NIOEC SPECIFICATION FOR

CO2 FIRE EXTINGUISHING SYSTEM

SECOND EDITION JULY, 2009

THIS SPECIFICATION IS THE PROPERTY OF NATIONAL IRANIAN OIL ENGINEERING & CONSTRUCTION COMPANY. IT IS CONFIDENTIAL AND ALL RIGHTS RESERVED TO THE OWNER. NEITHER WHOLE NOR ANY PART OF THIS DOCUMENT MAY BE DISCLOSED TO ANY THIRD PARTY, REPRODUCTED, STORED IN ANY RETRIEVAL SYSTEM OR TRANSMITTED IN ANY FORM OR BY ANY MEANS WITHOUT THE PRIOR WRITTEN CONSENT OF THE NATIONAL IRANIAN OIL ENGINEERING & CONSTRUCTION COMPANY

JULY, 2009

NIOEC-SP-47-32(2)

JULY, 2009

NIOEC-SP-47-32(2)
REV. PAGE

REVISION INDEX
REV. PAGE

REV. PAGE

REV. PAGE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 X X X X X

26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75

76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100

NOTES:
1) 2) 3) 4) THIS SHEET IS A RECORD OF ALL REVISIONS TO THIS SPECIFICATION. REMARKS RELATED TO EACH REVISION SHOW A BRIEF DESCRIPTION. THESE REMARKS SHALL BE INTERPRETED IN CONJUNCTION WITH THE REVISED TEXT MARKED BY REVISION NUMBERS. WHEN APPROVED EACH REVISION SHALL BE CONSIDERED AS A PART OF THE ORIGINAL DOCUMENT. NUMBER OF PAGES EXCLUDES THIS SHEET AND THE COVER SHEET.

5 4 3 2 1 0 JULY, 2009 JULY, 2005 GH.R.OLADRASOOL M.KHEZRI M BEHROUZFAR M.FARZAM M.R.FARZAM M.A.A.SAJEDI M.A.A.SAJEDI

REV.

DATE

PREPARED

CHECKED

APPROVED

AUTHORIZED

JULY, 2009

NIOEC-SP-47-32(2) PAGE NO.

CONTENTS:

0. 1. 2.

INTRODUCTION SCOPE REFERENCES 2.1 Equivalent to IPS-E-SF-160

2 2 2 2 3 3

3. 4.

UNITS ADDENDUM TO IPS-E-SF-160

JULY, 2009 0. INTRODUCTION

NIOEC-SP-47-32(2)

To satisfy the requirements of this NIOEC standard, Iranian petroleum standard IPS-E-SF-160 (1993) with the considerations as specified herein after shall be strictly followed. Articles 1 through 4 of this document replace entirely the related articles in the referenced IPS Standard. 1. SCOPE This NIOEC Specification covers the minimum requirements for carbon dioxide systems, design and provision of piped supply of Carbon dioxide for the extinguishing of fire. 2. REFERENCES Throughout this Specification the following dated and undated standards/ codes are referred to. These referenced documents shall, to the extent specified herein, form a part of this Specification. For undated references, the latest edition of the referenced document (including any supplements and amendments) applies. For dated references, the edition cited applies. The applicability of changes in dated references that occur after the cited date shall mutually be agreed upon by NIOEC and the Vendor/Contractor. NIOEC-SP (NIOEC SPECIFICATIONS) NIOEC-SP-00-10 "NIOEC Specification for Units"

IPS (IRANIAN PETROLEUM STANDARD) IPS-E-SF-160 "CO2 Gas Fire Extinguishing Systems"

BSI (BRITISH STANDARD INSTITUTION) BS 5306 Part 4 "Fire Extinguishing Installations and Equipment on Premises; Specification for Carbon Dioxide Systems"

NFPA (NATIONAL FIRE PROTECTION ASSOCIATION) NFPA 12 "Carbon Dioxide Extinguishing Systems"

