CONTENTS OF THE DRAWING OR PART THEREOF MAY NOT BE USED OR REPRODUCED WITHOUT
1030
1220
1220
1030
33 KV
THE PERMISSION OF
RAJKHOWAS AARCHI
GUWAHATI.
M.D ROAD,CHANDMARI,
2 x MC 100 INCOMING OVERHEAD LINE OUT GOING CABLE ` GANG MC75 90 LBS. RAIL OR. EQVT. 2 x MC 75 DROP - OUT FUSE 50 X 50 X 6 LA
1200 600
NOTES
1.ALL DIMENSIONS ARE TO BE READ AND NOT TO BE MEASURED. 2.ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED
33KV
PLAN
TWO POLE STRUCTURE FOR CABLE TERMINATION
INCOMING OVERHEAD LINE LA
50 X 50 X 6 CABLE BOX
10500 300 2440 3660 5500
4500
OUTGOING CABLE
DETAIL - A
2000
300
1200
REVISIONS
150
G. L.
150
ELEVATION
CLIENT'S SIGN
DETAIL - A
NOTES:1. STRUCTURE/MEMBER/FOUNDATION SIZES GIVEN ARE THE MINIMUM REQUIRED. CONTRACTOR TO CALCULATE THE ACTUAL REQUIREMENTS BASED ON FORCES, SAG, WIND VELOCITY AND OTHER STRUCTURAL PARAMETERSAND PROVIDE THE SAME WITHOUT ANY COST/SCHEDULE IMPLICATIONS. THEFOUNDATION SHALL BE DESIGNED FOR CALCULATED FORCE USING CONCRETE OF MIN. GRADE M20. SUITABLE PROTECTIVE GAURD WIRE SHALL BE PROVIDED AS PER REC STANDARDS AT ROAD CROSSINGS. THE POLE HEIGHTS ARE SUITABLE FOR A MAXIMUM SAG OF 1510 MM FOR 33KV LINES AT THE HIGHEST OPERATATIVE TEMP. SUITABLE GUY WIRE ARRANGEMENT SHALL BE PROVIDED FOR POLE STRUCTURES AS REQUIRED. ESPECIALLY AT THE END OF LINE AND AT TURNINGS. THE ARRANGEMENT SHALL BE USED AT TERMINATING POINT OF OVERHEAD LINES.
ARCHITECT'S SIGN
2. 3. 4. 5.
CONSULTANT
ARCHITECTS, ENGINEERS, VALUERS & PLANNERS M.D. ROAD, CHANDMARI GUWAHATI-781003
R AJKHOWAS A ARCHI
DRAWING TITLE
DOUBLE POLE STRUCTURE