Protection Systems

2.0
Protection Systems

Chapter-Content

Page 2 5 8 9 10

2.0 2.1 2.2 2.3 2.4

Protection Systems Introduction ComProtect GDT-Magazines Overvoltage Protection Components Testing Device for Overvoltage Protection Components

23

http://www.krone-gmbh.at

2 - Page 1

2.0
Protection Systems Application
Overview

Protection Systems

The trend towards increasing investments in technical equipment for data processing and other communication systems at the workplace can result in substantial losses when this equipment is destroyed as a result of overvoltage. Damaged or destroyed equipment, which is integrated into manufacturing or data storage processes, does not only result in direct damage but also in high costs due to downtime. Furthermore, delays in production due to data loss, damaged process control computers or computerized warehouse and storage systems are by no means rare. These delays cost many times the amount of the direct damage. According to the insurance industry, indirect influences are responsible for 95% of the damage as a result of atmospheric discharges (lightning). This also gives weight to the fact that networks located kilometers away from the site of impact can be damaged. The total annual damage caused by this phenomenon in Germany alone totals more than EUR 250 million. Apart from the material loss, plant and network operators also face the danger to life and health. It is all too often that they suddenly realize that even small excess voltages have caused unforeseeable damage. Too late - if no precautions have been taken.

Planning phase Before the planning phase begins, the requirements for the protection system must be examined together with the operating conditions. Overrated protection hardly ever leads to damage, however, it does have an impact on the economic efficiency of the equipment. Over-rated protection also means an increase in repair costs and poses a risk to life and limb. Installation takes place after the distribution equipment has been set up. Retrofitting of existing equipment is in most cases not a problem if LSAPLUS and LSA-PROFILE systems are installed. Apart from the electrical characteristics, the conditions of the interface with the distributor system, and, if necessary, also the housing dimensions must be taken into consideration at the earliest possible stage. The following protection modules are available for the LSA-PLUS series (series 2): KRONE protection modules Magazine Network condition Selectioncondition < > Protection module LSA-PLUS distribution modules Jumpering with protection module in place no yes

connection/disconnection modules

1 pair connection/disconnection modules ComProtect A 1 pair disconnection/switching modules ComProtect B 1 pair disconnection/switching modules ComProtect C

Operating voltage Voltage resistance of the equipment to be protected Nominal current

Response voltage Impulse response voltage

yes

no

<

Nominal current

1 pair disconnection/switching modules ComProtect D 1 pair disconnection/switching modules ComProtect H

no

Cut-off frequency (Transmission rates)

<

Cut-off frequency

yes

2 - Page 2

http://www.krone-gmbh.at

23

Protection Systems

2.0
Protection Systems

Selection
Selection In line with signal potentials, a distinction is made between 3-point and 5-point protection. In case of connection modules, only 3-point protection is possible. Switching modules are basically recommended for 5-point protection (components in the signal path) because - once the protective plug has been removed - the contact in the module is open, so that possible faults cannot make their way to the downstream network. 5-point protection can also be implemented using disconnection modules. KRONE supplies various types of protective circuits: 3-point protection: pure overvoltage protection (high-voltage or secondary protection) 5-point protection: overvoltage protection combined with current protection 5-point protection: graded protection (high-voltage and secondary protection with current protection).

Fail-Safe Protective circuits with an integrated fail-safe feature are highly recommended. Components for overvoltage protection are usually designed for pulse-shaped loads only. Therefore, if permanent overloads are possible (e.g. mains contact), a safe short-circuit to earth must be ensured. Overloaded or overheated protection components would not only lose their protective function, they could cause fire or an explosion thereby leading to considerable damage.

Service Properly dimensioned overvoltage protection components have a serviceable life of several decades and require no additional maintenance. It is recommended that the nominal DC response voltage of overvoltage arrestors be tested every 6 years. If the protective circuit has been subjected to impulse current, it is recommended that the arrestors be replaced for safety reasons.

