Earthing and Short-circuiting Devices
EARTHING AND SHORT-CIRCUITING DEVICES

6
2

2
7
12

lI

lG

5
9
4

10
lH

Earthing and short-circuiting at the work location is a vital part of the five
safety rules. Earthing and short-circuiting ensure the protection of personnel from dangerous voltages that may be caused by induced voltages,
atmospheric surges or accidental reconnection of the supply voltage.
Isolation from supply voltages must be verified immediately before
installing portable earthing and short-circuiting devices at the installation
point.
When connecting the earthing and short-circuiting device, the earthing
cable must be connected to the earthing system first in order to discharge
any residual potential or induced voltages.
Portable earthing and short-circuiting devices according to IEC/EN
61230 (DIN VDE 0683 Part 100) are hand-hold devices used to approach
the connecting points of electrical parts of an installation for earthing and
short-circuiting purposes and to connect them to the connecting points.
These devices are applied without restricted guidance e.g. guide slots,
sockets, guide rails.
The device consists of an earthing and short-circuiting device (E+S
devices) and an earthing rod.
The purpose of earthing and short-circuiting devices is to earth and
short-circuit electrical circuits. It consists of an earthing device and a
short-circuiting device.
The earthing device connects the earthing system to a short-circuiting
device or to the equipment to be earthed (Figures a to d). It consists of
a connecting component (1) and earthing cable (4).
The short-circuiting device connects the phase conductors that have to
be short-circuited (6). It consists of connecting components (2), short-circuiting cables or short-circuiting busbars (3) and connecting pieces, if
required (5).
The short-circuiting bar is a rigid short-circuiting device.
Connecting pieces connect the short-circuiting cables to each other and
to the earthing cable or the short-circuiting bar to the earthing cable.
Connecting components connect the earthing and short-circuiting
cables or bars to the earthing system and parts of the installation either
directly or via connecting links such as cable lugs or, if required, connecting points.

1
6
11
Portable earthing and short-circuiting device
1 Connecting component to earthing
system
2 Connecting component to
conductor
3 Short-circuiting cable
4 Earthing cable
5 Connecting piece

6 Connecting point to earthing


system
7 Connecting point to conductor
8 Insulating part with length Il
9 Handguard
10 Handle with length lH
11 Sealing unit with plug-in
12 Coupling

2
3

5
4

Connecting points are points in the installation, to which coupling are


connected earthing and short-circuiting devices (e.g. cables, bars, fixed
ball points, cylinder bolts, brackets etc.). Maximum short-circuit strength
can be achieved by connecting the ball head cap of the earthing and
short-circuiting device to fixed ball points.

4
1

d
6

Two types of ball head caps are available:

Ball head cap, adjustable (4 x 90)

3
1
7

a 3-pole unit with short-circuiting


cables and earthing cable
b 3-pole unit with short-circuiting
bar and earthing cable
c Single-pole unit with shortcircuiting cables
d Single-pole unit with short-circuiting cable for earthing railways

www.dehn.de

Ball head cap, rigid

1 Connecting component to earthing


system
2 Connecting component to conductor
3 Earthing and short-circuiting cable
or earthing busbar
4 Earthing cable
5 Connecting piece
6 Phase conductor
7 Earthing system (earthing busbar, rail)

The adjustable ball head cap allows the user to position the earthing and
short-circuiting device in the most favourable operating position by
adjusting the ball head cap, even if the fixed ball points are unfavourably
located. Using angled fixed ball points is therefore mostly unnecessary.

Ball head cap, rigid

Ball head cap, adjustable (4 x 90)

91

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
An earthing rod is a hand-held insulating rod for approaching the connecting components of earthing and short-circuiting devices to parts of
electrical installations for earthing and short-circuiting purposes. It consists of an insulating part, black ring, handle and coupling for a connecting component. Earthing rods are selected according to the weight of the
respective earthing and short-circuiting devices (See specification: max.
load on operating head in kg).
The insulating part is the part of the earthing rod between the black ring
and the end of the earthing rod in the direction of the connecting component. It ensures that the user maintains a safe distance and provides sufficient insulation. The insulating part lI must have a minimum length of
500 mm.

Remark:
In the event of a short-circuit, the short-circuit current will flow through
the short-circuiting device. However, this is different for earthing devices
as they do not conduct short-circuit currents and can therefore be rated
for lower values.
Cable cross section:
For short-circuiting cables of our three-pole earthing and short-circuiting
devices with cross sections of 50 mm2 and higher, the cross section of
the earthing cable can be reduced according to the following table.
Cable cross section: Short-circuiting cable

A complete device for earthing and short-circuiting device according to


EN/IEC 61230 (DIN VDE 0683 Part 100) includes e.g.

4 Earthing rod
Earthing and short-circuiting devices as well as the fixed ball and
earthing points must be rated to withstand the short-circuit current
conditions expected on site.
The required cable cross section depends on the maximum short-circuit
current (Ik in A) and the maximum short-circuit time (Tk in s).

50
30

10

42.0 kA
33.5 kA
26.5 kA
19.5 kA

25 mm2

mm2

35 mm2

95 mm2

35 mm2

mm2

50 mm2

150 mm2

50 mm2

These earthing and short-circuiting devices with reduced earthing cable


cross sections can be used for all types of installations with compensated systems (no solidly earthed systems, i.e. with impedance neutral
earthing). For installations with solid earthing, earthing and short-circuiting cables must have equal cross sections (available on request).

Initial cable temperature

14.0 kA
10.0 kA

4.5 kA

A = 5.07 Ik" Tk

0.05

0.1

0.3

0.5

for Tk v 0.5 s

where
A

Cable cross section in mm2

Ik" Maximum initial short-circuit alternating current in kA


according to DIN VDE 0102
Tk

0.03

20 C

Final cable temperature 250 C

A=
1
A = 50 mm2
A = 120 m
m2
9
A = 5 mm2
70
A = mm2
5
A = 0 mm2
35
A = mm2
25
mm2
A=
16
mm2

1
0.01

50 mm2

Current carrying capacity of copper short-circuiting cables for use in a.c. and three-phase installations

7.0 kA
5

35 mm2

120

3 Fixed earthing point

Ik

25 mm2

mm2

70

2 Single-pole or three-pole earthing and short-circuiting device or shortcircuiting bar

kA
100

25 mm2
35

1 Fixed point / Fixed ball point

Earthing cable

Short-circuit time in s

10 s

Tk
kA
100

Ik

50
30

Current carrying capacity of copper short-circuiting cables for use in d.c. installations
66.9 kA
49.6 kA

Initial cable temperature

35.6 kA
24.8 kA
17.5 kA

10

A=
9
A = 5 mm2
70
A = mm2
50
A = mm2
35
A = mm2
25
mm2
A=
16
mm2

11.2 kA

5
3

1
0.01

A = 5.07 Ik" Tk

0.05

0.1

0.3

0.5

for Tk v 0.08 s

where
A

Cable cross section in mm2

Ik" Maximum initial short-circuit alternating current in kA


according to DIN VDE 0102
Tk

0.03

20 C

Final cable temperature 250 C

Short-circuit time in s

10 s

Tk

92

www.dehn.de

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
Earthing and Short-circuiting Devices
EARTHING AND SHORT-CIRCUITING DEVICES
The current carrying capacity of the short-circuiting cable and the shortcircuiting bar depends on the material, the cross section (A) and the shortcircuit time (Tk).
Calculations were based on the most critical case, i.e. an off-generator
short circuit ( = 1) and are maximum d.c. component ( = 1.8) with Ik
being the maximum initial short-circuit current, which, according to DIN
VDE 0102, is equal to the permanent short-circuit current, Ik and the
breaking current Ia:

The diagrams or the table help to determine the required cable or busbar
cross sections of short-circuiting devices according to the short-circuit current and the short-circuit time for an installation.

Ik" = Ik = Ia

kA
100

Ik

50
30

Current carrying capacity of copper short-circuiting cables for use on overhead contact lines of electrical railways
66.9 kA
49.6 kA
35.6 kA

Initial cable temperature

24.8 kA

Final cable temperature 400 C

17.5 kA
10

A=
9
A = 5 mm2
70
A = mm2
50
A = mm2
35
A = mm2
25
mm2
A=
16
mm2

11.2 kA

5
3

1
0.01

A = 4.1 Ik" Tk

0.05

0.1

0.3

0.5

for Tk v 0.12 s

where
A

Cable cross section in mm2

Ik" Maximum initial short-circuit alternating current in kA


according to DIN VDE 0102
Tk

0.03

20 C

Short-circuit time in s

10 s

Tk
kA
1000

Ik

Current carrying capacity of E-Cu F20 short-circuiting busbars

500

Initial cable temperature


300

A = 5.54 Ik" Tk

100

A = 1000 mm2
A = 800 mm2

50
30

A = 600 mm2
A = 500 mm22
A = 400 mm2
A = 300 mm
A = 200 mm2

10
0.1

20 C

Final cable temperature 250 C

0.3

0.5

for Tk v 0.2 s

where
A

Cable cross section in mm2

Ik" Maximum initial short-circuit alternating current in kA


according to DIN VDE 0102
Tk

Short-circuit time in s

10s

Tk
kA
1000

Ik

Current carrying capacity of E-AlMgSi 0.5 F17 short-circuiting busbars

500

Initial cable temperature


300

20 C

Final cable temperature 250 C


A = 8.79 Ik" Tk

100

for Tk v 0.2 s

where

50

A = 1000 mm2
A = 800 mm2
A = 600 mm2
A = 500 mm2
A = 400 mm2
A = 300 mm2

30

A = 200 mm2
10
0.1

0.3

0.5

Cable cross section in mm2

Ik" Maximum initial short-circuit alternating current in kA


according to DIN VDE 0102
Tk

Short-circuit time in s

10s

Tk

www.dehn.de

93

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
Calculation example:

Table:

Known:

Mains breaking capacity Sa


Short-circuit time Tk

Cable cross section of the earthing and short-circuiting device depending


on the maximum short-circuit Ik and maximum short-circuit time Tk.

Unknown:

Required cable or bar cross section A.

The calculation is based on an off-generator short-circuit.


Three-phase current

Single-phase a.c. current

Sa
Ik" = Ik = Ia =
3 UN
Ik" = Ik = Ia =

Sa

UN

Ik, the required cable or bar cross section can now be calculated with the
value of the above equation or can be taken from the diagrams. The permissible short-circuit current of an earthing and short-circuting device
expressed by indicating the cross-section of the short-circuiting cables or
bars.
Notes:
Earthing and short-circuiting devices can only be loaded once with
the permissible short-circuit currents depending on the short-circuit
time.

Cross section of the


copper
cable

Max. permissible short-circuit current Ik


at a duration of
10 s

5s

2s

1s

f 0.5 s

mm2

1 000 A

1 400 A

2 200 A

3 200 A

4 500 A

25 mm2

1 600 A

2 200 A

3 500 A

4 900 A

7 000 A

mm2

2 200 A

3 100 A

4 900 A

6 900 A

10 000 A

50 mm2

3 100 A

4 400 A

7 000 A

9 900 A

14 000 A

mm2

4 400 A

6 200 A

9 800 A 13 800 A

19 500 A

95 mm2

5 900 A

8 400 A

13 200 A 18 700 A

26 500 A

mm2

7 500 A

10 600 A

16 700 A 23 700 A

33 500 A

150 mm2

9 400 A

13 200 A

20 900 A 29 600 A

42 000 A

16
35
70
120

our
catalogue
data

Short-circuiting cables of multi-pole earthing and short-circuiting


devices must have equal cross sections.
Cable lengths of earthing and short-circuiting devices should be as
short as possible, as the cables move violently during a short-circuit.
They should be at least 120% of the distance between two termination points.
When connecting earthing and short-circuiting devices in parallel with
cables for achieving certain total cable cross sections, the following
conditions must be fulfilled:
1. Identical cable lengths and cross sections,
2. Identical connection parts and termination points,
3. Installing the devices directly next to each other, with parallel
arrangement of cables,
4. The loading capacity per lead must be reduced to 75% of the
loading capacity of the cable cross-section.
Remark:
If it is ensured that earthing and short-circuiting devices connected in
parallel are loaded with short-circuit currents only once (no interruption of the short circuit), the devices may be exposed to the full load.
Generally, this applies to installations for nominal voltages above
110 kV.

