Anda di halaman 1dari 5

T1900

DIESEL GENSET

MODEL
Stand-by Power @ 50Hz Prime Power @ 50Hz

T1900
1520kW / 1900 kVA 1382 kW / 1727 kVA

Standard Features
General features :
Engine (MITSUBISHI , S16R-PTA ) Charge alternator 24 V , Governor:Elec Alternator (LEROY SOMER , LSA512S55 ) Single bearing alternator IP 23 , insulation class H /H Radiator 50C [122F]C max. T air inlet with coolant cap Skid and vibration isolators Dry type air filter Main line circuit breaker Microprocessor control panel 24 V battery, rack and cable Industrial silencer (loose) User manual

Generator Ratings
Voltage 415/240 400/230 380/220 HZ 50 50 50 Phase 3 3 3 P.F 0.8 0.8 0.8 Standby Amps 2643 2742 2887 Standby Ratings kW/kVA 1520 / 1900 1520 / 1900 1520 / 1900 Prime Ratings kW/kVA 1382 / 1727 1382 / 1727 1382 / 1727

PRP : Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12-hour period of operation, in accordance with ISO 3046-1 ESP : The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed.

Conditions of sale
SDMO provides a full line of products with high quality recognized engines and alternators. Service and parts are available from SDMO distributors as a single source of responsibility. Each and every units is factory tested. All generator sets are also prototype tested. Warranty according to our standard conditions. Five years extended also available

T1900

specifications and design liable to modifications without prior notice

1/5

ENGINE DATA
Manufacturer / Model Cylinder Arrangement Displacement Bore and Stroke Compression ratio Rated RPM Piston Speed Max. stand by Power at rated RPM Frequency regulation, steady state BMEP Governor : type Exhaust System Exhaust gas flow Exhaust temperature Max back pressure Fuel System 110% (Stand By power ) 100% (of the Prime Power) 75% (of the Prime Power) 50% (of the Prime Power) Total fuel flow Oil System Total oil capacity w/filters Oil Pressure low idle Oil Pressure rated RPM Oil consumption 100% load Oil capacity carter Thermal balance 100% load Heat rejection to exhaust Radiated heat to ambiant Heat rejection to coolant Air intake Max. intake restriction Engine air flow Coolant System Radiator & engine capacity Max water temperature Outlet water temperature Fan power Fan air flow Available restriction on air flow Type of coolant Thermostat Emissions HC CO Nox PM MITSUBISHI S16R-PTA , 4-cycle, Turbo , N/A 16 X V 65.37L [3989.1C.I.] 170mm [6.7in.] X 180mm [7.1in.] 14.0:1 1500 Rpm 9m/s [29.5ft./s] 1620kW [2171BHP] +/-0. 25% 18.5bar [268psi] Elec 5150L/s [10913cfm] 539C [1002F] 600mm CE [24in. WG] 388L/h [102.5gal/hr] 353L/h [93.3gal/hr] 266L/h [70.3gal/hr] 188L/h [49.7gal/hr] 588L/h [155.3gal/hr] 230L [60.8gal] 2.5bar [36.2psi] 5.8bar [84.0psi] 1.32L/h [0.3gal/hr] 140L [37.0gal] 977kW [55552Btu/mn] 102kW [5800Btu/mn] 852kW [48445Btu/mn] 400mm CE [16in. WG] 1950L/s [4132cfm] 345L [91.1gal] 98C [208F] 95C [203F] 40.2 kW 33.5m3/s [70989cfm] 20mm CE [0.8in. WG] Gencool 82-94 C 100 mg/Nm3 560 mg/Nm3 3800 mg/Nm3 110 mg/Nm3

T1900

specifications and design liable to modifications without prior notice

2/5

ALTERNATOR SPECIFICATIONS
GENERAL DATA

Compliance with NEMA MG21, UTE NF C51.111, VDE 0530, BS 4999, CSA standards.

Vacuum-impregnated windings with epoxy varnish. IP21 drip proof.

ALTERNATOR DATA Manufacturer / Type Number of phase Power factor (Cos Phi) Altitude Overspeed Pole : number Exciter type Insulation : class, temperature rise Voltage regulator Sustained short circuit current Total harmonics (TGH/THC) Wave form : NEMA = TIF TGH/THC Wave form : CEI = FHT TGH/THC Bearing : number Coupling Voltage regulation 0 to 100% load Recovery time (20% Volt dip) ms SkVA with 90 % of nominal sustained voltage (at 0.4 PF) OTHER ALTERNATOR DATA Continuous nominal rating @ 40C Standby rating @ 27C Efficiencies @ 4/4 load Air flow Short circuit ratio;50 (Kcc) Direct axis synchro reactance unsaturated (Xd) Quadra axis synchro reactance unsaturated (Xq) Open circuit time constant;50 (Tdo) Direct axis transient reactance saturated (Xd) Short circuit transient time constant (Td) Direct axis subtransient reactance saturated (Xd) Subtransient time constant (Td) Quadra axis subtransient reactance saturated (Xq) Zero sequence reactance unsaturated (Xo) Negative sequence reactance saturated (X2) Armature time constant (Ta) No load excitation current (io) Full load excitation current (ic) Full load excitation voltage (uc) Recovery time (Delta U = 20% transitoire) Motor start (Delta = 20% perm. Or 50% trans.) Transient dip (4/4 charge) PF : 1.8 AR No load losses Heat rejection

LEROY SOMER LSA512S55 3 0.8 < 1000 m 2250 rpm 4 AREP H /H R449 3 IN = 10s <4% < 50 <2% 1 Direct +/- 1% < 700 ms N/A

2230 kVA 2375 kVA 95.4 % 2.5m3/s [5297.18cfm] 0.27 408 % 245 % 2700 ms 36.4 % 240 ms 16 % 22 ms 20.1 % 3.8 % 18.1 % 39 ms 1.5 A 6A 63 V < 700 ms 4320 kVA 12 % 28.2 kW 79.5 kW

T1900

specifications and design liable to modifications without prior notice

3/5

Control Panels
TELYS Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faults Oil pressure, water temperature, No start-up, Overspeed, Min/max alternator, Min/max battery voltage, Low fuel level, Emergency stop Engine parameters Hours counter, Oil pressure, Water temperature, Engine speed, Battery voltage, Fuel level

KERYS Specifications : Frequency meter, Ammeter, Voltmeter Alarms and faults Oil pressure, water temperature, No start-up, Overspeed, Min/max alternator, Min/max battery voltage, Low fuel level, Emergency stop Engine parameters Hours counter, Oil pressure, Water temperature, Engine speed, Battery voltage, Fuel level Additional specifications Website, Troubleshooting, Assistance and Maintenance, Plotting and logging, Load impact, 8 configurations available, Compliance with international standards...

M80

Specifications : Tachometer, Emergency stop button, client connection terminal strip, EC certified Engine parameters : Hours counter, Oil pressure gauge, Water temperature indicator, Oil pressure indicator

T1900

specifications and design liable to modifications without prior notice

4/5

Options
Engine and Radiator Heat shield protection Oil drain extension Heavy duty air filter Lube oil drain pump Radiator core guard Battery charger Block heater Alternator Anti condensation heater Enforced impregnation Oversized alternator Control panel NFPA 110 level 1 Paralleling system Remote annunciator Oil temperature shutdown Key start panel Literature Parts Maintenance

Exhaust Residential silencer Critical silencer Flexible exhaust conn.

Fuel Day tank Subbase fuel tanks UL Water separator fuel filter

Contenergy

ISO40CSi Silent 79 db @ 7m [23 Ft] (stby)

Weight and Dimensions


Open Model Excluding option

Overall size l x w x h : 4832mm [190in] x 2286mm [90in] x 2479mm [98in] Weight : 12891kg [28412lbs] Net 13516kg [29789lbs] Brut

With Optional Enclosure

Overall size l x w x h : 12192mm [480in] x 2438mm [96in] x 2896mm [114in] Weight : 19962kg [43996lbs] Net

20939kg [46150lbs] Brut

SDMO industries - Head Office 12bis, rue de la Villeneuve CS 92848 - 29228 BREST cedex 2 - FRANCE - www.sdmo.com

T1900

specifications and design liable to modifications without prior notice

5/5