PROTECCIONES DE BAJA Y MEDIA TENSIN


TRANSFORMADORES DE DISTRIBUCIN
1. Transformadores Trifsicos de 13,2 KV
Potencias

Corrientes B.T.

K.V.A.

Normal Sobrecarga

Protecciones B.T.
Normal

Sobrecarga

Corrientes M.T.
Normal Sobrecarga

Protecciones M.T.
Normal

Sobrecarga

1.44

2.0

10

10

0.043

0.1

7.2

10.1

10

10

0.2

0.3

10

14.4

20.2

15

20

0.4

0.6

15

21.7

30.3

25

30

0.6

0.9

20

28.9

40.4

30

40

0.9

1.2

1.5

25

36.1

50.5

40

50

1.1

1.5

1.5

30

43.3

60.6

50

60

1.3

1.8

1.5

35

50.5

70.7

60

75

1.5

2.1

37.5

54.1

75.8

60

80

1.6

2.2

45

65.0

90.9

70

80

1.9

2.7

50

72.2

101.0

75

90

2.1

3.0

75

108.3

151.6

125

150

3.2

4.5

100

144.3

202.1

150

200

4.3

6.0

150

216.5

303.1

225

300

6.4

9.0

10

200

288.7

404.1

8.6

12.0

10

15

1x400
2x225
1x500
2x250

1x400
2x200
1x500
2x225
2x300
3x200

10.7

15.0

12

20

12.8

18.0

15

20

300

250

360.8

505.2

300

433.0

606.2

400

577.4

808.3

2x300

2x350

17.1

23.9

20

25

500

721.7

1010.4

3x250

3x300

21.4

29.9

25

30

2. Transformadores Bifsicos de 13,2 KV


Potencias

Corrientes B.T.

K.V.A.

Normal Sobrecarga

1.5
3
5
10
15
25
30

6.5
13.0
21.7
43.5
65.2
108.7
130.4

9.1
18.3
30.4
60.9
91.3
152.2
182.6

Protecciones B.T.
Normal
10
15
25
50
70
120
150

Sobrecarga
10
20
40
70
100
175
200

Corrientes M.T.
Normal Sobrecarga
0.1
0.1
0.2
0.4
0.6
1.1
1.3

0.1
0.2
0.3
0.6
0.9
1.5
1.8

Protecciones M.T.
Normal

Sobrecarga

1
1
1
1
1.5
1.5
1.5

1
1
1
1
1
2
2

3. Transformadores Monofsicos de 7,62 KV (Retorno por Tierra)


Potencias

Corrientes B.T.

K.V.A.

Normal Sobrecarga

1.5
3
5
10
15
25
30

6.5
13.0
21.7
43.5
65.2
108.7
130.4

9.1
18.3
30.4
60.9
91.3
152.2
182.6

Protecciones B.T.
Normal
10
15
25
50
70
120
150

Sobrecarga
10
20
40
70
100
175
200

Corrientes M.T.
Normal Sobrecarga
0.2
0.4
0.7
1.3
2.0
3.3
3.9

0.3
0.6
0.9
1.8
2.8
4.6
5.5

Protecciones M.T.
Normal

Sobrecarga

1
1
1
1.5
3.0
4
4

1
1
1
2
3
5
7

La Sobrecarga es a un 40%

Protecciones de Bancos de Condensadores


Potencias
Corrientes M.T.
K.V.A.r. Normal Sobrecarga
300
12.8
18.0
350
15.0
21.0
400
17.1
23.9

