Circuit Breakers

MCCB | ELCB | MCB | RCBO

contents
general overview feature - company profile MCCB - NF series circuit breaker, double repulsion breaking method - double number of copper contacts, materials of the NF series - method of installation, MCCB cross sectional area, positive indication & operation - suitability for isolation, compliance with standards - selection | quick & easy selection table - power distribution | technical details - ambient temperature - characteristic curves | NF series - physical dimensions & mounting holes | NF series - accessories | phase insulation barriers, electrical accessories & shunt trip - accessories | under voltage device - accessories | signal switches, rotary handle - accessories | rotary handle - mounting position | internal accessory - internal resistance & power loss - short circuit table | DC voltage - selection table | motor circuit protection - motor selection - installation safety distance requirement - terminal-tightening torque - terminal-cable & copper busbar connection data ELCBs - EG series | with overload & short circuit protection - EG series | operating characteristics & dimensions MCBs - BHQ series | fixed type - BHP series | plug-in type - BHQ & BHP | operating characteristics & dimensions RCBOs - EQ series | fixed type - EP series | plug-in type - EQ & EP series | dimensions & operating characteristics ordering codes ... 2

... 6

... 7 ... 8 ... 9 ... 10 ... 11 ... 12 ... 16 ... 17 ... 22 ... ... ... ... ... ... ... ... ... ... ... ... 30 31 32 33 35 36 39 40 41 43 44 45

... 46 ... 48

... 52 ... 53 ... 54

... 56 ... 57 ... 58 ... 60

MCCB general overview

NF series
The NF series MCCBs are available from 50AF to 1200AF. Pole sizes from 1 to 4 are available for the various models. All NF series MCCBs are suitable for isolation. 10kA (2P & 3P)

50AF
NF-50MA

250AF
NF-250GP NF-250MA NF-250HA NF-250L
10kA 25kA 50kA 65kA
2

(3P) (1P to 4P) (1P to 4P) (3P)

100AF
NF-100GP NF-100HA
10kA 25kA 50kA 65kA

NF-100MA NF-100L

(2P & 3P) (1P to 4P) (1P to 4P) (3P)

1200AF
NF-1200HA
50kA (3P & 4P)

400AF
NF-400GP NF-400HA
25kA (3P & 4P) 50kA (3P & 4P) 65kA (3P)

NF-400L

600AF & 800AF


NF-600GP NF-600HA NF-600L
25kA (3P & 4P) 50kA (3P & 4P) 65kA (3P)

NF-800GP NF-800HA NF-800L

general overview

Accessories

shunt trip

under voltage trip

signaling switches

rotary handle

ELCB: EG series

with overload & short circuit protection

100AF
EG-100MA EG-100HA
4

250AF
EG-250MA EG-250HA
25kA (3P & 4P) 50kA (3P & 4P)

25kA (3P & 4P) 50kA (3P & 4P)

MCB: BHQ & BHP series


100AF
BHQ-1
6kA (1P)

100AF
BHQ-2
6kA (2P)

100AF
BHQ-3
6kA (3P)

100AF
BHP-1
6kA (1P)

100AF
BHP-2
6kA (2P)

100AF
BHP-3
6kA (3P)

RCBO: EQ & EP series |


50AF
EQ-1
10kA (1P)

with overload & short circuit protection

50AF
EQ-2
10kA (2P)

50AF
EQ-3
10kA (3P)

50AF
EP-1
10kA (1P)

50AF
EP-2
10kA (2P)

50AF
EP-3
10kA (3P)
5

feature

company profile
Since our inception in 1974, our company specializes in manufacturing low voltage circuit breakers and have a reputation of producing products of consistent quality and high reliability.

Our manufacturing facilities are certified to the international quality standards of ISO 9001, while our products are certified by ASTA Certification Services UK. With such high standards, our range of circuit breakers are able to meet your highest demands for quality, safety and reliability.

MCCB

NF series circuit breakers


The demand for economical and high performance circuit breakers is ever increasing in the global market. The NF series circuit breakers provide a simple and reliable solution to meet this global demand where quality, performance and compliance are required. The NF series circuit breakers have been engineered to provide effective protection to low voltage power distribution systems. The NF series is a complete range of MCCBs from 10A to 1200A with 1, 2, 3 and 4 pole versions. An extensive range of electrical accessories is also available.

double repulsion breaking method


The double repulsion method uses a reverse-loop of current (I) flowing in essentially opposite directions (see figure). This creates a repulsion action and results in a greater opening force (Fm) between the fixed and moving contacts. This force also assists to rapidly extinguish the arc, thereby causing the moving contacts to open faster. A faster breaking time is achieved with this design.
moving contacts

Fm

opening

Fm

7
fixed contact

MCCB

double number of contact coppers


For the NF600 and above circuit breakers, double moving contacts are used instead of a single contact. This additional moving contact improves the short circuit breaking performance and reduces contact wear.

double moving contacts in NF1200

materials of the NF series


The design of the NF series circuit breakers makes it suitable to be used in hot and humid climates. The material used for the circuit breaker casing consists of synthetic resins reinforced with glass fibers. Furthermore, the metal parts used in the breakers are chemically treated to protect against corrosion. The external copper terminals are tin-plated to prevent oxidation.

method of installation
The NF series circuit breakers can be installed in vertical or horizontal position without any impact on its performance or de-rating of characteristics.
horizontal vertical

MCCB cross sectional area


C B A Parts Index for cross-sectional area of MCCB A MCCB casing made of high-impact BMC material reinforced with glass fibres, providing a safe and strong housing in the event of breaking high-fault currents. B Trip-free mechanism ensuring positive operation and isolation suitability. Designed for long service life and high number of operating cycles. Metal parts in mechanism are chemically treated to withstand harsh tropical weather conditions. C Arc chutes with predefined steel plates arrangement, provide high breaking capabilities. D Fixed and moving contacts utilizing the reverse loop current method, creates a repulsion force thus rapidly extinguishing the arc. E Common trip mechanism to ensure breaking of all poles even when the fault occurs at a particular pole. F Trip release consists of thermal (bi-metal) and magnetic devices suitable for use in AC or DC supply voltages.

positive indication & operation


The circuit breaker operating handle is designed to indicate the exact position of its moving contacts. Its trip-free operating mechanism cannot indicate that the breaker is ON if the moving contacts are in the OFF position. If the breaker trips due to an electrical fault or overload the handle will be in between the ON and OFF position. This is the TRIP position. To switch the breaker ON after tripping, the handle position must be switched to OFF position first and so to reset the breaker and then switch to the ON position.

