PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

PUBLIC ELECTRICITY CORPORATION SPECIFICATION FOR 11 & 33 kV INDOOR METAL CLAD SWITCH GEAR

Specification NO. SW-01 Date: 5-sep. 2010 A - 33 kV METALCLAD SWITCHGEAR


33kV, symmetrical breaking capacity (31.5 kA) indoor, metal clad, Incoming feeder switch panel, incorporating the following equipment:(a) One 1250 A, three-phase equipment with fixed and moving portions, busbar and cable isolating devices with automatic safety shutters, earthing facilities and with a set of 2000A copper busbars and supports. (b) One 1250 A, Vacuum circuit- breaker,a spring operated, power closing, 110 V d.c. motor charged, operating mechanism, complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) Three,3phase set of current transformers with an output class and accuracy suitable for the following duty:i)Measuring instrument 400-800/1 A. ii) Overcurrent and earth fault protections ratio 400-800/ 1A. A -1

(e)
(f) (g) (h)

One set of padlocks and keys. Set of anti-condensation heaters. Incorporated on the switch panel shall be include but not necessary be limited. (i) Circuit breaker control switch open / close. (ii) Indicating instruments,100 mm dial, 240 deg movement flush pattern comprising -One Voltmeter (with transfer switch) -Three Ammeters with reverse scales with maximum demand indication. (iii) Three-pole, IDMTL, connection, directional overcurrent relay, quadrate setting range 50%-200%. (iv) Single-pole IDMTL, directional earth fault setting range 10%-40%. (v) Line diffrential protection relay over pilot cable. (vi) High speed protection hand/electrical reset. Trip relay, (vii) Trip circuit supervision relay with two coils for continuous supervision in both the circuit-breaker open and closed positions and one alarm coil with flag indicator. (viii) Set of fuses, links, MCB and injection test sockets and plugs. (ix) Indication and alarm for circuit breaker position (inservice, outservice,and test position...),And indication alarm for Re-5-sep-2010

One set of primary connections and cable sealing end box complete with connectors suitable for single-core, 33 kV XLPE copper cables.

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

protection operated(DO/C&DE/F.) (x) Energometers (kw,kvar,kwh,kvarh) is required to measure energy. NOTE All relays to be flush mounted. A-2 33kv , symmertrical breaking capacity (31.5 kA) indoor, metalclad, Transformer switch panel, incorporating the following equipment:(a) One, 1250 A, three-phase equipment with fixed and moving portions, busbar and cable isolating devices with automatic safety shutters, earthing facilities and with a set of 2000 A air insulated copper busbars and supports. (b) One, 1250 A Vacuum circuit- breaker, spring operated, power closing, 110 V d.c. motor charged, operating device, operating, handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) Three,3 phase sets of current transformers with an output class and accuracy suitable for the following duties:1. Measuring instrument 400-800/1 A. 2. Overcurrent and earth fault protections ratio 400-800/ 1A. 3. High impedance differential and restricted earth fault protection ratio 400800/1A.with the following protection differential should protect power TR-R aginst internal phase and earth fault .Differential relays shall have second harmonic restrain to prevent triping due to Mag.surge the relay shall remain stable under Max. Through faults conditions correspond to system S.C. level on any tap position. Current Transformer should be suitable for C.T 33 KV for class and ratio. (d) Three,3 phase sets of Voltage transformers with an output class and accuracy suitable for the following duties:1. Measuring instrument 33/3 : 0.11/3 kv. 2. Directional overcurrent and dirrectional earth fault. (e) One set of primary connections and cable sealing and box complete with connection suitable for 3 single core, 33 kV XLPE copper cables. (f) One set of padlocks and keys. (g) Set of anti-condensation heaters. (h) Incorporated on the switchpanel shall be:i)Circuit breaker control switch open / close. ii) Indicating instruments, 100 mm dial, 240 movement flush pattern comprising:iii) Three Ammeters with reverse scales with maximum demand indication. iv) Three pole , IDMTI, overcurrent relay, current setting range 50% 200%. v) Single pole IDMTL earth fault relay current setting range 10%40%. vi) High impedance differential relay. vii)High speed protection triping relay. viii)Trip circuit supervision relay with tow coils for continuous supervision in both the circuit-breaker open and closed positions and one alarm coil with flag indicator. Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