94

www.dehn.de

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

www.dehn.de

Earthing Rods

Installation Devices
Storage Devices

Selection Guide

Components

Page

Fixed Points

96

Three-pole Earthing and Short-circuiting Devices

104

Single-pole Earthing and Short-circuiting Devices

114

Cables

122

Connecting Elements

124

Earthing Rods

134

Installation Devices

140

Storage Devices

141

95

Three-pole
Devices

Fixed Points

Single-pole
Devices

Fixed Phase and Earthing Points


Fixed ball points, straight and
angled, ball 20 or 25 mm

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100) and DIN 48088 Part 1

Suitable for fixing cable lugs or


connecting busbars according to
DIN 43673 Part 1
Self-locking nut
Formed (not cut) M12 or M16 female
thread
M12 or M16 threaded bolt

Technical Data
Fixed point

E-Cu/gal Sn

Threaded bolt

StSt A2-70

Hexagon nut

DIN 985-M12-8 / gal Zn;


DIN 985-M16-8 / gal Zn

Tightening torque

M12: 80 Nm;
M16: 150 Nm

Straight fixed ball point installed on a busbar.

Type

Fixed ball
point Dimensions

Width
A/F

Max. cable Max. short-circuit


cross section current Ik 1 s

Part
No.

A Straight, with threaded Bolt and Nut


KFP 20 M12 35 SSM
KFP 20 M16 45 SSM
KFP 25 M12 25 SSM
KFP 25 M12 45 SSM
KFP 25 M16 45 SSM

20 mm
20 mm
25 mm
25 mm
25 mm

M12 x 35 mm
M16 x 45 mm
M12 x 25 mm
M12 x 45 mm
M16 x 45 mm

24 mm
24 mm
27 mm
27 mm
27 mm

120 mm2
120 mm2
150 mm2
150 mm2
150 mm2

23.7 kA
23.7 kA
29.6 kA
29.6 kA
29.6 kA

754 235
754 645
755 225
755 245
755 645

754 235
0,18
754 645
0,29
755 225
0,27
755 245
0,28
755 645
0,32
754 200
0,13
754 600
0,12
755 200
0,22
755 600
0,2020 M12 35 SSM
KFP
706 point
300 20 mm, M12x35 mm
ball
0,13
235
756 20
300M16 45 SSM
KFP
0,21point 20 mm, M16x45 mm
ball
645
KFP 25 M12 25 SSM
ball point 25 mm, M12x25 mm
225
KFP 25 M12 45 SSM
ball point 25 mm, M12x45 mm
245
KFP 25 M16 45 SSM
ball point 20 mm, M16x45 mm
645
KFP 20 M12
ball point 20 mm, M12
200
KFP 20 M16
ball point 20 mm, M16
600
KFP 25 M12
ball point 25 mm, M12
200
KFP 25 M16
ball point 25 mm, M16
600
KFP 20 S AL 12
ball point 20 mm, angled, with terminal lug
300
KFP 25 S AL 12
ball point 25 mm, angled, with terminal lug
300

B Straight, with female Thread


KFP 20 M12
KFP 20 M16
KFP 25 M12
KFP 25 M16

20 mm
20 mm
25 mm
25 mm

M12
M16
M12
M16

24 mm
24 mm
27 mm
27 mm

120 mm2
120 mm2
150 mm2
150 mm2

23.7 kA
23.7 kA
29.6 kA
29.6 kA

754 200
754 600
755 200
755 600

50 mm2
95 mm2

9.9 kA
18.7 kA

706 300
756 300

C Angled, with Terminal Lug


KFP 20 S AL 12
KFP 25 S AL 12

20 mm
25 mm

45 x 30 x 9 mm
50 x 30 x 9 mm

Other threaded bolt lengths are available on request.

96

www.dehn.de

1018
1018
1018
1018
1018
1018
1018
1018
1018
Fixed
1018
754
1018
Fixed
754
Fixed
755
Fixed
755
Fixed
755
Fixed
754
Fixed
754
Fixed
755
Fixed
755
Fixed
706
Fixed
756

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100) and DIN 48088 Part 1

Earthing Rods

Installation Devices
Storage Devices

Fixed Phase and Earthing Points


Fixed ball points, angled,
ball 20 or 25 mm

Suitable for fixing cable lugs or


connecting busbars according to
DIN 43673 Part 1
Self-locking nut
Formed (not cut) M12 or M16 female
thread
M12 or M16 threaded bolt

Technical Data
Fixed point

E-Cu/gal Sn

Threaded bolt

StSt A2-70

Hexagon nut

DIN 985-M12-8 / gal Zn;


DIN 985-M16-8 / gal Zn

Tightening torque

M12: 80 Nm;
M16: 150 Nm

Angled fixed ball point.

706 235
0,22
706 645
0,27
756 245
0,43
756 645
0,47
706 200
0,17
706 600
0,16
756 200
0,36
756 600
0,36
707 235
0,26
707 645
0,30
757 245
0,45
757 645
0,49
707 200
0,20
707 600
0,1920 W45 M12 35SSM
KFP
757 point
200 20 mm, 45, M12x35 mm
ball
0,40
235
757 20
600W45 M16 45SSM
KFP
0,37point 20 mm, 45, M16x45 mm
ball
645
KFP 25 W45 M12 45SSM
ball point 25 mm, 45, M12x45 mm
245
KFP 25 W45 M16 45SSM
ball point 25 mm, 45, M16x45 mm
645
KFP 20 W45 M12
ball point 20 mm, 45, M12
200
KFP 20 W45 M16
ball point 20 mm, 45, M16
600
KFP 25 W45 M12
ball point 25 mm, 45, M12
200
KFP 25 W45 M16
ball point 25 mm, 45, M16
600
KFP 20 W90 M12 35SSM
ball point 20 mm, 90, M12x35 mm
235
KFP 20 W90 M16 45SSM
ball point 20 mm, 90, M16x45 mm
645
KFP 25 W90 M12 45SSM
ball point 25 mm, 90, M12x45 mm
245
KFP 25 W90 M16 45SSM
ball point 25 mm, 90, M16x45 mm
645
KFP 20 W90 M12
ball point 20 mm, 90, M12
200
KFP 20 W90 M16
ball point 20 mm, 90, M16
600
KFP 25 W90 M12
ball point 25 mm, 90, M12
200
KFP 25 W90 M16
ball point 25 mm, 90, M16
600

1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
Fixed
1018
706
1 ST
1018
Fixed
1 ST
706
Fixed
756
Fixed
756
Fixed
706
Fixed
706
Fixed
756
Fixed
756

Type

Fixed ball
point Dimensions

Width Max. cable Max. short-circuit


A/F cross section current Ik 1 s

Part
No.

A Angled (45), with threaded Bolt and Nut


KFP 20 W45 M12 35SSM
KFP 20 W45 M16 45SSM
KFP 25 W45 M12 45SSM
KFP 25 W45 M16 45SSM

20 mm
20 mm
25 mm
25 mm

M12 x 35 mm
M16 x 45 mm
M12 x 45 mm
M16 x 45 mm

24 mm
24 mm
27 mm
27 mm

70 mm2
70 mm2
95 mm2
95 mm2

13.8 kA
13.8 kA
18.7 kA
18.7 kA

706 235
706 645
756 245
756 645

27 mm

95 mm2

18.7 kA

756 600

24 mm
24 mm
27 mm
27 mm

70 mm2
70 mm2
95 mm2
95 mm2

13.8 kA
13.8 kA
18.7 kA
18.7 kA

707 235
707 645
757 245
757 645

24 mm
24 mm
27 mm
27 mm

70 mm2
70 mm2
95 mm2
95 mm2

13.8 kA
13.8 kA
18.7 kA
18.7 kA

707 200
707 600
757 200
757 600

Fixed
707
Fixed
707
Fixed
757
Fixed
757

B Angled (45), with female Thread

Fixed
707
Fixed
707
Fixed
757
Fixed
757

KFP 20 W45 M12

mm

M16

C Angled (90), with threaded Bolt and Nut


KFP 20 W90 M12 35SSM
KFP 20 W90 M16 45SSM
KFP 25 W90 M12 45SSM
KFP 25 W90 M16 45SSM

20 mm
20 mm
25 mm
25 mm

M12 x 35 mm
M16 x 45 mm
M12 x 45 mm
M16 x 45 mm

D Angled (90), with female Thread


KFP 20 W90 M12
KFP 20 W90 M16
KFP 25 W90 M12
KFP 25 W90 M16

20 mm
20 mm
25 mm
25 mm

M12
M16
M12
M16

Other threaded bolt lengths are available on request.

www.dehn.de

97

Fixed Points

Three-pole
Devices

Single-pole
Devices

Fixed Phase and Earthing Points


Fixed ball points, for round
conductors, ball 20 or 25 mm

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

For round copper conductors


Installation bolts made of stainless
steel

Fixed ball point attached to the round copper conductor of a switchgear


installation.
Technical Data

Type

Ball pin

E-Cu/gal Sn

Round conductor components

Cu alloy/gal Sn

Installation bolts

Hexagon socket-head bolts, StSt

Fixed ball
point

For round
conductor d

Max. short-circuit
current Ik 1 s

10 mm
12 mm
14 mm
16 mm
18 mm
20 mm
10 mm
12 mm
14 mm
16 mm
18 mm
20 mm

9.9 kA
9.9 kA
9.9 kA
9.9 kA
9.9 kA
9.9 kA
18.7 kA
18.7 kA
18.7 kA
18.7 kA
18.7 kA
18.7 kA

Part
No.

A Round Conductor 10-20 mm


KFP 20 RL 10
KFP 20 RL 12
KFP 20 RL 14
KFP 20 RL 16
KFP 20 RL 18
KFP 20 RL 20
KFP 25 RL 10
KFP 25 RL 12
KFP 25 RL 14
KFP 25 RL 16
KFP 25 RL 18
KFP 25 RL 20

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm
25 mm
25 mm
25 mm
25 mm
25 mm
25 mm

720 010
720 012
720 014
720 016
720 018
720 020
725 010
725 012
725 014
725 016
725 018
725 020

720 010
0,31
720 012
0,35
720 014
0,33
720 016
0,31
720 018
0,30
720 020
0,28
725 010
0,41
725 012
0,40
725 014
KFP
0,3920 RL 10
ball
725 point
016 20 mm, round conductor 10 mm
010
0,37
KFP
725 20
018RL 12
ball
0,35point 20 mm, round conductor 12 mm
012
725 020
KFP
0,3220 RL 14
ball point 20 mm, round conductor 14 mm
014
KFP 20 RL 16
ball point 20 mm, round conductor 16 mm
016
KFP 20 RL 18
ball point 20 mm, round conductor 18 mm
018
KFP 20 RL 20
ball point 20 mm, round conductor 20 mm
020
KFP 25 RL 10
ball point 25 mm, round conductor 10 mm
010
KFP 25 RL 12
ball point 25 mm, round conductor 12 mm
012
KFP 25 RL 14
ball point 25 mm, round conductor 14 mm
014
KFP 25 RL 16
ball point 25 mm, round conductor 16 mm
016
KFP 25 RL 18
ball point 25 mm, round conductor 18 mm
018
KFP 25 RL 20
ball point 25 mm, round conductor 20 mm
020

Fixed ball points for round conductors with other diameters are available on request.
Note: Please specify the conductor diameter d when placing your order!

98

www.dehn.de

1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
1 ST
1018
Fixed
1 ST
720
1018
1 ST
Fixed
1018
720
1 ST
1018
1Fixed
ST
720
Fixed
720
Fixed
720
Fixed
720
Fixed
725
Fixed
725
Fixed
725
Fixed
725
Fixed
725
Fixed
725

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Fixed Earthing Points


Grooved ring 16 mm

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100) and DIN 48088 Part 2

For connecting earth connectors or


earth connecting plates according
to DIN 48088 Part 2
Self-locking nut
Formed (not cut) M12 or M16 female
thread
M12 or M16 threaded bolt

Fixed earthing point with grooved ring and earth connector.

Technical Data
Fixed point

Brass (CuNi2Si) / gal Sn

Threaded bolt

StSt A2-70

Hexagon nut

DIN 985-M12-8 / gal Zn;


DIN 985-M16-8 / gal Zn

Tightening torque

M12: 80 Nm;
M16: 150 Nm
16 mm

Type

Dimensions

Width
A/F

Max. cable Max. short-circuit


cross section
current Ik 1 s

Part
No.