23

http://www.krone-gmbh.at

2 - Page 3

2.0
Protection Systems Application
Operating voltage of the network Telecommunications: Operating current of the network

Protection Systems

Cut-off-frequency/ transmission rate

Recommended type *)

Analogue line telecommunication ISDN S 0 -interface ISDN U K0 -interface

160 V

< 100 mA

4 KHz

CP BI 180 A1 CP HGB 180 A1 CP AA 180 A1 CP BI 70 A1 CP HGB 180 A1 CP BI 70 A1 CP BI 180 A1 CP HGB 180 A1 CP BI 70 A1 CP HGB 180 A1 CP BI 12 A1 CP HGB 180 A1 CP BI 180 A1 CP HGB 180 A1

42 V 70 V 99 V

< 60 mA

192 kbit/s

< 60 mA

2 Mbit/s

Connection Pmux (primary multiplex connection) PCM (without external supply) PCM (with external supply 100 V) Modem for telecommunication line Modem for Datex P Data transmission: RS 232 RS 485 Ethernet Token-Ring Measuring and Control Technology: TTL - level

60 V

< 60 mA

2 Mbit/s

5V

< 60 mA

2 Mbit/s

100 V

< 60 mA

2 Mbit/s

60 V

< 60 mA

64 kbit/s

CP BI 70 A1

12 V

< 60 mA

48 kbit/s

CP BI 12 A1

12 V 5V 5V 5V

< 20 mA < 20 mA < 20 mA < 20 mA

20 kbit/s 2 Mbit/s 20 Mbit/s 16 Mbit/s

CP BI 12 A1 CP HIE 5 A1 CP HIE 5 A1 CP HIE 5 A1

5V

< 20 mA

64 kbit/s

CP BI 12 A1 CP CJ 12 A1 CP BI 24 A1 CP CJ 24 A1

TTY - level

24 V

< 20 mA

64 kbit/s

*) prefered types from the product range. Alternatives and solutions for other requirements on request.

2 - Page 4

http://www.krone-gmbh.at

23

ComProtect

2.1
Protection Systems

ComProtect - Protection Plug


ComProtect A-Series Pack pure overvoltage protection 5909 1 011-01 ComProtect 2/1 CP AA180A2 10 pcs 5909 1 011-11 ComProtect 2/1 CP AA280A2 10 pcs One packing unit of 10 pcs includes 1 pc earth rail 2/10 3-point overvoltage protection, 1-pair version. For a max. operating voltage of 180 V (Typ 2/1 CP AA 180A2) and 280 V (Typ 2/1 CP AA 280A2). For use as primary overvoltage protection for analogue telecommunication lines. The protection circuit consists of highly effective 2-pole GDTs (Gas Discharge Tubes) and fail-safe contacts (thermal overload protection of the arrestors). Jumpering work can be carried out on protected distribution modules. Installed height: approx. 21 mm above LSA-PLUS module. Type AA180A2 AA280A2 Max. operating voltage 180 V 280 V DC spark over voltage arrester @ 100V/s (a/b-e) 230 V 350 V Tolerance of DC spark-over voltage 20% 20% Max. operating current (a-a/b-b ) @ 20 C Max. output voltage @ 1kV/s (a/b-e) < 800 V < 900 V Nominal arrester surge current (8/20s; a/b-e) 5 kA 5 kA Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) 5 A 5A Nominal decoupling resistance (a-a/b-b) @ 20C Typ. operating frequency (3 dB, Z w = 600) > 65 MHz > 65 MHz Typ. operating frequency (3 dB, Z w = 150) > 100 MHz >100 MHz Order No.