Equivalent to IPS Standards Substitute the following IPS Standards as referred to throughout IPS-E-SF-160 for the relevant NIOECs Specifications as follows: IPS Standard IPS-E-GN-100 IPS-E-SF-140 IPS-E-SF-160 IPS-E-SF-200 IPS-E-SF-220 IPS-G-SF-240 IPS-E-SF-280 Relevant NIOEC Specification NIOEC-SP-00-10 NIOEC-SP-47-30 NIOEC-SP-47-32 NIOEC-SP-47-36 NIOEC-SP-47-28 NIOEC-SP-46-16 NIOEC-SP-70-53

JULY, 2009 3. UNITS

NIOEC-SP-47-32(2)

International system of units (SI) shall be used in accordance with NIOEC-SP-00-10, unless otherwise specified.

4. ADDENDUM TO IPS-E-SF-160 This addendum revises the below listed articles of the referenced standard as follows: Article 4. DEFINITIONS AND TERMINOLOGY (Addition) Addition: Company: Means National Iranian Oil Engineering & Construction Company. Addition: Purchaser: Means National Iranian Oil Engineering and Construction Company in cases where this specification is part of direct order by NIOEC and contractor where this specification is part of contract Documents.

Article 5.4.2 (Modification) Line 2 of the Article after dot till end should be replaced with below sentence. The amount of the main supply of carbon dioxide in the system shall be at least sufficient for the largest single hazard protected or group of hazards that are to be protected simultaneously. 100% reserve cylinder shall be considered. Article 6.1.3 Areas to be protected (Addition) Following areas may be protected with CO2 total flooding systems. ALL electrical substation room (Switch Gear room and Cable Gallery) All location Electrical Room All turbine Enclosure All control room

Article 6.3.2.2 (Modification)


Q P

X = 23 . 9

JULY, 2009 Article 6.4, System Distribution (Addition)

NIOEC-SP-47-32(2)

6.4.1 Piping shall be of metallic non-combustible material having physical and chemical characteristics such that its deterioration under stress can be predicted with reability. The following materials can be used : Black or Galvanized steel pipe shall be either ASTM seamless or electric welded, Grade A or B . in system using high-pressure supply using, in and smaller pipe shall be permitted to be schedule 40. Pipe is 1 in. though 4 in. shall be a minimum of schedule 80. In system using lowpressure supply, pipe shall be a minimum of schedule 40. 6.4.2 The following provides criteria for fittings for high and low pressure systems. a) High pressure systems class 300 malleable or ductile iron fittings shall be used through 2 in. Internal Pipe Size (IPS) and forged steel fittings in all larger sizes. Flanged joints upstream of any stop valves shall be class 600. flanged joints downstream of stop valves or in systems with no stop valves shall be permitted to be class 300. b) Low - pressure systems. Class 300 malleable or ductile iron fittings shall be used through 3 in. IPS and 1000 Lb ductile iron or forged steel fittings in all larger sizes.

Article 7.2, Table 3 (Modification) Kg CO2/m instead of kg CO2/m

Article 15.2 (Modification)

10 5 0 . 8725 ( D 5 . 25 Y ) Q = L + 0 . 04319 ( D 1 . 25 Z )
2

Y =

p p
1

dp

= Ln

JULY, 2009

NIOEC-SP-47-32(2)

Article 15.3, Table 11 (Modification) The last column contents should be shifted to the right (under Z column).

Article 15.4, Table 11 (Modification)

L D 1.25

10 5 0 .8725 Y = 0 .04319 Z (Q / D 2 ) 2

Article 15.5 Table 11 (Modification)

Q 454 = = 0.165(kg / min .) / mm2 2 D 2758

L D 1 .25

152 = 1 . 075 m / mm 1 .25 141 . 3

E.O. A =

454kg / min = 458mm 2 2 0.9913(kg / min) / mm

E.O.A=Equivalent Orifice Area

JULY, 2009

NIOEC-SP-47-32(2)

Q 227 = = 0 .136 ( kg / min .) / mm 2 2 D 1673

L D
1 . 25

61 = 0 . 59 m / mm 1 . 25 103 . 4