procedure beginning on page ix. Test using a meter rated at least 1000 V AC and DC to ensure all circuits are deenergized. The lock-out and tag-out procedure beginning on page ix in this manual only applies to installation of an inverter, not to servicing. If the inverter is already installed, additional steps are needed to de-energize, lock out, tag out, and verify internal voltages, and must only be performed by authorized service personnel. See the Service Bulletin for Conext Core XC Series Inverter Lock-Out and Tag-Out Procedures (document number 993-0438). Operation of the switches in or on the inverter does not remove all power from this inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC source have been disconnected externally. Additional external disconnecting means for the PV, AC, and external auxiliary AC source (if used), capable of being locked out and tagged out, must be provided as part of the installation to help facilitate safe installation and for certain servicing operations.

Failure to follow these instructions will result in death or serious injury.

990-4613B Revision C

31

Conext Core XC Series Planning and Installation Manual

Unloading
DANGER
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
The Conext Core XC Series weighs approximately 1900 kg (4189 lb), including the packing crate and pallet. Attempting to lift or move the inverter by other than the recommended lifting points and methods could cause the inverter to drop unexpectedly or fall over. Keep all the doors closed and latched when moving the inverter. Use appropriately rated lifting equipment.

Failure to follow these instructions will result in death or serious injury and/or damage to equipment.

NOTICE
EQUIPMENT DAMAGE
Before proceeding with the installation, determine the location and layout of the components, conduit penetration locations, conductor and conduit sizing, and method for anchoring the inverter. Make sure adequate space is provided for clearance for ventilation and serviceability. If necessary, review Chapter 2, Planning before proceeding.

Failure to follow these instructions will result in damage to the inverter.

32

990-4613B Revision C

Installation: Unloading

Removing the Conext Core XC Series from a Truck


To load or unload the inverter from a truck, a fork-lift must be used to lift the inverter, inside the packing crate, from either the left or right end. You will either need to use a fork-lift with extra long prongs, or you will need to add extensions to your existing fork-lift. The total length of the prongs needed to lift the inverter from the end is 2580 mm (101.6 in.). If you use extensions, the fork-lift prongs must be a minimum of 66% of the total length of the prongs plus the extension, as shown in Figure 3-1. Both the prongs and the extensions must be rated for the full weight of the inverter.

Total length 100% (minimum 2580 mm/101.6 in.) Maximum extension length 33% Minimum prong length 66%

Extension sleeve

Fork-lift prongs

Figure 3-1 Fork-lifting

990-4613B Revision C

33

Conext Core XC Series Planning and Installation Manual

Removing the Conext Core XC Series from the Pallet


To remove the Conext Core XC Series from the pallet: 1. Do a visual check for any damage to the wooden shipping crate. 2. Disassemble the shipping crate and remove the shrink-wrap from the inverter. Leave the plastic covers over the ventilation grills at the front of the inverter. 3. Remove the 12 bolts on the bottom of the pallet attaching it to the inverter in one of the two following ways: Reach under the pallet and locate the 12 bolts. These bolts attach from the bottom so use a torque, open-ended, or box wrench with a very short head to remove them, as shown in Figure 3-2).

Figure 3-2 Removing bolts without lifting the inverter Or Using an appropriately rated forklift, lift the inverter a maximum of 2 ft (610 mm) and remove the 12 bolts with a standard torque wrench. Return the inverter and pallet to the floor after removing the bolts.

DANGER
HAZARD OF CRUSH INJURY AND EQUIPMENT DAMAGE
Do not lift the inverter more than 2 ft (610 mm) with the forklift. Do not put any part of your body underneath the raised pallet, including your hands.

Failure to follow these instructions will result in death or serious injury and/or damage to equipment.

34

990-4613B Revision C

Installation: Mounting and Anchoring the Inverter

Figure 3-3 Removing bolts by lifting the inverter with a forklift

Mounting and Anchoring the Inverter


For general information about mounting and anchoring requirements, see Anchoring the Inverter on page 24. To mount and anchor the Conext Core XC Series: 1. Drill the floor or pad to accept masonry anchors unless it has pre-installed anchoring bolts that will fit the 13 mm mounting holes. See Figure 2-2 on page 24. 2. After removing the bolts connecting the Conext Core XC Series to the wooden pallet, connect an appropriately rated crane to the lifting bars installed on the top of the inverter. 3. Lift the Conext Core XC Series into place. 4. Secure the cabinet feet to the floor with the appropriate anchoring hardware. 5. Use a level to check that the inverter is both horizontally and vertically aligned and plumb. 6. Remove the lifting bars once the inverter is secured in its final mounting location.

Opening Access Doors


The AC and DC cabinet doors are opened with the key supplied with the inverter. Pull the handle towards you to unlatch the door. The power stage cabinet has additional latches at the top and bottom inside the left door.

990-4613B Revision C

35

Conext Core XC Series Planning and Installation Manual

General Wiring Requirements


All wiring methods and materials must be in accordance with applicable electrical installation codes. Examples include the US National Electrical Code ANSI/NFPA 70, IEC 60364, CENELEC HD 384, and DIN VDE 0100.

NOTICE
EQUIPMENT DAMAGE
When connecting external AC wires to the Conext Core XC Series, positive phasing sequence must be maintained throughout the installation process.

Failure to follow these instruction can result in damage to equipment.

Conductor Termination
The Conext Core XC Series has terminals and bus bars for making all wiring connections required for inverter installation. All terminals used for making AC and DC connections require the use of conductors with an insulation rating of 75 C (or higher). If conductors rated higher than 75 C are used, base the wire size on the requirements for 75 C wire to help prevent excessive heating of the bus bars, terminals, and connected devices. AC Wiring The AC output phase wiring connects to the AC terminals identified as XT1 (L1, L2, and L3) in the AC cabinet. These terminals require the use of a crimp-on type ring terminal or compression-type lug. Keep the cables close together as much as possible and make sure that all cables pass through the same conduit fittings and the same access point in the floor of the inverter. This allows any inductive currents to cancel. Each terminal has five bolts per pole and accommodates a maximum of one cable per bolt. For the location of these terminals and wiring instruction see Figure 3-11 on page 312. For bolt sizes torque values, see Table A-3 on page A4. For the dimensions of the terminal lug connections, see Figure 3-4.