MCCB

suitability for isolation


In compliance with IEC 60947-2 standard, NF series circuit breaker guarantees no leakage currents and overvoltage withstand between the supply and load terminals when its moving contacts are in the open position.

test trip button

isolation

compliance with standards


The NF series circuit breakers have been designed to meet international standards, complying with the following standards: 1. IEC 60947-2: International Electro Committee Standard 2. BSEN 60947-2: British Standard European Norm 3. JIS C 8201-2: Japan Industrial Standard 4. GB 14048-2: China Standard 5. CNS 14816-2: Taiwan Standard 6. CE: Conformity European

10

selection | quick & easy table


Rated Current In (A)
10 15 20 30 40 50 60 75 NF-100GP 80 100 125 150 160 175 200 225 250 250 300 NF-400GP 350 400 500 NF-600GP 600 700 NF-800GP 800 1000 NF-1200HA 1200 NF-800HA NF-800L 11 NF-600HA NF-600L NF-400HA NF-400L NF-250GP NF-250MA NF 250HA NF-250L NF-100GP NF-100MA NF-100HA NF-100L NF-50MA

Interrupting Capacity Icu (kA) Sym at 415 Vac 10 25 50 65

MCCB power distribution

technical details
model Code Ampere Frame (AF) NF-50
50AF

electrical characteristics
NF-100
100AF

NF-250
250AF

Rated Current: In (A) at Ambient Temp 50C Number of Poles Available Rated Insulation Voltage: U i(V) Rated Impulse withstand Voltage: U imp (kV) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) 690V 500V 440V IEC 60947-2 415V 400V 380V 230V DC 250V

10 15 20 30 40 50 2 3 600 8 MA 5 7.5 10 10 10 15 25 5 50

10 15 20 30 40 50 60 75 80 100 1 2 3 4 690 8 GP 5 7.5 10 10 10 15 25 5 50 8 MA 10 15 25 25 25 30 50 10 50 8 HA 10 40 50 50 50 60 85 20 50 8 L 35 50 65 65 65 100 125 40 50

125 150 160 175 200 225 250 3 4 690 8 GP 5 7.5 10 10 10 15 25 5 50 8 MA 10 15 25 25 25 30 50 10 50 8 HA 10 40 50 50 50 60 85 20 50 8 L 35 50 65 65 65 100 125 40 50

Rated Service Short Circuit Breaking Capacity: I cs = % I cu Rated Short Circuit Breaking Capacity: (kA) 600V JIS C 8201-2 (sym) 440V 380V 220V DC
12

7.5 10 15 25 5 A 2 20000

7.5 10 15 25 5 A 2

10 22 30 50 10 A 2

30 50 50 85 20 A 2

50 65 100 125 40 A 2

7.5 10 15 25 5 A 2

10 22 30 50 10 A 2

30 50 50 85 20 A 2

50 65 100 125 40 A 2

250V

Suitable for Isolation Utilization Category Pollution Degree No. of Electrical Operations
Notes: - denotes available.

15000

15000

technical details
model Code Ampere Frame (AF) NF-400
400AF

electrical characteristics
NF-600 & NF-800
800AF

NF-1200
1200AF

Rated Current: In (A) at Ambient Temp 50C Number of Poles Available Rated Insulation Voltage: U i(V) Rated Impulse withstand Voltage: U imp (kV) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) 690V 500V 440V IEC 60947-2 415V 400V 380V 230V DC 250V
8 GP 10 22 25 25 25 30 50 20 50

250 300 350 400 3 4 690 8 HA 10 40 50 50 50 60 85 40 50 8 L 35 50 65 65 65 100 125 40 50 8 GP 10 22 25 25 25 30 50 20 50

500 600 700 800 3 4 690 8 HA 10 40 50 50 50 60 85 40 50 8 L 35 50 65 65 65 100 125 40 50

1000 1200 3 4 690 8 HA 10 40 50 50 50 60 85 40 50

Rated Service Short Circuit Breaking Capacity: I cs = % I cu Rated Short Circuit Breaking Capacity: (kA) 600V JIS C 8201-2 (sym) 440V 380V 220V DC 250V

18 25 30 50 20 A 3

30 50 50 85 40 A 3 11000

50 65 100 125 40 A 3

18 25 30 50 20 A 3

30 50 50 85 40 A 3 11000

50 65 100 125 40 A 3

30 50 50 85 40 A 3 8000 13

Suitable for Isolation Utilization Category Pollution Degree No. of Electrical Operations
Notes: - denotes available.

MCCB power distribution

technical details
thermomagnetic trip release
model Code Ampere Frame (AF) Rated Ultimate Short Circuit Breaking Capacity: I cu (kA) Fixed thermal, Fixed Magnetic 10 x Ith Fixed thermal, Adjustable Magnetic NF-50
50AF MA GP

NF-100
100AF MA HA L GP

NF-250
250AF MA HA L

mechanical characteristics
Number of Poles (P)
a aa ca c

3 75 130 68 90 110 25

1 42

2 60

3 90 155

4 120 155

1 48 165 68 92 126 35

3 105 165 68(80) 92(104) 126 35 M8 screw 20000

4 140 165 68 92 126 35

a b c ca bb aa

50 130 68 90 110

155 155 68 90

ON

68 68(80) 68 90 90(102) 90 132 30 132 30

OFF

bb b

132 132 29.5

(mm)
Type of Terminals

M5 clamp terminal screw 25000 0.4 0.5 0.5

M8 screw 20000 0.7 1.0(1.2) 1.4 0.7

No of Mechanical Operations Weight (kg)

1.5(1.6)

1.9

accessories
Shunt Trip Device Under Voltage Trip Device Auxiliary Switch Alarm Switch
14

Auxiliary + Alarm Switch Rotary Handle

Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type. - denotes available; however, all accessories are not available for 1-pole models.

technical details
thermomagnetic trip release
model Code Ampere Frame (AF) Rated Ultimate Short Circuit Breaking Capacity: I imp (kA) Fixed thermal, Fixed Magnetic 10 x Ith Fixed thermal, Adjustable Magnetic
GP

NF-400
400AF HA L

NF-600 & NF-800


800AF GP HA L

NF-1200
1200AF HA

mechanical characteristics
Number of Poles (P)
a aa ca c

4 196 257 103 155 194 44

3 210 275 103 155 243 70

4 280 275 103 155 243 70

3 210 400 103 155 370 70

4 280 400 103 155 370 70

a b c ca bb aa

140 257 103 155 194 44

ON OFF

bb b

(mm)
Type of Terminals

M12 Bolt 25000 5.5(6.0) 7.2

M12 Bolt 20000 10.0(11) 12.0

M12 Bolt 20000 15.0 19.0

No of Mechanical Operations Weight (kg)

accessories
Shunt Trip Device Under Voltage Trip Device Auxiliary Switch Alarm Switch Auxiliary + Alarm Switch Rotary Handle
15

Notes: All L-type breakers are only available in the 3-pole version; ( ) denotes for L-type. - denotes available.

MCCB ambient temperature

The NF series circuit breakers are able to operate in temperatures between 25 to 70C. The nominal current of circuit breakers are rated 100% at 50C. Please refer to the table below for temperature derating. 1-Pole, 2-Pole, 3-Pole and 4-Pole In (A) 25C
10 15 20 30 40 50 60 75 80 100 125 150 160 175 200 225 250 300 350 400 500 600 700 800 16 1000 1200 11.2 16.8 22.4 33.6 42.2 52.8 63.3 79.1 84.4 105.5 138.1 165.8 176.8 193.4 221.0 248.6 282.5 339.0 395.5 452.0 557.5 669.0 763.0 872.0 1110.0 1308.0

30C
10.9 16.4 21.8 32.7 41.8 52.3 62.7 78.4 83.6 104.5 136.3 163.5 174.4 190.8 218.0 245.3 275.0 330.0 385.0 440.0 547.5 657.0 749.0 856.0 1090.0 1272.0

35C
10.8 16.2 21.6 32.4 41.4 51.8 62.1 77.6 82.8 103.5 134.4 161.3 172.0 188.1 215.0 241.9 270.0 324.0 378.0 432.0 537.5 645.0 735.0 840.0 1070.0 1260.0

40C
10.5 15.8 21.0 31.5 41.0 51.3 61.5 76.9 82.0 102.5 131.3 157.5 168.0 183.8 210.0 236.3 262.5 315.0 367.5 420.0 522.5 627.0 728.0 832.0 1045.0 1248.0

