BULLETIN 1600
AIR-COOLED
FLUID COOLERS

Manufacturing Inc.

FEBRUARY 1, 1999
REVISED

DIRECT DRIVE REMOTE


AIR COOLED FLUID COOLERS
33 MODELS

Model AFV with Vertical Air Discharge.


Also available in AFH Models with Horizontal Discharge.

Colmac coils are rated in accordance with standard industry practice.

SPECIFY COLMAC QUALITY

Page 1

TABLE OF CONTENTS
FIGURES

TABLES

PAGE

Features and Options ..................................................................................................................................................... 3


Nomenclature .............................................................................................................................................................. 3
Specifications
Physical Specifications ........................................................................................................ Table 1 ...................... 4
Electrical Specifications ...................................................................................................... Table 2 ....................... 5
Dimensions, Models 62 thru 384......................................................... Fig 1 ........................................................... 6
Dimensions, Models 119 thru 636 ....................................................... Fig 2 ........................................................... 7
Dimensions, Models 714 thru 1271 .................................................... Fig 3 ........................................................... 8
Dimensions, Models 1425 thru 1625. ................................................. Fig 4 ........................................................... 9
50 Hz Operation .................................................................................................................. Table 3 ..................... 10
Fan Speed/Sound Level ...................................................................................................... Table 4 ..................... 10
Selection Procedure
Glossary of Terms .................................................................................................................................................. 11
Selection Example .................................................................................................................................................. 12
Notes
............................................................................................................................................................ 13
Suggested Connection Sizes based on GPM ..................................................................... Table 5 ..................... 13
Optional Fan Control .............................................................................................................................................. 13
Fluid Heat Factors ............................................................................... Fig 5 ......................................................... 14
Capacity Correction Factors ................................................................ Fig 6 ......................................................... 14
Fluid Pressure Drop ............................................................................ Fig 7 ......................................................... 15
Pressure Drop Correction Factors ...................................................... Fig 8 ......................................................... 16
Altitude Correction Factor ................................................................... Fig 9 ......................................................... 16
(1) Fan Fluid Coolers........................................................................... Fig 10 ....................................................... 17
(2) Fan Fluid Coolers........................................................................... Fig 11 ....................................................... 18
(3) Fan Fluid Coolers........................................................................... Fig 12 ....................................................... 19
(4) Fan Fluid Coolers........................................................................... Fig 13 ....................................................... 20
(5) & (6) Fan Fluid Coolers .................................................................. Fig 14 ....................................................... 21
(8) Fan Fluid Coolers........................................................................... Fig 15 ....................................................... 22
(10) Fan Fluid Coolers ........................................................................ Fig 16 ....................................................... 23

Page 2

STANDARD FEATURES:
Colmac AFV/AFH model air-cooled fluid coolers are designed to provide cooling of Water, Ethylene Glycol/Water and
Propylene Glycol/Water mixtures in a variety of closed-loop applications. Closed-loop cooling eliminates the cost of fluid
treatment usually associated with the use of cooling towers.

Wide range of models and capacities - 33 models.

Corrosion resistant construction - Mill galvanized housing, powder coated steel fan guards, aluminum fan blades
on 3/4 Hp models, galvanized steel fan blades on 1 & 2 Hp models. Low speed, fully guarded fans for quiet
operation.

Built-in lifting eyes, and easy-to-install legs, make rigging and installation fast.

Low noise, 850 RPM fans, on 1 & 2 Hp models.

Compartmented fans to prevent short circuiting of air during fan cycling.

Units designed for efficient fan cycle control.

Versatile cabinet design for vertical or horizontal airflow.

Coil is made of 1/2" dia seamless copper tubes,and high efficiency aluminum plate fins, with self-spacing collars.

Exclusive Colmac Full Floating Core coil support system eliminates tubesheet leaks by shifting support of the
coil core from tubes to fins. Special Wear Guards allow expansion and contraction of fins and tubes without
chafing or wearing of tubes, or fins.

Heavy duty rigid foot-mounted direct drive fan motors with moisture protected rainshields (slingers) are internally
protected single or three phase on models 62 thru 384 (3/4 Hp), internally protected three phase only on models
119 thru 1271 (1 Hp), and three phase externally protected only on models 1425 thru 1625 (2 Hp). Motors are rated
for 150F maximum air temperature over the motor.

Weatherproof electrical enclosure features single point field wiring, and is easily accessible for fast installation.

OPTIONS:

Copper fins, or Polycoat Fins for corrosion resistance.

Baked phenolic coating available

Stainless or galvanized steel fan blades or cast aluminum.

UL 508 listed electrical panels

Stainless steel housing.

CSA listing available

Factory mounted and wired fused disconnect.

Factory wired fan cycle/fan speed control.

Customer specified control systems.

NOMENCLATURE:
AF V - 763 - D
AF

VOLTAGE CODE:
Air Cooled Fluid Cooler

V
V - Vertical Air Discharge
H - Horizontal Air Discharge
Model Number

A - 208-230/60/1
B - 208-230/60/3
C - 460/60/1
D - 460/60/3
E - 575/60/3
F - 380/60/3
G - 220-240/50/1
H - 200/50/3
Page 3

TABLE 1
AFV/AFH PHYSICAL SPECIFICATIONS
Fan
Model Dia. in.

No.
Fans

CFM

Coil
Face

Rows
Deep

Fins/
Inch

Internal
Vol. Cu/Ft.

Wt. (lbs.) of 40% Glycol


Mixture @ 135 F
Ethel.
Propyl.

Dry Wt.
lbs.