36

990-4613B Revision C

Installation: General Wiring Requirements

Figure 3-4 AC terminal lug connections Auxiliary AC wiring The auxiliary AC input wiring connects to the terminals identified as XT4 (1 and 2) in the AC cabinet. These terminals require a crimp-on ferrule properly sized for the wire and accommodate one wire per terminal. For the location of these terminals, see Figure 3-17 on page 318. For bolt sizes and torque values, see Table A-3 on page A4.

990-4613B Revision C

37

Conext Core XC Series Planning and Installation Manual DC Wiring The PV input wiring connects to the PV terminals identified as PV+ and PV- in the DC cabinet. These terminals require the use of a crimp-on type ring terminal or compression-type lug. Keep the cables close together as much as possible and make sure that all cables pass through the same conduit fittings and the same access point in the floor of the inverter. This allows any inductive currents to cancel. Each terminal has seven bolts per pole and a maximum of one cable per bolt. For the location of these terminals, see Figure 3-16 on page 315. For bolt sizes and torque values, see Table A-4 on page A4. For the dimensions of the terminal lug connections, see Figure 3-5.

Figure 3-5 DC terminal lug connections

38

990-4613B Revision C

Installation: General Wiring Requirements

Grounding
The connection point for the AC grounding conductor (also known as PE) is a copper grounding bar with several M10 bolts located at the bottom right side of the AC cabinet and marked with . The ground conductor size depends on the rating or setting of the overcurrent protection provided for the circuit. Refer to local applicable electrical installation codes for grounding requirements for your system. The ground wire for the external auxiliary AC source can also be terminated at this ground bar. Grounding terminals for PV array frames are provided in the DC cabinet.

Figure 3-6 Single point ground (PE); ground bar

990-4613B Revision C

39

Conext Core XC Series Planning and Installation Manual

Specific Wiring Requirements


This section provides information for connecting the AC, PV, and ground conductors. Table A-3 and Table A-4 on page A4 show the specifications for the provided wiring terminals.

AC Wiring
To help protect personnel, barriers are installed over the AC and DC electrical wiring compartments inside the Conext Core XC Series. To perform the initial installation you must remove these barriers. To remove the AC barriers: 1. Open the AC cabinet door. 2. Remove and save the five screws holding the external auxiliary AC source barrier in place, as indicated in Figure 3-7. 3. Pull the external auxiliary AC source barrier out; do not bend the metal.

Figure 3-7 Removing the external auxiliary AC source barrier 4. Remove and save the five screws holding the main AC barrier in place, as indicated in Figure 3-8. 5. Pull the barrier out; do not bend the metal. 6. Do not remove any other barriers.

Figure 3-8 Removing the main AC barrier

310

990-4613B Revision C

Installation: Specific Wiring Requirements To prepare the floor of the inverter for cable routing: Remove and save the four plates from the floor of the AC cabinet (see Figure 3-9). You must re-install the plates after routing the cables.

Figure 3-9 Removing the AC floor plates To connect the AC output (grid) to the AC cabinet: 1. Perform the following steps to remove the triangle-shaped metal guard on the right hand side of the AC cabinet wall to access L1, L2, and L3 (see Figure 3-10): a) Remove and save the two retaining screws at the front of the guard. b) Angle the guard to the left, and then pull it out to disengage the tab at the back.

Tab

Retaining screws

Figure 3-10 Removing the metal guard 2. Route the AC power conductors L1, L2, and L3 and ground cable(s) through the slit in the foam over the access point in the floor of the inverter. 3. Connect the AC power conductors at the L1 (A phase), L2 (B phase), and L3 (C phase) terminals using M12 hardware. Cables to these terminals must use a crimp-on type ring terminal or compression-type lug. See Figure 3-11 on page 312 for the location of these terminals. 4. Install appropriately sized retention clips on the rail below the terminals to hold the three AC power conductors in place.

990-4613B Revision C

311

Conext Core XC Series Planning and Installation Manual 5. Connect the AC output ground conductor to the ground bar (PE). Use M10 hardware to make terminations for the ground conductors within the AC cabinet at the ground bar. Cables to these terminals must use a crimp-on type ring terminal or compression-type lug. See Figure 3-11 for the location of these terminals.

L3 Phase terminal L2 Phase terminal L1 Phase terminal

Ground bar (PE)

Figure 3-11 AC terminal connections from the external transformer 6. Re-install the four plates on the floor of the AC cabinet (shown in Figure 3-9 on page 311). 7. Re-install the triangle-shaped guard by hooking the tab at the back of the guard into place, and then sliding the front end in and re-installing the two retaining screws. 8. If you plan to install an external auxiliary AC source, follow the procedure starting on page 316 now, and then return to step 9 in this procedure. 9. Do not re-install the AC barriers (page 43) until all other installation steps and the visual inspection on page 42 have been completed.

312

990-4613B Revision C

Installation: Specific Wiring Requirements

PV Array Wiring
To help protect personnel, the DC cabinet is provided with four barriers: A large plastic barrier over the entire upper half of the cabinet. A large steel mesh barrier over the entire lower half of the cabinet. A small plastic barrier over the PV auxiliary circuit breaker. A small plastic barrier over the PV surge protection devices.

These barriers overlap and must be removed in a specific order, as described in the procedure below. To remove the DC barriers: 1. Open the DC cabinet door. You will see two plastic barriers (shown in Figure 3-12): one small barrier over the surge protection devices and on top of that and to the left, one larger barrier with a label over the PV auxiliary circuit breaker. 2. Remove and save the two screws holding the plastic PV auxiliary circuit breaker barrier in place, as indicated in Figure 3-12.

Remove and save these two screws to access the PV auxiliary circuit breaker.

Do not remove this screw. Do not remove the small plastic barrier over the surge arrestors. This barrier must only be removed during maintenance to replace the surge protection devices.