45C
10.3 15.5 20.6 30.9 40.4 50.5 60.6 75.8 80.8 101.0 128.8 154.5 164.8 180.3 206.0 231.8 257.5 309.0 360.5 412.0 512.5 615.0 714.0 816.0 1025.0 1224.0

50C
10.0 15.0 20.0 30.0 40.0 50.0 60.0 75.0 80.0 100.0 125.0 150.0 160.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 500.0 600.0 700.0 800.0 1000.0 1200.0

55C
9.8 14.7 19.6 29.4 38.4 48.0 57.6 72.0 76.8 96.0 122.5 147.0 156.8 171.5 196.0 220.5 243.8 292.5 341.3 390.0 485.0 582.0 686.0 784.0 970.0 1176.0

60C
9.6 14.4 19.2 28.8 37.2 46.5 55.8 69.8 74.4 93.0 118.8 142.5 152.0 166.3 190.0 213.8 236.3 283.5 330.8 378.0 475.0 570.0 672.0 768.0 945.0 1140.0

65C
9.4 14.1 18.8 28.2 36.6 45.8 54.9 68.6 73.2 91.5 116.3 139.5 148.8 162.8 186.0 209.3 231.3 277.5 323.8 370.0 465.0 558.0 658.0 752.0 920.0 1128.0

70C
9.2 13.8 18.4 27.6 36.0 45.0 54.0 67.5 72.0 90.0 111.3 133.5 142.4 155.8 178.0 200.3 222.5 267.0 311.5 356.0 450.0 540.0 644.0 736.0 900.0 1104.0

MCCB characteristics

NF-50MA
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves
temperature characteristic

tripping curve
Operating Characteristics

Operating time Current rating (%)

Frame size: 50AF


10A 15A 20A 30A 40A 50A

300 250 200 150 100 80 70 20 30 40

Operating time

Max

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2 3 4 5 6 7 10 15 20 30 40

Rated ambient 50C 10

50

Rated ambient

60

Ambient temperature (C)


Min

x 100% of rated current

NF-100GP, MA & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves
temperature characteristic

Operating Characteristics

Frame size: 100AF


10A 15A 20A 30A 40A 50A 60A 75A 80A 100A

130 10A~30A 120

Current rating (%)

Max

110

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

Min

100 40A~100A 90

80 Rated ambient 50C 10

20

30

40

50

Rated ambient
60

Ambient temperature (C)


Time delay trip
3 4 5 6 7 10

17

Instantaneous trip
15 20 30 40

x 100% of rated current

MCCB characteristics

NF-250GP, MA & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves
temperature characteristic
130

Operating Characteristics

Frame size: 250AF


125A 150A 160A 175A 200A 225A 250A

120

Current rating (%)

Max

110

Operating time

30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

100

90

Max. Total interrupting time

80 Rated ambient 50C 10

20

30

40

50

Rated ambient
60

70

Ambient temperature (C)


Time delay trip
3 4 5 6 7 10

Instantaneous trip
15 20 30 40

x 100% of rated current

NF-400GP & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves
temperature characteristic

Operating Characteristics

130

Frame size: 400AF


120

Current rating (%)

Max

110

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec Max. Total interrupting time Min

100

90

80 Rated ambient 50C 10

20

30

40

50

Rated ambient
60

250A 300A 350A 400A

70

Ambient temperature (C)


Time delay trip
1 1.3 2 3 4 5 6 7 10

18

0.01sec

Instantaneous trip
15 20 30 40

x 100% of rated current

NF-600/800GP & HA
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves
temperature characteristic

Operating Characteristics

130 600AF 120

Frame size: 600A Frame size: 800A


500A 600A 700A 800A
Max

Current rating (%)

110

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 800AF 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1

100 800AF 90

Min

600AF

Max. Total interrupting time

80 Rated ambient 50C 10

20

30

40

Rated ambient
50 60

70

Ambient temperature (C)


Time delay trip
1.3 2 3 4 5 6 7

Instantaneous trip
10 15 20 30 40

100% of rated current

NF-1200HA
tripping curve
240 120 60 In
1000A 1200A

characteristic curves
temperature characteristic
130
High
6000A10% 7200A10%

Itr Low
3000A25% 3600A25%

Minute

Max: value

Current rating (%)

10 6 4 2 1 40 20 10 6 4 2 1 0.6 0.4 0.2 0.1 0.06 0.02 0.01


1.5 2 3 4 5 6 7 8 10

120

In: Rated current(A) Itr: Instantaneous trip current Mix: value

110

Operating time

100 1200AF 90

Adjustable Instantaneous tripping setting range Max total fault clearing time

Second

80 Rated ambient 50C 10

20

30

40

Rated ambient
50 60

20

1000AF

70

Ambient temperature (C)

19
15 20 30 40 50 80 100

Multiple of rated current

MCCB characteristics

NF-100L

characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

Operating Characteristics

Frame size: 100AF


10A 15A 20A 30A 40A 50A 60A 75A 80A 100A
Max

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

Min

Time delay trip


3 4 5 6 7 10 15

Instantaneous trip
20 30 40

x 100% of rated current

NF-250L

characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

Operating Characteristics

Frame size: 250AF


125A 150A 160A 175A 200A 225A 250A

Max

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec

Min

Max. Total interrupting time

20

0.01sec
1 1.3 2

Time delay trip


3 4 5 6 7 10

Instantaneous trip
15 20 30 40

x 100% of rated current

NF-400L

characteristic curves
tripping curve
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

Operating Characteristics

Frame size: 400AF


250A 300A 350 400A
In Max Ltr Lo Hi

250A 175025% 400010% 300A 210025% 480010% 350A 245025% 560010% 400A 280025% 640010%

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

Min

Adjustment range 400AF

Max. Total interrupting time

Time delay trip


3 4 5 6 7 10 15

Instantaneous trip
20 30 40

x 100% of rated current

NF-600L, 800L
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

characteristic curves

tripping curve
Operating Characteristics

Frame size: 600AF Frame size: 800AF


500A 600A 700A 800A
Inst. trip adjustment range (4 steps)

Max

Control setting Lo 2 3 Hi Lo 2 3 Hi

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1

600

Min Adjustment range 600AF Adjustment range 800AF

800

Inst trip current(%) 600AF 800AF 500100 800 1100 1400280 350100 550 750 950280

Max. Total interrupting time

Time delay trip


1.3 2 3 4 5 6 7

Instantaneous trip
10 15 20 30 40

21

x 100% of rated current

MCCB physical dimensions & mounting holes

NF-50MA
C L

front connection
Insulation barrier (removable)

Mounting hole

C L

Screw

110

C L
22 Trip button

130

50

24

84

50

8.5

25 50

50 75 4 61 68 72 90

27

2-pole
Breaker

3-pole

C L

Breaker

C L

C L

C L

110

C L

C L

R1

25 50 M4 Screw or 5mm 70

22.5

2-pole

3-pole

22

52

4.5

NF-100GP, MA & HA
C L
Mounting hole Insulation barrier (removable)

front connection

C L
Screw 50 24

C L

134

155

50

134

155

C L
22 Trip button 30 60 60 90

102

50

8.5

30 90 120 4 72 90 Neutral pole 61 68

27

4-pole 2-pole 3-pole


Breaker

C L

Breaker

C L

C L

Breaker

C L

C L

R1

C L

132

C L

4.5 28 52

30

M4 Screw or 5mm

30

57 86

2-pole

3-pole

4-pole

23

MCCB physical dimensions & mounting holes

NF-250GP, MA & HA
Mounting hole Insulation barrier (removable)

front connection

C L
100 Screw 24

C L

144

165

120

50

Trip button

22

100

70 105

30 105 140

45 61

Neutral pole 4

68 72 92

4-pole 3-pole

Breaker

C L

Breaker

C L

C L

126

C L

35

M4 Screw or 5mm

32.5 35 100

24
3-pole 4-pole

52

R1

4.5

8.5

NF-400GP & HA
110

|
C L

front connection
94.5 44 8 16 Conductor 43

C L

Insulation barrier (removable)