62
84
96
167
192
251
288
307
335
384

24
24
24
24
24
24
24
24
24
24

1
1
1
2
2
3
3
4
4
4

6310
6039
5734
12078
11468
18117
17202
24800
24156
22936

35 x 48
35 x 48
35 x 48
35 x 96
35 x 96
35 x 144
35 x 144
35 x 192
35 x 192
35 x 192

2
3
4
3
4
3
4
3
3
4

14
14
14
14
14
14
14
11
14
14

0.324
0.487
0.649
0.936
1.25
1.39
1.85
1.84
1.84
2.45

21.0
31.5
42.0
60.6
80.9
90.0
119.8
119.1
119.1
158.6

20.5
30.8
41.1
59.3
79.1
88.0
117.1
116.5
116.5
155.1

330
357
383
589
643
863
944
1056
1096
1203

119
127
223
238
254
357
381
446
476
509
595
636

30
30
30
30
30
30
30
30
30
30
30
30

1
1
2
2
2
3
3
4
4
4
5
5

8620
8090
18060
17240
16180
25860
24270
36120
34480
32360
43100
40450

45 x 54
45 x 54
45 x 108
45 x 108
45 x 108
45 x 162
45 x 162
45 x 216
45 x 216
45 x 216
45 x 270
45 x 270

3
4
3
3
4
3
4
3
3
4
3
4

14
14
11
14
14
14
14
11
14
14
14
14

0.698
0.931
1.35
1.35
1.80
2.00
2.66
2.65
2.65
3.53
3.30
4.40

45.2
60.3
87.4
87.4
116.5
129.5
172.2
171.5
171.5
228.5
213.6
284.8

44.2
58.9
85.5
85.5
114.0
126.6
168.4
167.8
167.8
223.5
208.9
278.6

513
552
815
843
921
1242
1358
1516
1572
1728
1971
2165

714
763
893
952
1017
1116
1190
1271

30
30
30
30
30
30
30
30

6
6
8
8
8
10
10
10

51720
48540
72240
68960
64720
90300
86200
80900

90 x 162
90 x 162
90 x 216
90 x 216
90 x 216
90 x 270
90 x 270
90 x 270

3
4
3
3
4
3
3
4

14
14
11
14
14
11
14
14

4.00
5.32
5.30
5.30
7.06
6.60
6.60
8.80

258.9
344.4
343.1
343.1
457.0
427.2
427.2
569.6

253.2
336.8
335.5
335.5
447.0
417.8
417.8
557.1

2374
2607
2927
3040
3351
3661
3803
4191

1425
1502
1625

36
36
36

10
10
10

111900
101600
88000

90 x 270
90 x 270
90 x 270

3
4
6

14
14
14

6.60
8.80
13.20

427.2
569.6
854.4

417.8
557.1
835.7

4368
4756
5532

Notes:
1. Weight of Liquid is calculated as follows:
Wt. Liquid (lbs) = Internal Vol. (cu. ft.) x Liquid Density(lbs/cu ft)
2. Operating Weight = Dry Weight + Weight Liquid
3. Units having finned length up to 216" use 1/2 x 0.016 copper tubes.
Units having finned length of 270" use 1/2 x 0.025 copper tubes.

Page 4

TABLE 2
AFV/AFH ELECTRICAL SPECIFICATIONS
Total FLA/60 Hz Supply
Model Fan
No.
dia,in. Fan

Fan
Hp

208-230/1 208-230/3

460/1

460/3

1.9
1.9
1.9
3.8
3.8
5.7
5.7
7.6
7.6
7.6

1.55
1.55
1.55
3.10
3.10
4.65
4.65
6.20
6.20
6.20

62
84
96
167
192
251
288
307
335
384

24
24
24
24
24
24
24
24
24
24

1
1
1
2
2
3
3
4
4
4

3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4

3.9
3.9
3.9
7.8
7.8
11.7
11.7
15.6
15.6
15.6

3.40
3.40
3.40
6.80
6.80
10.20
10.20
13.60
13.60
13.60

119
127
223
238
254
357
381
446
476
509
595
636

30
30
30
30
30
30
30
30
30
30
30
30

1
1
2
2
2
3
3
4
4
4
5
5

1
1
1
1
1
1
1
1
1
1
1
1

note 1

5.6
5.6
11.2
11.2
11.2
16.8
16.8
22.4
22.4
22.4
28.0
28.0

note 1

714
763
893
952
1017
1116
1190
1271

30
30
30
30
30
30
30
30

6
6
8
8
8
10
10
10

1
1
1
1
1
1
1
1

note 1

33.6
33.6
44.8
44.8
44.8
56.0
56.0
56.0

1425
1502
1625

36
36
36

10
10
10

2
2
2

note 1

86.0
86.0
86.0

Total FLA/50 Hz Supply


Note 3
200/3
400/3
4.2
4.2
4.2
8.4
8.4
12.6
12.6
16.8
16.8
16.8

2.1
2.1
2.1
4.2
4.2
6.3
6.3
8.4
8.4
8.4

2.8
2.8
5.6
5.6
5.6
8.4
8.4
11.2
11.2
11.2
14.0
14.0

4.2
4.2
8.4
8.4
8.4
12.6
12.6
16.8
16.8
16.8
21.0
21.0

2.1
2.1
4.2
4.2
4.2
6.3
6.3
8.4
8.4
8.4
10.5
10.5

note 1

16.8
16.8
22.4
22.4
22.4
28.0
28.0
28.0

25.2
25.2
33.6
33.6
33.6
42.0
42.0
42.0

12.6
12.6
16.8
16.8
16.8
21.0
21.0
21.0

note 1

43.0
43.0
43.0

93.7
93.7
93.7

46.9
46.9
46.9

Notes:
1. These units not available for single phase supply.
2. Models 62 through 384 (24 Fans)
Standard motors are 3/4 HP, 1140 RPM ODP, 60 Hz with internal thermal overload protection.
Models 119 through 1271 (30 Fans)
Standard motors are 1 HP, 850 RPM ODP, 60 Hz with internal thermal overload protection.
Models 1425 through 1625 (36 Fans)
Standard motors are 2 HP, 850 RPM TEFC, 60 Hz without internal thermal overload protection.
3. For 50 Hz operation:
(see Page 10)

1 HP motors are used in lieu of 3/4 HP.


1-1/2 HP motors are used in lieu of 1 HP.
2 HP motors are 950 RPM, 2 HP.
Page 5

FIGURE 1
PHYSICAL DIMENSIONS, Models 62 thru 384
(24" dia fans)

NOTES:

LIFTING EYE
(D) PLCS

ELECTRICAL
ENCLOSURE

39 3/4"
AIR

Fan Diameter is 24.