Figure 3-12 Location of small DC plastic barriers 3. Remove and save the seven screws holding the large plastic barrier in the upper half of the cabinet, as indicated in Figure 3-13 on page 314. 4. Pull the barrier out; do not bend the plastic.

990-4613B Revision C

313

Conext Core XC Series Planning and Installation Manual

Figure 3-13 Removing the large plastic barrier 5. Remove and save the ten screws holding the steel mesh barrier in the lower half of the DC cabinet, as indicated in Figure 3-14. 6. Pull the barrier out; do not bend the metal.

Figure 3-14 Removing the DC barrier To prepare the floor of the inverter for cable routing: Remove and save the four plates from the floor of the DC cabinet (see Figure 3-15). You must re-install them after routing the cables.

314

990-4613B Revision C

Installation: Specific Wiring Requirements

Figure 3-15 Removing the DC floor plates To make the connections from the PV array/combiner to DC cabinet: 1. Route the PV+ and PV- power conductors and the PV array frame ground conductor(s) through the slit in the foam in the access point in the floor of the inverter. 2. Terminate the PV power conductors at the PV+ and PV- terminals in the DC cabinet using M12 hardware (see Figure 3-16). Polarity must be observed or the inverter will fail to qualify the PV array voltage and will not generate output power. Conductors must be provided with crimp-on ring terminals or compression-type lugs. Torque the M12 bolts per Table A-4 on page A4. 3. Connect the ground conductor(s) from the PV array frames to the ground bar (PE) (see Figure 3-16). Make terminations for the ground conductor(s) within the DC cabinet at the ground bar with M10 hardware. 4. Re-install the four plates in the floor of the DC cabinet (shown in Figure 3-15). 5. Do not re-install the DC barriers (page 43) until all other installation steps and the visual inspection on page 42 have been completed.

Ground bar (PE)

PV-

PV+

Figure 3-16 PV array cable routing and terminations

990-4613B Revision C

315

Conext Core XC Series Planning and Installation Manual

Auxiliary AC Source Wiring


Power for the ventilation fans and heaters is provided by an internal auxiliary AC supply transformer (TC1). The source of supply to that transformer can be configured to be one of the following sources: An external auxiliary AC source (a separate source of supply provided at the installation site). The inverter AC output circuit.

The transformer has multiple taps that can be selected to allow for different AC supply voltage ranges. Two different transformer configurations exist for the auxiliary supply transformer (TC1). Original Conext Core XC Series inverters use auxiliary voltages of 208, 230, 315, or 400 VAC rms phase-to-phase. Newer Conext Core XC Series inverters use auxiliary voltages of 208, 230, 300, 350, or 380 VAC rms phase-tophase.

NOTICE
COMPONENT DAMAGE
For original Conext Core XC Series inverters, auxiliary power can only be supplied from the inverter AC output if the AC output voltage will always be in one of the following ranges: 284 346 VAC phase-to-phase 360 440 VAC phase-to-phase For newer Conext Core XC Series inverters, auxiliary power can only be supplied from the inverter AC output if the AC output voltage will always be in one of the following ranges: 270 330 VAC phase-to-phase 315 385 VAC phase-to-phase 342 418 VAC phase-to-phase Auxiliary AC supply transformer (TC1) taps must be set correctly according to the information in Table 3-1 or Table 3-2.

Failure to follow these instructions can result in damage to equipment. As shipped, the inverter is configured for auxiliary supply from the external AC auxiliary source and for a voltage of 230 VAC. If a 230 VAC auxiliary supply will be connected to the external AC auxiliary source input terminals (XT4), no further changes to the auxiliary AC source wiring or to the auxiliary AC supply transformer are needed. Proceed to To connect an external auxiliary AC source to terminal XT4 in the AC cabinet: on page 318. Changes to the configuration of the auxiliary supply wiring and transformer tap selection will be required if either of the following is true: The external AC auxiliary source is being used, but the voltage is not 230 VAC. The auxiliary AC will be supplied from the inverter output.

316

990-4613B Revision C

Installation: Specific Wiring Requirements

External AC Auxiliary Power Source


The external auxiliary AC source must be a nominal voltage that is compatible with the transformer configuration. If the source provided is 230 VAC, no change is needed. If the source provided is 208, 315, or 400 VAC (original configuration) or 208, 300, 350, or 380 VAC (newer configuration), then the tap selection for the auxiliary supply transformer (TC1) must be changed, according to Table 3-1 or Table 3-2. Instructions for changing taps are on page 318.

WARNING
HAZARD OF FIRE
External over-current protection must be installed for the AC auxiliary input circuit of the inverter.

Failure to follow these instructions can result in death or serious injury. The selection of external over-current protection for the AC auxiliary input circuit of the Conext Core XC Series inverters must be coordinated with both the internal inverter circuitry and your local electrical installation code(s). You must use an external over-current protection device with a maximum thermal trip current of 16A plus a suitable magnetic trip curve. The recommended magnetic trip curve is Type D, but there are many different trip curves available which vary between manufacturers. You may need to test a variety of over-current protection devices with your specific circuit to prevent nuisance tripping. For original Conext Core XC Series inverters using external auxiliary voltages of 208, 230, 315, or 400 VAC rms phase-to-phase, refer to Table 3-1. Table 3-1 Voltage ranges and transformer taps for external auxiliary AC source (original Conext Core XC Series)
External auxiliary AC source voltage (VAC rms phase to phase) 208 ( 10%) 230 ( 10%) 315 ( 10%) 400 ( 10%) Auxiliary AC supply transformer (TC1) primary tap 208 230 (as shipped) 315 400

For newer Conext Core XC Series inverters using external auxiliary voltages of 208, 230, 300, 350, or 380 VAC rms phase-to-phase, refer to Table 3-2. Table 3-2 Voltage ranges and transformer taps for external auxiliary AC source (newer Conext Core XC Series)
External auxiliary AC source voltage (VAC rms phase to phase) 208 ( 10%) 230 ( 10%) 300 ( 10%) 350 ( 10%) 380 ( 10%) Auxiliary AC supply transformer (TC1) primary tap 208 230 (as shipped) 300 350 380

990-4613B Revision C

317

Conext Core XC Series Planning and Installation Manual To connect an external auxiliary AC source to terminal XT4 in the AC cabinet: 1. Route the external auxiliary AC source conductors and their ground wire through the access point in the floor of the inverter to the AC cabinet. 2. Route the external auxiliary AC source ground conductor to one of the terminals on the ground bar in the AC cabinet. 3. Connect one external auxiliary AC source conductor to XT4:1 and the other one to XT4:2.