28

Mounting hole 257

12.5 39 Neutral pole 97 5

C L

C L
N

102

39

47 7 44

Trip button

51 112 140

14 M12 bolt

56 168 185 196

103 107 155

4-pole

C L

Breaker

C L

3-pole

Breaker

C L

194

C L

C L

C L

R6

44

M6 screw or 7mm 44

118

92

25
3-pole 4-pole

MCCB physical dimensions & mounting holes

NF-600/800GP & HA
Mounting hole

front connection
94.5 600A frame 44 800A frame 46 600A frame 8 800A frame 12

C L
110

Insulation barrier (removable)

C L
87

Conductor

32

15

C L
N
32 Trip button 32

275

102

14

600A frame 8 800A frame 12 600A frame 14 800A frame 46 97 103 107 155

15

14 70 40 210 140 210 280

Neutral pole

87

14 M12bolt

4-pole 3-pole

C L

Breaker

C L
R6

C L

C L

243

C L

C L

70

M6 Screw or 7mm

70 172

51

26
3-pole 4-pole

92

Breaker

NF-1200HA
Mounting hole 110

front connection
94.5 Conductor 46

C L

Insulation barrier (removable)

C L
87

17

32

15

C L
N
32 Trip button

400

102

40

87

14

17 46

20

14 40

70 210

Neutral pole 5

97 103 107 155

140 210 280

14 M12bolt

4-pole 3-pole

C L

Breaker

C L
R6

C L

C L

Breaker

370

C L

C L

70

M6 Screw or 7mm

70 172

51

92

27
3-pole 4-pole

MCCB physical dimensions & mounting holes

NF-100L
Mounting hole

front connection

Insulation barrier (removable) Screw 24

3-pole

C L

50

C L

Breaker

C L

132

134

155

102

50

R1

8.5

22 Trip button

4.5

30 60 90 73 80 4 84 102 27 M4 Screw or 5mm 86

3-pole

NF-250L
Mounting hole

front connection

Insulation barrier (removable) Screw 24

3-pole

C L

100

C L

Breaker

C L

126

144

165

102

50

8.5

22 Trip button

4.5

35 70 105 45 73 80 4 84 104 M4 Screw or 5mm 100

3-pole

28

52

R1

52

NF-400L
Insulation barrier (removable) 110

front connection
94.5 44 8 Conductor

C L

16

28

3-pole

C L
43 39

Breaker

C L

Mounting hole R6 12.5

C L

47 7

Trip button

39

M6 Screw or 7mm 44 14 M12 bolt 51 112 140 5 97 103 107 155 44 118

3-pole

NF-600/800L
Mounting hole

front connection
600A frame 44 800A frame 46 600A frame 8 800A frame 12

C L

Insulation barrier (removable)

94.5 Conductor

194

C L

C L

257

102

3-pole

110

C L

87

Breaker

C L
R6

275

15 102

92

C L

C L
8

243

C L

14

Trip button 32 87

600A frame 8 800A frame 12 600A frame 14 97 5 103 107 155 800A frame 46 70

14 40 140 210

15

M6 Screw or 7mm

172

3-pole

92

29

MCCB accessories

phase insulation barriers


Inter phase barriers are provided as standard. The use of the inter phase barriers is Model a b necessary to increase the clearance distances between 59 59 NF-50 phases to prevent electrical 59 59 NF-100 faults during the operation of the circuit breaker. NF-250 NF-400 NF-600 NF-800
dimensions of phase barrier insulators in mm

62 95 95 95 95

100 116 116 116 116

a top b

NF-1200

electrical accessories & shunt trip


All electrical accessories supplied for the breaker are prewired. Accessories such as Shunt Trip, Under Voltage Trip, Alarm Switch, Auxiliary Switch and combination Alarm and Auxiliary Switch can be fitted into the breaker accessory compartments. Please refer to the table in page 31 for the accessories installation guide. Shunt Trip Device The Shunt Trip device opens the circuit breaker by means of an electrical signal. Voltages between 70% and 110% of the coil voltage rating will operate the shunt trip device. All Shunt Trip devices are factory fitted with a cut-off supply switch.

30

50 / 60 Hz Coil Voltage
AC 110 - 240 AC 100 - 450 AC 200 - 240 AC 380 - 450 AC 380 - 550 DC 100 - 125 120 50 < 15 < 15 120

Coil Power Consumption (VA) NF-50


120

NF-100
120

NF-250
120

NF-400
20 (100V) 50 (200V) 120 (330V) 170 (450V)

NF-600
200

NF-800
200

NF-1200
200

200 200 200

200 200 200 10 8 to 15

200 200

120 10 < 15 8 to 15

10 8 to 15

70 8 to 15

Trip Time (ms)

Note: Other voltages can be supplied on demand.

under voltage trip device


The Under Voltage Trip device will open the circuit breaker contacts when the supply voltage to the coil drops below 70% of its voltage rating. After tripping, the circuit breaker can be closed manually again when the supply voltage is 85% of its coil voltage rating or more. The Under Voltage Trip device is always energized during normal conditions when supply voltage is healthy.

Model
NF-250 & below NF-400 NF-800 NF-1200 100-110 100-110 100-110 100-120

AC Coil Voltage
200-220 200-220 200-220 200-240 380-415 400-440 400-440 380-450 440-480

Consump (VA)
5 5 5 5

Trip Time (ms)


< 30 5 to 30 5 to 30 6 to 35 31

MCCB accessories

signaling switches
The Signaling switches allow the breaker status information to be obtained remotely. The signaling switch consists of several dry contacts with both normally open (N.O.) and normally closed (N.C.) positions. Auxiliary Switch - Provides breaker ON and OFF status information. Alarm Switch - Provides breaker TRIP status information. Auxiliary + Alarm Switch - Provides breaker ON, OFF and TRIP status information.
Please refer to the above circuit diagram for the switch terminal codes in order to obtain different contact positions, such as N.O. and N.C. to suit the application.
ALa ALc ALb

AXa AXc AXb

Auxiliary Switch

Alarm Switch

rotary handle

mechanism

The breaker mounted rotary handle mechanism allows the user to easily switch the breaker ON by a rotating action. The rotary handle mechanism is equipped with a safety device that prevents the panel door from being open when the breaker is in ON position. A bypass screw is provided for manual intervention when breaker is in ON position. Pad locking facility is available on the rotary handle. The handle can be pad locked when the breaker is in OFF position.