A Grooved Ring 16 mm, threaded Bolt and Nut


790 251
0,25
790 261
0,28
790 250
0,19
790 260
0,18

1 ST

1 ST

1 ST

1 ST

EFP 16 RN M12 35 SSM


earthing point, grooved ring m12x35 mm
251
EFP 16 RN M16 45 SSM
earthing point, grooved ring M16x45 mm
261
EFP 16 RN M12
earthing point, grooved ring M12
250
EFP 16 RN M16
earthing point, grooved ring M16
260

Fixed
790

EFP 16 RN M12 35 SSM


EFP 16 RN M16 45 SSM

M12 x 35 mm
M16 x 45 mm

22 mm
22 mm

150 mm2
150 mm2

29.6 *) kA
29.6 *) kA

790 251
790 261
16 mm

Fixed
790
Fixed
790
Fixed
790

B Grooved Ring 16 mm, with female Thread


EFP 16 RN M12
EFP 16 RN M16

M12
M16

22 mm
22 mm

150 mm2
150 mm2

29.6 *) kA
29.6 *) kA

790 250
790 260

*) For earthing and short-circuiting devices with cable lengths v 2.5 m: 18.7 kA / 1 s

www.dehn.de

99

Fixed Points

Three-pole
Devices

Single-pole
Devices

Fixed Earthing Points


Connectors

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100) and DIN 48088 Part 5

For welding or bolting of earth connectors with wing nut or wing bolt
Connectors with M12 or M16 threaded
bolt
M12 or M16 female thread

705 501
0,15
755 501
0,30
336 020
0,12
336 025
0,25
705 504
0,18
705 500
0,12
750 500
0,25
705 510
0,24

Earth connector with M12 threaded bolt for connection to an earthed


part of the installation.
Type

Dimensions

Width
A/F

Material

Part
No.

St/gal Zn
St/gal Zn

705 501
755 501

St/gal Zn
St/gal Zn

336 020
336 025

Cu alloy/gal Sn

705 504

AS SCHW M12 25
Welding type connector, M12x25 mm
501
AS SCHW M16 30
Welding type connector, M16x30 mm
501
AS SCHW M12
Welding type connector, M12
020
AS SCHW M16
Welding type connector, M16
025
AS SCHR M12 M12 40
Bolted type connector, M12/M12x40 mm
504
AS SCHR M12 55
Bolted type connector, M12x55 mm
500
AS SCHR M16 65
Bolted type connector, M16x65 mm
500
AS SCHR M16 55 M12
Bolted type connector, M12x20/M16x55 mm
510

A Welding-type Connector, with threaded Bolt


AS SCHW M12 25
AS SCHW M16 30

M12 x 25 mm
M16 x 30 mm

B Welding-type Connector, with female Thread


AS SCHW M12
AS SCHW M16

M12
M16

C Bolted-type Connector, with female Thread


AS SCHR M12 M12 40

M12 / M12 x 40 mm

27 mm

D Bolted-type Connector, with threaded Bolt and separate hexagon Nut


AS SCHR M12 55
AS SCHR M16 65

M12 x 55 mm
M16 x 65 mm

32 mm
41 mm

StSt / Cu alloy/gal Sn / St/tZn


StSt / Cu alloy/gal Sn / St/tZn

705 500
750 500

E Bolted-type Connector, for converting from M12 to M16 threaded Bolt


AS SCHR M16 55 M12 M12 x 20 / M16 x 55 mm

100

41 mm

StSt / Cu alloy/gal Sn

705 510

www.dehn.de

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

705
755
336
336
705
705
750
705

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Earth Connecting Plates

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
Fixed points according to EN/IEC 61230 (DIN VDE 0683 Part 100) and
DIN 48088 Part 1

For indoor and outdoor installations


Connecting plate with high short-circuit
carrying capacity
Allows for individual connection of the
short-circuiting cables
For fixed ball points 20, 25 mm or
grooved ring bolt 16 mm

Earth connecting plate with fixed ball points and ball head cap with
insulated handle.
Technical Data
Fixed point

Brass (CuNi2Si) / gal Sn

Threaded bolt

StSt A2-70

Hexagon nut

DIN 985-M12-8 / gal Zn;


DIN 985-M16-8 / gal Zn

Type
728 300
1,21
728 500
1,82
728 520
1,55

1 ST

1 ST

1 ST

EAP 3 20 KKH
connection plate, 20 mm, ball head cap
300
EAP 3 25 KKH
connection plate, 25 mm, ball head cap
500
EAP 3 16 RN
connection plate, 16 mm, grooved ring
520

Earth
728

Fixed
point

Max. cable
cross section

Max. short-circuit
current Ik 1 s

Part
No.

A With Ball Head Cap and 3 Fixed Ball Points

Earth
728
Earth
728

EAP 3 20 KKH
EAP 3 25 KKH

20 mm
25 mm

120 mm2
150 mm2

23.7 kA
29.6 kA

728 300
728 500

B With Earth Connector and 3 Fixed Earthing Points, with grooved Ring
EAP 3 16 RN

16 mm

95 mm2

18.7 kA

728 520

Other types are available on request.

www.dehn.de

101

Fixed Points

Three-pole
Devices

Single-pole
Devices

Fixed Phase Points

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
Clamp according to DIN 48088 Part 3

Coupling aid (clamp) for phase screw


clamps
For high-voltage installations up to
220 kV
Other types of clamps, e.g. for twin
conductors or with greater clamp
widths available on request

Fixed phase point installed on an overhead line conductor.

Technical Data
Clamp

Al or Cu alloy

Screws

StSt

Type

For conductor
d

Clamp width
b

Max. short-circuit
current Ik 1 s

Part
No.

A Fixed Phase Points for Al and Al/St Cables


PFP 11 33 AL 60 82
PFP 34 48 AL 60 98
PFP 49 70 AL 60 126

11.0 ... 33 mm
33.1 ... 48 mm
48.1 ... 70 mm

82 mm
98 mm
126 mm

23.7 kA
23.7 kA
23.7 kA

731 011
731 013
731 015

23.7 kA
23.7 kA

731 027
731 037

731 011
0,62
731 013
0,85
731 015
1,00
731 027
1,97
731 037
2,66

1 ST

1 ST

1 ST

1 ST

1 ST

PFP 11 33 AL 60 82
phase point, 11.0 ... 33 mm, Al
011
PFP 34 48 AL 60 98
phase point, 33.1 ... 48 mm, Al
013
PFP 49 70 AL 60 126
phase point, 48.1 ... 70 mm, Al
015
PFP 11 33 CU 60 82
phase point, 11.0 ... 33 mm, Cu
027
PFP 34 48 CU 60 98
phase point, 33.1 ... 48 mm, Cu
037

Fixed
731

B Fixed Phase Points for round Copper Conductors


b

PFP 11 33 CU 60 82
PFP 34 48 CU 60 98

11.0 ... 33 mm
33.1 ... 48 mm

82 mm
98 mm

Note: Please indicate the conductor diameter d when placing your order.

102

www.dehn.de

Fixed
731
Fixed
731
Fixed
731
Fixed
731

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

Earthing Rods

Installation Devices
Storage Devices

Quick Overview

EN/IEC 61230 (DIN VDE 0683 Part 100)

Components

Type

Page

Phase connecting elements

Earthing and Short-Circuiting Devices


Ball Head Cap, rigid, hexagon Shaft

Ball Head Cap, rigid, T pin Shaft

Three-pole

104

Single-pole

114

Three-pole

105

Single-pole

115

Three-pole

106

Single-pole

116

Three-pole

107

Single-pole

117

Earthing and Short-Circuiting Devices


Ball Head Cap, adjustable (4 x 90), hexagon Shaft

Ball Head Cap, adjustable (4 x 90), T pin Shaft

Earthing and Short-Circuiting Devices


Universal Clamp, Clamping Range 20 / 25 mm, hexagon Shaft

Universal Clamp, Clamping Range 20 / 25 mm, T pin Shaft

Three-pole

108

Single-pole

118

Three-pole

109

Single-pole

119

Earthing and Short-Circuiting Devices


Universal Clamp, Clamping Range 25 / 30 mm, hexagon Shaft

Universal Clamp, Clamping Range 25 / 30 mm, T pin Shaft

www.dehn.de

Three-pole

110

Single-pole

120

Three-pole

111

Single-pole

121

103

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Ball head cap, rigid, hexagon shaft EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

Phase connecting elements

Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

KKH 20 SK
KKH 25 SK

EAS EK FM 12

EAS EK FS 12

EAB RN 16 FS

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 618
735 618
750 350
770 350
794 350
711 350

725 317
735 317
750 317
770 317
794 317
711 317

725 358
735 358
750 358
770 358
794 358
711 358

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 350
712 350
715 350

795 317
712 317
715 317

795 358
712 358
715 358

c = 600 mm

725 618
3,25
735 618
3,76
750 350
3,97
770 350
4,63
794 350
6,04
711 350
6,82
795 350
6,85
712 350
7,72
715 350
8,25
725 317
3,26
735 317
3,75
750 317
725
618
3,97
770 317
735
618
4,63
794 317
750
350
6,10
711 317
770
350
6,85
795 317
794
350
6,86
712 317
711
350
7,75
715 317
795
350
8,25
725 358
712
350
3,66
735 358
715
350
4,16
750 358
725
317
4,38
770 358
735
317
5,03
794 358
750
317
6,46
711 358
770
317
7,25
795 358
794
317
7,27
712 358
711
317
8,13
715 358
795
317
8,70
725 362
712
317
3,21
735 362
715
317
3,70
750 362
725
358
3,93
770 362
735
358
4,63
794 362
750
358
6,00
711 362
770
358
6,82
795 362
794
358
6,81
712 362
711
358
7,72
715 362
795
358
8,20
725 363
712
358
3,27
735 363
715
358
3,77
750 363
725
362
4,00
770 363
735
362
4,63
794 363
750
362
6,10
711 363
770
362
6,85
795 363
794
362
6,88
712 363
711
362
7,72
715 363
795
362
8,30
725 360
712
362
3,58
735 360
715
362
4,06
750 360
725
363
4,30
770 360
735
363
4,90
794 360
750
363
6,36
711 360
770
363
7,10
795 360
794
363
7,17
712 360
711
363
8,00
715 360
795
363
8,60
725 619
712
363
3,47
735 619
715
363
3,97
750 356
725
360
4,20
770 356
735
360
4,89
794 356
750
360
6,27
711 356
770
360
7,07
795 356
794
360
7,34
712 356
711
360
8,20
715 356
795
360
8,75
725 357
712
360
3,60
735 357
715
360
4,10
750 357
725
619
4,30
770 357
735
619
4,89
794 357
750
356
6,40
711 357
770
356
7,12
795 357
794
356
7,46
712 357
711
356
8,30
715 357
795
356
8,85
725 359
712
356
3,67
735 359
715
356
4,05
750 359
725
357
4,40
770 359
735
357
4,99
794 359
750
357
6,47
711 359
770
357
7,22
795 359
794
357
7,40
712 359
711
357
8,20
715 359
795
357
8,80
712 357
715 357
725 359
735 359
750 359
770 359
794 359
711 359
795 359
712 359

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s
d = 1800 mm

EAS EK FM 16

EAS EK FS 16

EFK FL30 SKN

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 362
735 362
750 362
770 362
794 362
711 362

725 363
735 363
750 363
770 363
794 363
711 363

725 360
735 360
750 360
770 360
794 360
711 360

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 362
712 362
715 362

795 363
712 363
715 363

795 360
712 360
715 360

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

UEK 25 FS
UEK 30 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 619
735 619
750 356
770 356
794 356
711 356

725 357
735 357
750 357
770 357
794 357
711 357

725 359
735 359
750 359
770 359
794 359
711 359

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 356
712 356
715 356

795 357
712 357
715 357

795 359
712 359
715 359

715 359

Other cable lengths as well as types with unreduced cross sections of earthing cables, other earth clamps
and earth connection units are available on request. Earthing rod is not included in delivery.
104

