Anda di halaman 1dari 76

Contents

1.
1.1 1.2

MAIN CONTROL UNIT..................................................................................................... 6


MCU ................................................................................................................................................................ 6 Accessories for MCU211 .............................................................................................................................. 7

2.
2.1 2.2 2.3

OPERATING AND DISPLAY PANELS .......................................................................... 10


SecuriLan ................................................................................................................................................... 10 SecuriLine .................................................................................................................................................. 15 SecuriPro cases for panels ...................................................................................................................... 17

3.
3.1 3.2 3.3 3.4

INPUT AND OUTPUT MODULES, INTERFACES, REPEATERS ................................. 19


Modules SecuriLan .................................................................................................................................... 19 Modules SecuriLine ................................................................................................................................... 25 Networking interfaces................................................................................................................................. 36 Boxes for modules ...................................................................................................................................... 37

4.
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9

DETECTORS.................................................................................................................. 38
Automatic fire detectors SecuriStar addressable.................................................................................. 38 Automatic fire detectors SecuriStar conventional................................................................................. 41 Sockets and accessories for SecuriStar detectors ............................................................................... 43 Room indication lamps............................................................................................................................... 46 Automatic fire detectors conventional ex-proofed.................................................................................. 48 Flame detector............................................................................................................................................. 52 Ventilation duct detector ............................................................................................................................ 54 Manual call points addressable ................................................................................................................. 55 Manual call points conventional................................................................................................................ 57

4.10 Accessories for MCP .................................................................................................................................. 59 4.11 Wireless detectors ...................................................................................................................................... 60

5.
5.1 5.2 5.3 5.4

ACCESSORIES.............................................................................................................. 62
Sirens ........................................................................................................................................................... 62 Flash lights .................................................................................................................................................. 65 Other accessories ....................................................................................................................................... 66 Detector removal and test tools ................................................................................................................ 67

6.
6.1 6.2

POWER SUPPLY ........................................................................................................... 69


Batteries ....................................................................................................................................................... 69 External Power Supply ............................................................................................................................... 71

7. 8.

COMMISSIONING TOOLS............................................................................................. 73 SOFTWARE ................................................................................................................... 74

Securiton Product Catalogue 2007 - SecuriPro

9.
9.1 9.2 9.3 9.4 9.5

SPARE PARTS .............................................................................................................. 75


Spare parts for MCU ................................................................................................................................... 75 Spare parts for operating and display panels.......................................................................................... 75 Spare parts for modules SecuriLan......................................................................................................... 75 Spare parts for modules SecuriLine........................................................................................................ 76 Spare parts for commissioning set ........................................................................................................... 76

Securiton Product Catalogue 2007 - SecuriPro

Introduction

This product catalogue describes the most important components within the fire alarm system SecuriPro. All Securiton fire alarm systems, system components and detectors are developed and manufactured in Switzerland/Germany and comply with the most currently applicable standards (European standards, specifications made by fire brigades as well as European Institutes for Testing and Certification, etc.), as well as representing the cutting edge of technology based upon the most up-to-date scientific knowledge. Securiton's high quality standard has been documented by means of a quality assurance system, which has been certified for all divisions of the company in accordance with ISO 9001:2000. The planning of fire alarm systems, as well as the installation, commissioning and maintenance of products and the systems which they form, require special technical knowledge, and may therefore only be carried out by professionals who have been trained in this field. The product-specific training of technical staff must therefore either be carried out by Securiton or by persons who have been authorised by Securiton for this specific purpose. Additionally, the prevailing regulations and directives specific to the respective country with regard to planning, installation and use of products must be noted and observed without exception. Securiton is not liable for damages and consequential damages occurring as a result of tampering with or modifying our products, or as a result of their improper usage. This is also the case where items have been improperly stored or where there have been other external factors involved. The descriptions and technical data included in this catalogue are up-to-date at the time of release. We reserve the right to make alterations to them, particularly where justified by technological advancements. The illustrated products may also differ visually from the products supplied as a result of continuous further development of products. The layout of this catalogue is subject to copyright. The copying or reuse of text, illustrations and photos in any media (e.g. print, CD-ROM, Internet, etc.) contained within this catalogue - also in an abridged form - is only allowed with our explicit written permission. We assume no liability for typographic errors and obvious mistakes. Please quote the relevant item numbers when making enquiries or placing an order. Delivery conditions are regulated in the General Terms and Conditions of Securiton AG for Export Deliveries

Example of a typical entry for an item


Type & Article Number Please quote this number when making an enquiry or ordering. SecuriLine control board SCB 01 A For the connection of one multifunctional detector loop having up to 127 participants. The SCB01 A is used for the extension of SecuriPro or with one further loop Is plugged into the main board MCB Technical data Operating voltage Current consumption Ambient temperature Dimensions (H x W x D) Illustration 4300580-0002

20 to 30 V DC 60 mA -5 C to +45 C 120 x 60 x 50 mm Description and technical data

Securiton Product Catalogue 2007 - SecuriPro

Overview Fire Alarm System SecuriPro


System architecture R0400

SecuriLan devices MCU Main Control Unit MIC Main Indication and Control Map PCM Partial indication and Control Map PIM Partial Indication Map FBM Fire Brigade Map SIB Serial Interface Board PIB Printer Interface Board OCB Open Collector output Board ARB Alarm Routing Board FTR Fibre Optic Repeater

SecuriLine devices COM Command Module ICM Indication and Control Map IOM Input /Output Module LKM Ventilation Duct Detector MDI Multiple Detector Interface RMU Radio Master Unit ROM Relay Output Module SCI Special-detection Connection Interface SCU Stub Control Unit SDI Single Detector Interface SLI SecuriLine Interface SOM Surveyed Output Module SecuriStar Addressable Fire Detectors SSD Scattered Light Smoke Detector UTD Universal Smoke Detector STD Combined Heat and Smoke Detector

Special Fire Detection ASD Aspiration Smoke Detector ADW Linear Heat Detector TSC Temperature Sensor Cable Wireless Detectors RSD Radio Smoke Detector RCM Radio Contact Module

Securiton Product Catalogue 2007 - SecuriPro

1. Main Control Unit 1.1 MCU


Main Control Unit MCU 211B-47 Decentralised Main Control Unit within the fire alarm system Se curiPro . One MCU controls two detector loops and up to 10 LAN communication devices. On the LAN communication bus up to 60 devices can be connected to a network, mounted at the desired location: further MCU 211B Operation panel MIC 732/734 Indication panel PIM 731/732 Serial interface module SIB 71 Printer interface module PIB 71 Open collector output board OCB 71 Alarm routing board ARB 71 The MCU 211 contains: Power supply unit 24 V DC 3 A Basic module MCB 02 B one SecuriLine module SCB 01 A for the connection of one loop having up to 127 devices. Emergency alarm module EDB 03 Low discharge protection for the backup battery (max. battery size 12 V/45 Ah) Technical data Mains voltage Operating voltage Ambient temperature Protection class Dimensions (H x W x D) Case cover material VdS-Number Main Control Unit MCU 211B-48 Same as MCU 211B-47, except: Power supply unit 24 V DC 5 A 5300691-0048 5300691-0047

230 V AC (50 Hz) 10 to 30 V DC -5 C to + 45 C IP 32 695 x 456 x 231 mm Steel untreated G 298007

Securiton Product Catalogue 2007 - SecuriPro

1.2 Accessories for MCU211


SecuriLine control board SCB 01 A For the connection of one multifunctional detector loop having up to 127 participants. The SCB01 A is used for the extension of SecuriPro or with one further loop Is plugged into the main board MCB Technical data Operating voltage Current consumption Ambient temperature Dimensions (H x W x D) MCU Extension Set MCB 02B-2 Expansion Set for MCU 211-48 A/B. Extends the MCU for the connection of up to 4 detector loops. The MCB 02B-2 contains: MCB02B SPL 21 A (Support plate) Connection wires The SecuriLine module SCB 01 A must be ordered separately LAN Control Board LCB 02 Monitors LAN 1 and LAN 2 for short circuit and open circuit. There are 2 pcs. of the LCB02 necessary per SecuriPro installation, connected to each end of the LAN bus. Technical data Operating voltage Current consumption Ambient temperature Dimensions (H x W x D) VdS-number 4300771-0001

4300580-0002

20 to 30 V DC 60 mA -5 C to +45 C 120 x 60 x 50 mm

4300828-0002

20 to 30 V DC 36 mA -5 C to +45 C 85 x 90 x 20 mm G 204098

Securiton Product Catalogue 2007 - SecuriPro

Mains Filter Module MFM 31 The mains filter protects the system against malfunctions caused by electromagnetic disturbances in a wide frequency range, transmitted via mains connection. The MFM is highly recommended in industrial environments or wherever EMC may cause a problem. Technical data Mains voltage Rated current Ambient temperature Leak current Frequency range Dimensions (H x W x D) Overvoltage Arrester OVA 31 The over voltage arrester OVA 31 protects the system against damages due to over voltage on the mains. It conducts high-energy over voltages by means of gas-filled arresters to earth. Low-energy over voltages are eliminated by means of the zinc oxide varistors. Technical data Mains voltage Rated current Ambient temperature Dimensions (H x W x D) Support plate to built into the MCU for LAN and Line modules SPL 21 A Slew able support plate to build into the MCU for mounting LAN/Line modules 4300671 4300429 4300505