XT4:1 and XT4:2 connections

Cable tie location for auxiliary AC source voltage conductors

Figure 3-17 Connecting XT4:1 and XT4:2 To select the correct voltage tap for the control voltage transformer (TC1): The voltage taps are set at the XT2 terminal block.

XT2

Figure 3-18 XT2 location in AC cabinet 1. If changing from the factory default 230 VAC tap, move the auxiliary power cable from its factory location in terminal to the new terminal. 2. For original Conext Core XC Series inverters using external auxiliary voltages of 208, 230, 315, or 400 VAC rms phase-to-phase, refer to Table 3-3 and Figure 3-19. For newer Conext Core XC Series inverters using external auxiliary voltages of 208, 230, 300, 350, or 380 VAC rms phase-to-phase, refer to the voltage marking on the terminal block and Figure 3-20.

318

990-4613B Revision C

Installation: Specific Wiring Requirements Table 3-3 XT2:21 cable location for transformer tap (original Conext Core XC Series)
Cable XT2 location XT2:20 XT2:21 XT2:22 XT2:23 Transformer (TC1) tap 400 V 315 V 230 V (as shipped) 208 V

3. Do not re-install the DC barriers (page 43) until all other installation steps and the visual inspection on page 42 have been completed.
Move cable marked XT2:21 as needed to select voltage Insert a screwdriver into the hole beneath the old location to open the clip and release the wire. Insert a screwdriver into the hole beneath the new location to open the clip. Remove the screwdriver to close the clip and grip the wire.

Figure 3-19 Moving the voltage tap wire (original Conext Core XC Series)

Move the auxiliary power cable as needed to select voltage. Insert a screwdriver into the hole beneath the old location to open the clip and release the wire. Insert a screwdriver into the hole beneath the new location to open the clip. Remove the screwdriver to close the clip and grip the wire.

Figure 3-20 Moving the voltage tap wire (newer Conext Core XC Series)

Internal AC Auxiliary Power Source


For original Conext Core XC Series inverters, the auxiliary power supply can be taken from the AC output if the AC output will remain within one of the following ranges under all conditions: 990-4613B Revision C 284 346 VAC phase-to-phase 360 440 VAC phase-to-phase 319

Conext Core XC Series Planning and Installation Manual For newer Conext Core XC Series inverters, the auxiliary power supply can be taken from the AC output if the AC output will remain within one of the following ranges under all conditions: 270 330 VAC phase-to-phase 315 385 VAC phase-to-phase 342 418 VAC phase-to-phase

If one of these conditions cannot be met, then the auxiliary power must be supplied from an external auxiliary AC source as described on page 316. To configure the inverter for internal auxiliary power supplied from the AC output: 1. Change the factory configuration by moving the conductors connected to terminals XT2:39 and XT2:40 (external supply) over to terminals XT2:45 and XT2:46 (internal supply). See Figure 3-21 for the location of these terminals.
Internal auxiliary supply setting (XT2:45 and XT2:46)

Insert a screwdriver into the hole beneath the old location to open the clip and release the wire. Insert a screwdriver into the hole beneath the new location to open the clip. Remove the screwdriver to close the clip and grip the wire.

Figure 3-21 XT2 terminal block settings for internal auxiliary AC source 2. Using the procedure To select the correct voltage tap for the control voltage transformer (TC1): on page 318, adjust the tap selection on XT2 for the auxiliary supply transformer (TC1) according to Table 3-4 (original Conext Core XC Series inverters) or Table 3-5 (newer Conext Core XC Series inverters). Table 3-4 Tap selection for internal auxiliary AC source connection (original Conext Core XC Series)
AC output voltage (VAC rms phase-to-phase)a 284 to 346 360 to 440
a. Minimum to maximum absolute range.

TC1 primary tap on XT2 315 400

Table 3-5 Tap selection for internal auxiliary AC source connection (newer Conext Core XC Series)
AC output voltage (VAC rms phase-to-phase)a 300 ( 10%) 350 ( 10%) 380 ( 10%)
a. Minimum to maximum absolute range.

TC1 primary tap on XT2 300 350 380

320

990-4613B Revision C

Installation: Specific Wiring Requirements

Remote Communication and Control Wiring


In the Conext Core XC Series, the Modbus/RS485 circuits are to be connected only to external Modbus/RS485 circuits that are Safety Extra-Low Voltage (SELV). SELV is a common designation that refers to a circuit in which the voltages within the circuit and from the circuit to ground have values that are not a shock hazard, under both normal and single fault conditions. This is achieved by the design of the circuits, and by maintaining protective separation (fault-tolerant insulation and isolation) between the SELV circuits and all hazardous voltage circuits, both within the inverter and in the installation.

DANGER
HAZARD OF ELECTRIC SHOCK
Connect only to Safety Extra Low Voltage (SELV) circuits. The circuits provided for use with external communications and control equipment are designed to provide isolation from neighboring hazardous circuits within the inverter. The communications and control circuits within the Conext Core XC Series are floating from ground and are classified as SELV. They must be connected only to other SELV circuits in a manner which maintains all the circuits within SELV limits and prevents ground loops. Separate conduit entries must be provided for the communications and control circuits and the PV circuits and all AC circuits. Physical and electrical separation of the communications and control circuits from non-SELV electrical circuits must be maintained both within the inverter and external to the inverters.