32

rotary handle
104

external dimensions

150 Panel thickness 1.2~3.2 A2 130

104 45
Figure (a)

150 Extension handle (option)

20 50
Figure (b)

Panel thickness 1.2~3.2 A2

rotary handle
Center of breaker

drilling plan
breaker (x) (Y)

Center of breaker

C L
F
0 9

C L
F 112 78

18

(Y) 78 112 B
Figure (c) Figure (d) Figure (e)

(X) D

Type

Breaker Type

Figure No of External Drilling Pole Dimensions Plan


3P

Dimensions (mm) A
95 105

B
25

C
111

Mounting Screws
(X) breakers mounting screws (2pcs)

AC-NF-RHN0

NF-50MA NF-100GP MA HA

AC-NF-RHN1

NF-100L EG-100MA HA NF-250GP MA HA

3P 4P

30 a c e 117 107

132 (116)

M4 x 0.7 screw or 5
(Y) operating handle mounting screws (2pcs)

AC-NF-RHN2

NF-250L EG-250MA HA NF-400GP HA L NF-600GP HA L NF-800GP HA L NF-1200HA

3P 4P

35 119 44 b d e 183 70

126 (145)

33 AC-NF-RHN3 3P 4P 194 M6 screw or 7


(X) (Y) breakers mounting screws (4pcs)

AC-NF-RHN4

3P 4P

243

Note All rotary handles are supplied with M4 x 0.7 screws and self-tapping 5mm screws.

MCCB accessories

rotary handle

appearance

A direct rotating operating handle has a standard safety device which prevents the breaker from closing as long as the cover is open. It indicates the tripping of the breaker even in ON-lock position, but only in cases when a single padlock (35mm) is used. The degree of protection, in accordance with IEC529, is IP3X (or IP5X with provision of dustproof packing).

The use of the rotary handle mechanism increases the IP rating of the breaker

Center of hinge & Breaker Type Left hinge H


0 or more

Left hinge X1
(5H + 100) or more (8H + 100) or more

Right hinge H
Less than 10 10 or more 0 or more

Right hinge X2
170 or more (5H + 120) or more (4H + 70) or more

AC-NF-RHN0 to AC-NF-RHN2 AC-NF-RHN3 to AC-NF-RHN4

0 or more

Operating handle Front panel

Left hinge

Breaker
X1 X2

Right hinge

The figure above shows the relationship between the hinge and breaker viewed from the load side of the breaker.

34

MCCB

mounting position
Accessories NF-50 MA Shunt Trip Coil (STC) Under Voltage Trip (UVT)

internal accessory

MCCB models NF-100 NF-250 GP MA HA L GP MA HA L NF-400 GP HA L NF-600/800 GP HA L NF-1200 HA

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

R1 & 2

Auxiliary Switch (AUS)

L1 & L2

L1 & L2

L1 & L2

L1, L2

L1, L2, L3

L1, L2, L3

Alarm Switch (ALS) Auxiliary + Alarm Switch (AAS)

L1 & L2

L1 & L2

L1 & L2

L1, L2

L1, L2, L3

L1, L2, L3

L1 & L2

L1 & L2

L1 & L2

L1, L2

L1, L2, L3

L1, L2, L3

Notes 1) It is NOT possible to install both UVT and STC in the same MCCB. 2) For NF600 onwards, it is possible to install up to a maximum of 4 Auxiliary. Switches or 2 Alarm switches. 3) UVT requires a voltage module that is installed on the right side lead wire terminal.

right side

4 3 2 1
Accessory compartment slot markings

R
left side

MCCB front view

1 2 3 4

L = Left compartment; R = Right Compartment

35

MCCB

internal resistance & power loss


Type In A
10A 15A 20A 30A 40A 50A 60A 75A 80A 100A 125A 150A 160A 175A 200A 225A 250A 300A 350A 400A 500A 36 600A 700A 800A

NF-50MA
Resistance

NF-100GP
Resistance

NF-100MA
Resistance

NF-250GP
Resistance

NF-250MA
Resistance

NF-400GP NF-600GP NF-800GP


Resistance

Loss

Loss

Loss

Loss

Loss

Loss

Resistance

Loss

Resistance

Loss

15600 8700 6200 3570 1980 1480

1.6 2.0

60000 58000

6.0 1.3

7200 6700 6000 3100 1990 1480 1200 1100 980 770

0.7 1.5 2.4 2.8 3.1 3.7 4.3 6.2 6.5 7.7 450 400 380 350 310 260 7.0 9.0 9.7 10.7 12.4 13.2 575 525 425 395 365 335 9.0 11.8 10.9 12.1 14.6 16.9 196 162 148 120 12.3 14.6 18.1 19.2 100 90 25.0 32.4 70 60 34.3 38.4

2.5 45000 1.8 3.2 32000 2.9 3.4 19000 3.0 3.7 1650 1175 1120 1010 820 4.1 4.2 6.3 7.1 8.2

MCCB

internal resistance & power loss


Type In A
10A 15A 20A 30A 40A 50A 60A 75A 80A 100A 125A 150A 160A 175A 200A 225A 250A 300A 350A 400A 500A 600A 700A 800A 1000A 1200A

NF 100HA
Resistance u Loss W

NF 250HA
Resistance u Loss W

NF 400HA
Resistance u Loss W

NF 600HA
Resistance u Loss W

NF 800HA
Resistance u Loss W

NF 1200HA
Resistance u Loss W

31500 33500 17000 8500 6000 3300 2000 1500 1200 950

3.2 7.5 6.8 7.7 9.6 8.2 7.2 8.4 8.8 9.5 775 725 680 595 575 535 12.1 16.3 17.4 18.1 23.0 27.0 251 188 188 138 15.7 16.9 23.0 22.1 220 210 51.0 75.6 120 105 58.8 37 67.2 55 45 55.0 64.8

MCCB

internal resistance & power loss


Type In A
10A 15A 20A 30A 40A 50A 60A 75A 80A 100A 125A 150A 160A 175A 200A 225A 250A 300A 350A 400A 500A 38 600A 700A 800A

NF 100L
Resistance u Loss W

NF 250L
Resistance u Loss W

NF 400L
Resistance u Loss W

NF 600L
Resistance u Loss W

NF 800L
Resistance u Loss W

31500 33500 17500 9000 7000 4500 2200 1800 1500 1350

3.2 7.5 7.0 8.1 11.2 11.3 7.9 10.1 11.2 13.5 775 725 680 595 575 535 12.1 16.3 17.4 18.1 23.0 27.0 290 195 185 175 18.1 17.5 22.7 28.0 220 210 51.0 75.6 120 105 58.8 67.2

MCCB dc short circuit table

DC voltage
Model
NF-50MA

time constant 10ms or below

Pole
2 3 1 2 3 1 2 3 4 1 2 3 4 3 1 2 3 1 2 3 4 1 2 3 4 3 3 4 3 4 3 3 4 3 4 3 3 4

48V Icu/Ics 125V Icu/Ics 250V Icu/Ics 400V Icu/Ics 550V Icu/Ics 600V Icu/Ics
40 / 20 40 / 20 41 / 20 42 / 20 40 / 20 50 50 50 50 100 100 100 100 / / / / / / / / 25 25 25 25 50 50 50 50 15 / 8 15 / 8 15 / 8 15 / 8 15 / 8 30 30 30 30 80 80 80 80 / / / / / / / / 15 15 15 15 40 40 40 40 7.5 / 4 7.5 / 4 7.5 / 5 7.5 / 6 7.5 / 7 15 15 15 15 40 40 40 40 / / / / / / / / 8 8 8 8 20 20 20 20

6/3

NF-100GP

6/3

NF-100MA

10 / 5 10 / 5

8/4

8/4

NF-100HA

25 / 13 25 / 13 35 / 18

18 / 9

18 / 9

NF-100L

150 / 75 40 / 20 40 / 20 40 / 20 50 50 50 50 100 100 100 100 / / / / / / / / 25 25 25 25 50 50 50 50

100 / 50 15 / 8 15 / 8 15 / 8 30 30 30 30 80 80 80 80 / / / / / / / / 15 15 15 15 40 40 40 40

