Anda di halaman 1dari 1

THIS DRAWING IS A COPYRIGHT.

CONTENTS OF THE DRAWING OR PART THEREOF MAY NOT BE USED OR REPRODUCED WITHOUT

1030

1220

1220

1030

33 KV

THE PERMISSION OF

RAJKHOWAS AARCHI
GUWAHATI.

M.D ROAD,CHANDMARI,

1030 1220 1220 1030

2 x MC 100 INCOMING OVERHEAD LINE OUT GOING CABLE ` GANG MC75 90 LBS. RAIL OR. EQVT. 2 x MC 75 DROP - OUT FUSE 50 X 50 X 6 LA
1200 600

NOTES
1.ALL DIMENSIONS ARE TO BE READ AND NOT TO BE MEASURED. 2.ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED

33KV

PLAN
TWO POLE STRUCTURE FOR CABLE TERMINATION
INCOMING OVERHEAD LINE LA

50 X 50 X 6 CABLE BOX
10500 300 2440 3660 5500

2 x MC 100 DANGER BOARD ANTI - CLIMBING DEVICE OPERATING HANDLE


1250

4500

OUTGOING CABLE

40 x 5 MM G.I EARTH STRIP GROUND

GI PIPE 1 X 150 DIA.


S.NO. REVISIONS DATE

DETAIL - A

2000

KEY LINE DIAGRAM


150

300

1200

REVISIONS

CLIENT BRAHMAPUTRA CRACKER AND POLYMER LIMITED PROJECT

MIN 750 DIA PLAIN CONCRETE MIN. M20 GRADE

150

G. L.

300 X 300 X 10 MS BASE PLATE WELDED TO POLE (TYPICAL)

PROPOSED MASTER PLAN OF CISF TOWNSHIP, LEPETKATA,DIBRUGARH.


SCALE : JOB NO DEALT BY CHECKED BY 10/GU/2008

150

ELEVATION

CLIENT'S SIGN

DETAIL - A

NOTES:1. STRUCTURE/MEMBER/FOUNDATION SIZES GIVEN ARE THE MINIMUM REQUIRED. CONTRACTOR TO CALCULATE THE ACTUAL REQUIREMENTS BASED ON FORCES, SAG, WIND VELOCITY AND OTHER STRUCTURAL PARAMETERSAND PROVIDE THE SAME WITHOUT ANY COST/SCHEDULE IMPLICATIONS. THEFOUNDATION SHALL BE DESIGNED FOR CALCULATED FORCE USING CONCRETE OF MIN. GRADE M20. SUITABLE PROTECTIVE GAURD WIRE SHALL BE PROVIDED AS PER REC STANDARDS AT ROAD CROSSINGS. THE POLE HEIGHTS ARE SUITABLE FOR A MAXIMUM SAG OF 1510 MM FOR 33KV LINES AT THE HIGHEST OPERATATIVE TEMP. SUITABLE GUY WIRE ARRANGEMENT SHALL BE PROVIDED FOR POLE STRUCTURES AS REQUIRED. ESPECIALLY AT THE END OF LINE AND AT TURNINGS. THE ARRANGEMENT SHALL BE USED AT TERMINATING POINT OF OVERHEAD LINES.
ARCHITECT'S SIGN

2. 3. 4. 5.

CONSULTANT
ARCHITECTS, ENGINEERS, VALUERS & PLANNERS M.D. ROAD, CHANDMARI GUWAHATI-781003

R AJKHOWAS A ARCHI

DRAWING TITLE
DOUBLE POLE STRUCTURE

DRAWING NO. RAA / CISF / EXTERNAL ELECTRIFICATION/E-13

Anda mungkin juga menyukai