Failure to follow these instructions will result in death or serious injury. In the Conext Core XC Series, the SELV circuits and their intended connections are: The Modbus/RS485 circuits on connectors S43 and S44, which must be connected only to external Modbus/RS485 circuits that are SELV. The external ENABLE/DISABLE switch circuit on terminals 5 and 6 of terminal block XT14, which must be connected only to a switch that has dry contacts (with no external voltage applied to them) and has protective separation to hazardous voltage circuits. The circuits for external control of active and reactive power, which must be connected only to 4-20 mA loop circuits that are SELV.

Make sure the communication and control cables enter the cabinet away from the PV and AC wiring and are routed and mechanically secured away from the PV and AC wiring throughout the length of the communications and control wiring. Maintain no less than 50 mm (2 in.) separation at all points and use the provided cable channels.

990-4613B Revision C

321

Conext Core XC Series Planning and Installation Manual

Modbus/RS-485 Wiring
Isolation and Surge Protection The recommended best practice is the use of fiber optic isolation, installed as close to the inverter as possible. This provides full isolation, removing the risk of damaging electrical surges coupling to the inverter, and, therefore, negating the need for additional surge protection.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Installations involving non-fiber optic cables exceeding 10 m (32 ft 9 inches) outside of a PV Box or building structure to the communication ports of the inverter must be able to withstand a 1.0 kV surge from line to ground. The recommended methods to meet this requirement are listed below in order of best practices: Galvanic isolation installed within 10 m (32 ft 9 inches) of the inverter such as, Schneider Electric gateway devices TSXETG100 or EGX300. No galvanic isolation surge protection devices that provide a minimum protection rating of 1.0 kV from line to earth are also acceptable but should be selected in accordance with the Schneider Electric Application Note: Modbus/RS485 Wiring for Conext Core XC inverters (document number: 990-4864).

Failure to follow these instructions can result in damage to equipment. Daisy-chaining The RS-485 bus is a multi-drop bus implemented as a daisy chain. The Conext Core XC Series provides two RJ-45 connectors to the same modbus ports to facilitate daisy chaining. Either port can be connected to the upstream or downstream device and a standard Ethernet (straight-through) patch cable may be used to connect the devices. Note: Ethernet cross-over cables must not be used. Shielding and Grounding The RJ-45 cable must use a shielded cable with the Modbus master end (not the inverter end) connected to protective ground. On the inverter end, the male connector must be shielded.

322

990-4613B Revision C

Installation: Specific Wiring Requirements

Connecting the Remote Communication and Control Devices


To route and connect the remote communication and control devices:

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Do not attempt to use this procedure to install communications wiring on an inverter that has already been energized or in operation. If the inverter has been previously energized, different lock-out and tag-out procedure steps are needed and the installation must be performed by authorized service personnel. See the Service Bulletin for Conext Core XC Series Inverter LockOut and Tag-Out Procedures (document number 993-0438).

Failure to follow these instructions will result in death or serious injury.

1. Route the communication and control cables along the following path (see Figure 322): a) Through the slit in the foam at the access point on the floor of the inverter. b) Through the cable channels on the left wall of the DC cabinet. c) Up the left side of the back wall of the DC cabinet. 2. Use cable ties to hold the cables in place to prevent contact from other field wiring and factory bus bars.

Figure 3-22 Routing the communication cable 3. Connect the remote control cables to the following locations:
Cable Type Active power control Reactive power control External enable/disable Connection Point XT14, terminals 1 and 2 XT14, terminals 3 and 4 XT14, terminals 5 and 6

If using a metallic cable that routes from XT14 to a location outside the PV shelter, ensure that the cable passes through an isolation device before exiting the box.

990-4613B Revision C

323

Conext Core XC Series Planning and Installation Manual

CAUTION
RISK OF POWER SURGES
Ensure that metallic conductors routed from XT14 to a location outside the PV shelter have proper isolation. Copper and other metallic conductors that are used to carry communication signals between the Conext Core XC Series inverter and devices outside the PV shelter may conduct power surges (from lightning or ground differentials between nodes) into the inverter.

Failure to follow these instructions can result in moderate or minor injury and damage to equipment.

XT14

Leave this jumper if you are not going to install an external ENABLE/ DISABLE switch

Figure 3-23 XT14 terminal block 4. Connect the remote communication cable to either RJ-45 port (S43 or S44 on the communications (CMX) board (see Figure 3-24 and Figure 3-25. If using a metallic cable that routes from the CMX board to a location outside the PV shelter, ensure that the cable passes through a surge protection device before exiting the box. 5. If you are connecting other inverters in a Modbus chain: a) Make sure SW2 is in the OFF (left) position, so that the Modbus communication is not terminated in this inverter. b) Connect a second RS-485/Modbus communication cable to the unused RJ-45 port (either S43 or S44). c) Connect the other end of the RJ-45 communication cable to the next inverter in the chain. 6. If you are not connecting other inverters in a chain, or if this is the last inverter in the chain, make sure switch SW2 is in the ON (right) position, so that the Modbus communication is terminated in this inverter. 7. If using the 4 20 mA loop circuits for external control of active and/or reactive power, connect the cables to terminal block XT14, terminals 1 and 2 (active power), and/or 3 and 4 (reactive power), with the direction of current as indicated in Figure 3-26.

324

990-4613B Revision C

Installation: Specific Wiring Requirements 8. Do not use the ports labelled CAN IN or CAN OUT. Make sure switch SW1 is set to ON (right).
SW2 SW1

Service use only

RS-485/Modbus

Do not use

Figure 3-24 Connecting the communication cable

Figure 3-25 Modbus/RJ-45 pinouts 9. Do not re-install the DC barriers (page 43) until all other installation steps and the visual inspection on page 42 have been completed.

990-4613B Revision C

325

Conext Core XC Series Planning and Installation Manual To install an external ENABLE/DISABLE switch:

WARNING
HAZARD OF ELECTRIC SHOCK
Do not apply external power to the external ENABLE/DISABLE switch.

Failure to follow these instructions can result in death or serious injury. Note: Use a switch rated for small signals. A switch rated for power circuits cannot function reliably over long term use. 1. Remove the jumper between XT14:5 and XT14:6. See Figure 3-26.