50 / 25 7.5 / 4 7.5 / 4 7.5 / 4 15 15 15 15 40 40 40 40 / / / / / / / / 8 8 8 8 20 20 20 20

NF-250GP

6/3

NF-250MA

10 / 5 10 / 5

8/4

8/4

NF-250HA

25 / 13 25 / 13 35 / 18 13 / 8 13 / 8 25 / 13 25 / 13 35 / 18 13 / 8 13 / 8 25 / 13 25 / 13 35 / 18 25 / 13 25 / 13

18 / 9

18 / 9

NF-250L NF-400GP

150 / 75 80 / 40 80 / 40 100 / 50 100 / 50 150 / 75 80 / 40 80 / 40 100 / 50 100 / 50 150 / 75 100 / 50 100 / 50

100 / 50 40 / 20 40 / 20 80 / 40 80 / 40 100 / 50 40 / 20 40 / 20 80 / 40 80 / 40 100 / 50 80 / 40 80 / 40

50 / 25 20 / 10 20 / 10 40 / 20 40 / 20 50 / 25 20 / 10 20 / 10 40 / 20 40 / 20 50 / 25 40 / 20 40 / 20

10 / 5

10 / 5

NF-400HA NF400L NF-600 / NF-800GP NF-600 / NF-800HA NF-800L NF-1200HA

18 / 9

18 / 9

10 / 5

10 / 5 39

18 / 9

18 / 9

18 / 9

18 / 9

MCCB selection table

motor circuit protection


Motor Capacity
[kW at 400/440]

3-phase motor | 400V 440V 50 / 60Hz

Motor Full-load Current [A]


1.1 1.5 1.9 2.8 3.5 5 6.6 8.6 11.5 15 22 29 36 42 56 68 83 98 135 158 193 232 282 349 430 520 545 610

MCCB In [A] 10
10 10 10 NF-50MA 10 10 10 15 15

Interrupting Capacity Icu (kA) Sym 25 50 65

0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 40 250 290 315 355

NF-100MA 20 30 40 NF-100GP 40 50 60 75 100 125 150 NF-250GP 200 225 250 300 NF-400GP 350 400 600 700 NF-600GP NF-250MA

NF-100HA

NF-100L

NF-250HA

NF-250L

NF-400HA

NF-400L

NF-600HA

NF-800L 700 800 NF-800GP NF-800HA

Short Circuit protection of electric motors The NF series circuit breakers are suitable to combine with motor starters. As defined in IEC 60947-4 standards, the starter switching device, usually a magnetic contactor, must be coordinated with the equipment capable of providing short circuit protection for circuit wiring/cables. The common starting methods for asynchronous squirrel-cage induction motors which the NF series can be used in combination are the direct-online-starters and star-delta-starters. The following selection tables, illustrating the above, shows the suitable breaker ratings that can accommodate motor starting currents. When more than one motor is connected to a branch circuit, the sum of the motor rated current equals to the rated current of the breaker.

motor selection
Motor Ratings kW HP 0.18 1/4
1.1 10 2 0.65 10 2 0.58 10 2

|
0.55 3/4
2.4 10 2 1.4 10 2 1.3 10 2

direct-online-starter
0.75 1
3.3 10 2 1.9 10 2 1.8 10 2

0.37 1/2
2.1 10 2 1.2 10 2 1.1 10 2

1.1 1.5
4.4 10 2 2.5 10 2 2.4 10 2

1.5 2
5.9 15 2 3.4 10 2 3.2 10 2

2.2 3
8.4 20 2 4.8 10 2 4.5 10 2

3 4
11 30 2 6.4 15 2 5.9 15 2

3.7 5
13.6 30 5.5 7.9 15 2 7.3 15 2

4 5.5
15.5 30 5.5 9 20 5.5 7.7 15 2

5.5 7.5
20 50 5.5 11.5 30 5.5 10.5 20 5.5

Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)

Motor Ratings

kW HP

7.5 10
26.5 60 14 15 30 5.5 14 30 5.5

11 15
38 75 22 22 50 8 20.5 50 8

15 20
50 100 38 29 60 14 27 60 14

18.5 25
61 100 38 36 75 22 33 75 22

22 30
71 125 60 41 100 38 38 75 22

30 40
97 150 60 56 100 38 52 100 38

37 50
120 175 80 70 150 60 65 125 60

45 60
145 200 100 84 125 60 77 125 60

55 75
180 225 125 104 150 80 95 150 80

75 100
240 400 200 143 200 100 130 175 100

90 125
290 500 200 170 225 125 154 200 100 41

Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)

Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.

MCCB

motor selection
Motor Ratings kW HP 110 150
349 600 200 202 400 150 185 300 150

direct-online-starter
160 220
500 800 325 290 500 200 260 500 200 360 600 200 330 600 200 450 800 325 415 700 325 570 1000 325 520 800 325

132 180
411 700 325 238 400 200 218 400 200

200 270
625

250 340
780

315 420
980

Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)

motor selection
Motor Ratings kW HP 5.5 7.5
20 50 8 11.5 30 3.5 10.5 30 3.5

|
11 15
38 75 22 22 50 8

star-delta-starter
15 20
50 100 22 29 60 14 27 60 14

7.5 10
28.5 50 8 15 30 5.5 14 30 5.5

18.5 25
61 125 38 35 75 22 33 75 22

22 30
71 150 38 41 100 38 41 100 22

30 40
97 200 60 56 100 38 52 100 38

37 50
120 225 60 70 150 50 65 150 50

45 60
145 300 80 84 175 50 77 175 50

55 75
180 400 80 104 225 60 95 200 60

75 100
240 400 100 143 225 80 130 225 80

Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) 42 Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)

20.5 50 8

Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.

motor selection
Motor Ratings kW HP 90 125
290 500 150 170 300 100 154 300 80 Motor Full-Load Current (A) Rated Current (A) 3 220V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 380V Wire Size (mm2) Motor Full-Load Current (A) Rated Current (A) 3 415V Wire Size (mm2)

|
110 150
349 600 150 202 400 125 185 300 100

star-delta-starter
132 180
411 800 200 238 400 125 218 400 125

160 220
500 1000 250 290 600 150 260 400 150

Please note that the breaker selection shown in the tables are subjected to the following: only 1 motor to be installed in the circuit and the starting current is less than 6 times of motor full load current.

installation
Model Operating Voltage
U<440V U<600V U<440V U<600V U<440V U<600V U<440V U<600V NF 50 NF 100-250 NF 400-600 NF 800-1200 25 50 75 80

safety distance requirements


Bare/Unpainted Sheetmetal (mm) B1 A B2
25 30 80 90 45 55 100 100 45 55 100 100

Insulation, Insulated Bars or Painted Sheetmetal (mm) B1 A B2


40 50 50 55 100 100 40 50 50 55 100 100

R metal plate of switchboard cable panel door It is compulsory to fit a piece of insulating sheet on the base plate if if R < 8mm

B1

43

base plate of MCCB B2 A R

MCCB

terminal-tightening torque
To ensure the correct operation of the MCCB, it is essential to make a proper cable or busbar termination to the MCCB. It is recommended that the supplied screws be used to connect the cables or busbars to the breaker terminals and tightened to the torque, as shown in the table below.