230 V AC (50 Hz) 6A -5 C to +45 C max. 0.5 mA 150 kHz to 300MHZ 73 x 22 x 80 mm

230 V AC (50 Hz) 6A -5 C to +45 C 55 x 60 x 60 mm

MCU extension box ADB 21A-04 Additional Box having the same dimensions as the MCU box for the extension with further system components and 2 batteries 12 V/40 Ah Technical data Protection class Dimensions (H x W x D) Casing
Securiton Product Catalogue 2007 - SecuriPro

4300673-0004

IP 32 695 x 456 x 231 mm Special steel blank


8

Lightning protection device for SecuriLan

BS 84/1 with BSP 84 Protection of a SecuriPro system from the effect of lightning strikes This unit is used for the connection of the SecuriLan , MDI lines, or any input/output lines. For two SecuriLan Varistor for low-energy surges Gas-filled arresters for high-energy surges Metallic mounting plate, plastic box Technical data Operating voltage (normal 12V/24V) Rated current Pluggable terminals Dimensions (H x W x D) Lightning protection device for SecuriLine BS 81/1 with BSP 81 Protection of a SecuriPro system from the effect of lightning strikes This unit is used for the connection of the SecuriLine. For two SecuriLine Varistor for low-energy surges Gas-filled arresters for high-energy surges Metallic mounting plate, plastic box Technical data Operating voltage Rated current Pluggable terminals Dimensions (H x W x D) Lightning protection device for SecuriLan and SecuriLine BS 85 with BSP 81 and 84 Protection of a SecuriPro system from the effect of lightning strikes. This unit is used for the connection of the SecuriLan and SecuriLine. For two SecuriLan For two SecuriLine Varistor for low-energy surges Gas-filled arresters for high-energy surges Metallic mounting plate, plastic box Technical data Operating voltage Rated current Pluggable terminals Dimensions (H x W x D)
Securiton Product Catalogue 2007 - SecuriPro

5700109

max.50V max. 4A 2 1.5 mm 260 x 220 x 85 mm

5700108

(normal 12V/24V) max.50V max. 4A 1.5 mm2 260 x 220 x 85 mm

5700110

(normal 12V/24V) max.50V max. 4A 1.5 mm2 260 x 440 x 110 mm


9

2. Operating and display panels 2.1 SecuriLan

Operating and display panel, SecuriLan MIC 732

5300643-0005

Main indication and control panel for SecuriPro fire alarm systems for the connection to the redundant communication and power supply bus. The MIC 732 provides a 4x 40 character display with backlight, a numerical input block of 12 keys, five soft keys and 16 LED indicators. Various display languages are implemented, based on the Latin character set. Several MIC 732 can be connected to a SecuriPro communica tion bus SecuriLan . The operating panel MIC 732 contains: Polycarbonate housing Key switch for operation release Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number

10 to 30 V DC 70 mA -5 C to +45 C IP 32 168 x 360 x 52 mm anthracite violet, RAL 3002005 G 298022

Securiton Product Catalogue 2007 - SecuriPro

10

Operating and display panel, SecuriLan MIC 734 Main indication and control panel for SecuriPro fire alarm systems for the connection to the redundant communication and power supply bus. The MIC 734 provides a 8x 40 character display with backlight, a numerical input block of 12 keys, five soft keys and 16 LED indicators. Various display languages are implemented, based on the Latin and Cyrillic character set. Several MIC 734 can be connected to a SecuriPro communica tion bus SecuriLan . The operating panel MIC 734 contains: Polycarbonate housing Key switch for operation release Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number

5300671-0005

10 to 30 V DC 70 mA -5 C to +45 C IP 32 168 x 360 x 52 mm anthracite violet, RAL 3002005 G 204097

Securiton Product Catalogue 2007 - SecuriPro

11

Operating and display panel, SecuriLan MIC 742

5300728-0302

Main indication and control panel for SecuriPro fire alarm systems for the connection to the redundant communication and power supply bus. The MIC 742 provides a 4x 40 character display with backlight, a numerical input block of 12 keys, five soft keys and 16 LED indicators. Various display languages are implemented, based on the Latin character set. Several MIC 742 can be connected to a SecuriPro communica tion bus SecuriLan . Furthermore the MIC 742 includes fire brigade control and indication according to Swedish Standard SS 3654. The operating panel MIC 742 contains: Polycarbonate housing No fire brigade key for operation release Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour SBSC-Number Operating and display panel, SecuriLan

10 to 30 V DC 70 mA -5 C to +45 C IP 32 168 x 360 x 52 mm anthracite violet, RAL 3002005 not received yet

PCM 731 A For switching and indicating functions in a SecuriPro system. Functions on buttons and LEDs can be configured via software. 16 LEDs (8 red and 8 yellow, pair wise) 8 push buttons Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Display panel, SecuriLan PCM 731 A Same as PCM 731A, 5300681-0002, except: without housing
Securiton Product Catalogue 2007 - SecuriPro

5300681-0002

10 to 30 V DC 15 mA -5 C to +45 C IP 32 168 x 120 x 52 mm anthracite violet, RAL 3002005 G 200033

5300681-0001

12

Display panel, SecuriLan

PIM 731 A For status indication of detectors, zones or any other system parts. 32 LEDs (16 red and 16 yellow, pair wise) Holder for inscription labels LEDs can be configured via software Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Display panel, SecuriLan

5300682-0002

10 to 30 V DC 15 mA -5 C to +45 C IP 32 168 x 120 x 52 mm anthracite violet, RAL 3002005 G 299005

PIM 731 A Same as PIM 731A, 5300682-0002, except: without housing Display panel, SecuriLan PIM 732 A For status indication of detectors, zones or any other system parts. 32 LEDs (all red) Holder for inscription labels LEDs can be configured via software Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Display panel, SecuriLan PIM 732 A Same as PIM 732A, 5300683-0002, except: without housing

5300682-0001

5300683-0002

10 to 30 V DC 15 mA -5 C to +45 C IP 32 168 x 120 x 52 mm anthracite violet, RAL 3002005 G 299007

5300683-0001

Securiton Product Catalogue 2007 - SecuriPro

13

Display panel, SecuriLan

PIM 733 A For status indication of detectors, zones or any other system parts. 32 LEDs (all yellow) Holder for inscription labels LEDs can be configured via software Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Display panel, SecuriLan

5300687-0002

10 to 30 V DC 15 mA -5 C to +45 C IP 32 168 x 120 x 52 mm anthracite violet, RAL 3002005 G 299006

PIM 733 A Same as PIM 733A, 5300687-0002, except: without housing Operating panel, SecuriLan KSW 731 For release of SecuriLan operating panels without an integrated key switch. Only in combination with another SecuriLan participant, e.g. PCM 731 Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Display panel, SecuriLan

5300687-0001

5300647-0005

10 to 30 V DC 0 mA -5 C to +45 C IP 32 168 x 120 x 52 mm anthracite violet, RAL 3002005 G 200037

KSW 731 Same as KSW 731, 5300647-0005, except: without housing

5300647-0003

Securiton Product Catalogue 2007 - SecuriPro

14

2.2 SecuriLine

Operating and display panel, SecuriLine ICM 731/1 Code input unit for indicating and controlling sectors or zones in SecuriPro FAS. Up to 9 functions free programmable 8 LED for status indication Code input key block Lamp test button Key switch Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Operating and display panel, SecuriLine ICM 731/1 Same as ICM 731, 5300676-0007, except: without housing

5300676-0007

15 to 30 V DC 0.074 mA -5 C to +45 C IP 32 120 x 168 x 52 mm anthracite violet, RAL 3002005 G 200031

5300676-0005

Securiton Product Catalogue 2007 - SecuriPro

15

Operating and display panel, SecuriLine KIM 732

5300678-0005

Operating and display unit for indicating and controlling sectors or zones in SecuriPro FAS. 6 LED (2 red, 2 yellow, 2 green) for status indication, free programmable 3 buttons, free programmable Lamp test button Key switch Technical data Operating voltage Operating current, constant Ambient temperature Protection class Dimensions (H x W x D) Colour VdS-Number Operating and display panel, SecuriLine KIM 732 Same as KIM 732, 5300678-0005, except: without housing 5300678-0003

15 to 30 V DC 0.074 mA -5 C to +45 C IP 32 120 x 168 x 52 mm anthracite violet, RAL 3002005 G 204093

Securiton Product Catalogue 2007 - SecuriPro

16

2.3 SecuriPro cases for panels


Cabinet small, SecuriPro panels FGG 716 Case base (bottom) for one of the small sized SecuriPro indication or operating panels, such as: PIM PCM KSW KIM ICM Technical data Dimensions (H x W x D) Material Colour Cabinet big, SecuriPro panels FGG 717 Case base (bottom) inclusive 2 separation rips CRB 01 for up to 3 of the small sized SecuriPro indication or operating panels, such as: PIM PCM KSW KIM ICM Technical data Dimensions (H x W x D) Material Colour Blind covering plate BCP 02 Covers an unused or reserve place in a big sized cabinet FGG 717. It has the size to cover the place of one small sized panel. Technical data Dimensions (H x W x D) Material Colour 4300533-0002 4300537-0003

4300534-0002

167 x 120 x 52 mm Polycarbonate anthracite violet, RAL 3002005

167 x 360 x 52 mm Polycarbonate anthracite violet, RAL 3002005

160 x 100 x 30 mm Polycarbonate anthracite violet, RAL 3002005

Securiton Product Catalogue 2007 - SecuriPro

17

Separation rip for FGG 716 CRB 01 Compensation rip in order to cover the gap between two small sizes panels aor blind plate which are fitted in a big sized cabinet FGG 716 Technical data Material Colour Table stand TST 01 For mounting a SecuriPro panel on a table or on a wall. Fits for cabinet FGG 716 or FGG 717 (2 units TST 01 needed) Technical data Material Colour