Figure 3-26 XT14 terminal identification 2. Connect the external ENABLE/DISABLE switch wiring to XT14:5 and XT14:6 in place of the jumper. 3. Do not re-install the DC barriers (page 43) until all other installation steps and the visual inspection on page 42 have been completed.

Completing the Installation


To complete the installation: 1. Follow the inspection steps in Chapter 4. 2. Do not re-install the AC and DC barriers (page 43 and page 43) until all other installation steps and the visual inspection on page 42 have been completed.

326

990-4613B Revision C

Inspection

DANGER
/

HAZARD OF ELECTRIC SHOCK, FIRE, EXPLOSION, AND ARC FLASH


To be installed and serviced only by qualified personnel equipped with appropriate personal protective equipment and following safe electrical work practices. This inverter is energized from multiple sources: the PV array, the AC grid, and the external auxiliary AC source (if used). Before opening doorsa or covers: Consult system diagram to identify all sources. De-energize, lock out, and tag out all sources following the procedure beginning on page ix. Wait at least 15 minutes for internal capacitors to discharge to safe voltages. Operation of the switches in or on the inverter does not remove all power from this inverter. Switch terminals remain live unless the PV, AC, and external auxiliary AC source have been disconnected externally. Before servicing, test using a meter rated at least 1000 V AC and DC, to ensure all circuits are de-energized. Additional external disconnecting means for the PV, AC, and external auxiliary AC source (if used), capable of being locked out and tagged out, must be provided as part of the installation to help facilitate safe installation and for certain servicing operations.

Failure to follow these instructions will result in death or serious injury.


a. A maintenance feature is available for equipped inverters that will allow the DC cabinet door to be opened without interrupting inverter operation (opening any other doors will interrupt inverter operation). Check with your country sales organization to determine whether your inverter is equipped with this feature.

990-4613B Revision C

41

Conext Core XC Series Planning and Installation Manual

Visual Inspection
These procedures help verify correct installation and proper wiring of the Conext Core XC Series. Prior to performing the following inspection steps on the Conext Core XC Series, review all safety requirements and procedures outlined in this manual and on any cautionary markings on the components within the system. To inspect the installation: 1. Visually inspect all the mechanical connections. This includes both electrical conduit fittings as well as cabinet anchoring and seismic bracing, if required. 2. Visually inspect the electrical connections and verify proper tightness of all terminations. 3. Visually inspect the utility interconnection transformer connections. Verify that the inverter-side winding of the transformer is not connected to ground at any point.

NOTICE
EQUIPMENT DAMAGE
Do not connect any point on the inverter-side winding of the isolation transformer to ground.

Failure to follow these instruction will result in damage to the inverter. 4. Visually inspect terminal block XT2 for correct tapping for both internal or external auxiliary AC power supply and for system voltage (see Auxiliary AC Source Wiring on page 316). 5. Perform corrective actions, if required.

42

990-4613B Revision C

Inspection: Re-installing AC and DC Barriers

Re-installing AC and DC Barriers


WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
All barriers must be properly replaced before energizing any circuits. Do not energize the inverter if any barriers are missing or damaged.

Failure to follow these instructions can result in death or serious injury. To re-install the AC barriers: 1. Slide the main AC barrier back into place, and then secure it with the five saved screws. For illustrations, see AC Wiring on page 310. 2. Slide the external auxiliary AC source barrier back into place, and then secure it with the five saved screws. For illustrations, see AC Wiring on page 310. To re-install the DC barrier: 1. Slide the bottom DC barrier back into place, and then secure it with the ten saved screws. For illustrations, see PV Array Wiring on page 313. 2. Slide the large plastic barrier back into place, and then secure it with the seven saved screws. For illustrations, see PV Array Wiring on page 313.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, AND ARC FLASH
Leave the PV auxiliary circuit breaker in the OFF position to maintain the locked-out and tagged-out status of the inverter.

Failure to follow these instructions will result in death or serious injury. 3. Slide the small plastic barrier covering the PV auxiliary circuit breaker back into place, and then secure it with the two saved screws. For illustrations, see PV Array Wiring on page 313.

Arranging for Commissioning and Configuration


The Conext Core XC Series inverter is locked via password (showing event code 2804 on the front panel user interface) until it is unlocked by an authorized service person performing the commissioning of the inverter. To arrange for commissioning and configuration: 1. Complete the Pre-Commissioning Checklist in Appendix B. This checklist provides Schneider Electric with details of the Conext Core XC Series installation and the site conditions. You may either complete the checklist manually or ask your local Schneider Electric entity to provide a digital copy. 2. Contact your local Schneider Electric entity to submit the checklist and book an appointment for authorized service personnel to perform the initial power on, commissioning, and configuration of the Conext Core XC Series.

990-4613B Revision C

43

44

Specifications

Appendix A provides electrical, environmental and mechanical specifications for the Conext Core XC Series. WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, FIRE, AND ARC FLASH HAZARD OF EQUIPMENT DAMAGE
Unsafe conditions and damage to the inverter can result if the instructions and electrical, physical, and environmental installation specifications in this manual are not obeyed.

Failure to follow these instructions can result in death or serious injury and/or damage to equipment.

990-4613B Revision C

A1

Conext Core XC Series Planning and Installation Manual

System Specifications
The specifications for a Conext Core XC Series are provided. The Conext Core XC Series has only been designed for use with photovoltaic power systems that operate within the following specifications.