60Hz Fan Speed is 1140 RPM.
Adjustable in 6 increments to 40-9/16.

FLOW

1.
2.
3.

12"

40 1/2"

INLET
16 9/16"

OUTLET

(SEE NOTE 3.)

30"

AFV, VERTICAL AIRFLOW

12"

OUTLET
INLET

LIFTING EYE
(D) PLCS

5/8 DIA MTG HOLE


(E) PLCS

28 5/8"

ELECTRICAL
ENCLOSURE

OUTLET
39 1/4"

AIR
FLOW

INLET

AFH, HORIZONTAL AIRFLOW

26 1/8"

5/8 DIA MTG HOLE


(E) PLCS

DIMENSIONS
MODEL

NO. FANS A

62
84
96
167
192
251
288
307
335
384

1
1
1
2
2
3
3
4
4
4

46
46
46
94
94
94
94
94
94
94

48
48
96
96
96

4
4
4
4
4
6
6
6
6
6

4
4
4
4
4
6
6
6
6
6

Page 6

48
48
48
96
96
144
144
192
192
192

MAX. INLET/OUTLET
CONN. SIZE, MPT
3
3
3
3
4
4
4
4
4
4

FIGURE 2
PHYSICAL DIMENSIONS, Models 119 thru 636
(30" dia fans)

NOTES:
1.
2.
3.

Fan Diameter is 30.


60Hz Fan Speed is 850 RPM.
Single Phase Motors Not Available.
Adjustable in 7-9/16 increments
to 37-3/4.

49 5/8"

LIFTING EYE
(E) PLCS

ELECTRICAL
ENCLOSURE

AIR
FLOW

12"

48 5/8"

INLET
OUTLET

22 5/8"

(SEE NOTE 3.)

AFV, VERTICAL AIRFLOW

5/8 DIA MTG HOLE


(F) PLCS

37 3/4"

12"

OUTLET
INLET

LIFTING EYE
(E) PLCS

30 1/4"

ELECTRICAL
ENCLOSURE

OUTLET
49 5/8"

AIR
FLOW

INLET
5/8 DIA MTG HOLE
(F) PLCS

26"

AFH, HORIZONTAL AIRFLOW

DIMENSIONS
MODEL

NO. FANS

119
127
223
238
254
357
381
446
476
509
595
636

1
1
2
2
2
3
3
4
4
4
5
5

54
54
108
108
108
162
162
216
216
216
270
270

50 1/2
50 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2

57 1/2
57 1/2

54
54
108
108
108
104 1/2
104 1/2

4
4
4
4
4
6
6
6
6
6
8
8

4
4
4
4
4
6
6
6
6
6
8
8

MAX. INLET/OUTLET
CONN. SIZE, MPT
4
4
4
4
4
4
4
4
4
4
4
4
Page 7

FIGURE 3
PHYSICAL DIMENSIONS, Models 714 thru 1271
(30" dia fans)

NOTES:
1.
2.
3.

Fan Diameter is 30.


60Hz Fan Speed is 850 RPM.
Single Phase Motors Not Available.
Adjustable in 7-9/16 increments
to 45-1/4.

A
94 7/8"

LIFTING EYE
(E) PLCS

ELECTRICAL
ENCLOSURE

AIR
FLOW

AIR
FLOW

12"

62 1/8"

INLET
OUTLET

30 1/8"

(SEE NOTE 3.)

AFV, VERTICAL AIRFLOW

5/8 DIA MTG HOLE


(F) PLCS

82 7/8"

12"

OUTLET
INLET

LIFTING EYE
(E) PLCS

30 1/4"

OUTLET
AIR
FLOW

ELECTRICAL
ENCLOSURE

94 7/8"

AIR
FLOW

INLET
26"

AFH, HORIZONTAL AIRFLOW

5/8 DIA MTG HOLE


(F) PLCS

DIMENSIONS
MODEL

NO. FANS

714
763
893
952
1017
1116
1190
1271

6
6
8
8
8
10
10
10

162
162
216
216
216
270
270
270

104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2
104 1/2

57 1/2
57 1/2
57 1/2

54
54
108
108
108
104 1/2
104 1/2
104 1/2

6
6
6
6
6
8
8
8

6
6
6
6
6
8
8
8

Page 8

MAX. INLET/OUTLET
CONN. SIZES, MPT
5
6
5
5
6
5
5
6

FIGURE 4
PHYSICAL DIMENSIONS, Models 1425 thru 1625
(36" dia fans)

NOTES:
1.
2.

Fan Diameter is 36.


60Hz Fan Speed is 850 RPM.
Single Phase Motors Not Available.
Adjustable in 7 increments to 44-1/8.

3.
A

94 7/8"
AIR

LIFTING EYE
(E) PLCS

ELECTRICAL
ENCLOSURE

FLOW

AIR

FLOW

12"

61 1/2"

INLET
30 1/8"

OUTLET

(SEE NOTE 3.)