4300530-0002

Polycarbonate anthracite violet, RAL 3002005

4300531-0002

Polycarbonate anthracite violet, RAL 3002005

Levelling Wedge LWE 716 The levelling wedge LWE 716 is used when several FGG 71x have to be mounted one under the other, or when no map inclination is desired. For FGG 716 1 LWE 716 is required For FGG 717 3 LWE 716 are required Technical data Material Colour 4300532-0002

Polycarbonate anthracite violet, RAL 3002005

Key hole covering set KCS 71 The key hole covering set is used for MICs, where no key switch is required for MIC731/732/733/734 Technical data Material Colour 234150

Polycarbonate anthracite violet, RAL 3002005

Securiton Product Catalogue 2007 - SecuriPro

18

3. Input and output modules, Interfaces, Repeaters 3.1 Modules SecuriLan


Open collector output board, SecuriLan OCB 71 32 free programmable open-collector outputs inclusive 4 supplyoutputs for the loads with distance holders, no box Technical data Operating voltage Operating current, constant OC outputs Ambient temperature Dimensions (H x W x D) VdS-Number Alarm routing board, SecuriLan

4300457-0003

20 to 30 V DC 13 mA 50 V/50 mA -5 C to +45 C 100 x 160 x 20 mm G 200039

ARB 71/1A Interface to an alarm transmission unit. Outputs for alarm / fault / switch on control / others and inputs for monitoring the status of the transmission unit. An emergency alarm path can activate the alarm output in case of a system failure. with distance holders, no box

4300811-0003

Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) VdS-Number

20 to 30 V DC 60 mA -5 C to +45 C 100 x 160 x 20 mm G 299003

Securiton Product Catalogue 2007 - SecuriPro

19

Serial interface board, SecuriLan

SIB 71/1A Interface to an alarm management system SLS. Interface type RS232 with distance holders, no box

4300773-0123

Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) Serial interface board, SecuriLan

10 to 30 V DC 15 mA -5 C to +45 C 160 x 100 x 30 mm

SIB 71/2A Interface to a serial log printer. Interface type RS232 with distance holders, no box Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) Serial interface board, SecuriLan

4300786-0223

10 to 30 V DC 15 mA -5 C to +45 C 160 x 100 x 30 mm

SIB 71/4A Interface to a paging system via ESPA protocol. Interface type RS 232 with distance holders, no box Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) Serial interface board, SecuriLan

4300829-0423

10 to 30 V DC 15 mA -5 C to +45 C 160 x 100 x 30 mm

SIB 71/4A Same as SIB 71/4A 4300829.0423, except: Interface type RS 422

4300829-0433

Securiton Product Catalogue 2007 - SecuriPro

20

Parallel Interface board, SecuriLan

PIB 71 Interface to a printer via standard parallel printer cable. with distance holders, no box Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) Printer module, SecuriLan ILP 151 Integrated log printer, for continuous logging of events in SecuriPro fire alarm systems, with paper winding device. Thermal printer to the SecuriPro FAS incl. LPM 151, PIB 71 and GPR/11347 Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) Printer module, SecuriLan

4300774-0002

10 to 30 V DC 15 mA -5 C to +45 C 160 x 100 x 30 mm

5700115-0002

10 to 30 V DC 6 to 10 mA -5 C to +45 C 360 x 167.5 x 60 mm

GPR/11347 Spare paper roll for Log Printer ILP151, 11m Delivery unit 1 pcs.

3610346

Securiton Product Catalogue 2007 - SecuriPro

21

LAN repeater module, SecuriLan

SLR 811 SecuriLan repeater for the extension of the system communication bus from 1500 m up to max. 2700 m. max. 1 repeater per LAN in fire alarm systems totally 2 repeaters (LAN 1 and LAN 2) inclusive support rail to be mounted in the MCU Technical data Operating voltage Operating current, constant Max. cable length LAN Ambient temperature Dimensions (H x W x D) Fibre optic module, multimode, SecuriLan FTR 811 Fibre optic twisted pair repeater for the connection of multimode fibre optic cable. Bus or loop topology is possible. Multimode cable (62,5/125 m); 1320 nm 2 repeater per fibre optic segment no configuration is necessary from Release R 01.03.00.004 no emergency path inclusive support plate APL21 to be mounted into the MCU Technical data Operating voltage Operating current, constant Max. cable length LAN (Twisted pair) Max. fibre optic cable length Fibre optic cable Wave length Ambient temperature Dimensions (H x W x D)

5700101

27 V DC 40 mA 2700 m 0 C to +60 C 95 x 45 x 38 mm

5700102

27 V DC 110 mA 1500 m 20 km Multimode 62,5/125 m 1320 nm - 40 C to +85 C 155 x 100 x 32 mm

Securiton Product Catalogue 2007 - SecuriPro

22

Fibre optic module, single mode, SecuriLan

FTR 813 consisting of 2 items: LR01 (Repeater bridging type) ATR 22 (Support rail) Photo without ATR22 Fibre optic twisted pair repeater for the connection of single mode fibre optic cable in a bus topology. Bridging type Single mode cable (9/125 m); 1320 nm 2 repeater per fibre optic segment LAN 1 2 repeater per fibre optic segment LAN 2 no configuration is necessary from Release R 01.03.00.004 no emergency path support rail ATR22 (to be ordered separately) to be mounted in the MCU Technical data Operating voltage Power consumption Max. cable length LAN (Twisted pair) Max. fibre optic cable length Fibre optic cable Wave length Ambient temperature Dimensions (H x W x D) 4700059 4700061

27 V DC 3W 1500 m 14 km Mono mode 9/125 m 1320 nm -5 C to +50 C 100 x 55 x 125 mm

Securiton Product Catalogue 2007 - SecuriPro

23

Fibre optic module, single mode, SecuriLan

FTR 813 PP consisting of 2 items: LR01 PP (Repeater end type) ATR 22 (Support rail) Photo without ATR22 Fibre optic twisted pair repeater for the connection of single mode fibre optic cable in a bus topology. End type (point to point) Single mode cable (9/125 m); 1320 nm 2 repeater per fibre optic segment LAN 1 2 repeater per fibre optic segment LAN 2 no configuration is necessary from Release R 01.03.00.004 no emergency path support rail ATR22 (to be ordered separately) to be mounted in the MCU Technical data Operating voltage Power consumption Max. cable length LAN (Twisted pair) Max. fibre optic cable length Fibre optic cable Wave length Ambient temperature Dimensions (H x W x D) 4700060 4700061

27 V DC 3W 1500 m 14 km Mono mode 9/125 m 1320 nm -5 C to +50 C 100 x 55 x 125 mm

Securiton Product Catalogue 2007 - SecuriPro

24

3.2 Modules SecuriLine


Special detector interface module, SecuriLine SCI 82

4300788-0003

Special detector connection interface for the integration of Securitons special fire detection systems such as ASD, ADW, TSC 4 inputs and 2 relay outputs, freely programmable. with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current, constant Relay outputs Ambient temperature Dimensions (H x W x D) VdS-Number Special detector interface module, SecuriLine SCI 82 Same as SCI 82, 4300788-0003, except: incl. installation box DOS816 sm Special detector interface module, SecuriLine

18 to 30 V DC 1 mA 30 V AC/2 A -5 C to +45 C 80 x 50 x 20 mm G 204096

4300788-0005

SCI 82 installation set Same as SCI 82, 4300788-0003, except: incl. fastening bow for mounting into the ADW511 box SecuriLine interface module, SecuriLine SLI 51A Communication interface for the integration of Securitons Aspira tion Smoke Detector system ASD 516 to SecuriLine . to be mounted into the ASD516 integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage 16 to 30 V DC Operating current SecuriLine (typically / max.) 0.9 / 1.3mA Relay output (VDC / A / W) 60 / 2 / 30 Ambient temperature -5 C to +45 C Dimensions (L x W x H) 95 x 58 x 17 mm

4300789-0201

4301018-0201

Securiton Product Catalogue 2007 - SecuriPro

25

Conventional detector interface module, SecuriLine MDI 82

4300464-0003

Provides 8 conventional fire detection lines. A max. of 32 detectors can be connected to each line. Additionally, 3 freely programmable open collector outputs are available with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) VdS-Number Conventional detector interface module, SecuriLine MDI 82 Same as MDI82, 4300464-0003, except: incl. installation box DOS816 sm Conventional detector interface module, SecuriLine MDI 82 Same as MDI82, 4300464-0003, except: incl. installation box Rittal IP 66

15 to 30 V DC 10 mA -5 C to +45 C 110 x 90 x 20 mm G 2000845

4300464-0005

4300464-0006

Securiton Product Catalogue 2007 - SecuriPro

26

Multiple Detector Interface module, for detector technology series 140/150, SecuriLine MDI 140

4301030-0003

With the Multiple Detector Interface MDI 140, fire detectors and alarm transmitters of series 140 and 150 can be connected to a SecuriPro fire alarm control panel MCU 211B. The MDI 140 permits the replacement / renovation of an HX/HS fire alarm control panel by a SecuriPro -MCU 211B without it being necessary to replace the existing fire detectors of series 140 or 150. The MDI 140 has emergency alarm capability and, in the event of a CPU failure (MDI or MCU), can recognize a fire alarm of a detector and process it as an emergency alarm. Supports the following 140 series devices: ORM 140; ORM 140K; WDM 240; WMM 241; UFM 840; IFM 841; DFM 155; FT 513; ADX 156 Supports the following 150 series devices: ORM 150; ORM 150K; WDM 152; WMM 153; DFM 155; FT 513; ADX 156; SBS 157; UAS 159; RKM 150 provides 8 fire detection lines or 4 loops with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (L x W x D) VdS-Number

