October 7-9-2002
175,000 gsf facility for 277 people Bacterial research Viral research Immunology
Affiliated Engineers
Fluent, Inc.
11 x 32 planning module 1,056 square foot laboratory 176 square foot isolation rooms (4) 1760 square foot lab suite 9-8 ceiling height
Affiliated Engineers
Fluent, Inc.
Vary airflow based on actual use Determine minimum airflow rate Reduce system pressure drop Improve fan system efficiency
Affiliated Engineers
Fluent, Inc.
Need the thermostat Need connected equipment hoods Code Historical intuition
Affiliated Engineers
Fluent, Inc.
Equipment ? AC/HR
Equipment
16 14 12 10 8 6 4 2 0
Unoccupied
?
OSHA NIH NFPA
? ??
ASHRAE ANSI
?
Affiliated Engineers
Prudent Practices
Typical Clients
Fluent, Inc.
Isolation Room B
Affiliated Engineers
Fluent, Inc.
BSC 8-inch opening 100 fpm face vel 530 cfm Supply Diffuser 2-way 480 cfm
Return 2-ftx2-ft return 100 cfm Fume Hood 18-inch opening 100 fpm face vel Isolation 600 cfm Room Door 150 cfm out Supply Diffusers (5) 4-way / each 384 cfm
Flad & Associates Affiliated Engineers
Fluent, Inc.
12 ACH
8 ACH
Affiliated Engineers
Fluent, Inc.
Airflow modeling can determine the local mean age of air , Represents freshness of the air or expected turnover Can be used to identify poorly ventilated areas Ventilation effectiveness, related to mean age of air,
12 ACH
3600 / ACH
12 ACH
Airflow modeling can compute local conditions and predict thermal comfort
Predicted Mean Vote (PMV) Percent of People Dissatisfied (PPD)
8 ACH
Flad & Associates Affiliated Engineers Fluent, Inc.
Want to optimize laboratory energy performance by allowing for reduced ventilation flow rates when thermal loads permit it Use airflow modeling to help determine if laboratory will provide safe environment for workers in the event of chemical spill scenario 1-liter spill of methylene chloride in isolation room 4-liter spill of methylene chloride in central laboratory area Acceptability criteria:
MeCl concentration does not exceed 125 ppmv (STEL) for more than one hour
Although OSHA STEL is 125 ppmv for 15 minute average, assume laboratory is evacuated by unprotected personnel shortly after spill occurs
Affiliated Engineers
Fluent, Inc.
seconds
1-liter liquid methylene chloride spill in isolation room 1 m2 spill area Vaporization occurs over 300 seconds at constant rate Total simulation time = 1,800 seconds
color contours clipped at 125 ppmv
12 ACH
seconds
8 ACH
seconds
4-liter liquid methylene chloride spill in central laboratory 4 m2 spill area Vaporization occurs over 300 seconds at constant rate Total simulation time = 3,600 seconds
color contours clipped at 125 ppmv
12 ACH
seconds
8 ACH
Budget Building Design Fume hood / exhaust device density Plug loads Same as proposed design
1.8 W / sf (net)
100 fpm face velocity with vertical rising sash 18 open 100% outside air, constant volume, without heat recovery
As designed
All other characteristics of the budget building design and proposed design (e.g. envelope, etc.) shall remain the same as in the standard
Flad & Associates Affiliated Engineers Fluent, Inc.
New York State Energy Conservation Code New York State Energy Research and Development Authority (NYSERDA) New Construction Program ASHRAE / IESNA Standard 90.1 1999 (LEED) Labs21 Environmental Performance Criteria (EPC)
Affiliated Engineers
Fluent, Inc.
DOE2 Analysis
Comparison of 8 vs. 12 ACHs yielded a $280,000 annual operating savings Modeled ASHRAE 90.1 1999 and draft version of LABS 21 EPC
ASHRAE 90.1
$1,080,102
$1,200,000
LABS21 EPC
$1,000,000
$801,719
$800,000
$781,635
$790,177
$764,490
$??
$600,000
$400,000
$200,000
$0
8 ACH 12 ACH Design Without fan power limits With fan power limits With CV supply & exhaust
Affiliated Engineers
Fluent, Inc.
Questions / Discussion
Garrick Maine, AIA, Flad & Associates As an advocate of environmental design Garrick is Flads representative to the U.S. Green Building Council, the Wisconsin Green Building Alliance and member of the Board of Directors of WasteCap Wisconsin, a non-profit organization promoting responsible waste management practices.
Steven G. Frei, PE, Affiliated Engineers Mr. Frei has extensive experience designing mechanical systems for research and testing facilities. This experience includes the design of new facilities and renovation of existing structures.
Walter Schwarz, Fluent Inc. Walter Schwarz has over 20 years of experience in the areas of flow modeling, heat transfer, and turbulence. He is currently working on delivering airflow modeling solutions to the HVAC industry related to ventilation system performance with respect to indoor air quality, thermal comfort, health and safety, and contamination control.