AFV, VERTICAL AIRFLOW


OUTLET
INLET

12"

5/8 DIA MTG HOLE


(F) PLCS

82 7/8"

LIFTING EYE
(E) PLCS

35"

OUTLET
AIR
FLOW

ELECTRICAL
ENCLOSURE

94 7/8"

AIR
FLOW

INLET

AFH, HORIZONTAL AIRFLOW

30 3/4"

2 DIA MTG HOLE


(F) PLCS

DIMENSIONS

MODEL

NO. FANS

1425
1502
1625

10
10
10

270
270
270

104 1/4
104 1/4
104 1/4

57 3/4
57 3/4
57 3/4

104 1/4
104 1/4
104 1/4

8
8
8

8
8
8

MAX. INLET/OUTLET
CONN. SIZES, MPT
5
6
6
Page 9

OPERATION WITH 50 Hz POWER


COLMAC AFV and AFH fluid coolers are designed to operate with either 60 Hz, or 50 Hz supply power. Cooling capacity
for 50 Hz operation will be the same as capacity for 60 Hz operation, since COLMAC uses fan blades matched to the 50
Hz rotational speed of 950 RPM.
Motor horsepower on most models will be different, however. The 60 Hz, 3/4 HP motors will be replaced with 1.0 HP motors,
and 60 Hz, 1.0 HP motors will be replaced with 1.5 HP motors for 50 Hz operation.

50 Hz FAN SPEED/SOUND LEVEL:


Operation of fluid coolers at 50 Hz will change the rotational speed of the fans. All fans will turn at 950 RPM. The 24 in.
dia. fans will turn slower than those used for 60 Hz operation, and will run quieter. The 30 and 36 in. dia. fans will turn faster
than those used for 60 Hz operation and will be somewhat louder. Fan and tip speeds, and sound levels for 60 Hz and 50
Hz are shown in tables 3 and 4.

TABLE 3
FAN SPEEDS

Models

Fan
Dia

Fan
RPM

62 thru 384
119 thru 1271
1425 thru 1625

24"
30"
36"

1140
850
850

60 Hz
Tip Spd
FPM
7163
6676
8011

Fan
RPM

50 Hz
Tip Spd
FPM

950
950
950

5969
7464
8958

TABLE 4
AFV/AFH SOUND LEVELS (Approx.)*

No. Fans

60 Hz Operation
dBA @ Distance from Unit, Ft
5
25
50
100

50 Hz Operation
dBA @ Distance from Unit, Ft
5
25
50
100

24 dia
1
2
3
4

70
73
75
76

56
59
61
62

50
53
55
56

44
47
49
50

66
69
71
72

52
55
57
58

46
49
51
52

40
43
45
46

30 dia
1
2
3
4
5
6
8
10

69
72
74
75
76
77
78
79

55
58
60
61
62
63
64
65

49
52
54
55
56
57
58
59

43
46
48
49
50
51
52
53

71
74
76
77
78
79
80
81

57
60
62
63
64
65
66
67

51
54
56
57
58
59
60
61

45
48
50
51
52
53
54
55

36 dia
10

85

71

65

59

87

73

67

61

*Based on free field sound data, with no background noise.


Page 10

SELECTION PROCEDURE:
The selection of a COLMAC AFV/AFH fluid cooler is mostly graphical and is easy to make.
Glossary of Terms
ACF =
CCF =
EAT =
EFT =
FF
=
FHF =
GPM =
LAT =
LFT =
LF
=
MBH =
Pfluid=
PDF =

Altitude Correction Factor (Fig. 9)


Capacity Corr. Factor, Fluid Mixture (Fig. 6)
Entering Air Temp.
Entering Fluid Temp.
Flow factor (Figs. 10 thru 16)
Fluid Heat Factor (Fig. 5)
Gallons per Minute
Leaving Air Temp.
Leaving Fluid Temp.
Length factor (Figs. 10 thru 16)
BTUH x 1000
Fluid Pressure Drop, psi (Fig. 7)
Pressure Drop Factor (Fig. 8)

Step 1. Calculate Avg Fluid Temp., AFT.


AFT = (EFT + LFT) / 2
Step 2. Calculate Fluid T.
T = EFT - LFT
Step 3. Calculate temperature difference, TD
TD = EFT - EAT
Step 4. Find Fluid Heat Factor, FHF, (Fig. 5).
Step 5. Calculate MBH required per degree of temperature difference.
MBH / TD = (GPM x T x FHF) / TD
Step 6. Correct MBH / TD with CCF (Fig. 6) and ACF (Fig. 9).
MBH / TD = (MBH / TD) x CCF x ACF
Step 7. Choose Model, using GPM and MBH / TD in Figs. 10 thru 16.
** (Use Models whose performance curves fall on, or above MBH / TD)
Step 8. Find Fluid Pressure Drop:
- Using GPM, find FF and LF from Figure used in step 7.
- Using FF and LF, go to Fig. 7, to find Pfluid.
Step 9. Correct Fluid Pressure Drop with PDF (Fig. 8).
Pfluid = Pfluid x PDF
Step 10. (Optional) Unit capacity can be approximated by the following method:

MBH actual =

MBH/TD (Curve value)


x TD
CCF x ACF

Page 11

EXAMPLE
1. AFT = (125 + 115.5) / 2
AFT = 120.3F

Given: % Glycol = 30% Ethylene Glycol


GPM = 80
EFT = 125F
LFT = 115.5F
EAT = 95F
Alt.= 2,000 ft

2. T = 125 - 115.5
T = 9.5F
3. TD = 125 - 95
TD = 30F
4. From Fig. 5, we see that FHF = 0.466
5. Calculate MBH / TD = (GPM x T x FHF) / TD
MBH/TD = (80 x 9.5 x 0.466) / 30
MBH/TD = 11.8
6. Correcting capacity for 30% Eth. Gly. and 2,000 ft alt.
using CCF (Fig. 6) and ACF (Fig. 9):
CCF = 1.002 and ACF = 1.04
MBH/TD = 11.8 x 1.002 x 1.04
MBH/TD = 12.3
7. Looking at Fig. 11, using 80 GPM and 12.3 MBH/TD:
a. Choose

