Australian made Protection and Control Relays

THE RELAY SPECIALISTS

relay monitoring systems pty ltd

www.rmpl.com.au

2H34 Four Stage Frequency Relay

2H34 Four Stage Frequency Relay


Frequency Stages The 2H34 Series relay is a frequency monitoring relay with four stages of adjustable frequency pick up & drop out points. Each frequency set point can be set for under or over frequency operation & has an independent time delay driving an output relay. An undervoltage lockout is used to disable the four frequency outputs when the voltage falls below a preset level.

2H34 Frequency Set Points


Inputs: Setting stages: Operating range: Setting range: Measurement resolution: Accuracy: Hysterisis: Over frequency function: Single pole 63.5 or 110V AC 4 independent stages 40 to 60 Hz 41 to 59Hz in 0.05Hz steps 0.01Hz at 50Hz +/-0.03Hz (70 to 121V) at 50Hz 0.05 to 0.5Hz in 0.05Hz steps PU at set point DO at set point hysterisis +/-0.03Hz Under frequency function: PU at set point DO at set point + hysterisis +/-0.03Hz

Frequency Element Time Delay Setting

The 2H34 allows for a separate time range for each of the four frequency stage set points. Setting range: 0.1 to 100s in 0.05s steps. Minimum operate time: 0.1s typical Timing error: <20ms + 0.1% of time delay setting

2H34 Rate of Change Of Frequency


Each setting stage can also have a rate of change of frequency threshold, df/dt, established. Each dF/dt stage has an independent time delay but drives the same output relay as the frequency stage. Two logic options are available to control how the output contact responds to the frequency and dF/dt pick up as follows: OR logic AND Logic either frequency of dF/dt will trigger the stage output contact. both the frequency and dF/dt must pick up to activate the stage output relay.

2H34 dF/dt Sampling Engines


dF/dt measurements are based on the difference between successive frequency readings recorded on each cycle of the AC signal being monitored. dF/dt measurements based on 2 samples is required for fast response but is not suitable for detecting low dF/dt rates. dF/dt measurements based on 5 samples is required to detect very slow dF/dt rates but is consequently slower to respond & is not suitable for detecting high dF/dt rates.

2H34 dF/dt Sampling Engines

To allow dF/dt setting flexibility while remaining within the constraints described in Table 1, two dF/dt sampling engines (A & B) are provided: dF/dt activation: Sample time A: dF/dt rejection A: Sample time B: dF/dt rejection B: Set to ON or OFF 2 to 5 cycles in 1 cycle steps 2 to 18Hz/s in 0.1Hz/s steps 2 to 5 cycles in 1 cycle steps 0.2 to 18Hz/s in 0.1Hz/s steps

2H34 dF/dt Set Points

Four independent dF/dt elements are provided. When this function is activated the dF/dt pick up is used to initiate an independent dF/dt timer. Setting stages: 4 independent stages Setting range: 0.13 to 9.0Hz/s in 0.1Hz/s steps dF/dt function: PU at set point DO at set point hysterisis dF/dt engine: Select dF/dt sampling engine A or B

2H34 dF/dt Time Delay Setting


The 2H34 allows for a separate time range for each of the four dF/dt stage set points: Setting range: Timing error: 0.00 to 100s in 0.02s steps. <20ms + 0.1% of the time delay setting

2H34 dF/dt Setting Criteria


Sample time (Cycles) Maximum setting (Hz/s) Minimum setting (Hz/s) Minimum time delay setting dF/dt Measurement time Hysterisis (Hz/s) Accuracy at 50Hz (Hz/s) 2 9 0.70 40ms 100ms 0.24 +/-0.2 3 7 0.50 60ms 160ms 0.12 +/-0.1 4 6 0.20 80ms 200ms 0.07 +/-0.07 5 5 0.13 100ms 240ms 0.05 +/-0.05

2H34 Voltage Stages


Voltage Alarm / Lockout Stages

The 2H34 Series relay also provides a number of independent voltage stages: An undervoltage lockout is available to disable the four frequency outputs when the voltage falls below a preset level; An undervoltage alarm stage with independent output contact; An over voltage alarm stage with independent output contact.

2H34 Four Stage Frequency Relay


Summary of Output Stages

Front Panel Settings & Indicators


SET page DATA page Diagnostics page 4 Stage trip status LEDs
Flash when timing, solid when timed out

Relay disabled LED Under voltage alarm LED Relay healthy LED Relay service LED RS232 configuration port

Micro MATRIX Protection & Control Relay Platform


Compact draw out case
- Screw terminals - CT shorting available

High accuracy Simple calibration Temperature compensation

Micro MATRIX Protection & Control Relay Platform


Self supervision
- Power supply - Software watchdog

Scaleable I/O Front accessible opto-

isolated programming port


Single PC program

suits all models

Micro MATRIX Protection & Control Relay Platform

Firmware control & upgrades

Separate BIOS &

application software levels

Micro MATRIX Protection & Control Relay Platform

uMATRIXwin PC Configuration Screen

Front Panel Layout

Menu Structure

Typical uMATRIX Platform PCBs

uMATRIX Platform HMI PCB

2H34 Terminals

Customer Generated Ordering Code


Generate the required ordering code as follows: e.g. 2H34 BBB 1 2 3

2H34
1 A B 2 AUXILIARY SUPPLY RANGE 20-70V DC 40-275V AC / 300V DC RELAY INITIATE INPUT

Opto-isolated input A 24-80V AC/DC B 75-150V AC/DC C 150-300V AC/DC 3 REMOTE FLAG RESET INPUT

Opto-isolated input A 24-80V AC/DC B 75-150V AC/DC C 150-300V AC/DC REQUEST DEFAULT APPLICATION SOFTWARE A B 2H34AUMX 2H34BUMX Frequency OR dF/dt output logic function Frequency AND dF/dt output logic function

2H34 Additional Information


Technical Bulletin User Guide Software downloads Auto Cad Mounting Drawings Price & Availability

www.rmspl.com.au/2H34.htm
Test Manuals

www.rmspl.com.au/search.asp