terminals for cable lugs connection


Cable size mm2 Model Min
NF-50 NF-100 NF-250 NF-400 NF-600 NF-800 NF-1200 1.6 1.6 38 150 2 x 150 N/A N/A

tightening range* Nm I
1.8 ~ 2.0 2.5 ~ 3.5 2.5 ~ 3.5 N/A N/A N/A N/A

Bolt/Screw Size
M5 screw M8 screw M8 screw M12 bolt x 2 M12 bolt x 2 N/A N/A

Screw Type
Pan head Screw Screw Bolts Bolts N/A N/A

Max
22 50 150 2 x 100 2 x 200 N/A N/A

II
N/A N/A N/A 10 ~ 14 10 ~ 14 N/A N/A

terminals for copper busbar connection


Copper busbar size mm2 Model Max t =
NF-50 NF-100 NF-250 NF-400 NF-600 NF-800 NF-1200 44
* Note Copper busbar Caution 1) Do not over tighten. If the tightening torque is exceeded, bolts/screws and copper bars may be damaged. 2) Failure to secure a terminal connection may cause an electrical fault. Make sure all terminal connections are tightly secured.

tightening range* kgf-cm I


1.8 ~ 2.0 2.5 ~ 3.5 2.5 ~ 3.5 N/A N/A N/A N/A

Bolt/Screw Size
M5 screw M8 screw M8 screw M12 bolt x 2 M12 bolt x 2 M12 bolt x 2 M12 bolt x 2

Max w =
12.5 16.5 23 25 40 44 44

II
N/A N/A N/A 10 ~ 14 10 ~ 14 10 ~ 14 10 ~ 14

5 5 7 8 8 10 17

w t

MCCB connection data

terminal-cable & copper busbar sizes


MCCB Rated Current In (A)
8 In > 0 12 In > 8 15 In > 12 20 In > 15 25 In > 20 32 In > 25 50 In > 32 65 In > 50 85 In > 65 100 In > 85 115 In > 100 130 In > 115 150 In > 130 175 In > 150 200 In > 175 225 In > 200 250 In > 225 275 In > 250 300 In > 275 350 In > 300 400 In > 350 500 In > 400 630 In > 500 800 In > 630 500 In > 400 630 In > 500 800 In > 630

ISO Square (mm2)


1 1.5 2.5 2.5 4 6 10 16 25 35 35 50 50 70 95 95 120 150 185 185 240 2 x 150 2 x 185 2 x 240 2 x (30 x 5) 2 x (40 x 5) 2 x (50 x 5)

CNS Standard Square (mm2)


1.6 2.0 2.0 2.0 5.5 8 14 22 38 38 38 50 60 80 100 100 125 150 200 200 250 2 x 150 2 x 185 2 x 240 2 x (30 x 5) 2 x (40 x 5) 2 x (50 x 5)

UL Standard AWG or kcmil at 75C


14 AWG 14 AWG 14 AWG 12 AWG 10 AWG 10 AWG 8 AWG 6 AWG 4 AWG 3 AWG 2 AWG 1 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG 250 MCM 300 MCM 350 MCM 500 MCM 2 x 3/0 AWG 2 x 250 MCM 2 x 350 MCM 3 x 300 MCM 2 x 250 MCM 2 x 350 MCM 3 x 300 MCM 45

ELCB

EG series
Ampere Frame (AF) Model Code

with overload & short circuit protection


100
EG-100MA

100
EG-100HA

Supply System Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Residual Operating Current Indication System Characteristics for DC Components Rated Breaking capacity AC 440V CNS 5422
(Asym/sym) kA

1 2W 1 3W 3 3W 3

3 4W 4

1 2W 1 3W 3 3W 3

3 4W 4

230-380-415 (Multi-voltage type) 10 15 20 30 40 50 60 75 80 100 30-100-300 (selectable) 10 15 20 30 40 50 60 75 80 100 30-100-300 (selectable)

Instantaneous Type

0.04 button Type: AC

0.04 button Type: AC

25 / 22 35 / 30 60 / 50 25 / 13 25 / 13 50 / 25 90 155 80 102 132 30 1.1 1.3 1.1 120 90

60 / 50 60 / 50 100 / 85 50 / 25 50 / 25 85 / 43 120 155 80 102 132 30 1.3

AC 380V AC 220V AC 415V

IEC 60947-2 CNS 14816-2


(Icu/Ics) kA

AC 380V AC 230V

a aa

ca c

a b c ca bb

ON

46

OFF

bb b

(mm)
Weight

aa kg

ELCB

EG series
Ampere Frame (AF) Model Code

with overload & short circuit protection


250
EG-250MA

250
EG-250HA

Supply System Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Residual Operating Current Indication System Characteristics for DC Components Rated Breaking capacity AC 440V CNS 5422
(Asym/sym) kA

1 2W 1 3W 3 3W 3

3 4W 4

1 2W 1 3W 3 3W 3

3 4W 4

230-380-415 (Multi-voltage type) 125 150 160 175 200 225 250 30-100-300 (selectable) 125 150 160 175 200 225 250 30-100-300 (selectable)

Instantaneous Type

0.04 button Type: AC

0.04 button Type: AC

25 / 22 35 / 30 60 / 50 25 / 13 25 / 13 50 / 25 105 165 80 104 126 35 1.6 1.8 1.6 140 105

60 / 50 60 / 50 100 / 85 50 / 25 50 / 25 85 / 43 140 165 80 104 126 35 1.8 47

AC 380V AC 220V AC 415V

IEC 60947-2 CNS 14816-2


(Icu/Ics) kA

AC 380V AC 230V

a aa

ca c

a b c ca bb

ON OFF

bb b

(mm)
Weight

aa kg

ELCB characteristics

EG series

operating characteristics: EG-100MA & EG-100HA

4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

EG-100MA, EG-100HA Frame size: 100AF


Rated current:

10A 15A 20A 30A 40A 50A 60A 75A 80A 100A
Max

Operating time

30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

Min

Time delay trip


3 4 5 6 7 10 15

Instantaneous trip
20 30 40

x 100% of rated current

EG series |
130

temperature & operating characteristics for instantaneous type

10A~30A 120

Current rating (%)

110

100 40A~100A 90

80 Rated ambient 50C 15 20

30

40

50

Rated ambient
60

48

Ambient temperature (C)

Residual Current % of rated residual current

ELCB characteristics

EG series

operating characteristics: EG-250MA & EG-250HA

4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min

EG-250MA, EG-250HA Frame size: 250AF


Rated current:

125A 150A 160A 175A 200A 225A 250A

Max

Operating time

30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2

Max Total Interrupting time.

Time delay trip


3 4 5 6 7 10 15

Instantaneous trip
20 30 40

x 100% of rated current

EG series |
130

temperature & operating characteristics for instantaneous type

120

Current rating (%)

110

100

90

80 Rated ambient 50C 10

Rated ambient
60

20

30

40

50

70

Ambient temperature (C)

Residual Current % of rated residual current

49

ELCB dimensions

EG series
Mounting hole

front connection: EG-100MA & EG-100HA

Insulation barrier (removable)

C L
Screw

C L

134

155

50

24

120

50

8.5

22 Trip button

60 90

30 90 120 4 Neutral pole 73 80 84 102

27

4-pole 3-pole Breaker

C L

Breaker

C L

C L

132

C L

R1

28 30 M4 Screw or 5mm 30 86

50
3-pole 4-pole

52

4.5

ELCB dimensions

EG series
Mounting hole

front connection: EG-250MA & EG-250HA

Insulation barrier (removable)