AFV-254

At 80 GPM, its performance is 12.9 MBH/TD, which is greater than 12.3

b. Using diagrams in Fig. 11 for Flow Factor (above) and Length Factor, (side):
for AFV-254 (Fig. 11): FF = 3.33
LF = 648
8. Looking at Fig. 7, using 80 GPM, FF = 3.33 and LF = 648
Pfluid = 7.5
9. Correct for Pfluid for 30% Eth. Gly mixture at 120f using Fig. 8: PDF = 1.175
Pfluid = Pfluid x PDF
Pfluid = 1.175 x 7.5
Pfluid = 8.8 psi

10. Actual Unit Capacity at 80 GPM, 120F AFT, 30TD, and 30% Ethylene glycol, is approximately:
MBH / TD
MBH actual = x TD
CCF X ACF

MBH actual = 371.37

Page 12

12.9 MBH/TD
x 30
1.002 x 1.04

Notes:
1. The selection procedure is optimized for system performance while keeping fluid pressure drops below a reasonable
maximum (less than 12 PSI). If calculated Pfluid is greater than that desired, it is possible to make another selection
on COLMACs CoilPRO III software, using a Hot Water/Sensible Cooling coil, or have COLMACs Factory Sales
people assist in making another circuiting selection.
2. Flow Factors greater than 3.5 are not recommended, and are not represented in Figs. 10 thru 16.
3. See Table 5. for suggested inlet/outlet pipe sizing.

TABLE 5.
Gallons Per
Minute

Suggested Inlet/Outlet
Connection Size, MPT

2-6
7 - 12
13 - 20
21 - 40
41 - 80
81 - 120
121 - 260
261 - 700

1"
1 1/4
1 1/2
2"
2 1/2
3"
4"
6"

* Based on mean head


loss of 2.5ft / 100ft,
ASHRAE Fundamentals
Handbook, 1993

OPTIONAL FAN CONTROL


COLMAC offers FC Fan Cycling and MS Modulated Speed control packages to compliment the selection of any fluid cooler.
Such controls may be used to maintain the desired Leaving Fluid Temperature regardless of operating conditions, or
seasons.
FC fan cycling controls will stop rotation of one or more fans in incremental stages to maintain temperature.
MS controls will slow rotation of one or more fans to maintain temperature. On multiple fan models, a combination of
Modulation and Cycling is used. If the fluid temperature falls below the point at which the Modulating fan(s) can maintain
temperature, one or more additional fans will be shut off and the remaining Modulating fans will gain more speed until the
desired fluid temperature is reached.
Note:

Because MS controls affect motor winding temperature, please consult the Factory for application information and
pricing.

Page 13

FIGURE 5
FLUID HEAT FACTORS, FHF
ETHYLENE GLYCOL MIXTURE
0.50
0%
0.49

PROPYLENE GLYCOL MIXTURE

10%

0.48

0.50

FHF

20%

0% &10%
0.49

0.47
30%

20%

FHF

0.46
40%

0.45

0.48

30%

0.47
40%

0.44

0.46

50%

50%
0.45

0.43
120

100

140

160

180

120

100

AVG. FLUID TEMP.

140

160

180

AVG FLUID TEMP

FIGURE 6
CAPACITY CORRECTION FACTORS, CCF
WATER & PROPYLENE GLYCOL
1.17
1.16
1.15
1.14
1.13
1.12
1.11
1.10

WATER & ETHYLENE GLYCOL


1.08

1.08

1.07

1.07

1.06

1.06

1.05

1.05

1.04

1.04

1.03

1.03

1.02

1.02
P.G.50%

1.01
1.00

1.01

E.G.50%

1.00
0.99

P.G.40%

0.99
0.98

P.G.30%
0.97
P.G.20%
0.96
P.G.10%
WATER
0.95
100 110 120 130 140 150 160 170 180

AVG. FLUID TEMP F


Page 14

CCF

CCF

1.09

E.G.40%

0.98
0.96

E.G.30%
E.G.20%
E.G.10%

0.95

WATER

0.97

0.94
100 110 120 130 140 150 160 170 180

AVG. FLUID TEMP F

3.5

3.2

3.0

2.7

2.5

2.4

2.3

14.000

13.000

2.20

12.000

2.10

11.000

2.00

1.90
9.000
8.000

25

3.

1.70

00

7.000

3.

75

2.

6.000

1.60

.50

2
0
2.4
0
2.30
2
.
2
0
2.1
0
0
.
2
1.90
1.80
1.70

5.000
4.000

3.000

2.000

1.60
1.50

1.000

1.20
1.00

Page 15

200

400

600

1.50

1.20
1.00

800

1000

1200

1400

LENGTH FACTOR, LF

1600

1800

2000

2200

2400

2600

FLOW FACTOR, FF

P FLUID, PSI

1.80

50

3.

FIGURE 7
FLUID PRESSURE DROP, P FLUID

10.000

FIGURE 8
CORRECTION FACTOR, PDF
FLUID PRESSURE DROP
WATER & PROPYLENE GLYCOL

1.55
1.50

WATER & ETHYLENE GLYCOL


1.45

CORRECTION FACTOR

1.35
1.30
1.25
1.20
1.15

50% E.G.

1.10

CORRECTION FACTOR

1.45

1.40

1.40
1.35
1.30
1.25
1.20
1.15

50% P.G.

1.10

40% E.G.
30% E.G.

1.05

40% P.G.

1.00

1.00

0.95

20% E.G.

0.95

30% P.G.
20% P.G.

0.90

10% E.G.
WATER
180

0.90

10% P.G.

1.05

0.85
100

110

120

130

140

150

160

170

0.85
100

110

AVG. FLUID TEMP F

120

130

140

1.170
1.160
1.150
1.140
1.130
1.120
1.110
1.100

ACF

160

AVG. FLUID TEMP F

FIGURE 9
ALTITUDE CORRECTION FACTOR

1.090
1.080
1.070
1.060
1.050
1.040
1.030
1.020
1.010
1.000
0

1000

2000

3000

4000

ALTITUDE, ft

Page 16

150

5000

6000

7000

170

WATER
180

FIGURE 10
CAPACITY - 1 FAN FLUID COOLERS
GPM
0

10

20

30

50

40

00 .5
3

2.