Electrical Specifications
Table A-1 Electrical specifications
Specification Number of output phases Nominal phase-to-phase AC voltage (VAC) Overvoltage category (AC Mains) Maximum AC output current Nominal AC frequency (f) Reactive power range (Q) Phase angle range Power factor range AC output current distortion Output power (S) Suggested PV array peak power Maximum open circuit PV voltage Maximum PV operating current Maximum array short circuit current at STC (standard test conditions) Maximum array short circuit current under any condition MPP (maximum power point) range PV operating voltage range External auxiliary AC source voltage 325 kVAr 37 degrees XC540 3 300 Vrms III 1040 Arms XC630 3 350 Vrms III 1040 Arms XC680 3 380 Vrms III 1040 Arms

50 Hz; configurable for 60 Hz 375 kVAr 37 degrees 400 kVAr 37 degrees

1 to 0.8 (leading and lagging) < 3% THD (total harmonic distortion) at rated power 540 kVA 621 kW 1000 VDC 1280 A 1600 A 2000 A 440a to 800 V 440a to 850 V 630 kVA 725 kW 1000 VDC 1280 A 1600 A 2000 A 510a to 800 V 510a to 850 V 680 kVA 782 kW 1000 VDC 1280 A 1600 A 2000 A 550a to 800 V 550a to 850 V

Original models: 208/230/315/400 Vrms Newer models: 208/230/300/350/380 Vrms 2000 VA 2000 VA 2000 VA

External auxiliary supply power required Euro efficiency without transformer

>98.0 % (per IEC-EN61683-2000)

a.Valid for power factor = 1 (Q = 0). Low limit of MPP range is dynamically adjustable based on nominal phase-to-phase AC voltage based on V_Mppt_min = 15V+ 2 x (VAC[V])2 + 4,021 x f[Hz] x Q[kVAr]

A2

990-4613B Revision C

Specifications: System Specifications

Physical and Environmental Specifications


Table A-2 shows the physical and environmental specifications for the Conext Core XC Series inverter. Table A-2 Physical and environmental specifications
Specification Dimensions Net weight Gross shipping weight (approximate) Allowable ambient temperature and humidity rangesa Conext Core XC Series 2400 mm W x 2085 mm H x 660 mm D (see Figure A-1) 94 in. W x 82 in. H x 26 in. D 1590 kg (3505 lbs) 1900 kg (4189 lbs) Operating: Class 3K3: -10 C to 45 C maximum (14 F to 113 F)b Maximum 95% relative humidity, non-condensing Transport: Class 2K2: -25 C to 55 C maximum (-13 F to 131 F) Maximum 95% relative humidity, non-condensing Storage: Class 1K2: -25 C to 55 C maximum (-13 F to 131 F) Maximum 95% relative humidity, non-condensing Class 3Z1a Class 2Z1a Class 1Z1a Class 3B1a Class 2B1a Class 1B1a Class 3C1a Class 2C1a Class 1C1a Class 3S1a Class 2S1a Class 1S1a Class 3M1a Class 2M1a Class 1M1a

Special climatic conditions

Operating: Transport: Storage: Operating: Transport: Storage: Operating: Transport: Storage: Operating: Transport: Storage: Operating: Transport: Storage:

Biological conditions

Chemically active substances

Mechanically active substances

Mechanical conditions

Altitude Storage air pressure Ingress protection class Cooling air flow power stage cabinet Cooling air flow AC/DC cabinet Total cooling air flow Clearance (ventilation and serviceability)

1000m with no deratingsc 700 to 1060 mbar IP20 3000 m/h 500 m/h each cabinet 4000 m/h Top: 300 mm (11 in.) Front: 1 m (39 in.) plus local safety standards for door clearance

a.Environmental range ratings correlate approximately to Classes shown, as defined by EN60721 standard series. b.Above 45 C (113 F), the inverter will derate its power output up to 50 C (122 F). c.Depending on ambient temperature at altitude, the output power may automatically derate above 1000 m. The installer must derate the PV and AC voltages above 2000 m. See Application Note: Altitude Derating for Conext Core XC Series.

990-4613B Revision C

A3

Conext Core XC Series Planning and Installation Manual

Regulatory Specifications
Regulatory specifications for the Conext Core XC Series are: CE marked for the Low Voltage Directive per EN50178 and EN 60529-1. CE marked for the EMC Directive per EN61000-6-4 (emissions) and EN61000-6-2 (immunity). For interconnect and country-specific regulatory compliance information, go to www.schneider-electric.com or speak with your country sales representative.

Bolt Sizes and Torque Requirements


Table A-3 provides acceptable bolt sizes and torque values for AC terminal connections. Table A-3 AC terminal bolt size and torque values
AC Terminal Connections Grounding (PE) AC output/grid (XT1) External auxiliary AC source (XT4) Max # Conductors per Terminal 2 5 1 Bolt (Hardware) Size M12 M12 cable cross section 2.5 - 10 mm use appropriate ferrules Torque Requirements 60 to 70 Nm (44 to 51.5 lb ft) 60 to 70 Nm (44 to 51.5 lb ft) 0.6 0.8 Nm (5.3 7.1 lb in)

# of Terminals 1 3 (L1, L2, L3) 2 (L1, L2)

Table A-4 provides acceptable bolt sizes and torque values for PV terminal connections. Table A-4 PV terminal bolt size and torque values
DC Terminal Connections PV Terminal (XT11) Max # Conductors per Terminal 7 Bolt (Hardware) Size M12 Torque Requirements 60 to 70 Nm (44 to 51.5 lb ft)

# of Terminals 2 (PV+, PV-)

A4

990-4613B Revision C

Specifications: Dimensions

Dimensions

2085

2400
Dimensions in mm

600 660

Figure A-1 Conext Core XC Series dimensions (XC680 model shown)

990-4613B Revision C

A5

A6

Site Evaluation Checklist

990-4613B Revision C

B1

Conext Core XC Series Planning and Installation Manual

Grid-Tie Photovoltaic Inverters Site Evaluation Checklist


Document Number 990-5118 Rev A

Use this checklist to record details of the site configuration and to verify correct installation of the inverter before a Schneider Electric technician is sent on site to commission the inverter.
Inspector Name & Phone Number: Project Information Project name: GPS coordinates: Site Contacts Project manager: Maintenance technician: Other teams that work on site (who, when, where, point of contact): Safety Safety protocol (e.g., boots, hard hat, etc.): Entrance requirements (contact person, location of keys, sign in/out procedure): Security officer: MV transformer operator: Street address (if applicable): Inspection Date:

1. Site Readiness
Cabling done percentages: Grid availability date Is inverter anchoring complete? Is ducting complete? AC cabling done: ____% DC cabling done: ____% _____ (ddmmyy) Yes __ Yes __ No __ No __