Protecciones M.T.
Normal
Sobrecarga
15
20
20
25
20
25

CRUCE DE LNEAS ENTRE SI


VOLTAJE LNEA
SUPERIOR KV
0.22
0.38
13.2
23
66
110
154
220
500

VOLTAJE LNEA INFERIOR KV


0.22 0.38 13.2
1.50
1.50
1.58
1.64
1.89
2.15
2.41
2.80
4.44

1.50
1.58
1.64
1.89
2.15
2.41
2.80
4.44

1.66
1.71
1.97
2.22
2.48
2.87
4.52

23

66

1.77
2.02
2.28
2.54
2.93
4.58

2.28
2.54
2.79
3.18
4.83

110

154

220

2.79
3.05 3.31
3.44 3.70 4.09
5.09 5.35 5.74

E DE LNEAS ENTRE SI
VOLTAJE LNEA INFERIOR KV
500

7.38

COORDINACIN ENTRE FUSIBLE TIPO T


(CORRIENTE MXIMA DE CORTO CIRUITO EN AMPERES)
FUSIBLE
FUSIBLE LADO FUENTE
LADO CARGA 6 T 8 T 10 T 12 T 15 T 20 T 25 T 30 T
1-2-3-5H
240
500
710
920 1,200 1,500 2,000
6T
350
680
920 1,200 1,500 2,000
8T
375
800 1,200 1,500 2,000
10 T
530 1,100 1,500 2,000
12 T
680 1,280 2,000
15 T
730 1,700
20 T
990
25 T
30 T
COORDINACIN ENTRE FUSIBLE TIPO K
(CORRIENTE MXIMA DE CORTO CIRUITO EN AMPERES)
FUSIBLE
FUSIBLE LADO FUENTE
LADO CARGA 6 K 8 K 10 K 12 K 15 K 20 K 25 K 30 K
1-2-3-5 H
75 165
190
340
475
650
830 1,100
6K
190
340
475
650
830 1,100
8K
260
430
600
800 1,050
10 K
350
560
760 1,020
12 K
450
680
970
15 K
530
900
20 K
680
25 K
30 K
COORDINACIN ENTRE FUSIBLE TIPO SS
(CORRIENTE MXIMA DE CORTO CIRUITO EN AMPERES)
FUSIBLE
FUSIBLE LADO FUENTE
LADO CARGA 5 SS 7 SS 10 SS 15 SS 20 SS 25 SS 30 SS 40 SS
1 SS
130 260
400
650
830
980 1,250 1,700
1,5 SS
120 250
400
650
830
980 1,250 1,700
2 SS
110 245
400
650
830
980 1,250 1,700
3 SS
80 230
390
650
830
980 1,250 1,700
5 SS
170
380
650
830
980 1,200 1,700
7 SS
280
590
790
960 1,200 1,700
10 SS
470
700
900 1,150 1,650
15 SS
400
680 1,000 1,550

40 T
2,540
2,540
2,540
2,540
2,540
2,500
2,100
1,400

40 K
1,450
1,450
1,450
1,400
1,350
1,300
1,150
950

50 SS
2,100
2,100
2,100
2,100
2,100
2,100
2,050
2,000

20 SS
25 SS
30 SS
40 SS

370

840 1,450 1,900


550 1,300 1,800
1,000 1,600
1,000

NACIN ENTRE FUSIBLE TIPO T


XIMA DE CORTO CIRUITO EN AMPERES)
FUSIBLE LADO FUENTE
50 T
3,200
3,200
3,200
3,200
3,200
3,200
3,200
2,600
1,500

NACIN ENTRE FUSIBLE TIPO K


XIMA DE CORTO CIRUITO EN AMPERES)
FUSIBLE LADO FUENTE
50 K
1,850
1,850
1,800
1,800
1,750
1,700
1,600
1,450
1,200

Combinacin de la Capacidad del Automtico Merln Gerin


Automticos de 400 Amp.

Ir

Io

400
1.00
0.90
0.80
0.70
0.63
0.50

1.00
400
360
320
280
252
200

0.98
392
353
314
274
247
196

0.95
380
342
304
266
239
190

0.93
372
335
298
260
234
186

0.90
360
324
288
252
227
180

0.88
352
317
282
246
222
176

0.85
340
306
272
238
214
170

0.80
320
288
256
224
202
160

0.88
554
499
444
388
349
277

0.85
536
482
428
375
337
268

0.80
504
454
403
353
318
252

Automticos de 630 Amp.

Ir

Io

630
1.00
0.90
0.80
0.70
0.63
0.50

1.00
630
567
504
441
397
315

0.98
617
556
494
432
389
309

0.95
599
539
479
419
377
299

0.93
586
527
469
410
369
293

0.90
567
510
454
397
357
284

Interruptor Automatico
Regulable Legrand DPX-250
1.00
0.93
0.86
0.80
0.77
0.74
0.72
0.69
0.66
0.64

=
=
=
=
=
=
=
=
=
=

250
233
215
200
193
185
180
173
165
160

Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.
Amp.

Automtico
3
5
10
15
20
25
30
40
45
50
60
70
80
90
100

KW
Monofsico
0.7
1.1
2.2
3.3
4.4
5.5
6.6
8.8
9.9
11.0
-

KW
Trifsicos
2.1
3.5
6.9
10.4
13.9
17.3
20.8
27.7
31.2
34.6
41.6
48.5
55.4
62.4
69.3

ESTROBOS

DIAMETRO
1/4''
5/16''
3/8''
7/16''
1/2''
9/16''
5/8''
3/4''
7/8''
1''
1 1/8''
1 1/4''
1 1/3''
1 1/12

500

375

1,000

996

966

870

707

500

180

585

1,560

1,554

1,507

1,358

1,103

780

1,215

911

2,430

2,421

2,347

2,115

1,718

1,215

1,472

1,104

2,944

2,933

2,844

2,563

2,082

1,472

2,170

1,628

4,340

4,323

4,192

3,778

3,069

2,170

2,380

1,785

4,760

4,742

4,598

4,143

3,366

2,380

3,110

2,333

6,220

6,196

6,008

5,414

4,398

3,110

4,390

3,293

8,780

8,746

8,481

7,643

6,208

4,390

5,880

4,410

11,760

11,715

11,359

10,237

8,316

5,880

8,220

6,165

16,440

16,377

15,880

14,311

11,625

8,220

10,220

7,665

20,440

20,362

19,743

17,792

14,454

10,220

12,440

9,330

24,880

24,785

24,032

21,657

17,593

12,440

14,900
17,560

11,175
13,170

29,800
35,120

29,686
34,986

28,784
33,923

25,940
30,571

21,072
24,834

14,900
17,560

STROBOS

259
404
629
762
1,123
1,232
1,610
2,272
3,044
4,255
5,290
6,440
7,713
9,090

N Diametro Seccin
Peso
AWG
mm
mm
Kg/Km
5000
56.8 2533.8830 22551.558
4000
50.8 2026.8299 18038.786
3000
44.0 1520.5308 13532.725
2000
35.9 1012.2290 9008.838
1750
33.6 886.6831 7891.480
1500
31.1 759.6450 6760.840
1250
28.4 633.4707 5637.890
1000
25.4 506.7075 4509.697
900
24.1 456.1671 4059.887
800
22.7 404.7078 3601.900
750
22.0 380.1327 3383.181
700
21.3 356.3273 3171.313
600
19.7 304.8052 2712.766
500
18.0 254.4690 2264.774
400
16.1 203.5831 1811.889
350
15.0 176.7146 1572.760
300
13.9 151.7468 1350.546
250
12.7 126.6769 1127.424
4/0
11.68 107.1459
953.599
3/0
10.40
84.9487
756.043
2/0
9.27
67.4915
600.675
1/0
8.25
53.4562
475.760
1
7.35
42.4292
377.620
2
6.54
33.5927
298.975
3
5.83
26.6948
237.584
4
5.19
21.1556
188.285
5
4.62
16.7639
149.198
6
4.11
13.2670
118.077
7
3.66
10.5209
93.636
8
3.26
8.3469
74.287
9
2.91
6.6508
59.192
10
2.59
5.2685
46.890
11
2.30
4.1548
36.977
12
2.05
3.3006
29.376
13
1.83
2.6302
23.409
14
1.63
2.0867
18.572
15
1.45
1.6513
14.697
16
1.29
1.3070
11.632
17
1.15
1.0387
9.244
18
1.02
0.8171
7.272
19
0.912
0.6533
5.814
20
0.813
0.5191
4.620
21
0.724
0.4117
3.664
22
0.643
0.3247
2.890
23
0.574
0.2588
2.303
24
0.511
0.2051
1.825
25
0.455
0.1626
1.447
26
0.404
0.1282
1.141
27
0.361
0.1024
0.911
28
0.320
0.0804
0.716