50

80

90

30 2.4

3.2

2.8

2.4

70

3.

60

2.

100

60

110

80

2.

2.

00

3.

120

130

140

20 3.40 0
5
3.

3.

AFV-127

LENGTH FACTOR
0
2.4

0
0
0
1.0 2.0 3.0
0

FLOW FACTOR

150

2.0

1.0

0
0
3.0 3.4
2.0

3.0

0
.0

0
.6

2
0

3.0

2.5

0
.4

MODEL

1.8

3.5

2.0

2.2

AFV-62

AFV-119
0

2.5

2.0

-84

40 .60 .80 .00 .20 .40


3
3
2
2
3

3.5

2.
0

2.5

3.5

3.0

-96

AFV-96
0

1.0

2.0

1.7

3.0

3.0

2.5

2.0

-119
0
0
1.5 2.0

1.8

0
3.5

0
0
2.5 3.0

2.0

AFV-84
0

40
2.
60
2.
80
3.
00
3.
20
3.
40

2.0

3.0

-127

2.

1.0

2.0

2.5

3.5

3.0

AFV-62
0

1.0

2.0

1.7

3.0

2.5

2.0

3.0

GPM
5 - 25
26 - 49
50 - 80
5 - 21
22 - 49
50 - 74
75 - 80
5 - 25
26 - 49
50 - 80
5 - 21
22 - 31
32 - 63
64 - 94
95 - 120
5 - 21
22 - 28
29 - 42
43 - 64
65 - 85
86 - 120

LENGTH
FACTOR
384
192
96
672
288
192
96
786
384
192
972
648
324
216
108
1296
972
648
432
324
216

7.0

MBH / TD

AFV-127

6.0

AFV-119

5.0

AFV-96

AFV-84

4.0
AFV-62

3.0
1 FAN FLUID COOLERS

2.0
0

10

20

30

40

50

60

70

80

90

100 110 120 130 140 150

GALLONS PER MINUTE


Page 17

4.0

5.0

6.0

7.0

8.0

9.0

10.0

11.0

12.0

13.0

14.0

15.0

AFV-167

AFV-192

AFV-238
AFV-223

Example, 12.9
MBH/TD

FLOW FACTOR

MBH / TD

Page 18

AFV-254

GPM

20

0
2.0

10

20

1.5

2.5

2.0

2.0

3.0

2.5

2.5

0
1.8

3.0

3.0

50

30

40

60

3.5

3.5

0
2.6

80

3
0

2.4

.40
0
0
0
0
0
2.6 2.8 3.0 3.2 3.4

2.4

90

60

70

80

2
2

.20

90

AFV-254

.00

GALLONS PER MINUTE

50

.80

40 60 80 00 20 40
2. 2. 2. 3. 3. 3.

1.7

.60

0
2.0

3.0

110

100

120

AFV-167

130

130

-254

-238

-223

-192

AFV-167

MODEL

Example, FF = 3.33

.00

AFV-238

.80

0
2.2

3.2

120

AFV-223

110

AFV-192

.40

1.8

2.8

0
1.8

2.6

100

0
0
0
0 0
0
0
0
0
1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4

.00

70

0 0 0 0 0
2.6 2.8 3.0 3.2 3.4

40 60 80 0 20 40
2. 2. 2. 3.0 3. 3.

0
2.2

0
0
3.0 3.5

40

2 FAN FLUID COOLERS

0
0
0
1.0 2.0 3.0

1.0

2.0

30

80 20 60 00 0
1. 2. 2. 3. 3.4

0
0
1.0 2.0

1.5

20 60 00 40 80 20
0. 0. 1. 1. 1. 2.

10

192

*Example, LF = 648

85 - 120

64 - 84

432

1944
1296
864
648

5 - 17
18 - 42
43 - 63

432
216

1296
648
33 - 63
64 - 95
96 - 120

16 - 32

216
1944

96 - 120
5 - 15

1296
648
432

1944

384
192
16 - 32
33 - 63
64 - 95

5 - 15

50 - 98
98 - 100

1344
768

74 - 120
5 - 24
25 - 49

1344
576
384

LENGTH
FACTOR

5 - 18
19 - 49
50 - 73

GPM

LENGTH FACTOR

FIGURE 11
CAPACITY - 2 FAN FLUID COOLERS

FLOW FACTOR

7.0

8.0

9.0

10.0

11.0

12.0

13.0

14.0

15.0

16.0

17.0

18.0

19.0

20.0

21.0

AFV-251

AFV-288

AFV-357

20

30

1.
7
1. 0
9
2. 0
1
2. 0
30

40

80

2.5

2.

20

3.0

10

20

50

30

60

3.5

2.

00

60

40

80

1.8

50

60

80

2.4

90

100

AFV-251

AFV-288

AFV-357

2.2

AFV-381

2.0

110

2.6

2.0

1.9

2.4

2.4

3.0

2.2

1.8

3.4

130

120 130

2.8

2.2

120

3.2

GALLONS PER MINUTE

70

1.8

1.8

3.0

110

2.0

2.8

2.6

2.4

100

90

0 0 0 0 0
0
2.4 2.6 2.8 3.0 3.2 3.4

0 0 0 0 0
2.6 2.8 3.0 3.2 3.4

70

0 0
0 0
0 0
0 0 0
1.8 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.4

3.

3 FAN FLUID COOLERS

0
0 0
0 0
0 0
1.0 1.4 1.8 2.2 2.6 3.0 3.4

1.5

40

2.0

1.

40 0 0
1. 1.8 2.2

1.

0 0 0 0
1.2 1.6 2.0 2.4

10

40

AFV-381

MBH / TD

1.
6
1. 0
8
2. 0
0
2. 0
2
2. 0
4
2. 0
60
2.
8
3. 0
0
3 0
.
2
3. 0
40
3.