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points
725 620
3,28
735 620
3,78
750 351
3,91
770 351
4,63
794 351
6,08
711 351
6,82
795 351
6,90
712 351
7,72
715 351
8,30
725 365
3,30
735 365
3,80
750 365
725
3,91620
770 365
735
4,63620
794 365
750
6,09351
711 365
770
6,85351
795 365
794
6,90351
712 365
711
7,75351
715 365
795
8,30351
725 372
712
3,24351
735 372
715
3,74351
750 372
725
4,00365
770 372
735
4,63365
794 372
750
6,04365
711 372
770
6,82365
795 372
794
6,85365
712 372
711
7,72365
715 372
795
8,30365
725 373
712
3,30365
735 373
715
3,80365
750 373
725
4,02372
770 373
735
4,63372
794 373
750
6,10372
711 373
770
6,85372
795 373
794
6,92372
712 373
711
7,72372
715 373
795
8,31372
725 368
712
3,70372
735 368
715
4,19372
750 368
725
4,41373
770 368
735
5,03373
794 368
750
6,50373
711 368
770
7,25373
795 368
794
7,30373
712 368
711
8,13373
715 368
795
8,70373
725 621
712
3,50373
735 621
715
4,02373
750 366
725
4,22368
770 366
735
4,89368
794 366
750
6,30368
711 366
770
7,07368
795 366
794
7,38368
712 366
711
7,32368
715 366
795
8,80368
725 367
712
3,62368
735 367
715
4,12368
750 367
725
4,35621
770 367
735
4,89621
794 367
750
6,52366
711 367
770
7,12366
795 367
794
7,50366
712 367
711
7,37366
715 367
795
8,90366
725 370
712
3,60366
735 370
715
4,10366
750 370
725
4,31367
770 370
735
4,90367
794 370
750
6,38367
711 370
770
7,10367
795 370
794
7,20367
712 370
711
7,35367
715 370
795
8,60367
725 369
712
3,70367
735 369
715
4,20367
750 369
725
4,45370
770 369
735
4,99370
794 369
750
6,50370
711 369
770
7,22370
795 369
794
7,44370
712 369
711
7,35370
715 369
795
8,85370

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

SAFETY EQUIPMENT
Three-pole Earthing and Short-Circuiting Devices
Ball head cap, rigid, T pin shaft
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

Earth connecting elements

Phase connecting elements

EAS EK FM 12

EAS EK FS 12

EAB RN 16 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 620
735 620
750 351
770 351
794 351
711 351

725 365
735 365
750 365
770 365
794 365
711 365

725 368
735 368
750 368
770 368
794 368
711 368

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 351
712 351
715 351

795 365
712 365
715 365

795 368
712 368
715 368

KKH 20 SQ
KKH 25 SQ

c = 600 mm

712 370
715 370
725 369
735 369
750 369
770 369
794 369
711 369
795 369
712 369
715 369

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

EAS EK FM 16

EAS EK FS 16

EFK FL30 SKN

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 372
735 372
750 372
770 372
794 372
711 372

725 373
735 373
750 373
770 373
794 373
711 373

725 370
735 370
750 370
770 370
794 370
711 370

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 372
712 372
715 372

795 373
712 373
715 373

795 370
712 370
715 370

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

UEK 25 FS
UEK 30 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 621
735 621
750 366
770 366
794 366
711 366

725 367
735 367
750 367
770 367
794 367
711 367

725 369
735 369
750 369
770 369
794 369
711 369

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 366
712 366
715 366

795 367
712 367
715 367

795 369
712 369
715 369

d = 1800 mm

Other cable lengths as well as types with unreduced cross sections of earthing cables, other earth clamps
and earth connection units are available on request. Earthing rod is not included in delivery.
www.dehn.de

105

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Ball head cap, adjustable (4 x 90), EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
hexagon shaft
Phase connecting elements

Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

KKH 20 D SK
KKH 25 D SK

EAS EK FM 12

EAS EK FS 12

EAB RN 16 FS

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 718
735 718
750 353
770 353
794 353
711 353

725 375
735 375
750 375
770 375
794 375
711 375

725 378
735 378
750 378
770 378
794 378
711 378

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 374
712 374
715 374

795 375
712 375
715 375

795 378
712 378
715 378

c = 600 mm

725 718
3,53
735 718
4,00
750 353
4,23
770 353
4,87
794 353
6,31
711 353
7,10
795 374
7,26
712 374
8,10
715 374
8,70
725 375
3,52
735 375
3,93
750 375
725
4,25718
770 375
735
4,87718
794 375
750
6,32353
711 375
770
7,10353
795 375
794
7,27353
712 375
711
8,10353
715 375
795
8,45374
725 382
712
3,48374
735 382
715
3,97374
750 382
725
4,20375
770 382
735
4,87375
794 382
750
6,27375
711 382
770
7,10375
795 382
794
7,22375
712 382
711
8,10375
715 382
795
8,65375
725 383
712
3,54375
735 383
715
4,03375
750 383
725
4,25382
770 383
735
4,87382
794 383
750
6,33382
711 383
770
7,10382
795 383
794
7,28382
712 383
711
8,10382
715 383
795
8,70382
725 378
712
3,93382
735 378
715
4,42382
750 378
725
4,65383
770 378
735
5,28383
794 378
750
6,72383
711 378
770
7,50383
795 378
794
7,68383
712 378
711
8,50383
715 378
795
9,10383
725 719
712
3,74383
735 719
715
4,24383
750 376
725
4,45378
770 376
735
5,15378
794 376
750
6,54378
711 376
770
7,40378
795 376
794
7,75378
712 376
711
8,60378
715 376
795
9,15378
725 377
712
3,85378
735 377
715
4,35378
750 377
725
4,58719
770 377
735
5,20719
794 377
750
6,65376
711 377
770
7,50376
795 950
794
7,63376
712 950
711
8,70376
715 950
795
9,10376
725 379
712
3,93376
735 379
715
4,43376
750 379
725
4,65377
770 379
735
5,28377
794 379
750
6,73377
711 379
770
7,50377
795 379
794
7,80377
712 379
711
8,70377
715 379
795
9,20950
725 380
712
3,83950
735 380
715
4,32950
750 380
725
4,55379
770 380
735
5,18379
794 380
750
6,62379
711 380
770
7,40379
795 380
794
7,58379
712 380
711
8,50379
715 380
795
9,00379
712 379
715 379
725 380
735 380
750 380
770 380
794 380
711 380
795 380
712 380

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s
d = 1800 mm

EAS EK FM 16

EAS EK FS 16

EFK FL30 SKN

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 382
735 382
750 382
770 382
794 382
711 382

725 383
735 383
750 383
770 383
794 383
711 383

725 380
735 380
750 380
770 380
794 380
711 380

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 382
712 382
715 382

795 383
712 383
715 383

795 380
712 380
715 380

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

UEK 25 FS
UEK 30 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 719
735 719
750 376
770 376
794 376
711 376

725 377
735 377
750 377
770 377
794 377
711 377

725 379
735 379
750 379
770 379
794 379
711 379

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 376
712 376
715 376

795 950
712 950
715 950

795 379
712 379
715 379

715 380

Other cable lengths as well as types with unreduced cross sections of earthing cables, other earth clamps
and earth connection units are available on request. Earthing rod is not included in delivery.
106

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points
725 720
3,54
735 720
4,03
750 354
4,40
770 354
4,91
794 354
6,35
711 354
7,10
795 384
7,35
712 384
8,10
715 384
8,75
725 385
3,55
735 385
4,04
750 385
725 720
4,30
770 385
735 720
4,91
794 385
750 354
6,35
711 385
770 354
7,20
795 385
794 354
6,35
712 385
711 354
8,20
715 385
795 384
8,75
725 392
712 384
3,50
735 392
715 384
4,00
750 392
725 385
4,30
770 392
735 385
4,91
794 392
750 385
6,30
711 392
770 385
7,20
795 392
794 385
7,30
712 392
711 385
8,20
715 392
795 385
8,75
725 393
712 385
3,56
735 393
715 385
4,05
750 393
725 392
4,30
770 393
735 392
4,91
794 393
750 392
6,36
711 393
770 392
7,20
795 393
794 392
7,36
712 393
711 392
8,20
715 393
795 392
8,80
725 388
712 392
3,95
735 388
715 392
4,45
750 388
725 393
4,70
770 388
735 393
5,32
794 388
750 393
6,75
711 388
770 393
7,60
795 388
794 393
7,75
712 388
711 393
8,60
715 388
795 393
9,15
725 721
712 393
3,76
735 721
715 393
4,26
750 386
725 388
4,50
770 386
735 388
5,15
794 386
750 388
6,56
711 386
770 388
7,50
795 386
794 388
7,82
712 386
711 388
8,70
715 386
795 388
9,25
725 387
712 388
3,88
735 387
715 388
4,38
750 387
725 721
4,60
770 387
735 721
5,24
794 387
750 386
6,68
711 387
770 386
7,60
795 951
794 386
7,96
712 951
711 386
8,80
715 951
795 386
9,35
725 389
712 386
3,95
735 389
715 386
4,45
750 389
725 387
4,70
770 389
735 387
5,32
794 389
750 387
6,75
711 389
770 387
7,60
795 389
794 387
7,90
712 389
711 387
8,80
715 389
795 951
9,30
725 390
712 951
3,85
735 390
715 951
4,35
750 390
725 389
4,60
770 390
735 389
5,22
794 390
750 389
6,65
711 390
770 389
7,50
795 390
794 389
7,65
712 390
711 389
8,60
715 390
795 389
9,10

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES Ball head cap, adjustable (4 x 90),
IEC/EN 61230 (DIN VDE 0683 Part 100)
T pin shaft
Phase connecting elements

Earth connecting elements

EAS EK FM 12

EAS EK FS 12

EAB RN 16 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 720
735 720
750 354
770 354
794 354
711 354

725 385
735 385
750 385
770 385
794 385
711 385

725 388
735 388
750 388
770 388
794 388
711 388

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 384
712 384
715 384

795 385
712 385
715 385

795 388
712 388
715 388

KKH 20 D SQ
KKH 25 D SQ

c = 600 mm

712 389
715 389
725 390
735 390
750 390
770 390
794 390
711 390
795 390
712 390
715 390

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

EAS EK FM 16

EAS EK FS 16

EFK FL30 SKN

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25/25
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 392
735 392
750 392
770 392
794 392
711 392

725 393
735 393
750 393
770 393
794 393
711 393

725 390
735 390
750 390
770 390
794 390
711 390

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 392
712 392
715 392

795 393
712 393
715 393

795 390
712 390
715 390

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

UEK 25 FS
UEK 30 FS

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Part No.

Part No.

Part No.

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 721
735 721
750 386
770 386
794 386
711 386

725 387
735 387
750 387
770 387
794 387
711 387

725 389
735 389
750 389
770 389
794 389
711 389

25 mm
25 mm
25 mm

95/35 mm2
120/50 mm2
150/50 mm2

18.7 kA
23.7 kA
29.6 kA

795 386
712 386
715 386

795 951
712 951
715 951

795 389
712 389
715 389

d = 1800 mm

Other cable lengths as well as types with unreduced cross sections of earthing cables, other earth clamps
and earth connection units are available on request. Earthing rod is not included in delivery.
www.dehn.de

107

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 20 / 25 mm, hexagon shaft
Phase connecting elements

Earth connecting elements

725 823
3,85
735 823
4,35
750 823
4,57
770 823
5,21
795 823
6,65
712 843
7,03
725 822
4,27
735 822
4,76
750 822
5,00
770 822
5,62
795 822
6,82
712 842
725
7,41823
725 825
735
4,40823
735 825
750
4,90823
750 825
770
5,12823
770 825
795
5,73823
795 825
712
7,20843
712 845
725
7,51822
725 821
735
4,16822
735 821
750
4,66822
750 821
770
4,88822
770 821
795
5,52822
795 821
712
6,96842
712 841
725
7,30825
725 826
735
4,27825
735 826
750
4,76825
750 826
770
4,98825
770 826
795
5,60825
795 826
712
7,06845
712 846
725
7,39821
735 821
750 821
770 821

EAS EK FM 12

EAB RN 16 FS

795 821
712 841
725 826

UK 25 SK

735 826

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 823
735 823
750 823
770 823
795 823
712 843

725 826
735 826
750 826
770 826
795 826
712 846

UEK 25 FS

EFK FL30 SKN

Part No.

Part No.

725 822
735 822
750 822
770 822
795 822
712 842

725 821
735 821
750 821
770 821
795 821
712 841

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm 25/25 mm2
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

750 826
770 826
795 826
712 846

c = 600 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
d = 1800 mm

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

mm2

20 mm 25/25
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UEK 25 HG

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 825
735 825
750 825
770 825
795 825
712 845

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm 25/25 mm2
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths as well as types with unreduced cross sections of earthing cables
or other earth clamps and earth connection units are available on request.
Earthing rod is not included in delivery.