ix)Set of fuses, links MCBs and secondary injection test sockets , plugs and C.T shorted. x) Indication and alarm for circuit breaker position (in- service, out-service,and test position...),And indication and alarm for protection opreted(O/C, E/F &, diff..) xi) Energometers (kw,kvar,kwh,kvarh) is required to measure energy. A-3 33kv, symmetrical breaking capacity (31.5 kA) indoor, metalclad, Bus section switchpanel, incorporating the following equipment:-

(a) One 2000A, 3phase equipment with fixed and moving portions, busbar and cable isolating devices with automatic safety shutters, earthing facilities and with a set of 2000 A air insulated copper busbars and supports. (b) One 2000 A, Vacuum circuit- breaker, complete with first filling of insulating medium, a spring operated, power closing, 110V d.c. motor charged, operating mechanism, complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) One, 3 phase set of current transformers with an output class and accuracy suitable for the following duty:(i) overcurrent and earth fault protection and instruments ratio 2000/1/1 A.
(d) Three,3 phase sets of Voltage transformers with an output class and accuracy suitable for the following duties:1. Measuring instrument 33/3 : 0.11/3 kv. 2. Synchronizing .

(e) One set of padlocks and keys. (f) One set of anti- condensation heaters. (g) Incorporated on the switchpanel shall be:(i) Circuit breaker control switch open/ close. (ii) Three Indicating ammeters, 100mm dial, 240movement flush pattern with reverse scales. (iii) Two Voltmeters 100mm dial- busbar volts. (iv) Three- pole, IDMTL, overcurrent relay current setting range 50%-200%. (v) High speed protection trip relay hand- electrical reset. (vi) Trip circuit supervision relay with two coils for continuous supervision in both the circuit- breaker open and closed position and one alarm coil with flag indicator. (vii) Set of fuses, Iinks, MCBs and secondary injection test sockets , plugs and C.T. shorted. (viii) Indication and alarm for circuit breaker position
Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

(inservice, outservice,and test position...), indication and alarm for protection opreted(O/C& E/F.) & Common alarm for 33 kv. NOTE ALL relay to be flush mounted.

A-4 33kV, symmetrical breaking capacity (31.5 kA) indoor, metalclad, Feeder switch panel, incorporating the following equipment:(a) One 1250 A, three-phase, equipment with fixed and moving portions, busbar and cable isolating devices with automatic safety shutters, earthirig facilities and with a set of 2000A air insulated copper busbars and supports. (b) One 1250 A, Vacuum circuit-breaker, a spring operated, power closing, 110 V d.c. motor charged, operating mechanism, complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) One, 3phase set of current transformers with an output class and accuracy suitable for the following duty:overcurrent and earth fault protection, and instruments , ratio 400-800/1A. (d) One, set of primary connections and cable sealing end box complete with connectors suitable for single-core, 33 kV XLPE copper cables. (e) Three,3 phase sets of Voltage transformers with an output class and accuracy suitable for the following duties:1-Measuring instrument 33/3:0.11/3 kv. 2-Directional overcurrent , dirrectional earth fault and distance protection. (f) One set of padlocks and keys. (g) Set of anti-condensation heaters. (g) Incorporated on the switch panel shall be (i) Circuit breaker control switch open / close. (ii) Indicating instruments,100 mm dial, 240 deg movement flush pattern comprising - One Voltmeter - Three Ammeters with reverse scales with maximum demand indication. (iii) Three pole, IDMTL, connection, overcurrent relay and directional overcurrent relay, quadrate setting range 50%-200%. (iv) Single pole IDMTL relay, earth fault , directional earth fault and sensitive earth fault current setting . (v) Line diffrential protection relay over pilot cable. (vi) High speed protection hand/electrical reset. Trip relay, (vii) Trip circuit supervision relay with two coils for continuous supervision in both the circuit-breaker open and closed positions Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

