MHD 535 Cable Terminator Module CTM 535


The Cable Terminator Module CTM 535 is the terminator module for the temperature sensor cable MHD 535. An MHD 535 system is not operational without the Cable Terminator Module CTM 535. The Cable Terminator Module CTM 535 contains the temperature-compensated reference current source which is required for the formation of the differential current signals used to transmit the sensor values to the Processor Unit PU.

Construction of the Cable Terminator Module CTM 535


The Cable Terminator Module CTM 535 comprises a plastic enclosure made of glass fiber reinforced polyester containing the electronic components for termination of the sensor bus system. The printed circuit board features a flat-ribbon connector for the direct connection of the sensor cable, and in addition a seven-pole plug-in terminal for connecting the sensor cable via a connecting cable.

Figure 1: Construction of the Cable Terminator Module CTM 535

Terminal block for connecting cable CCA 535 Flat-ribbon connector

Banana connector Cable entry

Mounting the Cable Terminator Module CTM 535


Mounting position of the Cable Terminator Module CTM 535 The Cable Terminator Module CTM 535 can be mounted on the X, Y or Z axis.

SECURITON AG Alpenstrasse 20 CH - 3052 Zollikofen Switzerland

T 800454

1/4

Data sheet

Figure 2: Drilling plan of the Cable Terminator Module CTM 535

Selecting the location for the Cable Terminator Module CTM 535 The location should be a site which is not rendered inaccessible by equipment on site (cable ducts, runs etc.) The mounting location is usually predetermined by the application in question (application and mounting type of the sensor cable). A minimum distance of 15 cm from parts on site (control cabinets, alcoves etc.) should be kept on the entry side of the sensor cable.

Notice
A minimum distance of half a sensor distance or 10 m connecting cable CCA 535 should be maintained between the last sensor and the Cable Terminator Module CTM 535.
Mounting should be carried out, whenever possible, immediately after the last sensor (i.e. without a connecting cable) (grounding concept, inductive coupling). After consultation with the manufacturer and after an accurate design check, remote mounting is also possible. Fastening the Cable Terminator Module CTM 535 The Cable Terminator Module CTM 535 is fastened using 4 screws. When mounting on cement or masonry in tunnel applications, special nail anchors CMS 511 with stainless steel V4A screws (5/15x35) should be used. A minimum distance of 15 cm from parts on site (control cabinets, alcoves etc.) should be kept on the entry side of the sensor cable.

Safety Notice
For protection against humidity, the enclosed desiccant bag should be left inside the Cable Terminator Module CTM 535.

2/4

T 800454

MHD535

Data sheet
Technical specifications of the Cable Terminator Module CTM 535

Figure 3: Dimensioned drawing of the Cable Terminator Module CTM 535

Module Type
CTM 535

Parameter
Operating voltage Power consumption Protection class Ambient conditions Temperature range Ambient condition humidity

Values

Remark
+10 ... +20 VDC Via sensor/connecting cable of the
Processor Unit PU

approx. 8.5 mA IP65 in accordance with IEC 529 / EN 60529


(1991)

3K5 / 3Z1 in accordance with IEC 721-3-3 / EN


60721-3-3 (1995)

-40 ... +85 C

95 % rel. hum. for a short time without condensation 70 % rel. hum. constant
Connection of connecting cable Connection of sensor cable Cable entry

2.5 mm2 maximum 8-pole

1 x seal insert MHD 535FX Sensor cable 1 x seal insert MHD 535SD 1 x seal insert MHD 535HD 1 x seal insert 8 - 5 mm Connecting cable
Material of enclosure Approval Dimensions Weight

glass-fiber reinforced polyester VdS EN54 75 x 138 x 56 mm incl. cable entries approx. 380 g

MHD535

T 800454

3/4

Data sheet
Danger
Prior to the implementation and commissioning of an installation, the technical documentation T800469 must be observed.

Connection overview
An overview of the connection of the various devices can be seen in the tables below.

Conductor
Shield pink blue white gray green yellow brown

Processor Unit PU
Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6 Tm 7

Earth Connecting Box ECB 535


Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6 Tm 7

Sensor cable module


Tm 0 Tm 1 Tm 2 Tm 3 Tm 4 Tm 5 Tm 6

Table 1: Overview of connection of connecting cable

Conductor
Shield Flat-ribbon cable

Processor Unit PU
Tm 0/1 Flat-ribbon connector

Earth Connecting Box ECB 535


Banana connector Flat-ribbon connector

Sensor cable module


Banana connector Flat-ribbon connector

Table 2: Overview of connection of sensor cable

Item numbers of cable module

Brief description
Earth Connecting Box ECB 535 Cable Terminator Module CTM 535 Connection and Filter Module CFM 535 Protection and Filter Module PFM 535 Sensor Separator Module SSM 535

Type
Rev G. Rev G. Rev G. Rev G.

Item number
MECB0000PEFGRST2 MCTM00R0PEFGRST2 MCFM00R0PEFGRST2 MPFM00R0PEFGRST2 MSSM00R0PEFGRST2

MHD535 T 800454 Revision: 11/05/09 vb The product specifications contained in this document are subject to change without notice. Copyright by Securiton

4/4