108

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST

Fixed Points
725 833
3,95
735 833
4,43
750 833
4,65
770 833
5,25
795 833
6,74
712 863
7,11
725 832
4,35
735 832
4,85
750 832
5,10
770 832
5,65
795 832
7,15
712 862
725
7,49833
725 835
735
4,50833
735 835
750
4,98833
750 835
770
5,20833
770 835
795
5,75833
795 835
712
7,28863
712 865
725
7,26832
725 831
735
4,25832
735 831
750
4,75832
750 831
770
5,00832
770 831
795
5,55832
795 831
712
7,05862
712 861
725
5,60835
725 836
735
4,35835
735 836
750
4,75835
750 836
770
5,10835
770 836
795
5,65835
795 836
712
7,15865
712 866
725
7,47831

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Three-pole Earthing and Short-circuting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 20 / 25 mm, T pin shaft
Earth connecting elements

Phase connecting elements

735 831
750 831
770 831

EAS EK FM 12

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 833
735 833
750 833
770 833
795 833
712 863

725 836
735 836
750 836
770 836
795 836
712 866

795 831
712 861
725 836
735 836
750 836
770 836
795 836
712 866

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm 25/25 mm2
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UK 25 SQ

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

mm2

20 mm 25/25
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UEK 25 FS

EFK FL30 SKN

Part No.

Part No.

725 832
735 832
750 832
770 832
795 832
712 862

725 831
735 831
750 831
770 831
795 831
712 861

c = 600 mm

d = 1800 mm

UEK 25 HG

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 835
735 835
750 835
770 835
795 835
712 865

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm 25/25 mm2
20 mm 35/35 mm2
20 mm 50/25 mm2
20 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths as well as types with unreduced cross sections of earthing cables,
other earth clamps and earth connection units are available on request.
Earthing rod is not included in delivery.

www.dehn.de

109

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 25 / 30 mm, hexagon shaft
Phase connecting elements

Earth connecting elements

725 804
4,24
735 804
4,73
750 804
4,96
770 804
5,20
795 804
7,03
712 804
7,83
725 115
4,78
735 115
5,27
750 803
5,50
770 803
5,65
795 803
7,57
712 803
725
8,37804
725 806
735
4,91804
735 806
750
5,41804
750 806
770
5,63804
770 806
795
5,85804
795 806
712
7,70804
712 806
725
8,50115
725 802
735
4,55115
735 802
750
5,04803
750 802
770
5,27803
770 802
795
5,45803
795 802
712
7,34803
712 802
725
8,13806
725 807
735
4,65806
735 807
750
5,15806
750 807
770
5,37806
770 807
795
5,53806
795 807
712
7,45806
712 807
725
8,25802
735 802
750 802
770 802

EAS EK FM 12

EAB RN 16 FS

795 802
712 802
725 807

UK 30 SK

735 807

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 804
735 804
750 804
770 804
795 804
712 804

725 807
735 807
750 807
770 807
795 807
712 807

UEK 30 FS

EFK FL30 SKN

Part No.

Part No.

725 115
735 115
750 803
770 803
795 803
712 803

725 802
735 802
750 802
770 802
795 802
712 802

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm 25/25 mm2
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

750 807
770 807
795 807
712 807

c = 600 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
d = 1800 mm

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

mm2

30 mm 25/25
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UEK 30 HG

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 806
735 806
750 806
770 806
795 806
712 806

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm 25/25 mm2
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths as well as types with unreduced cross sections of earthing cables,
other earth clamps and earth connection units are available on request.
Earthing rod is not included in delivery.

110

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points
725 813
4,32
735 813
4,82
750 813
5,13
770 813
5,25
795 813
7,12
712 813
7,85
725 117
4,86
735 117
5,36
750 812
5,60
770 812
5,69
795 812
7,66
712 812
725
8,40813
725 815
735
5,00813
735 815
750
5,50813
750 815
770
5,35813
770 815
795
5,89813
795 815
712
7,80813
712 815
725
8,60117
725 811
735
4,63117
735 811
750
5,12812
750 811
770
5,35812
770 811
795
5,49812
795 811
712
7,45812
712 811
725
8,20815
725 816
735
4,75815
735 816
750
5,23815
750 816
770
5,50815
770 816
795
5,57815
795 816
712
7,53815
712 816
725
8,30811

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 25 / 30 mm, T pin shaft
Earth connecting elements

Phase connecting elements

735 811
750 811
770 811

EAS EK FM 12

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 813
735 813
750 813
770 813
795 813
712 813

725 816
735 816
750 816
770 816
795 816
712 816

795 811
712 811
725 816
735 816
750 816
770 816
795 816
712 816

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm 25/25 mm2
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UK 30 SQ

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

mm2

30 mm 25/25
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UEK 30 FS

EFK FL30 SKN

Part No.

Part No.

725 117
735 117
750 812
770 812
795 812
712 812

725 811
735 811
750 811
770 811
795 811
712 811

c = 600 mm

d = 1800 mm

UEK 30 HG

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 815
735 815
750 815
770 815
795 815
712 815

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm 25/25 mm2
30 mm 35/35 mm2
30 mm 50/25 mm2
30 mm 70/35 mm2

95/35 mm2

120/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths as well as types with unreduced cross sections of earthing cables,
other earth clamps and earth connection units are available on request.
Earthing rod is not included in delivery.

www.dehn.de

111

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Short-circuiting bar
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

With longitudinal slot for reliable


contact
For copper or aluminium busbars up to
a thickness of 25 mm
Other bar and earthing cable lengths
available on request
Operation by earthing rods with hexagon or T pin shaft

Short-circuiting bar with earthing cable in a switchgear installation.


The short-circuiting bar with longitudinal slot can be used for installations
with compensated systems.
The earthing cable is fitted with a ball head cap with wing nut for fixed
ball points 20 mm for connection to the earthing system (other equipment is available on request).
The short-circuiting bars are available with 2 different coupling devices
for operation with earthing rods:

Technical Data
Earthing cable

Cu, highly flexible

Cable cross section

50 mm2

Cable length

2500 mm

Operating temperature range

25 C ... + 55 C

busbar

27

SK: Hexagon shaft

40

125

short-circuiting bar

M8x30

Fixed clamping point


with funnel-shaped
nut and contact claw

94

SQ: T pin shaft (bayonet type)

112

www.dehn.de

Three-pole
Devices

Fixed Points
795 038
4,70
795 039
5,80
795 041
4,70
795 045
5,80
795 042
3,20
795 043
3,50
795 048
3,20
795 049
3,50

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

KSS 60 8 CU SK ....
Short-circuiting bar, 60x8 mm, SK, Cu
038
KSS 60 12 CU SK ....
Short-circuiting bar, 60x12 mm, SK, Cu
039
KSS 60 8 CU SQ ....
Short-circuiting bar, 60x8 mm, SQ, Cu
041
KSS 60 12 CU SQ ....
Short-circuiting bar, 60x12 mm, SQ, Cu
045
KSS 60 8 AL SK ....
Short-circuiting bar, 60x8 mm, SK, Al
042
KSS 60 12 AL SK ....
Short-circuiting bar, 60x12 mm, SK, Al
043
KSS 60 8 AL SQ ....
Short-circuiting bar, 60x8 mm, SQ, Al
048
KSS 60 12 AL SQ ....
Short-circuiting bar, 60x12 mm, SQ, Al
049

Single-pole
Devices

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

Three-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

795
795
795
795

795
795

795
795

lG

Type

Coupling
device

Profile
hxw

Total length
IG

Max. short-circuit
current Ik 1 s

520 mm
520 mm
520 mm
520 mm

70.0 kA
90.0 kA
70.0 kA
90.0 kA

Part
No.

A Short-circuiting Bar made of E-Cu F20


KSS 60 8 CU SK ....
KSS 60 12 CU SK ....
KSS 60 8 CU SQ ....
KSS 60 12 CU SQ ....

SK
SK
SQ
SQ

60 x 8 mm
60 x 12 mm
60 x 8 mm
60 x 12 mm

795 038
795 039
795 041
795 045
lG
SA

B Short-circuiting Bar made of AlMgSi 0.5

50

coupling
device

KSS 60 8 AL SK ....
KSS 60 12 AL SK ....
KSS 60 8 AL SQ ....
KSS 60 12 AL SQ ....

SK
SK
SQ
SQ

60 x 8 mm
60 x 12 mm
60 x 8 mm
60 x 12 mm

520 mm
520 mm
520 mm
520 mm

45.0 kA
70.0 kA
45.0 kA
70.0 kA

795 042
795 043
795 048
795 049

SB

Note: Please specify the bar distance (SA) and bar width (SB) when placing your order.

50 mm2
2500 mm long

795 040
0,89

1 ST

KLFP M12 KSS


clamping point for busbars
040

Fixed
795

Accessories for Three-pole Earthing and Short-circuiting Devices

Fixed Clamping Points for Busbars


With funnel-shaped nut and contact claw
Part
No.
795 040

Type
KLFP M12 KSS

795 214
0,12

1 ST

SA KLFP SK
Screw adapter, hexagon
214

795

SK Screw Adapter
Hexagon terminal, width across flats 19
Type
SA KLFP SK

Total length
IG
60 mm

Part
No.
795 214

Total length
IG
100 mm

Part
No.
795 213

SQ Screw Adapter
795 213
0,11

1 ST

SA KLFP SQ
Screw adapter, T pin
213

795

www.dehn.de

T pin shaft (bayonet type)


Type
SA KLFP SQ

113

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Ball head cap, rigid, hexagon shaft EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)

Phase connecting elements

Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

EAB RN 16 FS

Part No.

Part No.

Part No.

725 025
1,92
735 025
2,25
750 025
2,77
770 025
3,28
794 025
4,17
711 025
4,75
795 025
4,69
712 025
5,00
715 025
6,00
725 044
2,03
735 044
2,34
750 044
725
2,83025
770 044
735
3,22025
794 044
750
4,29025
711 044
770
4,81025
795 044
794
4,81025
712 044
711
5,10025
715 044
795
6,10025
725 045
712
1,90025
735 045
715
2,47025
750 045
725
3,05044
770 045
735
3,49044
794 045
750
4,36044
711 045
770
4,90044
794 048
794
4,75044
712 045
711
5,04044
725 048
795
2,00044
735 048
712
2,36044
750 048
715
2,80044
725 046
725
2,10045
735 046
735
2,47045
750 046
750
2,92045
770 046
770
3,48045
794 046
794
4,35045
711 046
711
4,90045
795 046
794
4,62048
712 046
712
5,20045
715 046
725
5,92048
735 048
750 048
725 046
735 046
750 046
770 046

KKH 20 SK
KKH 25 SK

mm2

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 025
735 025
750 025
770 025
794 025
711 025

725 044
735 044
750 044
770 044
794 044
711 044

725 046
735 046
750 046
770 046
794 046
711 046

25 mm
25 mm
25 mm

95 mm2
120 mm2
150 mm2

18.7 kA
23.7 kA
29.6 kA

795 025
712 025
715 025

795 044
712 044
715 044

795 046
712 046
715 046

UEK 25 FS
UEK 30 FS

EFK FL30 SKN

Part No.

Part No.
725 048
735 048
750 048

794 046
711 046
795 046
712 046
715 046

a = 2500 mm

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s
20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 045
735 045
750 045
770 045
794 045*)
711 045*)

25 mm
25 mm

95 mm2
120 mm2

18.7 kA
23.7 kA

794 048*)
712 045*)

*) Earth side for fixed ball points only


Other cable lengths and earth clamps are available on request.
Earthing rod is not included in delivery.

114

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points
725 031
1,93
735 031
2,29
750 031
2,77
770 031
3,34
794 031
4,62
711 031
4,75
795 031
4,70
712 031
5,00
715 031
6,00
725 053
2,05
735 053
2,40
750 053
725
2,83031
770 053
735
3,40031
794 053
750
4,30031
711 053
770
4,81031
795 053
794
4,83031
712 053
711
5,10031
715 053
795
6,15031
725 049
712
2,11031
735 049
715
2,48031
750 049
725
3,05053
770 049
735
3,49053
794 049
750
4,31053
711 049
770
4,90053
794 052
794
4,75053
712 049
711
5,04053
725 052
795
1,80053
735 052
712
2,37053
750 052
715
2,80053
725 050
725
2,11049
735 050
735
2,48049
750 050
750
2,92049
770 050
770
3,48049
794 050
794
4,36049
711 050
711
4,90049
795 050
794
4,64052
712 050
712
5,20049
715 050
725
5,95052

1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

735 052
750 052
725 050
735 050
750 050

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Ball head cap, rigid, T pin shaft
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)

Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Phase connecting elements

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

EAB RN 16 FS

Part No.

Part No.

Part No.