Order No. ComProtect B-Series Pack 5909 1 084-00 ComProtect 2/1 CP BI12A1 10 pcs 5909 1 083-00 ComProtect 2/1 CP BI24A1 10 pcs 5909 1 082-00 ComProtect 2/1 CP BI70A1 10 pcs 5909 1 076-00 ComProtect 2/1 CP BI180A1 10 pcs One packing unit of 10 pcs includes 1 pc earth rail 2/10 5-point overvoltage protection, 1-pair version. Primarily designed to protect exchange equipment and terminal units for analogue and ISDN telecommunication lines. The protection circuit consists of 3-pole GDTs (Gas Discharge Tubes), fail-safe contacts, current limiting protection elements and secondary overvoltage protection. Jumpering work can be carried out on protected distribution modules. Installed height: approx. 21 mm above LSA-PLUS-module. Type Max. operating voltage DC spark over voltage arrester @ 100V/s (a/b-e) Tolerance of DC spark-over voltage Max. operating current (a-a/b-b) @ 20 C Max. output voltage @ 1kV/s (a/b-e) Nominal arrester surge current (8/20s; a/b-e) Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) Nominal decoupling resistance (a-a/b-b) @ 20C Typ. operating frequency (3 dB, Z w = 600) Typ. operating frequency (3 dB, Z w = 150) BI12A1 12 V 90 V 20% 90 mA < 30 V 5 kA 5A 25 Ohm 8 MHz 30 MHz BI24A1 24 V 90 V 20% 90 mA < 60 V 5 kA 5A 25 Ohm 8 MHz 30 MHz BI70A1 70 V 90 V 20% 90 mA < 190 V 5 kA 5A 25 Ohm 8 MHz 30 MHz BI180A1 180 V 230 V 20% 120 mA < 350 V 5 kA 5A 10 Ohm 8 MHz 30 MHz

23

http://www.krone-gmbh.at

2 - Page 5

2.1
Protection Systems ComProtect - Protection plug
Order No. ComProtect B-Series 5909 1 078-00 ComProtect 2/1 CP BOD180A1 5909 1 078-30 ComProtect 2/1 CP BOD180A4 One packing unit of 10 pcs includes 1 pc earth bar 2/10 5-point overvoltage protection, 1-pair version. Primarily designed to protect exchange equipment. The protection circuit consists of 3-pole GDTs (Gas Discharge Tubes), current limiting protection elements and secondary overvoltage protection. The current protection serves as resettable line protection. Jumpering work can be carried out on protected distribution modules. Installed height: approx. 21 mm above LSA-PLUS module. Type Max. operating voltage DC spark over voltage arrester @ 100V/s (a/b-e) Tolerance of DC spark over voltage Max. operating current (a-a /b-b) @ 20 C Max. output voltage @ 1kV/s (a/b-e) Nominal arrester surge current (8/20s; a/b-e) Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) Nominal decoupling resistance (a-a/b-b) @ 20C Typ. operating frequency (3 dB, Z w = 600) Typ. operating frequency (3 dB, Z w = 150) Order No. ComProtect - C-Series 5909 1 037-03 ComProtect 2/1 CP CJ24A1 5909 1 037-00 ComProtect 2/1 CP CJ60A1 One packing unit of 10 pcs includes 1 pc earth bar 2/10 Modular 5-point protection plug, 1-pair version. Primarily designed to protect exchange equipment and terminal units for analogue and ISDN telecommunication lines. The protection circuit consists of 3-pole GDTs (Gas Discharge Tubes), fail-safe contacts, current limiting protection elements and secondary overvoltage protection. Installed height: approx. 56 mm above LSA-PLUS-module. Type Max. operating voltage DC spark overvoltage arrester @ 100V/s (a/b-e) Tolerance of DC spark overvoltage Max. operating current (a-a /b-b) @ 20 C Max. output voltage @ 1kV/s (a/b-e) Nominal arrester surge current (8/20s; a/b-e) *) Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) Nominal decoupling resistance (a-a/b-b) @ 20C Typ. operating frequency (3 dB, Z w = 600) Typ. operating frequency (3 dB, Z w = 150) CJ24A1 24 V 230 V 20% 370 mA 90 V 5 kA 5A 1.7 Ohm 0.5 MHz 0.15 MHz CJ60A1 60 V 230 V 20% 370 mA 150 V 5 kA 5A 1.7 Ohm 0.5 MHz 0.15 MHz Pack 10 pcs 10 pcs BOD180A1 180 V 500 V 20% 90 mA < 350 V 5 kA 5A 20 Ohm 8 MHz 30 MHz BOD180A4 180 V 230 V 20% 100 mA < 500 V 5 kA 5A 30 Ohm 65 MHz 100 MHz Pack 10 pcs 10 pcs