15 to 18 V DC 57 mA -5 C to +45 C 160 x 100 x 17 mm not yet received

Securiton Product Catalogue 2007 - SecuriPro

27

Single detector interface module, SecuriLine SDI 82A

4300808-0001

Addressing module for detectors, contacts, controls and signalling devices. With emergency alarm transmission. Provides 3 inputs and 1 open collector output, freely programmable integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current, constant Ambient temperature Colour Dimensions (H x W x D) Single detector interface module, SecuriLine SDI 81A Addressing module for detectors, contacts, controls and signalling devices. No emergency alarm transmission. Provides 3 inputs and 1 output, freely programmable integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current, constant Ambient temperature Colour Dimensions (H x W x D) 4300808-0001

15 to 30 V DC 0.5 mA -55 C to +70 C red 32 x 22 x 14 mm

15 to 30 V DC 0.5 mA -55 C to +70 C green 32 x 22 x 14 mm

Securiton Product Catalogue 2007 - SecuriPro

28

Single detector interface module, SecuriLine SDI 81/1-2

4300645-0002

Same as SDI81A, 4300808-0001, except: Mounted into a phoenix box Provides 3 inputs and 2 output, freely programmable

Single detector interface module, SecuriLine SDI 81/A-2

4300807-0002

To be mounted on the mounting rail into the EPSU. For technical monitoring of the power supply EPSU and fault transmission to the SecuriPro Same as SDI81A, 4300808-0001, except: Mounted into a phoenix box

Securiton Product Catalogue 2007 - SecuriPro

29

In- output module, SecuriLine

COM 81 Command module for control and signal reception Provides 1 relay output and 1 input, freely programmable with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current, constant Relay contact Ambient temperature Dimensions (H x W x D) VdS-Number In- output module, SecuriLine COM 81 Same as COM 81, 4300458-0003, except: incl. installation box DOS816 sm In- output module, SecuriLine

4300458-0003

15 to 30 V DC 0.5 mA 50 VDC /1 A -5 C to +45 C 42 x 39 x 15 mm G 200029

4300458-0005

COM 81 Same as COM 81, 4300458-0003, except: incl. installation box Rittal IP 66

4300458-0006

Securiton Product Catalogue 2007 - SecuriPro

30

Relay output module, SecuriLine

ROM 81/1 For control of loads up to 230VAC. Provides 3 changeover relay output contacts and 1 input, freely programmable with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current, constant Relay contact Ambient temperature Dimensions (H x W x D) VdS-Number Relay output module, SecuriLine

4300647-0003

15 to 30 V DC 0.2 mA 250 V /6 A -5 C to +45 C 110 x 90 x 40 mm G 204094

ROM 81/1 Same as ROM 81/1 4300647-0003, except: incl. installation box DOS816 sm Relay output module, SecuriLine ROM 81/A For repair and extensions only. Compatible to Release 0101 - 0103 with distance holders, no box Relay output module, SecuriLine ROM 81/A For repair and extensions only. Compatible to Release 0101 - 0103 incl. installation box DOS816 sm

4300647-0005

4300755-0003

4300755-0005

Securiton Product Catalogue 2007 - SecuriPro

31

In- output module, SecuriLine

IOM 81A For control of loads up to 60VDC. Provides 5 changeover relay output contacts and 3 optocoupler inputs, freely programmable with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current, constant Relay contact Input voltage Ambient temperature Dimensions (H x W x D) VdS-Number Relay output module, SecuriLine IOM 81A Same as IOM 81 4300461-0003, except: incl. installation box DOS816 sm

4300757-0003

15 to 30 V DC 0.2 mA 60 V /1 A 5 to 50 V DC -5 C to +45 C 120 x 60 x 20 mm G 200025

4300757-0005

Securiton Product Catalogue 2007 - SecuriPro

32

Surveyed relay output module, SecuriLine SOM 81

4300460-0003

In combination with the line termination device LUG 81 or LUG82, the SOM81 provides 3 monitored relay outputs, especially designed for driving alarm devices. An input for the emergency alarm path allows the alarm transmission even in case of a system processor failure. The 3 outputs are freely programmable. Per output, one LUG device is needed. with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current Fuses at each output Max. output voltage Ambient temperature Dimensions (H x W x D) VdS-Number Surveyed relay output module, SecuriLine SOM 81 Same as SOM 81, 4300460-0003, except: incl. installation box DOS816 sm Surveyed relay output module, SecuriLine SOM 81 Same as SOM 81, 4300460-0003, except: incl. installation box Rittal IP 66

15 to 30 V DC 15 mA 2 A-T 60 V DC -5 C to +45 C 110 x 90 x 35 mm G 200021

4300460-0005

4300460-0006

Securiton Product Catalogue 2007 - SecuriPro

33

Line terminator, for SOM 81 LUG 82 Line termination device, to be built-in alarm medias, connected to SOM 81 outputs. Technical data Operating voltage Operating current (monitoring) Rated current Ambient temperature Line terminator, for SOM 81 LUG 81 Line termination device, to be built-in alarm medias, connected to SOM 81 outputs. Technical data Operating voltage Operating current (monitoring) Rated current Ambient temperature Stick control unit, SecuriLine

5700089

15 to 30 V DC 4 mA 1A -20 C to +50 C

5700088

15 to 30 V DC 4 mA 4.5 A -20 C to +50 C

SCU 81 Driver module for a stub line within a SecuriLine . Up to 32 Se curiLine devices can be connected to one SCU 81. with distance holders, no box integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current, constant Ambient temperature Dimensions (H x W x D) VdS-Number Stick control unit, SecuriLine SCU 81 Same as SCU 81, 4300459-0003, except: incl. installation box DOS816 sm

4300459-0003

15 to 30 V DC 1.2 mA -5 C to +45 C 60 x 60 x 20 mm G 204095

4300459-0005

Securiton Product Catalogue 2007 - SecuriPro

34

Radio Master Unit, SecuriLine

RMU 251AP The RMU 251 is the interface between wireless detectors and the SecuriLine . Is consists of the Radio SecuriLine Interface RSI 51 and the Radio Master Module RMM51 (antenna) It is monitoring all 28 radio communication channels against foreign signals and manages the communication from and to the associated radio detectors. Controls up to 60 radio detectors For wireless smoke detectors RSD 532, radio contact module RCM 51 and wireless picture detectors RPD 412 RSI51 in installation box DOS816 sm, for surface mounting The battery for the RSI is an option and has to be ordered separately integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current, max Ambient temperature Protection class Dimensions RSI51 (L x W x D) Dimensions RMM51 (D x H) VdS-Number Radio Master Unit, SecuriLine

5700120-0001

RMM 51

RSI 51

9 to 29 V DC 110 mA -5 C to +45 C IP 30 160 x 130 x 50 mm 90 x 40 mm not yet received

RMU 251UP Same as RMU 251 AP (5700120-0001), except: RSI 51 in installation box DOS816 fm, for flush mounting Radio Master Unit, SecuriLine RMM 51 RSI 51 Same as RMU 251 AP (5700120-0001), except: RSI 51 with distance holders, no box for installation inside the MCU box Battery 9 V for RSI 51, option BAT 9V Optional 9V alkaline block battery for RSI 51

5700121-0001

5700122-0001 5700123-0001

2360039-0001

Securiton Product Catalogue 2007 - SecuriPro

35

3.3 Networking interfaces


GMA OPC Gateway Hardware, interface networking unit OPC Gateway HW The GMA-OPC gateway is intended to supply an interface coupling of a danger warning system (GMA) based on the OPC standard to a super ordinate system. The states of the GMA objects are made available to the super ordinate system according to the OPC standard. Technical data Operating voltage Temperature Protection class Dimensions (H x W x D) Weight Housing material Housing colour GMA OPC Gateway Software, interface networking unit OPC Gateway SW OPC Gateway Software package 0.102112 0.102113

10 to 32 V DC 0 to +50 C IP 40 135 x 64 x 135 1000 g Aluminium Electrolytically oxidized black

Securiton Product Catalogue 2007 - SecuriPro

36

3.4 Boxes for modules


Installation box DOS 816 SM Installation box, surface mounting, for general propose or SecuriLine modules, such as: SCU 81, IOM 81, ROM 81, MDI 82 SOM 81, COM 81, SCI 82 Technical data Temperature Protection class Dimensions (H x W x D) Material Colour Installation box DOS 816 FM Installation box, flush mounting, for general propose or Se curiLine modules, such as: SCU 81, IOM 81, ROM 81, MDI 82 SOM 81, COM 81, SCI 82 Technical data Temperature Protection class Dimensions (H x W x D) Material Colour Installation box Rittal Installation box, flush mounting, for general propose IP 66 Technical data Temperature Protection class Dimensions (H x W x D) Material Colour 2850341 2850343 2850342

-25 to +60 C up to IP 54 125 x 160 x 45 mm ABS pure white, similar RAL 9010

-25 to +60 C up to IP 54 125 x 160 x 45 mm ABS pure white, similar RAL 9010

-25 to +60 C up to IP 66 125 x 160 x 45 mm ABS grey

Securiton Product Catalogue 2007 - SecuriPro

37

4. Detectors 4.1 Automatic fire detectors SecuriStar addressable


SecuriStar fire detector STD 531 Combined smoke and temperature detector, complying to EN 54/7 (smoke) and EN 54/5 (heat). Early detection of smothering and open fire with and without smoke emission. addressable self monitoring of all detector parts false alarm resistant alarm evaluation 2 pre-warning levels for smoke constant sensitivity through dust compensation 2 contamination levels heat detection classes A1, A2 and B heat class setting via system database warning signal for high ambient temperature separate alarm signalisation for smoke and heat smoke and heat part can be temporary or permanent disabled, independently. programmable control output integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Colour Dimensions (D x H) Complies regulation VdS-Number SecuriStar fire detector STD 531 CP same as STD 531, except: higher protection level of the electronic circuit board. more resistant in environments where the humidity can temporary reach a higher level. 5000571-0002