2
.
4
2. 0
60
2.
80
3.
0
3 0
.
20
3.
40

GPM

140

150

2.8

150

2.1

2.6

2.6

2.0

140

3.0

2.3

160

2.8

2.2

160

170

3.2

2.4

170

3.4

180

2.5

180

190

190

-381

-357

-288

AFV-251

MODEL

324

648
127-180

972
85 - 126

1296
64 - 84

30 - 63

324
1944

5 - 29

96 - 180

972
648

64 - 95

1944

5 - 21

576
288

98 - 160

22 - 63

1152
50 - 98

2016
19 - 49

5 - 18

288

576
74 - 140

864

5 - 49

LENGTH
FACTOR

50 - 73

GPM

LENGTH FACTOR

FIGURE 12
CAPACITY - 3 FAN FLUID COOLERS

Page 19

11.0

12.0

13.0

14.0

15.0

16.0

17.0

18.0

19.0

20.0

21.0

22.0

23.0

24.0

25.0

26.0

27.0

28.0

AFV-335
AFV-307

AFV-384

AFV-476
AFV-446

AFV-509

30

40

50

0 0
20
2. 2.6 3.0

30

40

50

0
0
0
2.5 3.0 3.5

0
0
2.5 3.0

8
1.

60

70

60

80

100

110

70

120

0
1.8

2.0

2.2

2.2

0
0
0
0
0
0
2.0 2.2 2.4 2.6 2.8 3.0

0
1.8

0
2.0

130

80

90

140

150

160

170

180 190

200

210

220

230

240

2.6

2.6

AFV-307

AFV-335

3.0

AFV-384

2.8

2.8

GALLONS PER MINUTE

3.2

100 110 120 130 140 150 160 170

2.4

2.4

180 190

AFV-446

AFV-476

AFV-509

3.4

200 210 220 230 240

80 1.90 .00 .10 2.20 2.30 2.40 .50 2.60 2.70 2.80 .90 .00 .10 .20 3.30 .40
3
3
3
2
2
3
2
2

1.

40 .60 .80 3.00 .20 3.40


2
2.
3
2

90

4 FAN FLUID COOLERS

1.8

2.4
2.6 0
0
2.8
3.0 0
3.2 0
3.40
0

FLOW FACTOR

MBH / TD

1.8
2.00
2.20
2.40
2.60
0

2.
0
2. 0
20
2.
4
2. 0
60
2.
8
3. 0
00
3
.
2
3. 0
40

2.
20
2
.
40
2.
60
2
.
80
3
.
00
3.
20
3.
40

Page 20

1.
60
1.
80
2
.
00
2.
20
2
.
40
2.
60
2
.
80
3.
00
3
.
20
3.
40

GPM

1296
864
432

82 - 126
126-240

1728
48 - 81

5 - 47

95 - 180
-509

864
432

58 - 94

-446
-476

384

99 - 160

1296

768

43 - 98

1536

384
5 - 42

768
74 - 140

1152

LENGTH
FACTOR

50 - 73

5 - 49

GPM

5 - 57

-384

-335

AFV-307

MODEL

LENGTH FACTOR

FIGURE 13
CAPACITY - 4 FAN FLUID COOLERS

AFV-714

AFV-595

AFV-636

14.0

16.0

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

34.0

36.0

38.0

40.0

42.0

40

60

80

2.0

1.8

2.2
0

40
60

200

220

240
0
1.8
2.4

5 FAN FLUID COOLERS

AFV-636

AFV-714

300

360

0
0

2.2

0
3.0

2.8

0
2.0

GALLONS PER MINUTE

300 320 340 360 380

380
2.6

340

3.4
0

320
2.4
3.2

280

400

420

440

460

480

400 420 440 460 480

6 FAN FLUID COOLERS

260

2.6
0

180 200 220 240 260 280

20 .40
3

2.4
0

3.

100 120 140 160

AFV-595

AFV-763

80 .00 .20 .40 .60 .80


2 2 2 2 2

1.

2.

180
2.8

160
3.0

140

60 80 00 20 0
2. 2. 3. 3. 3.4

120

00
2.0

100

80

80
2.8

AFV-763

1.8
2.20
0

3.

20

60

3.

3.0
0

1.4
0
1.
8
0
2.2
0

1.8
2.20
2.60
0

1.4
0
1.
8
0
2
.
2
0
2.6
0

3.

3.2
0 2.2

2.

2
.
40
2.
60
2
.
80
3.
00
3.
20
3.
40
2

1.6
0
2.
0
0
2.4
0
2
.
8
0
3.2
0

2.0
2.20
2.40
2.60
2.8 0
3. 0
3.200
3.40
0

2.
0
1.8

.60

40
0
3.4

1.
6
1. 0
8
2. 0
0
2. 0
2
2. 0
4
2. 0
6
2. 0
8
3. 0
0
3. 0
2
3. 0
40

2.8
3.0 0
0
3.2
0
3.4
0

1.
8
2. 0
0
2. 0
2
2. 0
4
2. 0
6
2. 0
8
3. 0
0
3. 0
2
3. 0
40

FLOW FACTOR

MBH / TD

3.2

40

500

500

0
3.4

GPM

-763

-714

-636

AFV-595

MODEL

253-500

324

648

972
169-252

1296
123-168

1944

324
59 - 122

30 - 58

190-380

648

972
127-189

1296

44 - 92

1944
93 - 126

30 - 43

540

1080
127-240

68 - 126

540
1620

95 - 180
30 - 67

1620
1080

30 - 51

LENGTH
FACTOR
52 - 94

GPM

LENGTH FACTOR

FIGURE 14
CAPACITY - 5 AND 6 FAN FLUID COOLERS

Page 21

FLOW FACTOR

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

34.0

36.0

38.0

40.0

42.0

44.0

46.0

48.0

50.0

52.0

54.0

56.0

AFV-952
AFV-893

40

60

80

40

180

80

60

AFV-952

220

240
1.8
2.4

0
0

40

AFV-893

300
2.4

2.2

0
3.0

0
2.8

2.6
0

2.0

3.