770 050
794 050
711 050
795 050
712 050
715 050

mm2

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 031
735 031
750 031
770 031
794 031
711 031

725 053
735 053
750 053
770 053
794 053
711 053

725 050
735 050
750 050
770 050
794 050
711 050

25 mm
25 mm
25 mm

95 mm2
120 mm2
150 mm2

18.7 kA
23.7 kA
29.6 kA

795 031
712 031
715 031

795 053
712 053
715 053

795 050
712 050
715 050

KKH 20 SQ
KKH 25 SQ

a = 2500 mm

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

UEK 25 FS
UEK 30 FS

EFK FL30 SKN

Part No.

Part No.
725 052
735 052
750 052

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 049
735 049
750 049
770 049
794 049*)
711 049*)

25 mm
25 mm

95 mm2
120 mm2

18.7 kA
23.7 kA

794 052*)
712 049*)

*) Earth side for fixed ball points only


Other cable lengths and earth clamps are available on request.
Earthing rod is not included in delivery.

www.dehn.de

115

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Ball head cap, adjustable (4 x 90), EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
hexagon shaft
Phase connecting elements

Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

EAB RN 16 FS

Part No.

Part No.

Part No.

725 325
2,00
735 325
2,31
750 325
2,85
770 325
3,34
794 325
4,25
711 325
4,75
795 325
4,85
712 325
5,00
715 325
6,15
725 068
2,12
735 068
2,43
750 068
725
2,92325
770 068
735
3,40325
794 068
750
4,38325
711 068
770
4,81325
795 068
794
4,95325
712 068
711
5,10325
715 068
795
6,25325
725 060
712
2,20325
735 060
715
2,56325
750 060
725
3,00068
770 060
735
3,49068
794 060
750
4,45068
711 060
770
4,90068
795 060
794
4,89068
712 060
711
5,04068
725 063
795
2,10068
735 063
712
2,45068
750 063
715
2,88068
725 061
725
2,19060
735 061
735
2,55060
750 061
750
2,50060
770 061
770
3,48060
794 061
794
4,45060
711 061
711
4,90060
795 061
795
4,76060
712 061
712
5,20060
715 061
725
6,05063
735 063
750 063
725 061
735 061
750 061
770 061

KKH 20 D SK
KKH 25 D SK

mm2

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 325
735 325
750 325
770 325
794 325
711 325

725 068
735 068
750 068
770 068
794 068
711 068

725 061
735 061
750 061
770 061
794 061
711 061

25 mm
25 mm
25 mm

95 mm2
120 mm2
150 mm2

18.7 kA
23.7 kA
29.6 kA

795 325
712 325
715 325

795 068
712 068
715 068

795 061
712 061
715 061

UEK 25 FS
UEK 30 FS

EFK FL30 SKN

Part No.

Part No.
725 063
735 063
750 063

794 061
711 061
795 061
712 061
715 061

a = 2500 mm

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s
20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 060
735 060
750 060
770 060
794 060*)
711 060*)

25 mm
25 mm

95 mm2
120 mm2

18.7 kA
23.7 kA

795 060*)
712 060*)

*) Earth side for fixed ball points only


Other cable lengths and earth clamps are available on request.
Earthing rod is not included in delivery.

116

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points
725 331
2,00
735 331
2,37
750 331
2,85
770 331
3,34
794 331
4,26
711 331
4,75
795 331
4,85
712 331
5,00
715 331
6,15
725 069
2,13
735 069
2,50
750 069
725
2,92331
770 069
735
3,40331
794 069
750
4,38331
711 069
770
4,81331
795 069
794
4,98331
712 069
711
5,10331
715 069
795
6,30331
725 064
712
2,20331
735 064
715
2,56331
750 064
725
3,00069
770 064
735
3,49069
794 064
750
4,46069
711 064
770
4,90069
795 064
794
4,91069
712 064
711
5,04069
725 067
795
2,10069
735 067
712
2,45069
750 067
715
2,88069
725 065
725
2,20064
735 065
735
2,53064
750 065
750
3,00064
770 065
770
3,48064
794 065
794
4,45064
711 065
711
4,90064
795 065
795
4,79064
712 065
712
5,20064
715 065
725
6,10067

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

735 067
750 067
725 065
735 065
750 065

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES Ball head cap, adjustable (4 x 90),
IEC/EN 61230 (DIN VDE 0683 Part 100)
T pin shaft
Earth connecting elements

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

Phase connecting elements

KKH 20 FS
KKH 25 FS

KKH 20 HG
KKH 25 HG

EAB RN 16 FS

Part No.

Part No.

Part No.

770 065
794 065
711 065
795 065
712 065
715 065

mm2

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 331
735 331
750 331
770 331
794 331
711 331

725 069
735 069
750 069
770 069
794 069
711 069

725 065
735 065
750 065
770 065
794 065
711 065

25 mm
25 mm
25 mm

95 mm2
120 mm2
150 mm2

18.7 kA
23.7 kA
29.6 kA

795 331
712 331
715 331

795 069
712 069
715 069

795 065
712 065
715 065

KKH 20 D SQ
KKH 25 D SQ

a = 2500 mm

Fixed ball Cable cross Max. short-circuit


point
section
current Ik 1 s

UEK 25 FS
UEK 30 FS

EFK FL30 SKN

Part No.

Part No.
725 067
735 067
750 067

20 mm
20 mm
20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

725 064
735 064
750 064
770 064
794 064*)
711 064*)

25 mm
25 mm

95 mm2
120 mm2

18.7 kA
23.7 kA

795 064*)
712 064*)

*) Earth side for fixed ball points only


Other cable lengths and earth clamps are available on request.
Earthing rod is not included in delivery.

www.dehn.de

117

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 20 / 25 mm, hexagon shaft
Phase connecting elements

Earth connecting elements

725 103
2,30
735 103
2,67
750 103
3,30
770 103
3,95
795 103
4,56
712 073
4,88
725 106
2,00
735 106
2,80
750 106
3,24
770 106
3,82
795 106
4,69
712 076
725
5,27103
725 101
735
2,20103
735 101
750
2,56103
750 101
770
3,00103
725 104
795
2,90103
735 104
712
3,26073
750 104
725
3,59106
770 104
735
4,19106
795 104
750
5,15106
725 105
770
2,30106
735 105
795
2,67106
750 105
712
3,11076
770 105
725
3,70101
795 105
735
4,56101
712 075
750
5,14101
725 104
735 104
750 104
770 104
795 104
725 105
735 105

UEK 25 FS

UEK 25 HG

750 105
770 105
795 105

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

UK 25 SK

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

712 075

Part No.

Part No.

725 103
735 103
750 103
770 103
795 103*)
712 073*)

725 106
735 106
750 106
770 106
795 106*)
712 076*)

*) Earth side for fixed ball points only

a = 2500 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA

EFK FL30 SKN

EFK FL40 SKN

Part No.

Part No.

725 101
735 101
750 101

725 104
735 104
750 104
770 104
795 104

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 105
735 105
750 105
770 105
795 105
712 075

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths and earth clamps are available on request.


Earthing rod is not included in delivery.

118

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST

Fixed Points
725 110
2,34
735 110
2,70
750 110
3,12
770 110
3,70
795 110
4,59
712 171
4,94
725 114
2,47
735 114
2,83
750 114
3,24
770 114
3,83
795 114
4,72
712 173
725 110
5,04
725 108
735 110
2,23
735 108
750 110
2,60
750 108
770 110
3,00
725 112
795 110
2,93
735 112
712 171
3,29
750 112
725 114
3,59
770 112
735 114
4,19
795 112
750 114
5,18
725 113
770 114
2,33
735 113
795 114
2,70
750 113
712 173
3,11
770 113
725 108
3,70
795 113
735 108
4,58
712 172
750 108
4,92

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST
1011
1 ST

1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 20 / 25 mm, T pin shaft
Earth connecting elements

Phase connecting elements

725 112
735 112
750 112
770 112
795 112
725 113
735 113
750 113
770 113

UEK 25 FS

UEK 25 HG

Part No.

Part No.

725 110
735 110
750 110
770 110
795 110*)
712 171*)

725 114
735 114
750 114
770 114
795 114*)
712 173*)

795 113
712 172

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UK 25 SQ

*) Earth side for fixed ball points only

a = 2500 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA

EFK FL30 SKN

EFK FL40 SKN

Part No.

Part No.

725 108
735 108
750 108

725 112
735 112
750 112
770 112
795 112

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
20 / 25 mm
/ 25 mm

725 113
735 113
750 113
770 113
795 113
712 172

15 mm
15 mm
15 mm
15 mm
15 mm

20 mm
20 mm
20 mm
20 mm

25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths and earth clamps are available on request.


Earthing rod is not included in delivery.

www.dehn.de

119

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
IEC/EN 61230 (DIN VDE 0683 Part 100)
range 25 / 30 mm, hexagon shaft
Phase connecting elements

Earth connecting elements

725 125
2,56
735 125
2,92
750 125
3,37
770 125
3,97
794 125
4,80
712 125
5,38
725 123
2,70
735 123
3,05125
725
750 123
3,51125
735
770 123
4,11125
750
795 123
4,95125
770
712 123
5,40125
794
725 132
2,33125
712
735 132
2,69123
725
750 132
3,13123
735
725 134
3,03123
750
735 134
3,38123
770
750 134
3,72123
795
770 134
4,32123
712
794 134
5,28132
725
725 135
2,42132
735
735 135
2,80132
750
750 135
3,25134
725
770 135
3,85134
735
794 135
4,68134
750
712 135
5,52134
770
794 134
725 135
735 135

UEK 30 FS

UEK 30 HG

750 135
770 135
794 135

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

UK 30 SK

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

712 135

Part No.

Part No.

725 125
735 125
750 125
770 125
794 125*)
712 125*)

725 123
735 123
750 123
770 123
795 123*)
712 123*)

*) Earth side for fixed ball points only

a = 2500 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA

EFK FL30 SKN

EFK FL40 SKN

Part No.

Part No.

725 132
735 132
750 132

725 134
735 134
750 134
770 134
794 134

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 135
735 135
750 135
770 135
794 135
712 135

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths and earth clamps are available on request.


Earthing rod is not included in delivery.

120

www.dehn.de

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Fixed Points

725 127
2,59
735 127
2,95
750 127
3,37
770 127
3,97
794 127
4,84
712 127
5,38
725 107
2,73
735 107
3,08
725 127
750 107
3,51
735 127
770 107
4,11
750 127
795 107
4,98
770 127
712 107
5,40
794 127
725 136
2,36
712 127
735 136
2,72
725 107
750 136
3,13
735 107
725 138
3,06
750 107
735 138
3,42
770 107
750 138
3,72
795 107
770 138
4,32
712 107
794 138
5,30
725 136
725 139
2,46
735 136
735 139
2,82
750 136
750 139
3,13
725 138
770 139
3,85
735 138
794 139
4,71
750 138
712 139
5,52
770 138

1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST
1011
1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Single-pole Earthing and Short-circuiting Devices


SAFETY EQUIPMENT
Universal clamp, clamping
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)
range 25 / 30 mm, T pin shaft
Earth connecting elements

Phase connecting elements

794 138
725 139
735 139
750 139
770 139

UEK 30 FS

UEK 30 HG

Part No.

Part No.

725 127
735 127
750 127
770 127
794 127*)
712 127*)

725 107
735 107
750 107
770 107
795 107*)
712 107*)

794 139
712 139

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

UK 30 SQ

*) Earth side for fixed ball points only

a = 2500 mm

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

mm2

25
35 mm2
50 mm2
70 mm2
95 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA

EFK FL30 SKN

EFK FL40 SKN

Part No.

Part No.

725 136
735 136
750 136

725 138
735 138
750 138
770 138
794 138

EAB RN 16 FS

Fixed ball Phase T pin


Rd / Fl Cable cross Max. short-circuit
point Collar width Clamping range section
current Ik 1 s

Part No.

25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm
25 / 30 mm

725 139
735 139
750 139
770 139
794 139
712 139

18 mm
18 mm
18 mm
18 mm
18 mm

30 mm
30 mm
30 mm
30 mm

25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA

Other cable lengths and earth clamps are available on request.


Earthing rod is not included in delivery.

www.dehn.de

121

Fixed Points

Three-pole
Devices

Single-pole
Devices

Earthing and Short-circuiting Cables

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

To be equipped with connecting components


Transparent sheathing
Waterproof plastic-sheathed cable
entries and node unit, with additional
protection against twisting
Standard crimped cable lugs, type PK1,
protected against twisting

Equipped three-pole earthing and short-circuiting device in a switchgear


installation.
Technical Data
Cable

E-Cu, extra finely stranded and highly flexible

Sheath

Thermoplastic polymer (flexible PVC compound


YM2), uncoloured and transparent

Hole in terminal lug

12.5 mm

Operating temperature
range
25 C ... + 55 C
Crimped cable lugs, PK1 type:
Standard cable lug with cut-out
for protection against twisting.