5000571-0001

15 to 30 V DC max. 0.25 mA -20 C to +60 C (incl. USB 501) IP 44 white 118 x 78 mm EN 54/7 and EN 54/5 G 204015

Securiton Product Catalogue 2007 - SecuriPro

38

SecuriStar fire detector STD 531 MC Scattered Light Smoke Detector, personalized colour. Same as STD 531, except: Colour according to any RAL Number 5000571-0291

SecuriStar fire detector SSD 531 Scattered light smoke detector. Optical detector for early detection of smothering and open fire. addressable self monitoring of all detector parts false alarm resistant alarm evaluation Pre-warning and alarm level constant sensitivity through dust compensation several colour versions available integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Colour Dimensions (D x H) Complies regulation VdS-Number SecuriStar fire detector SSD 531 MC Scattered Light Smoke Detector, personalized colour. Same as SSD 531, except: Colour according to any RAL Number 5000573-0291 5000573-0001

15 to 30 V DC max. 0.25 mA -20 C to +60 C (incl. USB 501) IP 44 white 118 x 78 mm EN 54/7 G 297050

Securiton Product Catalogue 2007 - SecuriPro

39

SecuriStar fire detector UTD 531-1 Universal temperature detector for early detection of open fire creating a high temperature rise. addressable false alarm resistant alarm evaluation maximum and differential heat alarm integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current (normal) Ambient temperature Protection class (incl. USB 501) Colour Dimensions (D x H) Complies regulation VdS-Number SecuriStar fire detector UTD 531-2 same as UTD 531-1, except: Complies regulation SecuriStar fire detector UTD 531-3 same as UTD 531-1, except: Complies regulation EN 54/5 B 5100154-0003

5100154-0001

15 to 30 V DC max. 0.15 mA -20 C to +70 C IP 22 white 118 x 78 mm EN 54/5 A1 G 297048

5100154-0002

EN 54/5 A2

Securiton Product Catalogue 2007 - SecuriPro

40

4.2 Automatic fire detectors SecuriStar conventional


SecuriStar fire detector SSD 521 Scattered light smoke detector. Optical detector for early detection of smothering and open fire. conventional self monitoring of all detector parts false alarm resistant alarm evaluation constant sensitivity through dust compensation Connection to SecuriLine via MDI module Technical data Operating voltage Operating current (normal) Ambient temperature Protection class (incl. USB 501) Colour Dimensions (D x H) Complies regulation VdS-Number SecuriStar fire detector SSD 521 MC Scattered Light Smoke Detector, personalized colour. Same as SSD 521, except: Colour according to any RAL Number 5000545-0291

5000545-0001

18 to 30 V DC 0.12 mA -20 C to +60 C IP 44 white 118 x 78 mm EN 54/7 G 297050

Securiton Product Catalogue 2007 - SecuriPro

41

SecuriStar fire detector UTD 521-1 Universal temperature detector for early detection of open fire creating a high temperature rise. conventional false alarm resistant alarm evaluation maximum and differential heat alarm Connection to SecuriLine via MDI module Technical data Operating voltage Operating current (normal) Ambient temperature Protection class (incl. USB 501) Colour Dimensions (D x H) Complies regulation VdS-Number SecuriStar fire detector UTD 521-2 same as UTD 521-1, except: Complies regulation SecuriStar fire detector UTD 521-3 same as UTD 521-1, except: Complies regulation EN 54/5 B 5100153-0003 EN 54/5 A2 5100153-0002

5100153-0001

18 to 30 V DC max. 0.15 mA -20 C to +70 C IP 22 white 118 x 78 mm EN 54/5 A1 G 297048

Securiton Product Catalogue 2007 - SecuriPro

42

4.3 Sockets and accessories for SecuriStar detectors


SecuriStar detector socket USB 501-1 Base for addressable and conventional SecuriStar detectors For dry rooms, surface mounting integrated 6 wire terminal detector fixing be means of bayonet connection Technical data Ambient temperature Protection class Colour Dimensions (D x H) SecuriStar detector socket USB 501-2 Base for addressable and conventional SecuriStar detectors For hollow ceilings, flush mounting integrated 6 wire terminal detector fixing be means of bayonet connection Optional extra large cover ring 177mm available (3110470) Technical data Ambient temperature Protection class Colour Dimensions (D x H) SecuriStar detector socket USB 501-3 Base for addressable and conventional SecuriStar detectors For dump rooms, surface mounting integrated 6 wire terminal detector fixing be means of bayonet connection Technical data Ambient temperature Protection class Colour Dimensions (D x H) 5000547-0003 5000547-0002

5000547-0001

-20 C to +70 C IP 44 white 118 x 25 mm

-20 C to +70 C IP 44 white visible 118 x 4.5 mm

-20 C to +70 C IP 54 white 118 x 50 mm

Securiton Product Catalogue 2007 - SecuriPro

43

SecuriStar detector socket USB 501-4 Base for addressable and conventional SecuriStar detectors For concrete mounting integrated 6 wire terminal detector fixing be means of bayonet connection Optional extra large cover ring 177mm available (3110470) Technical data Ambient temperature Protection class Colour Dimensions (D x H) SecuriStar fire detector USB 501 MC Base for addressable and conventional SecuriStar detectors, personalized colour. Same as USB 501, except: Colour according to any RAL Number 5000573-0291 5000547-0004

-20 C to +70 C IP 44 white visible 118 x 4.5 mm

Securiton Product Catalogue 2007 - SecuriPro

44

Cover ring RING 158 MC Cover ring for USB501-2 and USB501-4, personalized colour Extra large cover ring, diameter 177mm. For detector base USB501-2 and USB501-4 Existing white ring has to be removed and replaced by this coloured ring. Colour Inscription plate for SecuriStar detectors DNP Detector numbering plate for SecuriStar detectors Additional terminal block for SecuriStar detector socket USB Term Optional reserve terminal block for cross-connections 2510802

3110464

according to any RAL Number

3110320

Dust cover for SecuriStar detectors DPROT 500 Dust cover for SecuriStar Detectors, 500 units Cover ring RING 177 Extra large cover ring, diameter 177mm. For detector base USB501-2 and USB501-4 For replacement of older detector sockets, which cover ring was bigger than the USB standard cover ring 3110470 VE100383

Securiton Product Catalogue 2007 - SecuriPro

45

4.4 Room indication lamps


Room indication lamp for SecuriStar detector RAL 720 Detector alarm indication lamp for SecuriStar detectors. for dry environment, surface mounting 3 decoupled inputs, up to 3 detectors can be connected to 1 lamp Technical data Operating voltage Operating current Protection class Colour lamp Colour cover Ambient temperature Dimensions (H x W x D) Room indication lamp for SecuriStar detector RAL 721 Detector alarm indication lamp for SecuriStar detectors. for wet environment, surface mounting Technical data Operating voltage Operating current Protection class Colour lamp Colour cover Ambient temperature Dimensions (H x W x D) 6900243

209708

6 to 30 V DC max. 2.7 mA IP 42 red white -20 C to +60 C 85 x 85 x 30 mm

5 to 30 V DC max. 4.9 mA IP 65 red white -20 C to +60 C 53 x 70 x 53 mm

Securiton Product Catalogue 2007 - SecuriPro

46

Room indication lamp for SecuriStar detector RAL 722 Detector alarm indication lamp for SecuriStar detectors. For direct installation in ceiling panels or door frame. Can be used with or without cover plate for dry environment Technical data Operating voltage Operating current Protection class Colour lamp Colour cover Ambient temperature Dimensions (H x W x D) Room indication lamp for SecuriStar detector Cover plate RAL 722 Accessory for RAL 722 Technical data Dimensions (L x W) 192198

6900244

5 to 30 V DC max. 4.9 mA IP 42 red white -20 C to +60 C 86 x 86 x 68 mm

86 x 86 mm

Room indication lamp for SecuriStar detector Raised floor console HKS 718 Accessory for RAL 722 and USB501 Technical data Dimensions (Length) 144223

extendable 375 x 550 mm

Securiton Product Catalogue 2007 - SecuriPro

47

4.5 Automatic fire detectors conventional ex-proofed


Optical smoke detector Ex-i, only in combination with GTW ORM 130 Ex-i For use in explosion zones 1 and 2. Smoke detection via scattered light measurement, approved by VdS and ATEX. Conventional detector, connected via GTW and MDI module to the SecuriLine max. 10 detectors per GTW line LED indication on the detector 2-wire connection fits to socket base 143 Ex-i Socket is an option Technical data Operating voltage Operating current (normal) Ambient temperature Colour Protection class Dimensions (D x H) Flammability protection cat. VdS-Number Ex approval 5000512