ComProtect

2 - Page 6

http://www.krone-gmbh.at

23

ComProtect

2.1
Protection Systems

ComProtect - Protection plug


Order No. ComProtect H-Series 5909 1 120-00 ComProtect 2/1 CP HIE5A1 10 pcs One packing unit of 10 pcs includes 1 pc earth bar 2/10 Pack

Modular 5-point protection plug, 1-pair version. For use in data networks with non-shielded cables. The protection circuit consists of highly effective 3-pole GDTs (Gas Discharge Tubes) and fail-safe contacts, current limiting protection elements and low capacitance secondary overvoltage protection. Jumpering work can be carried out on protected distribution modules. Installed height: approx. 33 mm above LSA-PLUS module.

Type Max. operating voltage DC spark overvoltage arrester @ 100V/s (a/b-e) Tolerance of DC spark overvoltage Max. operating current (a-a /b-b) @ 20 C Max. output voltage @ 1kV/s (a/b-e) Nominal arrester surge current (8/20s; a/b-e) Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) Nominal decoupling resistance (a-a/b-b) @ 20C Typ. operating frequency (3 dB, Z w = 600) Typ. operating frequency (3 dB, Z w = 150)

HIE5A1 5V 230 V 20% 120 mA < 18 V 5 kA 5A 8 Ohm -

Order No. Accessories 6089 2 122-00 LSA-PROFIL earth clip

Pack 10 pcs

Provides the contact between the earth bar 2/8 or 2/10 and the profile rods of the LSA-PROFILE system.

5909 3 041-00 ComProtect earth bar 2/10 5909 3 042-00 ComProtect earth bar 2/8

10 pcs 10 pcs

Earth connection for 1-pair protection plugs (ComProtect) between the protection plugs and the distribution frame.

23

http://www.krone-gmbh.at

2 - Page 7

2.2
Protection Systems Overvoltage protection magazines
Order No. Magazine for Series 2 (8x6-GDTs) 6089 2 024-01 LSA-GDT magazine 2/10, 8x6 6036 2 004-01 LSA-GDT magazine 2/8, 8x6 Pack 10 pcs 10 pcs

GDT Magazines

Unequipped LSA-PLUS overvoltage protection magazine 2/10 (2/8), can be equipped with 20 pcs (16 pcs) 2pole GDTs 8 x 6 and with 20 pcs (16 pcs) fail-safes. Primary overvoltage protection, 3-point overvoltage protection. Order No. Accessories 6417 3 022-01 LSA-GDT magazine cover transparent Pack 1 pc

Order No. 6717 3 341-00 6717 3 343-00 6717 3 343-01 6717 3 344-00

2-pole overvoltage arrester 8x6 GDT 8x6, MC, 90V,20kA GDT 8x6, MC, 230V,20kA GDT 8x6, MC, 230V,10kA GDT 8x6, MC, 350V,20kA