C L
100 Screw 24

C L

144

165

102

50

8.5

22 Trip button

70 105

35 105 140 4 Neutral pole

45 73 80 84 104

4-pole 3-pole Breaker

C L

Breaker

C L

C L

C L

126

32.5 35 M4 Screw or 5mm 35 100

3-pole

4-pole

52

R1

4.5

51

MCB

BHQ series | fixed type


Ampere Frame (AF) Model Code 100
BHQ-1

100
BHQ-2

100
BHQ-3

Number of Pole (P) Rated Voltage: Ue Vac Rated Current: In (A) at Ambient Temperature: 50 C Breaking capacity (kA) AC 220V CNS 2931
(Asym/sym) kA

1 220 / 415

2 220 / 415

3 220 / 415

10 15 20 30 40 10 15 20 30 40 10 15 20 30 40 50 60 75 80 100 50 60 75 80 100 50 60 75 80 100

10 6/3

10 6/3 1 50 95 58.5 77.5 100 25 0.31

10 6/3 75 95 58.5 77.5 100 50 0.46

AC 110/220V AC 220/415V IEC 60947-2 CNS 14816-2 DC 125V a


a aa ca c

25 95 58.5 77.5 100 0 0.15

b c

b bb

ca bb aa

Weight

kg

52

BHP series | plug-in type


Ampere Frame (AF) Model Code 100
BHP-1

100
BHP-2

100
BHP-3

Number of Pole (P) Rated Voltage: Ue Vac Rated Current: In (A) at Ambient Temperature: 50 C Breaking capacity (kA) AC 220V CNS 2931
(Asym/sym) kA

1 220 / 415

2 220 / 415

3 220 / 415

10 15 20 30 40 10 15 20 30 40 10 15 20 30 40 50 60 75 80 100 50 60 75 80 100 50 60 75 80 100

10 6/3

10 6/3 1 50 74 60.5 77.5 25 0.26

10 6/3 75 74 60.5 77.5 50 0.39

AC 110/220V IEC 60947-2 CNS 14816-2


(Icu/Ics) kA

AC 220/415V DC 125V a

25 74 60.5 77.5 0 0.13

a aa

ca c

b c ca bb aa

Weight

kg

53

MCB characteristics

BHQ & BHP series


4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min 30sec 20sec 10sec 5sec 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2 3 4 5 6 7 10

operating characteristics

Type : BHQ, BHP


Rated current:

10A 15A 20A 30A 40A 50A 60A 75A 80A 100A

Max (10~50A) Max (60~100A)

Operating time

Min (10~50A)

Min (60~100A)

15

20

30

40

x 100% of rated current

BHQ & BHP series


150 145 140 135

temperature characteristics

Current rating (%)

130 125

10A

40A~50A 120 115 110 105 100 15A~30A 60A~100A

95 Rated ambient 50C 10

15 20

25 30 35 40

45 50 55

Rated ambient
60

54

Ambient temperature (C)

MCB dimensions

BHQ series | fixed type

front connection
32

M5 Screw Mig bracket (Line side & Load side)

73

95

57

100 74

C L

25

50

58.5 Mig bracket 63.5 77.5

25

50

75

22

47

47

5.5

13.5

1-pole

2-pole

3-pole

BHP series | plug-in type


7.5

front connection
Plug-in terminal (Line side)

57.5

71.5

M5 Screw (Load side)

113

87

55
25 25 50 25 75 25 60.5 65.5 77.5 Mig Slot

1-pole

2-pole

3-pole

RCBO

EQ series | fixed type


Ampere Frame (AF) Model Code 50
EQ-1

with overload & short circuit protection


50
EQ-2

50
EQ-3

Supply System

1 2W

1 2W

1 2W 1 3W 3 3W 3 220 / 240 10 15 20 30 40 50

Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Characteristics for DC Components Rated Breaking capacity (kA) AC 220/380V CNS 5422
(Asym/sym) kA

1 220 / 240 10 15 20 30 40 50

2 220 / 240 10 15 20 30 40 50

30

30

30

Instantaneous Type

0.04 Type: AC

0.04 Type: AC

0.04 Type: AC

10

10

10

AC 110/220V IEC 60947-2 CNS 14816-2


(Icu/Ics) kA

AC 220/240V a

10 / 5

10 / 5

10 / 5

25 96 58 77 100 0.2

50 96 58 77 100 25 0.3

75 96 58 77 100 50 0.5

ca c

b c

b bb

56

ca bb aa

Weight

kg

EP series | plug-in type


Ampere Frame (AF) Model Code 50
EP-1

with overload & short circuit protection


50 50
EP-3

EP-2

Supply System

1 2W

1 2W

1 2W 1 3W 3 3W 3 220 / 240 10 15 20 30 40 50

Number of Pole (P) Rated Operational Voltage: Ue Vac Rated Current: In (A) at Ambient Temp 50C Rated Residual Operating Current In (mA) Max Operating Time at 5 In (Sec) Characteristics for DC Components Rated Breaking capacity (kA) AC 220/380V CNS 5422
(Asym/sym) kA

1 220 / 240 10 15 20 30 40 50

2 220 / 240 10 15 20 30 40 50

30

30

30

Instantaneous Type

0.04 Type: AC

0.04 Type: AC

0.04 Type: AC

10

10

10

AC 110/220V IEC 60947-2 CNS 14816-2


(Icu/Ics) kA

AC 220/240V a

10 / 5

10 / 5

10 / 5

25 83 62 81 0.2

50 83 62 81 0.3

75 83 62 81 0.5 57

ca c

b c

ca bb aa

Weight

kg

RCBO characteristics

EQ & EP series
4hr 2hr 1hr 30min 20min 14min 10min 6min 4min 2min 1min 30sec 20sec 10sec 5sec Min 2sec 1sec 0.5sec 0.2sec 0.1sec 0.05sec 0.02sec 0.01sec
1 1.3 2 3

operating characteristics

Type: EQ-1, EQ-2, EQ-3, EP-1, EP-2, EP-3


Rated current:

10A 15A 20A 30A 40A 50A

Operating time

Max

5 6 7

10

15

20

30

40

x 100% of rated current

EQ & EP series |
150 145 140 135

temperature & operating characteristics for instantaneous type

Current rating (%)

130 125 120 115 110 105 100 30A~50A 10A~20A

95 Rated ambient 50C 10

15 20

25 30 35 40

45 50 55

Rated ambient
60

58

Ambient temperature (C)

Residual Current % of rated residual current

RCBO dimensions

EQ series | fixed type

front connection

EP series | plug-in type

front connection

59

ordering codes | MCCB NF 400 HA 300A 3P


type frame size breaking capacity nominal current pole

STC
accessory

3
accessory frame size

breaking capacity, Icu @ 415V ~


Frame Size Icu 50AF GP MA HA L
10kA

100AF
10kA 25kA 50kA 65kA

250AF
10kA 25kA 50kA 65kA

400AF
25kA

600AF
25kA

800AF
25kA

1200AF

50kA 65kA

50kA 65kA

50kA 65kA

50kA

accessories
Item Shunt trip coil (240Vac) UVT (415Vac) Auxiliary switch Alarm switch Auxiliary + alarm switch Rotary handle Code
STC UVT AUS ALS AAS RHN

accessory frame size


Code 0 1 2 3 Size
50AF 100AF 250AF 400AF to 1200AF

poles
No of Poles Description 1 2 3 4
1 phase 2 phase 3 phase 3 phase + neutral

Example: NF
60

400

HA

300A

3P

STC

400A frame size breaker with Rated Nominal current of 300A, 3-poles and complete with 400A frame size Shunt trip coil.

what is quality ?
We define quality as products having the highest level of reliability, performance and design. Our aim for quality is to meet the requirements of other global markets and to exceed the current international standards. With our in-house design and development team, our range of products are currently manufactured in accordance and compliance to various international standards.