24 V max. 0.15 mA -20 C to +60 C white IP 42 80 x 32 mm EEx ia IIC T4 G 296035 ZELM 01 ATEX 0066

Securiton Product Catalogue 2007 - SecuriPro

48

IR-flame detector Ex-i, only in combination with GTW DF 1101 Ex Flame detector for explosion-hazard areas with three infrared sensors and the specially developed evaluating algorithms for the highest application requirements VdS approved, without socket. Conventional, two-wire installation Triple-sensor infrared flame detector Two sensors for detection in various wavelengths (4...4.8m and 5.1...6m) Third sensor for increased resistance to sunlight (0.7...1.1m) Microprocessor-controlled signal evaluation Selective evaluation of flicker frequency Excellent immunity to false alarms due to specially developed fuzzy algorithms and the latest wavelet diagnosis Selectable application algorithms Extremely high resistance to: electromagnetic influence, sunlight and heat radiation, humidity and corrosion Two different sensitivity and integration stages Large angle of vision (min. 90) High IP protection category (IP 67) Large operating temperature range (-35... +70C) Connection to SecuriLine via MDI and GTW0x module Technical data Detection angle Operating temperature Operating voltage Operating current Protection class Colour Dimensions (W x H x D) Flammability protection cat. VdS-Number Detector base and accessories to DF 1101 Ex Please refer to flame detectors DF1191 / 1192 6400004

90 -35 C to +70 C 16 - 28 V DC 0.5 mA IP 67 white RAL9010 135 x 135 x 77mm EEx ib IIC T4 G299085

Securiton Product Catalogue 2007 - SecuriPro

49

Heat detector Ex-i, only in combination with GTW WMM 216 Ex-i For use in explosion zones 1 and 2. The alarm criteria is the max. temperature, approved by VdS and ATEX. Conventional detector, connected via GTW and MDI module to the SecuriLine max. 10 detectors per GTW line LED indication on the detector semiconductor temperature sensor 2-wire connection fits to socket base 143 Ex-I Socket is an option Technical data Operating voltage Operating current (normal) Ambient temperature Colour Alarm threshold Max. heat alarm level Protection class Dimensions (D x H) Flammability protection cat. VdS-Number Ex approval Detector socket Ex-i 143 Ex-i Base for explosion proofed detectors ORM 130 Ex-i, WDM 215 Ex-i and WMM 216 Ex-I in explosion zones 1 and 2. For dry and dump rooms, surface mounting Technical data Colour Dimensions (D x H) Protection class VdS-Number 5000515 5100146

24 V max. 0.15 mA -20 C to +60 C white according EN54, class A1 57 C 3 C IP 22 80 x 32 mm EEx ia IIC T6 G 296034 ZELM 01 ATEX 0066

white 80 x 32 mm IP 42 G 297056

Securiton Product Catalogue 2007 - SecuriPro

50

DC isolating converter, for detector series 130 Ex-i GTW 01 Barrier between safe area and hazardous area for the connection of one conventional detector line. Max 10 conventional detectors per line For ORM 130 Ex-i,WDM 130 Ex-i,WMM 130 Ex-i Limitation of voltage and current Galvanic decoupling of intrinsically safe fire detectors Mounted outside of the hazardous area Technical data Ex-zone Input voltage Rated current Output voltage Signal transmission Protection class Dimensions (H x W x D) Flammability protection cat. VdS-Number DC isolating converter, for detector series 130 Ex-i GTW 02 same as GTW 01, except: Barrier between safe area and hazardous area for the connection of two conventional detector line. 5700081 5700080

IIA, IIB, IIC 20 to 30 V DC 0 mA to 35 mA min. 15.5 V DC max. 21.5 V DC Current increase IP 54 CW 159 x 167 x 82 mm EEx ia G 297052

Securiton Product Catalogue 2007 - SecuriPro

51

4.6 Flame detector


IR-flame detector DF 1191 Flame detector with one infrared sensor for simple applications. VdS approved, without socket. Conventional, two-wire installation Selectable application algorithms Extremely high resistance to electromagnetic influence and humidity / corrosion Two different sensitivity and integration stages Large angle of vision (min. 90) Large operating temperature range (-25... +70C) Connection to SecuriLine via MDI module Technical data Detection angle Operating temperature Operating voltage Operating current Protection class Colour Dimensions (W x H x D) VdS-Number IR-flame detector DF 1192 Flame detector with three infrared sensors and the specially developed evaluating algorithms for the highest application requirements VdS approved, without socket. Conventional, two-wire installation Triple-sensor infrared flame detector Two sensors for detection in various wavelengths (4...4.8m and 5.1...6m) Third sensor for increased resistance to sunlight (0.7...1.1m) Microprocessor-controlled signal evaluation Selective evaluation of flicker frequency Excellent immunity to false alarms due to specially developed fuzzy algorithms and the latest wavelet diagnosis Selectable application algorithms Extremely high resistance to: electromagnetic influence, sunlight and heat radiation, humidity and corrosion Two different sensitivity and integration stages Large angle of vision (min. 90) High IP protection category (IP 67) Large operating temperature range (-35... +70C) Connection to SecuriLine via MDI module 6400003 6400002

90 -25 C to +70 C 16 - 28 V DC 0.5 mA IP 44 white RAL9010 135 x 135 x 77mm G299085

Securiton Product Catalogue 2007 - SecuriPro

52

Technical data Detection angle Operating temperature Operating voltage Operating current Protection class Colour Dimensions (W x H x D) VdS-Number Detector base for DF 1191 / 1192 / 1101 Ex DFB 1190

90 -35 C to +70 C 16 - 28 V DC 0.5 mA IP 67 white RAL9010 135 x 135 x 77mm G299085

6800078

Base for DF 1191, DF 1192 and DF 1101 Ex For indoor application, surface mounting for outdoor application, a rain hood is available

Rain hood for DF 1191 / 1192 / 1101 Ex Rain hood Rain protection for outdoor application Rain hood for DF 1191 / 1192 / 1101 Ex Mounting bracket This mounting bracket is used to fix the flame detector at the correct angle. Ball and socket joint for DF 1191 / 1192 / 1101 Ex Ball and socket joint The ball and socket joint is used to line up the flame detector with the object to be monitored. Current limitation resistor for DF 1191 / 1192 / 1101 Ex Current limitation resistor 470 , 5%, 2W 1110089 6800081 6800080 6800079

End of line resistor for DF 1191 / 1192 End of line resistor 3k 3k , 1%, 0.6 W , 1%, 0.6 W 1130262

Test lam for DF 1191 / 1192 / 1101 Ex Flame detector test lamp for non-explosion hazard areas for explosion hazard areas
Securiton Product Catalogue 2007 - SecuriPro

On request

53

4.7 Ventilation duct detector


SecuriStar ventilation duct detector socket LKM 531 Ventilation duct smoke detector. Complete detector unit containing the addressable smoke detector SSD531 K, the box, the detector socket USB501-1, sampling pipe and blow out pipe Applicable on round and square air ducts Simple and easy installation Alarm LED visible through transparent cap Addressable smoke detector SSD531K VdS approved, according to EN54-7 Technical data Protection class External dimensions (without pipes) Ventilation duct diameter ( ) Ventilation duct side length ( ) Air flow speed VdS-Number 5000616-0201

IP 54 247 x 135 x 95.3 mm 20 to 100 cm 15 to 100 cm 1 to 20 m/s G206086

Securiton Product Catalogue 2007 - SecuriPro

54

4.8 Manual call points addressable


Manual call point, EN54/BS, IP 24 MCP 545-1 Single action break glass, according to EN54-11. Delivered with transparent plastic cover and with test key. for dry rooms surface mounting Integrated status LED integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine . Technical data Operating voltage Operating current (norm) Ambient temperature Protection class Colour Dimensions (W x H x D) Manual call point, EN54/BS, IP 24 MCP 545-2 Same as MCP 545-1, except: flush mounting 225711 225762

15 to 30 V DC 0.5 mA -20 C to +50 C IP 24 red, RAL 3001 87 x 87 x 55 mm

Manual call point, EN54/BS, IP 67 MCP 545-4 Single action break glass, according to EN54-11. Delivered with transparent plastic cover and with test key. for high humidity environment conditions Integrated status LED integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current (norm) Ambient temperature Protection class Colour Dimensions (W x H x D)
Securiton Product Catalogue 2007 - SecuriPro

225799

15 to 30 V DC 0.5 mA -20 C to +50 C IP 67 red, RAL 3001 123 x 123(145) x 61 mm


55

Manual call point, Vds, IP 52 MCP 535-1 Double action break glass, according to VdS. Delivered without inscription label and key, to be ordered separately. for dry rooms surface or flush mounting key protected integrated status LED blue and yellow versions available IP54 versions available integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Operating voltage Operating current (norm) Ambient temperature Protection class Colour Dimensions (H x W x D) VdS-Number Manual call point, VdS, IP 54 MCP 535-2 Same as MCP 535-1, except: Protection class IP 54 6200146-0002 6200146-0001

15 to 30 V DC max. 0.25 mA -20 C to +50 C IP 52 red, RAL 3000 135 x 135 x 37 mm G 299036