Longitud
Resistencia Fusibles
Km/Kg
Km/Ohm
Ohm/Km Amperes
0.000044
0.0070
142.05769 34246.21
0.000055
0.0088
113.63065 28965.80
0.000074
0.0117
85.24588 23349.04
0.000111
0.0176
56.74884 17208.05
0.000127
0.0201
49.71033 15581.13
0.000148
0.0235
42.58816 13874.92
0.000177
0.0282
35.51442 12107.86
0.000222
0.0352
28.40766 10240.96
0.000246
0.0391
25.57421 9464.89
0.000278
0.0441
22.68923 8652.24
0.000296
0.0469
21.31147 8255.13
0.000315
0.0501
19.97686 7864.29
0.000369
0.0585
17.08837 6995.03
0.000442
0.0701
14.26636 6109.40
0.000552
0.0876
11.41353 5168.07
0.000636
0.1009
9.90719 4647.58
0.000740
0.1175
8.50742 4145.84
0.000887
0.1408
7.10192 3620.73
0.001049
0.1665
6.00695 3193.41
0.001323
0.2100
4.76250 2683.12
0.001665
0.2643
3.78379 2257.93
0.002102
0.3337
2.99693 1895.71
0.002648
0.4204
2.37872 1594.12
0.003345
0.5310
1.88332 1338.00
0.004209
0.6682
1.49660 1126.14
0.005311
0.8431
1.18605
945.89
0.006702
1.0640
0.93984
794.43
0.008469
1.3445
0.74379
666.58
0.010680
1.6954
0.58983
560.16
0.013461
2.1370
0.46795
470.89
0.016894
2.6819
0.37287
397.13
0.021327
3.3856
0.29537
333.46
0.027044
4.2932
0.23293
279.05
0.034042
5.4041
0.18504
234.81
0.042719
6.7816
0.14746
198.05
0.053845
8.5478
0.11699
166.48
0.068043
10.8018
0.09258
139.68
0.085969
13.6475
0.07327
117.21
0.108174
17.1726
0.05823
98.66
0.137505
21.8289
0.04581
82.41
0.172001
27.3050
0.03662
69.68
0.216441
34.3598
0.02910
58.64
0.272925
43.3266
0.02308
49.28
0.346018
54.9300
0.01820
41.25
0.434207
68.9300
0.01451
34.79
0.547871
86.9741
0.01150
29.22
0.691031 109.7006
0.00912
24.55
0.876511 139.1455
0.00719
20.54
1.097756 174.2680
0.00574
17.35
1.397076 221.7849
0.00451
14.48

29
30
31
32
33
34
35
36
37
38
39
40

0.287
0.254
0.226
0.203
0.180
0.160
0.142
0.127
0.114
0.102
0.089
0.079

0.0647
0.0507
0.0401
0.0324
0.0254
0.0201
0.0158
0.0127
0.0102
0.0082
0.0062
0.0049

0.576
0.451
0.357
0.288
0.226
0.179
0.141
0.113
0.091
0.073
0.055
0.044

1.736826
2.217444
2.800936
3.471587
4.415451
5.588306
7.094853
8.869776
11.008050
13.750540
18.060930
22.922708

275.7199
352.0177
444.6467
551.1120
700.9498
887.1396
1126.3030
1408.0708
1747.5203
2182.8887
2867.1599
3638.9639

0.00363
0.00284
0.00225
0.00181
0.00143
0.00113
0.00089
0.00071
0.00057
0.00046
0.00035
0.00027

12.30
10.24
8.60
7.32
6.11
5.12
4.28
3.62
3.08
2.61
2.12
1.78

TABLAS CARACTERSTICAS DE CONDUCTOR


A.W.G.

mm

mm

6
5
4
3
2
1
1/0
2/0
3/0
4/0
250 MCM
300 MCM
350 MCM
400 MCM

4.12
4.62
5.18
6.61
7.42
8.34
8.36
10.51
12.5
13.5
14.59
15.97
17.25
18.44

13.3
16.8
21.1
34.3
43.2
54.6
54.9
86.8
122.7
143.1
167.2
200.3
233.7
267.1

(*)
(**)

Kg/Km
118.0
150.0
188.0
237.0
300.0
377.0
475.0
600.0
755.0
972.0
1,149.0
1,378.0
1,609.0
1,836.0

124.0
157.5
192.7
243.0
307.5
386.0
487.0
615.0
775.0
996.0
1178.0
1412.5
1694.0
1882.0

A
95
90
110
130
150
175
200
235
270
335
350
395
435
475

Factor de potencia de distribucin en MT


Factor de potencia de distribucin en BT

A/mm
120
140
170
190
220
270
310
360
420
480
540
610
670
760
0.96
0.9

4.50
4.30
4.10
3.90
3.60
3.40
3.25
3.05
2.85
2.60
2.30
2.20
2.10
2.00

Kw
MT (*) BT (**)
2,180
56
2,050
53
2,506
65
2,961
81
3,417
94
3,986
109
4,556
125
5,353
147
6,151
168
7,631
209
7,973
218
8,998
246
9,909
271
10,820
296

ERSTICAS DE CONDUCTOR
50
C/Km
1.490
1.180
0.930
0.760
0.600
0.480
0.380
0.300
0.240
0.190
0.160
0.140
0.120
0.100

Dimetros en
pulgadas
1 1/2
2
2 1/2
3

Carga Mxima en Kg.


Flexin
Traccin
Compresin
110
500
200
680
225
385
900
450
550
1000
995

KVA
10.0
15.0
20.0
25.0
30.0
35.0
37.5
45.0
55.0
60.5
67.5
75.0
100.0
112.5
108.0
115.0
120.0
135.0
150.0
160.0
195.0
223.0
228.0
242.5
250.0
265.0
270.0
275.0
300.0
300.0
325.0
340.0
350.0
375.0

TRIFASICOS
Carga de Carga Sobrecarga
80 %
100 %
de 140 %
0.3
0.4
0.6
0.5
0.6
0.9
0.7
0.8
1.2
0.8
1.1
1.5
1.0
1.3
1.8
1.2
1.5
2.1
1.3
1.6
2.2
1.5
1.9
2.7
1.9
2.3
3.3
2.0
2.6
3.6
2.3
2.9
4.0
2.5
3.2
4.4
3.4
4.2
5.9
3.8
4.8
6.7
3.7
4.6
6.4
3.9
4.9
6.8
4.1
5.1
7.1
4.6
5.7
8.0
5.1
6.3
8.9
5.4
6.8
9.5
6.6
8.2
11.5
7.5
9.4
13.2
7.7
9.6
13.5
8.2
10.2
14.3
8.5
10.6
14.8
9.0
11.2
15.7
9.1
11.4
16.0
9.3
11.6
16.3
10.1
12.7
17.7
10.1
12.7
17.7
11.0
13.7
19.2
11.5
14.4
20.1
11.8
14.8
20.7
12.7
15.8
22.2