Pack 1 pc 1 pc 1 pc 1 pc

6417 2 010-00 LSA-GDT-fail-safe 1 pc Fail-safe for overvoltage protection magazines 2/10 or 2/8 with 8 x 6 mm GDTs. For thermal overload protection in the event of overheating. Only for use in conjunction with metal-ceramic-type GDTs. Order No. Magazine for Series 2 (8x13-GDTs) Pack 6089 2 023-01 LSA-GDT magazine 2/10, 8x13 10 pcs 6036 2 003-01 LSA-GDT magazine 2/8, 8x13 10 pcs Unequipped LSA-PLUS overvoltage protection magazine 2/10 for 10 pcs 3pole GDTs 8x13. 3-point, primary overvoltage protection. Unequipped LSA-PLUS overvoltage protection magazine 2/8 for 8 pcs 3pole GDTs 8x13. 3-point, primary overvoltage protection. Order No. Accessories 6417 3 022-01 LSA-GDT magazine cover transparent Pack 1 pc

Order No. 3-pole overvoltage arrester 8x13 6717 3 503-00 GDT 8x13, MK, 230V, 10kA 6717 3 504-00 GDT 8x13, MK, 350V, 5kA GDTs with fail-safe 6717 3 513-00 GDT 8x13, MK, 230V, 10kA, T 6717 3 513-90 GDT 8x13, MK, 230V, 20kA, T 6717 3 514-00 GDT 8x13, MK, 350V, 10kA, T Nominal arrester surge current (a/b-e)

Pack 1 pc 1 pc

1 pc 1 pc 1 pc

2 - Page 8

http://www.krone-gmbh.at

23

Protection Systems

2.3
Protection Systems

Protection components for LSA-NT and 2 pairs connections


Order No. ComProtect for NT-Series Pack 7019 1 007-00 ComProtect NTP I180A1-NT/10 10 pcs 7019 1 010-00 ComProtect NTP OD180A1-NT/10 10 pcs 7019 1 010-01 ComProtect NTP OD 180 A-NT/8 8 pcs One packing unit of 10 pcs (8 pcs) includes 1 pc earth bar NT/10 (NT/8) Modular 5-point protection plug, 1-pair version. Suitable for partial or complete equipping of LSA-PLUS NT (LSA PROFIL NT) disconnection or switching modules in conjunction with the earth bar (7019 3 016-00 (8 pairs) or 7019 3 017-00 (10 pairs)). Used for exchange linecard equipment and terminal units. The protection circuit consists of 3-pole GDTs (Gas Discharge Tubes), fail-safe contacts, current limiting protection and secondary protection by diodes. Mounted height: approx. 32mm from the LSA-PLUS NT module. Order No. Accessories 7019 3 017-00 ComProtect earth bar NT/10 7019 3 016-00 ComProtect earth bar NT/8 Order No. Magazine for Series NT 7019 2 003-00 LSA-GDT-magazine-NT/10-180B1 230 V, 10 A, 10 kA, T 7019 2 003-01 LSA-GDT-magazine-NT/10-180B2 230 V, 10 A, 20 kA, T 7019 2 003-02 LSA-GDT-magazine-NT/10-280B3 350 V, 10 A, 20 kA, T 7019 2 003-04 LSA-GDT-magazine-NT/10-330B5 420 V, 10 A, 10 kA, T 7019 2 006-00 LSA-GDT-magazine-NT/8-180B1 230 V, 10 A, 10 kA, T 7019 2 006-01 LSA-GDT-magazine-NT/8-280B2 350 V, 10 A, 20 kA, T 7019 2 006-02 LSA-GDT-magazine-NT/8-330B3 420 V, 10 A, 20 kA with 3pole GDTs, T version equipped with fail safe . Order No. ComGuard graded protection 5909 1 138-00 ComGuard 2 DA OD180A5 5909 1 152-00 ComGuard 2xRJ45 OD180A5 Pack 1 pc 1 pc Pack 10 pcs 10 pcs 10 pcs 10 pcs 10 pcs 10 pcs 10 pcs