Crimped cable lugs, PK2 type:


Cable lug without cut-out for connecting parts from other manufacturers are available on request.

Example of price calculation:


For earthing and short-circuiting devices with customised lengths
Three-pole earthing and short-circuiting device, cable cross section
70 mm2, like Part No. 770 350, but with conductor lengths of
a = 1000 mm and b = 2200 mm

Crimped cable lugs, PK3 type:


Hook-type cable lugs up to cable
cross sections of 35 mm2 are
available on request.

Standard type:

a: 70 mm2, 3 x 600 = 1800 mm


b: 35 mm2, 1 x 1800 = 1800 mm

Customised type:

a: 70 mm2, 3 x 1000 = 3000 mm


b: 35 mm2, 1 x 2200 = 2200 mm

Difference between cable lengths: a: 70 mm2 = 1200 mm


b: 35 mm2 = 400 mm
Price of standard type, Part No. 770 350

Euro

460.

per 1000 mm

Euro

49.20

Part No. 735 001, 400 mm x 20.70 per 1000 mm

Euro

9.08

Price of customised unit, total

Euro 518.28

Price of difference between cable lengths


Part No. 770 001, 1200 mm x 41.

Note:
Other hole diameters for terminal lugs are available on request.

122

Prices without obligation (as of 2009).

www.dehn.de

Fixed Points
725 604
1011
1,58
1 ST
735 604
1011
2,08
1 ST
750 604
1011
2,21
1 ST
770 604
1011
2,96
1 ST
795 604
1011
4,38
1 ST
712 604
1011
4,63
1 ST
715 604
1011
5,80
1 ST
776 425
1011
1,48
1 ST
776 435
1011
2,23
1 ST
776 450
1011
3,10
1 ST
776 470
1011
4,22
1 ST
EKS3
PK1 25 25
776 495
1011
Earthing
and short-circuiting cable, 3-pole, 25/25 mm12,ST
5,96
5000
mm
725
776 412
1011
604
7,06
1 ST
EKS3
PK1 35 35
776 415
1011
Earthing
and short-circuiting cable, 3-pole, 35/35 mm12,ST
8,55
5000 mm
735
604
EKS3 PK1 50 25
Earthing and short-circuiting cable, 3-pole, 50/25 mm2,
5000 mm
750
604
EKS3 PK1 70 35
Earthing and short-circuiting cable, 3-pole, 70/35 mm2,
5000 mm
770
604
EKS3 PK1 95 35
Earthing and short-circuiting cable, 3-pole, 95/35 mm2,
5000 mm
795
604
EKS3 PK1 120 50
Earthing and short-circuiting cable, 3-pole, 120/50 mm2,
5000 mm
712
604
EKS3 PK1 150 50
Earthing and short-circuiting cable, 3-pole, 150/50 mm2,
5000 mm
715
604
EKS1 PK1 25 5000
Earthing and short-circuiting cable, single-pole, 25 mm2,
5000 mm
776
425
EKS1 PK1 35 5000
Earthing and short-circuiting cable, single-pole, 35 mm2,
5000 mm
776
435
EKS1 PK1 50 5000
Earthing and short-circuiting cable, single-pole, 50 mm2,
5000 mm
776
450
EKS1 PK1 70 5000
Earthing and short-circuiting cable, single-pole, 70 mm2,
5000 mm
776
470
EKS1 PK1 95 5000
Earthing and short-circuiting cable, single-pole, 95 mm2,
5000 mm
776
495
EKS1 PK1 120 5000
Earthing and short-circuiting cable, single-pole, 120 mm2,
5000 mm
776
412
EKS1 PK1 150 5000
Earthing and short-circuiting cable, single-pole, 150 mm2,
5000 mm
776
415

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Earthing and Short-circuiting Cables


SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
A

Type

Type of crimped
cable lug

Cable cross
section

Max. short-circuit
current Ik 1 s

Part
No.

A Three-pole Earthing and Short-circuiting Cables


Without equipment
EKS3 PK1 25 25
EKS3 PK1 35 35
EKS3 PK1 50 25
EKS3 PK1 70 35
EKS3 PK1 95 35
EKS3 PK1 120 50
EKS3 PK1 150 50

PK1
PK1
PK1
PK1
PK1
PK1
PK1

25/25 mm2
35/35 mm2
50/25 mm2
70/35 mm2
95/35 mm2
120/50 mm2
150/50 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA
29.6 kA

725 604
735 604
750 604
770 604
795 604
712 604
715 604

c = 600 mm

d = 1800 mm

B Single-pole Earthing and Short-circuiting Cables


Without equipment
EKS1 PK1 25 5000
EKS1 PK1 35 5000
EKS1 PK1 50 5000
EKS1 PK1 70 5000
EKS1 PK1 95 5000
EKS1 PK1 120 5000
EKS1 PK1 150 5000

PK1
PK1
PK1
PK1
PK1
PK1
PK1

25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2
150 mm2

4.9 kA
6.9 kA
9.9 kA
13.8 kA
18.7 kA
23.7 kA
29.6 kA

776 425
776 435
776 450
776 470
776 495
776 412
776 415

a = 5000 mm

Other cable lengths, types with unreduced earthing cable cross sections as well as line and earth clamps
and cables with crimped cable lugs without protection against twisting (PK2) are available on request.

716 001
0,18

1M

725 001
0,21

1M

735 001
0,37

1M

750 001
ES
0,54YM2 16
Earthing cable, 16 mm2
001 001
770
ES YM2 25
0,75
Earthing cable, 25 mm2
001 001
795
ES YM2 35
1,00
Earthing cable, 35 mm2
001 001
712
ES YM2 50
1,23
Earthing cable, 50 mm2
001 001
715
ES YM2 70
1,52
Earthing cable, 70 mm2
001
ES YM2 95
Earthing cable, 95 mm2
001
ES YM2 120
Earthing cable, 120 mm2
001
ES YM2 150
Earthing cable, 150 mm2
001

1M
716

1M
725

1M
735

1M
750

1M
770

Accessories for Earthing and Short-circuiting Cables

Earthing Cables in accordance with IEC 61138


For earthing and short-circuiting devices with customised lengths

795
712
715

www.dehn.de

Type
ES YM2 16
ES YM2 25
ES YM2 35
ES YM2 50
ES YM2 70
ES YM2 95
ES YM2 120
ES YM2 150

Cable cross section


16 mm2
25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2
150 mm2

Part
No.
716 001
725 001
735 001
750 001
770 001
795 001
712 001
715 001

123

Fixed Points

Three-pole
Devices

Single-pole
Devices

Phase Connecting Elements


Phase screw clamps for overhead
line conductors 4 to 85 mm

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)
Threaded T pin shaft DIN 48087

Phase clamps for connecting single-pole


and three-pole earthing and short-circuiting devices to overhead lines
Coupling aid for safe coupling to overhead line conductors
Easy coupling due to spring tension
Type PK1 or PK2 protected against
twisting, long threaded T pin shaft
Phase screw clamps used on an overhead line.

Technical Data

Phase screw clamp with fixed coupling aid for safe coupling

Phase screw clamp with spring


tension

Crimped cable lugs, PK1 type:


Standard cable lug with cut-out
for protection against twisting.

Crimped cable lugs, PK2 type:


Standard cable lug without cutout which can be connected to
components from other manufacturers. Only available on request.

124

Spring load unit

Al alloy

Clamping unit

Al alloy

Shaft

Cu alloy/gal Sn or StSt

Coupling aid

St/gal Zn

Clamp with long shaft and earthing rod with aluminium cone coupling.

www.dehn.de

Three-pole
Devices

Fixed Points
784 201
0,88
784 301
1,70
784 401
1,30
784 501
1,95
784 480
0,60
784 085
0,87
784 032
0,95

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

PSK 4 30 SQ
Phase screw clamp, 4 ... 30 mm, SQ
201
PSK 10 65 SQ
Phase screw clamp, 10 ... 65 mm, SQ
301
PSK 4 30 SQ EH
Phase screw clamp, 4 ... 30 mm, SQ, EH
401
PSK 10 65 SQ EH
Phase screw clamp, 10 ... 65 mm, SQ, EH
501
PSK FV 4 30 SQ
Phase screw clamp, 4 ... 30 mm, SQ FV
480
PSK 10 85 SQ
Phase screw clamp, 10 ... 85 mm, SQ
085
PSK 12 30 SQ
Phase screw clamp, 12 ... 30 mm, SQ
032

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Phase Connecting Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

784
784
784
784

784
784

784

Type

Clamping
range

Protection against
twisting

For cable Max. short-circuit


cross section current Ik 1 s

Part
No.

A Standard Phase Screw Clamps


Short-circuit-proof, even in case of corroded conductor cables due to weathering
PSK 4 30 SQ
PSK 10 65 SQ

4 ... 30 mm
10 ... 65 mm

PK1
PK1

25 ... 70 mm2
25 ... 120 mm2

13.8 kA
23.7 kA

784 201
784 301

B Phase Screw Clamps with Coupling Aid


Short-circuit-proof, even in case of corroded conductor cables due to weathering
PSK 4 30 SQ EH
PSK 10 65 SQ EH

4 ... 30 mm
10 ... 65 mm

PK1
PK1

25 ... 70 mm2
25 ... 120 mm2

13.8 kA
23.7 kA

784 401
784 501

25 ... 70 mm2

13.8 kA

784 480

C Phase Screw Clamp with Spring Tension


Easy coupling with spring-loaded clamp
PSK FV 4 30 SQ

4 ... 30 mm

PK1

D Phase Screw Clamp with wide Clamping Range


Ideally suited for use with Al and Al/St conductor cables, tubular busbars and fixed phase points
PSK 10 85 SQ

10 ... 85 mm

PK2

25 ... 120 mm2

23.7 kA

784 085

PK2

25 ... 95 mm2

18.7 kA

784 032

E Phase Screw Clamp


Ideally suited for angled positions
PSK 12 30 SQ

12 ... 30 mm

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

www.dehn.de

125

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Phase Connecting Elements


SAFETY EQUIPMENT
Ball head caps and universal clamps EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)
Threaded T pin shaft DIN 48087

Phase clamps for connecting single-pole


and three-pole earthing and short-circuiting devices
Type PK1 protected against twisting

Connecting the universal clamp to a fixed ball point.

Technical Data
Clamping unit

Cu alloy/gal Sn

Shaft

Cu alloy/gal Sn

Spring load unit

Cu alloy/gal Sn or St/Zn

Two types of ball head caps are available:


Rigid ball head cap
Adjustable ball head cap (4x 90)
The adjustable ball head cap allows the user to connect the earthing and
short-circuiting device to fixed ball points that are installed in difficult
positions. In the vast majority of cases, the use of angled fixed ball points
is therefore no longer necessary.
SK: Hexagon shaft

Rigid ball head cap

Adjustable ball head cap (4 x 90)

SQ: T pin shaft (bayonet locking mechanism)

126

www.dehn.de

Fixed Points
772 310
0,47
772 320
0,79
772 311
0,48
772 321
0,76
772 330
0,56
772 340
0,88
772 331
0,57
772 341
0,90
773 034
0,63
773 130
0,80
773 234
0,66
KKH
20 SK
773 330
head
0,83 cap 20 mm, SK
310
KKH 25 SK
head cap 25 mm, SK
320
KKH 20 SQ
head cap 20 mm, SQ
311
KKH 25 SQ
head cap 25 mm, SQ
321
KKH 20 D SK
head cap 20 mm, adjustable, SK
330
KKH 25 D SK
head cap 25 mm, adjustable, SK
340
KKH 20 D SQ
head cap 20 mm, adjustable, SQ
331
KKH 25 D SQ
head cap 25 mm, adjustable, SQ
341
UK 25 SK
Universal earthing clamp 25 mm, SK
034
UK 30 SK
Universal earthing clamp 30 mm, SK
130
UK 25 SQ
Universal earthing clamp 25 mm, SQ
234
UK 30 SQ
Universal earthing clamp 30 mm, SQ
330

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST
Ball

772
1 ST

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

Earthing Rods

Installation Devices
Storage Devices

Phase Connecting Elements

Ball
772
Ball
772
Ball
772
Ball
772
Ball
772
Ball
772
Ball
772
773
773
773
773

Type

Fixed ball
point

Phase T pin
Rd / Fl
For cable Max. short-circuit
Collar width Clamping range cross section current Ik 1 s

Part
No.

A Ball Head Cap, rigid, hexagon Shaft


KKH 20 SK
KKH 25 SK

20 mm
25 mm

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 310
772 320

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 311
772 321

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 330
772 340

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 331
772 341

B Ball Head Cap, rigid, T pin Shaft


KKH 20 SQ
KKH 25 SQ

20 mm
25 mm

C Ball Head Cap, adjustable (4 x 90), hexagon Shaft


KKH 20 D SK
KKH 25 D SK

20 mm
25 mm

D Ball Head Cap, adjustable (4 x 90), T pin Shaft


KKH 20 D SQ 20 mm
KKH 25 D SQ 25 mm

E Universal Clamp, hexagon Shaft


*) see table for clamping ranges and maximum cable cross sections for universal clamps
UK 25 SK
UK 30 SK

20 / 25 mm
25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

773 034
773 130

F Universal Clamp, T pin Shaft


*) see table for clamping ranges and maximum cable cross sections for universal clamps
UK 25 SQ
UK 30 SQ

20 / 25 mm
25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

773 234
773 330

*) Clamping range and maximum cable cross section for


universal clamps at:
Fixed ball
Phase T pin
Rd / Fl
Cable
point
Collar width Clamping range cross section
20 / 25 / 30 mm
15 / 18 mm

95 mm2
/ 25 / 30 mm

120 mm2
Clamps must have the same maximum short-circuit current as earthing and
short-circuiting conductors (lk 1 s in A)!

www.dehn.de

127

Fixed Points

Three-pole
Devices

Single-pole
Devices

Phase Connecting Elements


Clamps with long shaft

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)
Threaded T pin shaft according to DIN 48087

Phase clamps for connecting single-pole


and three-pole earthing and short-circuiting devices to overhead lines
Long threaded T pin shaft for earthing
rods with robust aluminium cone coupling
Type PK1 protected against twisting

Clamp with long shaft and earthing


rod with aluminium cone coupling.

Rigid ball head cap with long shaft and earthing rod.
*) Clamping range and maximum cable cross section for
universal clamps at:
Fixed ball
Phase T pin
Rd / Fl
Cable
point
Collar width Clamping range cross section
20 / 25 / 30 mm
15 / 18 mm

95 mm2
/ 25 / 30 mm

120 mm2

Type

Fixed ball
point

Technical Data
Clamping unit

Cu alloy/gal Sn

Shaft

Cu alloy/gal Sn

Spring load unit

Cu alloy/gal Sn or St/Zn

Phase T pin
Rd / Fl
For cable Max. short-circuit
Collar width Clamping range cross section current Ik 1 s

Part
No.

772 314
0,45
772 324
0,72
773 236
0,71
773 331
0,79

1 ST

1 ST

1 ST

1 ST

A Ball Head Cap, rigid, long T pin Shaft


KKH 20 SQL
KKH 25 SQL

20 mm
25 mm

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 314
772 324

KKH 20 SQL
head cap 20 mm, SQL
314
KKH 25 SQL
head cap 25 mm, SQL
324
UK 25 SQL
Universal earthing clamp 25 mm, SQL
236
UK 30 SQL
Universal earthing clamp 30 mm, SQL
331

B Universal Clamp, long T pin Shaft


*) see table for clamping ranges and maximum cable cross sections for universal clamps
UK 25 SQL 20 / 25 mm
UK 30 SQL 25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

773 236
773 331

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

128

www.dehn.de

Ball
772
Ball
772
773
773

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

Earthing Rods

Installation Devices
Storage Devices

Earth Connecting Elements


Universal earth clamps, clamping
range 20 or 30 mm

For earth connection to fixed ball


points, phase T pins, round and flat
conductors
For wide clamping ranges up to 30 mm
Type PK1 protected against twisting

Universal earth clamp with insulated handle connected to a fixed ball


point.

*) Clamping range and maximum cable cross section for


universal clamps at:
Fixed ball
Phase T pin
Rd / Fl
Cable
point
Collar width Clamping range cross section
20 / 25 / 30 mm
15 / 18 mm

95 mm2
/ 25 / 30 mm

120 mm2

Technical Data

774 034
0,66
774 130
0,78
774 234
0,77
774 330
0,94
774 434
0,71
774 530
0,70

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

UEK 25 FS
Universal earthing clamp 25 mm, FS
034
UEK 30 FS
Universal earthing clamp 30 mm, FS
130
UEK 25 HG
Universal earthing clamp 25 mm, HG
234
UEK 30 HG
Universal earthing clamp 30 mm, HG
330
UEK 25 SKN
Universal earthing clamp 20 mm, SKN
434
UEK 30 SKN
Universal earthing clamp 30 mm, SKN
530

774

Clamping unit, shaft

Cu alloy/gal Sn

Spring load unit

St/gal Zn

Type

Fixed ball
point

Phase T pin
Rd / Fl
For cable Max. short-circuit
Collar width Clamping range cross section current Ik 1 s

Part
No.

A Universal Earth Clamps, with Wing Bolt


*) see table for clamping ranges and maximum cable cross sections for universal clamps

774
774
774
774
774

UEK 25 FS
UEK 30 FS

20 / 25 mm
25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

774 034
774 130

B Universal Earth Clamps, with insulated Handle


*) see table for clamping ranges and maximum cable cross sections for universal clamps
UEK 25 HG 20 / 25 mm
UEK 30 HG 25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

774 234
774 330

C Universal Earth Clamps, with Tommy Bar


*) see table for clamping ranges and maximum cable cross sections for universal clamps
UEK 25 SKN 20 / 25 mm
UEK 30 SKN 25 / 30 mm

15 mm
18 mm

20 mm
30 mm

25 ... 120 *) mm2


25 ... 120 *) mm2

23.7 kA
23.7 kA

774 434
774 530

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

www.dehn.de

129

Fixed Points

Three-pole
Devices

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Earth Connecting Elements


SAFETY EQUIPMENT
Ball head caps 20 or 25 mm, rigid EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

For earth connection to fixed ball


points, 20 or 25 mm
Ball head cap with wing bolt or insulated handle
Type PK1 protected against twisting

Ball head cap with insulated handle connected to an earth connecting


plate.
Technical Data

Type

Clamping unit, shaft

Cu alloy/gal Sn

Spring load unit

Cu alloy/gal Sn

Fixed ball
point

For cable
cross section

Max. short-circuit
current Ik 1 s

Part
No.
772 312
0,48
772 322
0,75
772 313
0,40
772 323
0,88

A Ball Head Caps, rigid, with Wing Bolt


KKH 20 FS
KKH 25 FS

20 mm
25 mm

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 312
772 322

KKH 20 FS
head cap 20 mm, FS
312
KKH 25 FS
head cap 25 mm, FS
322
KKH 20 HG
head cap 20 mm, HG
313
KKH 25 HG
head cap 25 mm, HG
323

B Ball Head Caps, rigid, with insulated Handle


KKH 20 HG
KKH 25 HG

20 mm
25 mm

25 ... 120 mm2


25 ... 150 mm2

23.7 kA
29.6 kA

772 313
772 323

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

130

www.dehn.de

1 ST

1 ST

1 ST

1 ST

Ball
772
Ball
772
Ball
772
Ball
772

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

Earthing Rods

Installation Devices
Storage Devices

Earth Connecting Elements


Earth connection units

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

For earth connection to M12/M16 connection units or grooved ring 16 mm


Wing bolt or tommy bar
Type PK1 or PK2 protected against
twisting

Earth connection unit with wing bolt.

Technical Data
Terminal lug

E-Cu/gal Sn

Wing nut

Cu alloy/gal Sn

Type

Dimensions

Protection against
twisting

For cable Max. short-circuit


cross section current Ik 1 s

Part
No.

A Earth Connection Units with Wing Nut


775 621
0,31
775 631
0,29
775 626
0,34
775 636
0,35
790 150
0,45
790 160
0,74

1 ST

1 ST

1 ST

1 ST

1 ST

1 ST

EAS EK FM 12
connection unit, wing-nut bolt M12
621
EAS EK FM 16
connection unit, wing-nut bold M16
631
EAS EK FS 12
connection unit, wing screw M12x15 mm
626
EAS EK FS 16
connection unit, wing screw M16x15 mm
636
EAB RN 16 FS
connector, wing screw
150
EAB RN 16 SKN
connector, grooved ring
160

Earth
775

EAS EK FM 12
EAS EK FM 16

M12
M16

PK1
PK1

25 ... 150 mm2


25 ... 150 mm2

29.6 kA
29.6 kA

775 621
775 631

25 ... 150 mm2


25 ... 150 mm2

29.6 kA
29.6 kA

775 626
775 636

Earth
775
Earth
775
Earth
775
Earth
790
Earth
790

B Earth Connection Units with Wing Bolt


EAS EK FS 12
EAS EK FS 16

M12 x 15 mm
M16 x 15 mm

PK1
PK1

C Earth Connection Sockets for Fixed Earthing Point with grooved Ring
*) for cable lengths v 2500 mm: max. up to 95 mm2
EAB RN 16 FS

16 mm

PK2

25 ... 150 *) mm2

29.6 kA

790 150

D Earth Connection Sockets for Fixed Earthing Point with grooved Ring
*) for cable lengths v 2500: max. up to 95 mm2
EAB RN 16 SKN

16 mm

PK2

25 ... 120 *) mm2

23.7 kA

790 160

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

www.dehn.de

131

Fixed Points

Three-pole
Devices

Single-pole
Devices

Earth Connecting Elements


Earth milling clamps

Cables, Connecting
Elements

Installation Devices
Storage Devices

Earthing Rods

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES
EN/IEC 61230 (DIN VDE 0683 Part 100)

For earth connection to flat profiles up


to 40 mm
Milling plate, disc springs and long
tommy bar for reliable contact
Type PK1 protected against twisting

Earth milling clamp used for coated steel masts.

Technical Data

Type

Clamping unit

MCI/gal Zn

Shaft

Ms/gal Zn

Milling plate

hardened steel/chrome-plated

Spring

Spring steel

Clamping
range

For cable
cross section

Max. short-circuit
current Ik 1 s

Part
No.

EFK FL40 SKN


milling clamp, 40 mm
190
EFK FL30 SKN
milling clamp, 30 mm, tommy bar
030

A Earth Milling Clamp for flat Profiles


With disc springs
EFK FL40 SKN

up to 40 mm

792 190
1,20
792 030
0,61

25 ... 95 mm2

18.7 kA

792 190

25 ... 50 mm2

9.9 kA

792 030

B Earth Milling Clamp for flat Profiles


EFK FL30 SKN

up to 30 mm

Clamps must have the same maximum short-circuit current as earthing and short-circuiting conductors
(lk 1 s in A)!

132

www.dehn.de

1 ST

1 ST

Earth
792
Earth
792

Three-pole
Devices

Fixed Points

Single-pole
Devices

Cables, Connecting
Elements

SAFETY EQUIPMENT
EARTHING AND SHORT-CIRCUITING DEVICES

Earthing Rods

Installation Devices
Storage Devices

Earth Connecting Elements


Earthing kit

For overhead line systems


For driving the tubular earth electrode
into the ground
Kit includes tubular earth electrode,
three-pole earthing busbar and
artificial leather bag

Earthing busbar and earthing cables mounted on a tubular earth


electrode.
Crimped cable lugs, PK3 type:
Hook-type cable lug protected
against twisting mounted on a threepole earthing busbar.

Technical Data
Tubular earth electrode St/tZn
Bolt

M10 x 35 mm StSt (V2A)

Handle

Wood

Earthing busbar

St/tZn

Type
799 009
0,00

A Earthing Kit
Pos. Qty.

1 ST

Type

Description

Part No.

Tubular earth electrode with drill

644 000

ESS 3P M10 FM

Three-pole earthing busbar

799 019

KLT 121 25 16

Artificial leather bag, empty

766 601

ES 3P FL ER

Earthing kit, complete

1000 mm

799 009 new

Single Parts for Earthing Kit

Tubular earth electrode with drill

644 000

Total length
lG
1000 mm
799 019
0,33

Part
No.

1 ST

ES 3P FL ER
799 009

644 000
4,45

Total length
lG

Model

1 ST

Position
1

Part No.
644 000

Three-Pole Earthing Busbar


With slot, to be mounted on the tubular earth electrode and for hook-type cable lug type PK3

ESS 3P M10 FM
799 019

Type
ESS 3P M10 FM

www.dehn.de

Dimensions
180 x 30 x 5 mm

Position
2

Part
No.
799 019 new