MONOFASICOS
Carga de Carga
80 %
100 %
1.0
1.3
1.5
1.9
2.0
2.5
2.5
3.2
3.0
3.8
3.5
4.4
3.8
4.8
4.6
5.7
5.6
7.0
6.1
7.7
6.8
8.6
7.6
9.5
10.1
12.7
11.4
14.3
11.0
13.7
11.7
14.6
12.2
15.2
13.7
17.1
15.2
19.0
16.2
20.3
19.8
24.7
22.6
28.3
23.1
28.9
24.6
30.7
25.4
31.7
26.9
33.6
27.4
34.2
27.9
34.9
30.4
38.0
30.4
38.0
33.0
41.2
34.5
43.1
35.5
44.4
38.0
47.5

400.0
425.0
445.0
450.0
452.5
475.0
520.0
550.0
730.0
825.0
828.0
955.0
1,400.0
1,050.0
1,250.0
1,300.0
1,307.5
1,500.0
1,648.0

13.5
14.4
15.0
15.2
15.3
16.1
17.6
18.6
24.7
27.9
28.0
32.3
47.3
35.5
42.3
43.9
44.2
50.7
55.7

16.9
18.0
18.8
19.0
19.1
20.1
22.0
23.2
30.8
34.9
35.0
40.4
59.2
44.4
52.8
54.9
55.3
63.4
69.6

23.7
25.1
26.3
26.6
26.8
28.1
30.8
32.5
43.2
48.8
49.0
56.5
82.8
62.1
74.0
76.9
77.4
88.7
97.5

40.6
43.1
45.1
45.6
45.9
48.2
52.7
55.8
74.0
83.7
84.0
96.9
142.0
106.5
126.8
131.8
132.6
152.1
167.1

50.7
53.9
56.4
57.1
57.4
60.2
65.9
69.7
92.5
104.6
105.0
121.1
177.5
133.1
158.5
164.8
165.8
190.2
208.9

ONOFASICOS
Sobrecarga
de 140 %
1.8
2.7
3.5
4.4
5.3
6.2
6.7
8.0
9.8
10.7
12.0
13.3
17.7
20.0
19.2
20.4
21.3
24.0
26.6
28.4
34.6
39.6
40.5
43.0
44.4
47.0
47.9
48.8
53.2
53.2
57.7
60.3
62.1
66.6

Voltaje 13.8

Sobrecarga 1.4

Coseno

71.0
75.4
79.0
79.9
80.3
84.3
92.3
97.6
129.6
146.4
147.0
169.5
248.5
186.4
221.9
230.7
232.1
266.2
292.5

0.99

Postes
8.70
10.00
11.50
13.00
15.00

Angulo
30
45
30
45
30
45
30
45
30
45

Largo del Tirante T


para enterramiento
1/10 + 0,5 m
8.46
10.36
9.87
12.09
11.37
13.43
12.93
15.84
15.00
18.38

Cateto X
4.23
7.33
4.94
8.55
5.48
9.50
6.46
11.20
7.50
13.00

Alambres

Cables

Cu
4/0
3/0
2/0
1/0
1
2
3
4
5
6
7
8

N
Hebras
7
7
7
7
7
7
7
1
1
1
1
1

Z1 =

Z2

Ohm / Km
0.189 +
0.237 +
0.300 +
0.377 +
0.476 +
0.600 +
0.755 +
0.938 +
1.100 +
1.495 +
1.870 +
2.370 +

j 0.364
j 0.370
j 0.377
j 0.385
j 0.392
j 0.400
j 0.406
j 0.417
j 0.423
j 0.432
j 0.440
j 0.445

Z0
Ohm / Km
0.336 +
0.381 +
0.447 +
0.527 +
0.522 +
0.750 +
0.905 +
1.080 +
1.320 +
1.640 +
2.020 +
2.510 +

j 1.660
j 1.667
j 1.740
j 1.682
j 1.690
j 1.696
j 1.703
j 1.714
j 1.721
j 1.730
j 1.736
j 1.745

