ohm-m
x 2 mm (Cross section area of grid conductor) (Diameter of grid conductor) (Depth of grid conductors buried) (Short-side grid length) (Grid spacing between parallel conductors at short-side) (Long-side grid length) (Grid spacing between parallel conductors at long-side) (Geometric mean of number of conductors at short-side) (Geometric mean of number of conductors at long-side) (Total length of grid conductors) (Area covered by grid conductors) (Coefficient related to the length-to-width ratio of the system) (Coefficient related to the length-to-width ratio of the system)
6300 1 1000000 0.3 0.870 0.2 1 1.025 62 74.548 1.013 1 1 75.530 0.241 11.822 50 2398.970 6.051
A s ohm-m m m
(As advised by Electrical Consultant/Power grid) (Fault duration according to the SPPG) (Concrete surface resistivity) (Concrete surface thickness) (Surface layer derating factor) (Spacing between parallel conductor) (Corrective factor for grids with ground rods along the perimeter) (Corrective weighting factor emphasizes the effect of grid buried depth) (Peripheral length of the grid) (Geometric factor a) (Geometric factor b) (Geometric factor c) (Geometric factor d) (Geometric factor ) (Spacing factor for touch potential) (Correction factor for grid geometry) (Total length of all ground rods) (Effective length of Lc + LR for mesh voltage) (Spacing factor for step voltage)
m m
14 3.6 0.017
nos m m
(6 earth bar within the room, and each riser cable is connected to 2 earth rods (Average length of each ground rod) (Diameter of ground rods)
151420.371
605333.48
7.484
253.751
C. Summary 1. Proposed Earth Mat Dimension and Corresponding Resistance Length Width (m) Grid Size Grid Spacing Grid Buried= 12 0.2 0.05 Width (mm) Grid Conductor 25 19 0.2 m Depth (mm) 2 Diameter (mm) 0.0172 Material (m)
Material
Criteria (ohm) 1
Material
2. Mesh Voltage and Step Voltage Calc. Value Mesh Voltage Step Voltage Note: 1. Soil resistivity of 75ohm-m encabsulated with Marconite for 50% reduction is for the earth mat calculation. The figures of soil resistivity 150ohm-m conducted 2. The earth calculation is based on IEEE Std 80-2000 entitled as 'IEEE Guide for Safety in AC Substation Grounding'. 7.484 Criteria (Volt) 151420.371 Meet Criteria? Yes Yes
253.751 605333.48