Securiton Product Catalogue 2007 - SecuriPro

56

4.9 Manual call points conventional


Manual call point, BS, IP 24 MCP 521-1 Single action break glass, according to EN54-11. Delivered with transparent plastic cover and with test key. for dry rooms surface mounting connection to SecuriLine via MDI82 Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Colour Dimensions (W x H x D) Manual call point, BS, IP 24 ECP 521-1E Same as MCP 521-1, except: Colour yellow Manual call point, BS, IP 67 MCP 521-4 Single action break glass, according to EN54-11. The detector offers IP67 class protection (waterproof). The cable entry occurs via means of cable screw connection M20 from above or below. The detector case is attached to the wall by means of three screws. Delivered with transparent plastic cover and with test key. outdoor rooms, waterproof surface mounting connection to SecuriLine via MDI82 Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Colour Dimensions (W x H x D) 227668 225789 225770

max. 30 V DC 0 mA -20 C to +50 C IP 24 red, RAL 3001 87 x 87 x 55 mm

max. 30 V DC 0 mA -30 C to +70 C IP 67 red, RAL 3001 87 x 87 x 55 mm

Securiton Product Catalogue 2007 - SecuriPro

57

Manual call point, Ex proof FTX 515 Single action break glass, for hazardous areas. The detector offers IP67 class protection. The cable entry occurs via means of cable screw connection from below. surface mounting connection to SecuriLine via MDI82 Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Colour Dimensions (W x H x D) Certificate Number Manual call point, VdS, Ex, IP 52 MCP 525-1 Double action break glass, according to VdS, ATEX approved. Delivered without inscription label and key, to be ordered separately. for dry rooms surface or flush mounting connection to SecuriLine via MDI82 key protected integrated status LED blue and yellow versions available IP54 versions available For Ex-zone 2 Technical data Operating voltage Operating current (normal) Ambient temperature Protection class Flammability protection cat. Colour Dimensions (H x W x D) VdS-Number Ex approval Manual call point, VdS, Ex, IP 54 MCP 525-2 Same as MCP 525-1, except: Protection class IP 54 6200149-0002 6200149-0001 203793

max. 30 V DC 0 mA -30 C to +70 C IP 67 red, RAL 3001 120 x 126 x 75 mm BAS02 ATEX2105X

15 to 30 V DC 0 mA -20 C to +50 C IP 52 EEx n l IIB T6 red, RAL 3000 135 x 135 x 37 mm G 299102 PTB 01 ATEX 2163 X

Securiton Product Catalogue 2007 - SecuriPro

58

4.10

Accessories for MCP


CPG 845 Spare break glass for MCP EN54/BS types. MCP 545-x,MCP521-1,ECP521-1E,FTN516,FTX515 Delivery unit 1 pcs. 225797

Accessory for MCP

Accessory for MCP GLASS MCP Spare break glass for MCP VdS types. MCP 525, MCP 535 Delivery unit 1 (10?) pce. Accessory for MCP KEY MCP Key to open the MCP. MCP 525, MCP 535 Accessory for MCP Inscription label MCP525/535 Inlay label for the MCP 525/535, with Logo Securiton. Available in the following versions [Language/Text]: German / Fire brigade (0001); German / House Alarm (0003) English / Fire Alarm (0011) Italian / Fire (0016) Swedish / Fire (0021) Croatia / Fire (0026) Russian / Fire (0031) Czech / Fire (0036) Hungarian / Fire (0041) Slovakian / Fire (0046) Polish / Fire (0051) Portuguese / Fire (0056) Spanish / Fire (0061) Neutral (0100) Accessory for MCP CPS 845 Seal for locking the MCP EN54/BS types. MCP 545-x,MCP521-1,ECP521-1E,FTN516,FTX515 Delivery unit 5 pcs. Accessory for MCP UP Set Adapter Plate for MCP 521-2 and MCP 545-2
Securiton Product Catalogue 2007 - SecuriPro

6200010

6200147

3740835-xxxx

222860

193801

59

4.11

Wireless detectors
RSD 532 Wireless smoke detector, complying with EN 54/7. Early detection of smothering and open fire with smoke emission. High reliability of the radio connection through the use of 28 channels in 2 frequency ranges. The radio system is fulfilling the highest existing standard for intrusion systems VdS class 2. The radio master unit RMU 251 is the interface to SecuriPro and controls up to 32 RSD 532. The RSD532 is delivered inclusive socket, without battery. addressable self monitoring of all detector parts periodical radio link test pre-warning levels for smoke adjustable sensitivity constant sensitivity through dust compensation 2 contamination levels 2 battery warning levels socket switch for monitoring against detector removal up to 5 years battery lifetime Technical data Operating voltage Operating current (average) Radio frequency bands Ambient temperature (permanent) Protection class Colour Dimensions (D x H) Complies regulation VdS-Number 5000593-0201

Radio smoke detector

3 V DC 0.12 mA 433.15 to 434.65 MHz 868.07 to 868.53 MHz -20 C to +60 C (incl. USB 501) IP 42 white 80 x 92 mm EN 54/7 and EN 54/5 G 205098

Battery for radio smoke detector LBP 301 Lithium Battery Pack for RSD 532 4000256-0201

Securiton Product Catalogue 2007 - SecuriPro

60

Radio contact module RCM 51 Wireless contact detector module, having 4 surveyed alarm lines. Any kind of contacts can be monitored and transmitted to Se curiPro , typically magnet contacts for doors and windows and glass break detectors.. High reliability of the radio connection through the use of 28 channels in 2 frequency ranges. The radio system is fulfilling the highest existing standard for intrusion systems VdS class 2. The radio master unit RMU 251 is the interface to SecuriPro and controls up to 60 RCM 51. The RCM 51 is delivered without battery. Each line individually addressable periodical radio link test magnet for window or door monitoring available (option) up to 3 years battery lifetime Technical data Operating voltage Operating current (average) Radio frequency bands Ambient temperature (permanent) Environmental class VdS 2227 Colour Dimensions (L x W x D) 5700145-0101

3.6V DC 138 to 258 mA 433.15 to 434.65 MHz 868.07 to 868.53 MHz -5 C to +45 C I RAL 9003 190 x 54 x 23.4 mm

Battery for radio contact module LBP 303 Lithium Battery Pack for RCM 51 4000266-0201

Permanent magnet for radio contact module PMA 41 For external mounting beside the RCM 51 module. Activates the RCM internal reed contact 234990

Securiton Product Catalogue 2007 - SecuriPro

61

5. Accessories 5.1 Sirens


Siren, 24V, VdS RO/W/S/HEK Acoustical alarm device for fire alarm systems. Surface mounting. Robust construction, High reliable, high protection class, low power consumption. 26 signal tones Signal tones according to DIN 33404 part 3 International emergency signal tone Fixing to socket be means of bayonet connection Improved version of formed siren BMT28 Technical data Volume Operating voltage Operating current Ambient temperature Protection class Dimensions (D x H) Colour VdS-Number Siren, 230V, VdS BSE 10 Acoustical alarm device for fire alarm systems. Surface mounting. Robust construction, High reliable, high protection class, low power consumption. 26 signal tones Signal tones according to DIN 33404 part 3 International emergency signal tone Fixing to socket be means of bayonet connection Technical data Volume Operating voltage Operating current Ambient temperature Protection class Dimensions (D x H) Colour VdS-Number 6300069 6300068

103 dB (A) in 1 m distance 10 to 28 V DC 9 to 29 mA -40 C to +80 C IP 54 93 x 77 mm white G 296013

103 dB (A) in 1 m distance 230 V AC 35 mA -40 C to +80 C IP 54 93 x 77 mm white G 296013

Securiton Product Catalogue 2007 - SecuriPro

62

Siren, 24V SP 205 Acoustical alarm device for fire alarm systems. Surface mounting. 1 signal tone, 2.3 Hz modulation Technical data Volume Operating voltage Operating current Ambient temperature Protection class Dimensions (H x W x D) Colour Siren, for mounting in detector socket USB501 SIR 715 Electronic siren for mounting into the detector socket base USB501-x. The siren is driven directly from the fire alarm detector. At the socket terminal, either a socket siren or a room indication lamp can be connected. 1 signal tone, 4 Hz modulation Technical data Volume Operating voltage Operating current Ambient temperature Protection class Dimensions (H x W x D) 218847 6300068

90 to 113 dB (A) in 1 m distance 24 V DC max. 40 mA 0 C to +50 C IP 30 97 x 135 x 36 mm white

ca. 60 dB (A) in 1 m distance +6 to +10 V DC max. 5 mA 0 C to +60 C mounted in USB 501 35 x 152 x 10 mm

Securiton Product Catalogue 2007 - SecuriPro

63

Siren, loop siren for SecuriPro

LSW 750 For use in a SecuriPro Fire alarm system. This low power siren is designed to connect directly to SecuriLine via 2 wire. No further power supply line is necessary. It is activated and powered from SecuriLine. 3 signal tones, hard wired controllable volume 2nd tone for 2 stage alarm also available in white colour integrated SecuriLine interface for automatic addressing and automatic short circuit isolation by fully functionality of the multifunctional detector loop SecuriLine. Technical data Volume Operating voltage Operating current Ambient temperature Protection class Dimensions (H x W x D) Material Colour

4300873-0201

Available in red and white

max. 100 dB (A) at 24 V DC 12 to 30 V DC 5 mA at 24 V DC -25 C to +70 C IP 42 109 x 109 x 95 mm ABS red

Securiton Product Catalogue 2007 - SecuriPro

64

5.2 Flash lights


Flash light, 24V BMT 20 Electronic flash light for general purpose, surface mounting. Robust construction, high reliable, high protection class, low power consumption. Fixing to socket be means of bayonet connection Also available in further colours: green, orange and transparent Technical data Operating voltage Operating current Flash energy Flash frequency Ambient temperature Protection class Dimensions (D x H) Colour VdS-Number Flash light, 24V BMT 21 Same as BMT 20, except: Colour orange 6300080 6300070

10 to 30 V DC 160 mA 2J 2 Hz -20 C to +55 C IP 54 93 x 77 mm red G 296014

Securiton Product Catalogue 2007 - SecuriPro

65

5.3 Other accessories


Semiconductor relay PMR 81 Opto-coupler isolated MOS relay for driving loads up to 4 A. A low consumption input circuits allows activation directly from OC outputs. with distance holders, no box Technical data Driving voltage Driving current Load current continuous Load current briefly (<100ms) Dimensions (L x W x D) 4300554