and one alarm coil with flag indicator. (viii) Set of fuses, links, MCB and injection test sockets and plugs. (ix) Indication and alarm for circuit breaker position (inservice, outservice,and test position...),And indication alarm for protection operated(DO/C&DE/F.) (x) Energometers (kw,kvar,kwh,kvarh) is required to measure energy. NOTE All relays to be flush mounted.

33kV, symmetrical breaking capacity (16 kA) indoor, metal clad, Aux. TR-R incorporating the following equipment:(a) One 630A, three-phase, equipment with fixed and moving portions, busbar and cable isolating devices, earthinig facilities and with a set of 1000A insulated copper busbars and supports. (b) One 630A, Load break switch, a spring operated, handle closing, power openning, auxiliary switches and interlocks. (c) One set of primary connections and cable sealing end box complete with connectors suitable for single-core, 33 kV XLPE copper cables. A-6 33Kv, symmetrical breaking capacity (31.5 kA) indoor, single busbar metal clad, metering switch panel, incorporating the following equipment:(a) One, 3phase set encapsulated type voltage transformer, ratio
33 / 0.1 1 / 0.1 1 kV

A-5

dual winding with output, class and accuracy suitable for metering instruments and protection. (b) Voltmeter selectors switch : - scale : 0-33kv. - class : 1.5. - size : 100mm. (c) Energometers (kw,kvar,kwh,kvarh) is required to measure overal energy .

Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

B - 11 kV METALCLAD SWITCHGEAR
B -1 11 kV, 31.5kA symmetrical breaking capacity, indoor, single busbar, metalclad, transformer switch panel, incorporating the following equipment: (a) One 1250A, 3phase equipment with busbar and cable isolating devices, with automatic safety shutters, earthing facilities and with a set of 2000 A copper busbars and supports. (b) One 1250A,vacuum circuit-breaker complete, spring operated, power closing 110 V d.c. motor charged operating mechanism complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) One , 3phase, withdrawabe voltage transformer ratio with output
11 3 / 0.1 1 3 kV

class and accuracy suitable for metering, indication and voltage control, complete with H.V, L.V. fuses. (d) One , 3phase set of current transformers, ratio 600-1200/1 A with an output class and accuracy suitable for instruments and metering. (e) One , 3phase set of current transformers, ratio 600-1200/1 A with an output; class and accuracy suitable for:Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

- Overcurrent , earth fault protection and directional Overcurrent & earth fault. (f) One , 3phase set of current transformers, ratio 600-1200/1A with an output class and accuracy suitable for:- Transformer high impedance with harmonic filter differential protection. (g) One flush pattern 100 mm ammeter with dual scales, scaled 01200 A and 0-600 A over 240 deg, with external reversible label to show scale in use, complete with maximum demand pointer and phase selector switch. (h) One Flush pattern, 100mm voltmeter with scale 0-13 kV over 240 degree. (j) One 100 mm kilowatt meter with dual scales, scaled 0 24.000 kW and 0-12,000 kw over 240 deg, with external reversible label to indicate the scale in use. (k) One 100 mm power factor indicator. (m) One 100 mm kilowatt hour meter, and Kvarh meter for summating total load with maximum demand indicatior. (n) One single-pole, flush pattern IDMTL relays for earth fault protection with current setting 10%-40% with hand and elec. reset f1ag indicator. (o) One, three - pole, flush pattern IDMTL relays for overcurent protection with current setting 50% 200% with hand reset flag indicator. (p) One, three - pole , flush pattern IDMTL relays for directional overcurent protection with hand reset flag indicator. (q) Two instantaneous transformer restricted & Stand by earth fault relays, complete with hand and elec. reset flag indicators and mounted in flush pattern cases. Suitable stabilizing resistors are to be supplied with the relays. (r) One high speed protection trip relay with hand and elec. reset contacts and flag indicator mounted in a flush pattern case. (s) One trip circuit supervision relay with two coils for continuous supervision in both the circuit breaker open and closed positions and one alarm coil with flag indicator. (t) One Set of test links blocks and C.T. shorted links. (u) One Set of Castell key type interlocking designed to prevent on--load operation of the associated 11kv isolator. (v) One Circuit-breaker, switch pistolgrip type control switch (w) Indication and alarm for circuit breaker position (in-service, out-service,and test position...),And indication and alarm for protection operated(O/C, E/F& diff.. .) (x) Energometers (kw,kvar,kwh,kvarh) is required to measure energy.

Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

B-2 11 kV, 31.5kA symmetrical breaking capacity, indoor, single busbar, metalclad, feeder switch panel, incorporating the following equipment: (a) One 630/800 A, 3phase equipment with busbar and cable isolating devices, with automatic safety shutters,, erthing facilities and with a set of 2000 A copper basbers and supports. (b) One 630/800 A,vacuum circuit-breaker complete, spring operated, power closing 110 V d.c. motor charged operating mechanism complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. (c) Three, 3phase set of current transformers, with an output class and accuracy suitable for : Re-5-sep-2010

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

Measuring instruments 300-600/1 A. Overcurrent & earth fault and sensetive earth fault protections ratio 300-600/ 1A. (d) Three moving iron spring controlled ammeters each in a 100mm flush pattern case scaled 0-150/0-300 A, and complete with maximum demand indicator. (e) One, Three-pole. IDMTL over current relay with current setting Range of 50%--200%, mounted in a flush pattern case and complete with hand and elec, reset flag indicators. (f) One, single pole 1DMTL. earth fau1t relay wit;h a current setting range of 10% - 40% , mounted in a flush pattern case and complete with hand and elec, reset flag indicators. (g) One, single pole 1DMTL sensetive earth fau1t relay . (h) One, trip circuit supervision relay with two coils for continous supervision in both the circuit- breaker open and closed positions and one alarm coil with flag indicator. (i) One set of test link blocks. (j) One Circuit-breaker pistolgrip type control switch Closed/Open. (k) One Circuit-breaker closed/open mechanical indicator. (m) One set of primary connections and cable sealing end box complete with connectors and gland to accommodate one 3-core copper stranded 11kV XLPE cable complete with cable termination kits. (n) One, Set of padlocks and keys. (o) Set of anti-condensation heaters. (p) One Indicating lamp for spring discharged. (q) One Check alarm device. (r) Indication and alarm for circuit breaker position (inservice, outservice,and test position...),And indication and alarm for protection operated(O/C, E/F& .) (s) Energometers (kw,kvar,kwh,kvarh) is required to measure energy.

B -3 11 kV, 31.5kA symmetrical breaking capacity, indoor, single busbar, metalclad, Bus- Section switch panel, incorporating the following equipment: (a) One 2000A, 3phase equipment with busbar and cable isolating devices, with automatic safety shutters, earthing facilities and with a set of 2000 A copper busbars and supports. Re-5-sep-2010

SW-01

PEC Technical Specification (b)

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

(c)

(d)

(e) (f) (g) (h) (i) (j) (k) (l) (m) (n)

One 2000A,vacuum circuit-breaker complete, spring operated, power closing 110 V d.c. motor charged operating mechanism complete with an electrical release device, operating handle for emergency hand charging of the spring, and all necessary auxiliary switches and interlocks. Three, 3phase set of current transformers, with an output class and accuracy suitable for : Measuring instruments 1200-1250/1 A. Overcurrent & earth fault protections ratio 1200-1250/ 1A. One flush pattern 100 mm ammeter with dual scales, sealed 01200 A and 0-2500 A, with external reversible label to show scale in use, complete with maximum demand pointer and phase selector switch. One Flush pattern, 100mm voltmeter with scale 0-13 kV over 240 degree. One 100 mm kilowatt meter with dual scales, scaled 0 24.000 kW and 0-12,000 kw over 240 deg, with external reversible label to indicate the scale in use. One 100 mm power factor indicator. One 100 mm kilowatt hour meter, for summating total load with maximum demand indicatior. One, three-pole, flush pattern IDMTL relays for overcurrent protection with current setting 50% 200% with hand reset flag indicator. One high speed protection trip relay with hand and elec. reset contacts and flag indicator mounted in a flush pattern case. One trip circuit supervision relay with two coils for continuous supervision in both the circuit-breaker open and closed positions and one alarm coil with flag indicator. One Set of test. links blocks and C.T. shorted links. One Circuit-breaker, switch pistolgrip type control switch Indication and alarm for circuit breaker position (in-service, outservice,and test position...), indication and alarm for protection opreted(O/C, E/F.. .) and common alarm.

Re-5-sep-2010

10

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

B-4 11 kV, 31.5kA symmetrical breaking capacity, indoor, single busbar metalclad, SF6/ air insulated, metring switch panel, incorporating the following equipment: (a) One, 3phase, withdrawabe voltage transformer ratio with output,
11 3 / 0.11 3 / 0.11 3 kV

class and accuracy suitable for metering, indication and voltage control, complete with H.V, L.V fuses. (d) Energometers (kw,kvar,kwh,kvarh) is required to measure overal energy .

Re-5-sep-2010

11

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

C - D.C. EQUIPMENT
All the substation covered by this Specification are to be capable of being extended, and consequently the station battery systems shall be designed to be uprated with the minimum of disruption . (a) 2-110 V batteries of the nickel cadmium high performance type with stands and accessories having a combined capacity to supply the requirements of up to seven 33kv indoor metal clad circuits for and seven 11kv indoor metal clad circuits for a 12 hour period under the site environmental conditions. At the end of this period, the voltage level and remaining capacity shall be adequate for a full operation of the busbar protection . (b) Two sets of main battery withdraw able fuses in wall mounted box to be mounted outside battery room with through wall copper connections into the battery room, and bottom entry cable gland plate. (C) Two sets of copper connections, connectors and fixings within the battery room from the 110V batteries to the wall mounted fuse- box. 110 V battery charger board consisting of floor mounted sheet steel cubicles with rear access doors and containing all necessary anciliary equipment, busbar, etc., and including :Two chargers each with rated output to supply 100% of the float and boost charge requirement of the batteries specified. The chargers shall normally work in parallel, but shall be suitable for isolation for fault location or maintenance purposes. Each charger shall be complete with the following :Boost charge switch with automatic timer. Input a.c. supply switch and fuses. Output d.c. double pole switch and fuses. Output d.c. ammeter, flush type, 100mm dial. Output d.c. voltmeter, flush type, 100mm dial. Charge failure relay to give remote alarm and local indication . Voltmeter and auxiliary circuit double- pole fuses. Cable gland plates . C-3 one set of manual changeover equipment, including counter emf diodes if required. The following fuctions are required from this changeover equipment:(a) connect either charger to both batteries, the other being isolated . (b) connect both chargers in parallel to both batteries . (c) connect either battery to a charger, the substation load being fed from the other battery and charger . 110 V d.c. distribution board of floor mounted sheet steel cubicle rear access doors and containing all necessary anciliary equipment, busbars, complete with connections to chargers and batteries, and including:(a) Battery input/ ouput d.c. ammeter, flush type, 100mm dial with high/1ow sensitivity switch .

C-1

C-2

C-4

Re-5-sep-2010

12

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

(b)

Load ouput d.c. ammeter, flush type, 100mm dial .

(c) Ouput d.c. voltmeter, flush type, 100mm dial with selecto switch for off/distribution board/battery/battery bias voltage position . (d) Battery negative bias system with battery earth relay, earth link and contacts give remote alarm and local indication . (e) Battery fail relay to give remote alarm and local indication (f) Double- pole circuit fuse switches for twelve distribution outlets (g) Supervision AC Relay

C-4 Self contained battery operated emergency lights normally supplied from the susbtation a.c. 220 volts supply but on failure shall be supplied by a integral nickel cadmium battery designed for a minimum 3 hour duration.

Re-5-sep-2010

13

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

D L.V AC SWITCHBOARDS.
400/230 V(nominal) three- phase, four wire, extenible, floor mounted indoor switchboard with cable access at the bottom comp lete with three-phase and neutral busbars rated to suit equipment being supplied and all anciliary equipment The neutral busbar shall be earthed at one point only through a removable link .

L.V AC BOARD :
(a) Two incoming circuit- breakers. Supply derived from auxiliary transformer. (b) To prevent paralleling of normal incoming supplier, one set of interlocking equipment. (c) One incoming supply voltage failure realy to cover failure of any phase with a pair of contacts to give remote indication . (d) One voltmeter scaled O-500V having a 100mm dial . (e) One ammeter and phase selectal switch, 100mm dial . (f) 12 outgoing circuit- breakers /Fuse switch units . (g) Supervision AC Relay

Re-5-sep-2010

14

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

E - CABLE AND ACCESSORIES:E-1 POWER CABLES AND ACCESSORIES Each item shall complete with all necessary cables joints, Termination, earthing , connectors, et., including warning tapes. E.1.1 33KV POWER CABLES AND ACCESSORIES: a) From 33kv OHL Terminal for both circuits (100m) to cable box on 33kv indoor switch panel each circuit 10 MVA cable circuit compnring 33kv three-single core circular stranded copper XLPE cable . b) From cable box on transformer to cable box on 33kv indoor switch panel 3 phase single core, 10MVA for each circuit .

E-1-2 11 KV POWER CABLES AND ACCESSORIES a) From 11kv cable box on transformer to cable box on 11kv indoor switch 10MVA, 3 phase cable circuit comprising 11kv three single XLPE cable . b) From indoor 11kv switch panel to 11kv OHL, 3 phase 4 circuits total 800 meter either single core ie .3x1x240mm2cu /XLPE/SWA/PVC or 3x240 mm2 cu /XLPE/SWA/PVC . N.B. 1) refer to drawings Fig (1) and Fig (2) 2) cables shall be circular stranded copper conductor XLPE/ unarmoured / screened, with outer sheet, single core minimum cross sectional area 400 mm2 11kv, schedule shall be completely fill . 3) All shall be complete with accessories, terminations E-2 Control CABLES AND ACCESSORIES

F - Fire protection equipment


Set of portable fire extinguishers comprising a minimum of :2-3 kg olry powder

G- Lighting and low voltage power equipment .


One complete set of industrial pattern lightning and low voltage power supplies equipment generally :-

Re-5-sep-2010

15

SW-01

PEC Technical Specification

11 & 33 kV INDOOR METAL CLAD SWITCH GEAR AND ACCESSORIES

(a) Necessary fluorescent, flood and bulkhead lighting fittings, with control switches and associated cabling. (b) In addition to 220V a.c. 13A, single phase socket outlets prorided in all area of 380V, a.c. 60A 3-phase and neutral soctet outlet shall be provided in the vicinity of the outdoor transformers including power supply distribution beards .

I- AIR - CONDITIONING EQUIPMENTS


provisions of packaged type wall A/C units to maintain 20 co at 50 percent availability.

J- Surge Arresters
- set of three surge arresters, separately mounted for use on the 33&11 kv system, complete with all connections and supports. J-1 J-2 Surge arresstor 36 KV Station Type, 10 KA with fixing bracket Surge arresstor 12KV Station Type, 10 KA with fixing bracket

Re-5-sep-2010