Type I180A1 OD180A1 Max. operating voltage 180 V 180 V DC spark overvoltage arrester @ 100V/s (a/b-e) 230 V 420 V Tolerance of DC spark overvoltage . 20% 20% Max. operating current (a-a /b-b) @ 20 C 100 mA 70 mA Max. output voltage @ 1kV/s (a/b-e) < 450 V < 350 V Nominal arrester surge current (8/20s; a/b-e) 5 kA 2.5 kA Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) 5 A 2.5 A Nominal decoupling resistance (a-a/b-b) @ 25C 10 Ohm 25 Ohm Typ. operating frequency (3 dB, Z w = 600) 8 MHz 8 MHz

Pack 1 Set 1 Set

ComGuard is a system-neutral protection system for 2 pairs (LSA or RJ45). In analog, ISDN-networks preferably used for the protection of electronic equipment, such as fax, modem, answering machines and computers. The protection system consists per pair of one 3pole arrester, fail-safe, current and secondary protection (diodes). The current protection is realized as a reversible line protection. Easy installation, no special tools are needed. 1 set includes 1 pc LSA-PLUS simple tool (6417 1 830-00). Type Max. operating voltage DC spark overvoltage arrester @ 100V/s (a/b-e) Tolerance of DC spark overvoltage . Max. operating current (a-a /b-b) @ 20 C Max. output voltage @ 1kV/s (a/b-e) Nominal arrester surge current (8/20s; a/b-e) *) Nominal arrester alt. discharge current (50Hz, 1s; a/b-e) Nominal decoupling resistance (a-a /b-b ) @ 20C Capacity (1kHz/1Vrms, a/b-e) Diode leakage current (at 100V) OD180A5 180 V < 350 V 20 % 120 mA < 30 V 5 kA 5 A 10 Ohm20% 200 pF < 2 A

23

http://www.krone-gmbh.at

2 - Page 9

2.4
Protection Systems Testing Device for Overvoltage Protection Components
Order No. Test device 0637 0 011-66 ComProtect-A46 test device with adapter LE10R for LSA Series 2 Pack 1 pc

Testing Device for Overvoltage Protection Components

Portable ComProtect testing device for measuring tolerance limits, interruptions and short-circuits in protection circuits. Automatic measurement of wall positions of the adapter used. Visual and audible fault signals. Supplied in a case with adapter for LSA-PLUS 2/10 for testing of LSA-PLUS magazines 2/10 and ComProtect. Dimensions: 170 x 400 x 70 mm

Order No. Software 0637 0 011-67 ComProtect-A46 software for ComProtect-A46 test device

Pack 1 pc

Software for A46 software and adapter cable for the portable ComProtect test device for statistic measured value acquisition and evaluation on the PC. MS-DOS-version for PCs up to 200MHz. Version for Windows2000/XP comming soon. Order No. Adapter for LSA-NT 5909 1 306-00 ComProtect-A46LSA-PLUS NT Adapter Pack 1 pc

LSA-PLUS NT adapter for the portable ComProtect test device with a slot for LSA-PLUS NT magazines and 1-pair NT protection plugs Order No. Adapter for LSA-PLUS 7/10 5909 1 307-00 ComProtect-A46 LSA-PLUS 7/10 Adapter Pack 1 pc

LSA-PLUS 7/10 adapter for the portable ComProtect test device with a slot for LSA-PLUS magazines 7/10 Other adapters on request

Technical Data: Measuring range Resolution internal Resolution of the display Measuring precision static voltage rise 1) Dynamic voltage rise Test current during continuity check Operating voltage mains power supply Operating current (display) Operating current (measurement) Battery (IEC 6F22; NEMA-1604-A) 5 - 800 0.2 1 1 +/- 100 +/- 1000 10 8 - 36 7 35 V V V % V/sec V/sec mA VDC mA mA

1) in agreement with VDE 0845 and ITU-T K.12 CE-indication according to low-voltage guideline 73/23/EWG and EMV-guideline 89/336/EWG

2 - Page 10

http://www.krone-gmbh.at

23