5 to 30 V DC max. 3 mA 4A 9A 40 x 23 x 15 mm

Securiton Product Catalogue 2007 - SecuriPro

66

5.4 Detector removal and test tools


Detector removal tool, for SecuriStar detectors UDR 521/531 Removal and insertion of detectors from the series SecuriStar . With gum joint Pluggable on telescopic pole UTP 6 Technical data Working height up to Detector removal tool, for SecuriStar detectors UDR 521/531 K Removal and insertion of detectors from the series SecuriStar . With cardan joint Pluggable on telescopic pole UTP 7 Technical data Working height up to Detector removal tool, for detector series 130, 140, 150, Ex-i UDR 918 Removal and insertion of detectors from the series 130, 140, 150, Ex-i. Pluggable on telescopic pole UTP 6 Technical data Working height up to Smoke detector test device, for SecuriStar detectors SDT 521/531 Test device for smoke detectors, holder for aerosol test gas can, with gas release mechanism. Pluggable on telescopic pole UTP 6 Technical data Working height up to 5600074 5600078

5600075

4.5 m

5600076

5.5 m

5.5 m

4.5 m

Securiton Product Catalogue 2007 - SecuriPro

67

Telescopic pole UTP 6 Pole for various detector removal and test devices. Technical data extendable from Telescopic pole UTP 7 Pole for various detector removal and test devices. Technical data extendable from Telescopic pole extension UTP 5 Extension piece 1.35 m for the telescopic pole types UTP 6 and UTP 7. Technical data Working height up to Smoke test aerosol 918/5 test gas can For function test of approx. 200 smoke detector in maintenance mode. Free of halogenated hydrocarbons. 6900124 3330253 5600073 5600072

1.7 to 3.0 m

2.2 to 4.0 m

6.0 m / 7,00 m

Detector protection basket SRS 01 Basket against mechanical damages. Suitable for detector series SecuriStar and 130. Technical data Material 5000586

Steel, nickel-plated

Securiton Product Catalogue 2007 - SecuriPro

68

6. Power Supply 6.1 Batteries


Battery Battery 1.9 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity Battery Battery 7 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity Battery Battery 12 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity 2310021 2310030 2310008

69 x 36 x 180 mm 12 V DC 1.9 to 2.2 Ah

153 x 67 x 102 mm 12 V DC 7 Ah

153 x 92 x 102 mm 12 V DC 12 Ah

Securiton Product Catalogue 2007 - SecuriPro

69

Battery Battery 18 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity Battery Battery 26 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity Battery Battery 45 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity Battery Battery 65 Ah 2 units necessary for 24V systems VdS approved Technical data Dimensions (H x W x D) Operating voltage Capacity 2310006 2310003 2310002 2310034

183 x 78 x 169 mm 12 V DC 18 Ah

168 x 177 x 127 mm 12 V DC 26 Ah

199 x 167 x 172 mm 12 V DC 45 Ah

392 x 168 x 176 mm 12 V DC 65 Ah

Securiton Product Catalogue 2007 - SecuriPro

70

6.2 External Power Supply


External Power Supply Unit, battery buffered, VdS approved EPSU This power supply is designed for supplying special fire protection systems such as ADW, ASD, TSC and fire alarm systems or their peripheral devices. A modular case system is available for made-to-measure installation of the EPSU 24/10, which allows, along with the installation of a power supply, power supply clips and a temperature sensor, for housing the necessary battery capacity based on the customers requirements. The EPSU is approved according to EN54-4 and VdS 2541 Standard configuration. The EPSU consists of the following items: EPSU WS + EPSU (24/10 or 24/03) + EPSU TEMP Option. - EPSU BAT: Cabinet for additional batteries - SDI 81/A-2: Fault transmission interface to SecuriPro (see Modules SecuriLine ) Technical data Operating voltage 230 VAC Output voltage 24 VDC Output current depending on EPSU type and battery size Operation temperature +5 C to +35 C Battery capacity up to 45 Ah Dimensions (H x W x D) 600 x458 x 254 mm Protection category IP 31 Case Colour grey RAL 7016 VdS-Number G 204050 Cabinet for EPSU EPSU WS Cabinet for EPSU incl. cabling, max 2x45Ah batteries 6100030-0102 Components have to be ordered separately

Securiton Product Catalogue 2007 - SecuriPro

71

Power Supply Unit EPSU 24/10 Power supply unit for EPSU. Technical data Operating voltage Output voltage Output current Dimensions (H x W x D) Protection category Case Colour Weight VdS-Number Power Supply Unit EPSU 24/03 Same as EPSU 24/10, except: Output current max. 3 A. This product is in preparation and is not available at this moment. Temperature Sensor for EPSU 24V/10A EPSU TEMP Temperature Sensor for EPSU 24V/10A To ensure optimal battery charging conditions, the power supplys charging voltage is checked by an external temperature sensor module. Intolerable battery temperatures of over 45 C are displayed by the built-in LEDs on the front side of the EPSU 24/10. The use of this temperature is according to the VdS regulations compulsory and not an option. Cabinet for additional batteries EPSU BAT Cabinet for additional batteries max. 4x45Ah 6100030-0103 4400053 4400052

230 VAC 19.8 26.4 VDC max. 10.0 A 160 x160 x 90 mm IP 20 light grey RAL 7035 1.7 kg G 297034

Securiton Product Catalogue 2007 - SecuriPro

72

7. Commissioning tools
Commissioning set standard, for SecuriPro IBS Standard Tool set for commissioning, bug fixing, maintenance and test of SecuriPro installations. The set consist of the following parts: SecuriLine Monitor, including flat cable for connection to the SCB01 Serial-LON-Talk-Adapter SLTA Connection cable, SLTA-SecuriLan Adapter plug, SLTA cable-SecuriLan Key, type DOM Standard PC communication cable 9 pin GALEP EPROM programmer IC removing tool PLCC Antistatic mat with accessories Tool-suitcase SecuriLine tester STB 01 A Hand held control device for testing and trouble shooting of the SecuriLine installation and their participants. Includes the AD/DC adapter (230VAC/24VDC) and an RS232 serial interface to a PC. 6900376

VE010903

Radio Tool Connection Set, for SecuriPro RTC 95 Special flat-type communication cable to be connected between the RSI 51 and a computer. This cable allows the RSI 51 box to be closed during a long term data logging Range Measuring Equipment for radio detectors, for SecuriPro RME 961 Using the RME 961 (Radio Measurement Equipment) and a laptop, the best possible location for the RDS 96 (detector simulators) and the RMM 96 (remote antenna) can be determined. Sources and transmitters that cause disturbances can be found using measured values. Data gathering on the PC permits longterm tests and detection of sporadic disturbances. The RME 961 is a suitcase, containing the following parts: Radio detector simulator RDS 96 (4 pcs.) Antenna: RMM 96 pre-fabricated with 10 m cable and connector Radio measurement interface RMI 96 12V DC plug-in power supply unit RS 232 serial connection cable USB serial converter with CD-ROM Tesa Powerstrips, large Lithium Battery Pack LBP 303
Securiton Product Catalogue 2007 - SecuriPro

4300876

230804

73

8. Software

PC Software for SecuriPro SecuriWin PC Software for personalizing, commissioning and test of SecuriPro fire alarm systems. Interface licence SIB-IF-LICENCE Interface protocoll for Alarm Management Systems. Connection via SIB71 module VE010810 VE010809

Securiton Product Catalogue 2007 - SecuriPro

74

9. Spare parts 9.1 Spare parts for MCU


Main control board MCB 02B-1 Power supply unit PSU 313 Power supply unit PSU 315 Lithium Battery for MCB, SIB, PIB CR 2032 Battery cable incl. temperature sensor ACA 31 4300475-0002 2310032 4400040-0002 4400039-0002 4300828-0001

9.2 Spare parts for operating and display panels


Cover plate for LED labels TCP 16 Transparent cover plate for 16 LED inscription label 2640400

9.3 Spare parts for modules SecuriLan


LAN interface board LIB 01 Spare PCB for PCM 73x / PIM 731 / PIM 732 LAN interface board LIB 02 Spare PCB for MIC 732 / MIC734 LAN interface board LIB 02 B Spare PCB for MIC 732 / MIC734 LAN interface board LIB 07 Spare PCB for SIB71/xA, PIB71
Securiton Product Catalogue 2007 - SecuriPro

4300529-0002

4300528-0002

94300833

4300773-0002

75

MIC732 spare front MIC 732-02 Spare Front for MIC 732 incl. ICB 05, ICB 02, LCD and hole for key switch MIC734 spare front MIC 734 Spare Front Spare Front for MIC 734 incl. ICB 05, ICB 12, LCD 02 and hole for key switch ILP 151 printer module LPM 151 Spare LPM 151 printer module 4300763 95300671 5300643-0002

9.4 Spare parts for modules SecuriLine


PCB holders DOS 816 LP

3610319

Spare holders for circuit boards mounted in DOS 816 box

9.5 Spare parts for commissioning set


Please refer to the price list

Securiton AG, Alarm- and Security Systems Alpenstrasse 20 CH-3052 Zollikofen/Berne Phone +41 31 910 11 22, Fax +41 31 911 25 32 www.securiton.eu - export@securiton.ch Securiton Product Catalogue 2007 - SecuriPro

Representative Office Asia No. 19A, Lorong Rahim Kajai 13 T.T.D.I. 60000 Kuala Lumpur, Malaysia Phone. +60 3 7725 1699, Fax +60 3 7725 1677 www.securiton.eu - asia@securiton.com.my

A company of the Swiss Securitas Group SQS-Certificate ISO 9001:2000

76

Anda mungkin juga menyukai