Z0
Z1 = Z2
0 / 1 / Km
0 / 1 / Km
BASE 100 MVA
13,2 KV
0.108 + j 0.208 0.193 + j 0.951
0.136 + j 0.213 0.219 + j 0.956
0.172 + j 0.216 0.267 + j 0.960
0.216 + j 0.221 0.302 + j 0.965
0.274 + j 0.225 0.357 + j 0.970
0.345 + j 0.230 0.430 + j 0.970
0.434 + j 0.233 0.520 + j 0.977
0.540 + j 0.239 0.620 + j 0.980
0.678 + j 0.243 0.760 + j 0.988
0.868 + j 0.248 0.940 + j 0.992
1.080 + j 0.253 1.160 + j 0.994
1.360 + j 0.256 1.440 + j 1.000

Z1 = Z2
0 / 1 / Km
BASE 100 MVA
23 KV
0.036 + j 0.069
0.045 + j 0.070
0.057 + j 0.071
0.071 + j 0.073
0.090 + j 0.074
0.114 + j 0.075
0.143 + j 0.077
0.177 + j 0.079
0.233 + j 0.080
0.282 + j 0.081
0.353 + j 0.083
0.447 + j 0.084

Z0
BASE 100 MVA
23 KV
0.063 +
0.072 +
0.084 +
0.099 +
0.118 +
0.142 +
0.171 +
0.204 +
0.250 +
0.310 +
0.381 +
0.475 +

j 0.314
j 0.316
j 0.316
j 0.318
j 0.320
j 0.321
j 0.322
j 0.323
j 0.325
j 0.327
j 0.328
j 0.330

Alambres

Cables

Cu
4/0
3/0
2/0
1/0
1
2
3
4
5
6
7
8

N
Hebras
7
7
7
7
7
7
7
1
1
1
1
1

Cos = 0,8
r Cos x Cos
0.151
0.218
0.190
0.222
0.240
0.226
0.302
0.231
0.381
0.235
0.480
0.240
0.604
0.244
0.750
0.250
0.944
0.254
1.196
0.259
1.496
0.264
1.896
0.267

Total
0.369
0.412
0.466
0.533
0.616
0.720
0.848
1.000
1.198
1.455
1.760
2.163

Cos = 0,9
r Cos x Cos
0.170
0.158
0.213
0.161
0.270
0.164
0.339
0.167
0.428
0.170
0.540
0.174
0.680
0.176
0.844
0.181
1.062
0.184
1.346
0.187
1.683
0.191
2.132
0.193

Total
0.328
0.374
0.434
0.506
0.598
0.714
0.856
1.025
1.246
1.533
1.874
2.325

Cos = 1
r Cos Total
0.185
0.237
0.300
0.377
0.476
0.600
0.755
0.938
1.180
1.455
1.870
2.370

Nivel de
Tensin
B.T.

M.T.

A.T.

Voltaje Mnimos
204 V

-7.5%

Voltajes
Nominales
220 V

Voltaje Mximos
7.5%

237 V

352 V

380 V

409 V

11.3 kV

12.0 kV

12.7 kV

12.4 kV

13.2 kV

14.0 kV

13.0 kV

13.8 kV

14.6 kV

14.1 kV

15.0 kV

15.9 kV

21.6 kV

-6.0%

23.0 kV

6.0%

24.4 kV

31.0 kV

33.0 kV

35.0 kV

62.0 kV

66.0 kV

70.0 kV

103.4 kV

110.0 kV

116.6 kV

124.1 kV

132.0 kV

139.9 kV

146.3 kV

154 kV

161.7 kV

-5.0%

5.0%

209.0 kV
A.T.

327.8 kV
361.0 kV
475.0 kV

220 kV
-5.0%

345 kV
380 kV
500 kV

231.0 kV
5.0%

362.3 kV
399.0 kV
525.0 kV