20

340

360

3.2

380
0

320
2.6

280

3.4
0

260

400
0

420

440

460

480

500

GALLONS PER MINUTE

100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500

8 FAN FLUID COOLERS

AFV-1017

200
2.8

160
0

140
3.0

120
0

100

2.

1.5
0
2.0
0

1.
4
1 0
.
6
1. 0
8
2. 0
0
2. 0
2
2. 0
4
2. 0
60

1.
40
1
.
80
2.
20
2.
60

2.

2
.
40
2.
60
2.
80
3
.
00
3.
20
3.
40

80

00
0

AFV-1017

MBH / TD

3.
2.0

2.
00
2
.
20
2.
40
2.
60
2.
80
3.
00
3.
20
3.
40

2.0
2.2 0
2.40
2.6 0
2.80
3.0 0
3.2 0
3.40
0

2.
0
1.8

3.
0

Page 22
2.2

60
3.2

40
0
3.4

GPM

-1017

-952

432

864
253-500

1296
164-252

1728

51 - 94
95 - 163

2592

30 - 50

432

864
190-380

1296
123-189

432
1728

30 - 70
71 - 122

864
190-380

1296

30 - 70
71 - 122

AFV-893

123-189

1728

GPM

MODEL

LENGTH
FACTOR

LENGTH FACTOR

FIGURE 15
CAPACITY - 8 FAN FLUID COOLERS

FLOW FACTOR

AFV-1190
AFV-1116

34.0

36.0

38.0

40.0

42.0

44.0

46.0

48.0

50.0

52.0

54.0

56.0

58.0

60.0

62.0

64.0

66.0

68.0

70.0

72.0

74.0

76.0

78.0

80.0

82.0

80

1.

.8
0

AFV-1271

84.0

1.6
1.8 0
0
2.0
2.20
0

20

2.

2
.
2 40
2..860
0

2.

20

0
AFV-1116

AFV-1190

AFV-1425

0
AFV-1502

2.5

2.4

AFV-1271

2.8

2.7

0
AFV-1625

3.3

.20

3.1

3.0

2.9

2.6

3.4

GALLONS PER MINUTE

80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 640 660 680 700 720 740

10 FAN FLUID COOLERS

60

60

1.8

1.8

AFV-1425

AFV-1502

MBH / TD

2.

2.

2.
0
2 0
.
2
2. 0
4
2. 0
6
2. 0
8
3. 0
0
3. 0
2
3. 0
40

2
2 .20
.
2 40
2..860
0

2.0
0
.00

0
2.4
0

1.
80
2
.
00
2.
20
2
.
40
2.
60
2.
80
3
.
00
3.
20
3.

2
2

1.8

0
0

40

2.0
0
2.2
0
2.4
0
2.6
0
2.8
0
3.0
0
3
.
2
0
3.4
0
0
2.4

2.6
0
0
2.6

1.8
.20
.20

2.
00
2.
20
2
.
40
2.
60
2
.
80
3.
00
3
.
20
3.
40

2.
0
2 0
.
2
2. 0
4
2. 0
6
2. 0
8
3. 0
0
3. 0
2
3. 0
40

2
2

1.8
0

2.0
2.6
0 2.00

2.4

2.6
0
3.4

0
0

1.9

2.8

0
0
0

3.4 2.
6
0

2.8
.80 2
.2
.80
2.2

2.0
3.0

3.0
3.0
0

3.0

3.2
0

2.1
3

2.8

0
3
2.4
3

2.2

.20
3.2
0

3.0

2.4
.20
.20

2.3
3.4

AFV-1625

80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 620 640 660 680 700 720 740

3.4

GPM

-1625

-1502

-1425

-1271

-1190

AFV-1116

MODEL

540

540

379-740

1620
1080

203-378

152-202

2160

540
80-151

1080

135-252

1620
253-500

80-134

540

1080
190-378

102-189

540
1620

253-500
80-101

1080

135-252

1620

1080

102-189
190-378
80-134

540
1620

80-101

1080

1620

LENGTH
FACTOR

190-378

102-189

80-101

GPM

LENGTH FACTOR

FIGURE 16
CAPACITY - 10 FAN FLUID COOLERS

Page 23

COLMAC
COIL
Manufacturing Inc.

A Tradition of Quality
Colmac Coil began as a spin-off of a successful laundry equipment manufacturing company. Since 1971,
Colmac has been distinguished for its commitment to quality in the new and replacement coil markets.
Located in scenic Colville, Washington in the beautiful inland Northwest, Colmac has grown to prominence
as a trusted coil manufacturer with HVAC, commercial/industrial heating & cooling, and refrigeration
customers worldwide.

OTHER QUALITY COLMAC PRODUCTS


HEAT EXCHANGERS

PACKAGED EQUIPMENT

WATER COILS
STEAM COILS
EVAPORATOR COILS
CONDENSER COILS
OEM COILS
SPECIAL USE & CUSTOM COILS

AMMONIA EVAPORATORS
-

LOW, MEDIUM, HIGH PROFILE UNIT COOLERS

Contact your Local Representative or:

AIR COOLED CONDENSERS


FLUID COOLERS
PRODUCT COOLERS
UNIT COOLERS
BLAST FREEZERS

HEAT RECOVERY
-

AIR SOURCE HEAT PUMP WATER HEATERS

COLMAC COIL MFG., INC.


370 North Lincoln
P.O. Box 571
Colville, WA 99114-0571
Phone: (509) 684-2595
Fax: (509) 684-8331
e-mail: mail@colmaccoil.com
Website: www.colmaccoil.com

Page 24