3. PV Box (contd)
Is an exhaust ventilation system installed? If possible, attach a diagram. Are exhaust fans (if installed) speed controlled? Cooling air flow: Is air conditioning installed? If yes, record the cooling capacity: Min __ C (__ F) Max __ C (__ F) ____ m (__ ft) None __ Single __ Double __ If a duct system is used, are dampers provided? AC cable type: AC cable shielding: AC cable area: No. of AC cable runs per phase: Yes __ # of filters ___ Yes __ Type: ______ No __ No __

____ m3/hr (__ CFM) Yes __ No __

2. Environment
Ambient temperature range: Altitude: Array tracking axis: Describe any shading concerns:

____ tonnage (____ BTU) Yes __ Copper __ Shielded __ No __ Aluminum __ Armored __

___ sq. mm (___sq. ft.) ___ runs/phase Copper __ Shielded __ Aluminum __ Armored __

3. PV Box
Height: Number of inverters per PV box: Service access at front of inverter: Service access at top of inverter: Service power receptacle easily accessible? Type of lighting: Box construction material: Is the floor level? Is an intake ventilation/filtration system installed? If possible, attach a diagram. ______ m (______ in.) ____ /PV box ______ m (______ in.) ______ m (______ in.) Yes __ No __

DC cable type: DC cable shielding: DC cable area: No. of DC cable runs per polarity (+/-): Is the inverter chassis connected to ground? Ground cable type: Ground cable shielding: Ground cable area:

_____ sq. mm (_____sq. ft.) ___ PV+ runs Yes __ Copper __ Shielded __ ___ PV- runs No __ Aluminum __ Armored __

_______________________ _______________________ Yes __ Yes __ # of filters ___ No __ No __

___ sq. mm (___sq. ft.)

Describe any accessibility problems with the PV box:

April 2013

When printed, this document is uncontrolled. Confidential - Property of Schneider Electric - Solar Business

Page 1 of 2

B2

990-4613B Revision C

Site Evaluation Checklist:

4. Communication
Modbus addresses of inverters: _______ ________ ________ _________ _________ _________ _________ _______ ________ ________ _________ _________ _________ _________ _______ ________ ________ _________ _________ _________ _________ Modbus addresses of array boxes (if monitored): _______ ________ ________ _________ _________ _________ _________ _______ ________ ________ _________ _________ _________ _________ _______ ________ ________ _________ _________ _________ _________ Baud rate, stop bits, parity: Are the inverters in a BUS? Are the connections between PV boxes isolated/ protected? Does the inverter use an Internet connection? If an Internet connection is used, select the functions that it provides: _____ baud _____ bits Yes __ Yes __ Yes __ Remote monitoring __ _____ parity No __ No __ No __ SCADA __ Type:______

6. PV Array (contd)
Module maximum power point: Module short circuit current: PV array grounding scheme: ___ Vmpp ___ Isc Floating __ Positive grounded __ Negative grounded __ Yes (please attach) __ ____ strings ____ modules/string Yes __ No __ No __

Module data sheet or module parameters available, with temperature coefficients? Number of strings: Number of modules per string: Are all panels mounted?

7. Array Boxes (attach site map)


Sourced through Schneider Electric? Number of strings per array box: Number of array boxes per inverter: Are all array boxes grounded? Impedance of cable insulation: Yes __ No __

Other _________________ If the inverter uses remote monitoring, is the monitoring data available? Type of communication cable used for Modbus/ RS485 connections: If copper cable is used, is surge isolation protection installed? Yes __ OFC __ Yes __ No __ Copper __ No __

____ strings/array box ____ array boxes/inverter Yes __ Max _____ : Type: ________________ Rating: _____________ Shielding: _______________ Type: ___________ ___________ ___________ Yes __ Qty: ___ ___ ___ No __ No __

5. MV Transformer
MV transformer model and type: Transformer rating: Is impedance Z within the following range? MV - LV1: 4.5% to 6.5% (6% nominal) MV - LV2: 4.5% to 6.5% (6% nominal) LV1 - LV2: 7% to 11% (10% nominal) Can each low voltage winding withstand a voltage of 900 VAC to ground? Can the LV windings handle non-sinusoidal voltages with a voltage gradient (dU/dt) of up to 500 V/s of ground? Is medium voltage available and connected? Have the medium voltage rings and distribution been tested? Medium voltage transformer tap setting: Nominal LV AC output: Does the MV transformer have LV alarms? Does the MV transformer have MV alarms? _____________________ _________________ kVA Yes __ No __

Type of cabling from array box to combiner box: Cable shielding from array box to combiner box: Type of protection (e.g., fuses, DC switch, overvoltage). If possible, attach a diagram.

Yes __ Yes __

No __ No __

Is LOTO easily applied to the array boxes?

Describe any accessibility problems with the array boxes:

Yes __ Yes __

No __ No __

8. Combiner Boxes (attach site map)


Sourced through Schneider Electric? Number of inputs: Record the input cable connections: Yes __ ____ inputs No __

_____% (e.g., 2%, 5%,...) ____ VAC Yes __ Yes __ No __ No __

Impedance of cable insulation: Location of fuses:

Max _____ : PV+ __ PV - __ Yes __ Yes __ Yes __ Ref _______ Rating ____A Type: ___________ ___________ ___________ ___________ ___________ Both __ No __ No __ No __ Qty __ Qty: ___ ___ ___ ___ ___

If the MV transformer has alarms, record the cable connections: Does the MV transformer have LV protection? Does the MV transformer have MV protection? Transformer grounding type (e.g., IT) Yes __ Yes __ No __ No __

Are all combiner boxes grounded? Is LOTO easily applied to the combiner boxes? Do the boxes have master/slave functionality? If yes, record the quantity, reference & rating of DC contactors

Type _____________

6. PV Array
Module technology: Thin film __ Monocrystalline silicon __ Polycrystalline silicon __ Other (describe) _________ ___ Voc

Type of protection (e.g., fuses, DC switch, overvoltage). If possible, attach a diagram.

Module open circuit voltage: