ALSTOM T&D India Limited, P.O. NAINI, ALLAHABAD 211008 (U.P.) INDIA
: +91 (532) 2699990, Extension: 1460/1490 : +91 (532) 2697604/ 606 : +91 (532) 2699990, Extension: 1508
E-mail : customer-service.pti@alstom.com
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 2 of 205
CONTENTS
Section
1 2 3 4 5 6 7 8 9 10 11 12 13 General Transport, Packing & Despatch Storage Installation Insulation Dryout at Site Commissioning Erection Checklists Commissioning Checklists Operation Maintenance Trouble Shooting Reference Standards Transformer Accessories: (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) Temperature Indicator Gas & Oil Operated Relays Condenser Type OIP Bushings Silica Gel Breather Oil Level Indicator Pressure Relief Valve Exhaust Fan Flow Indicators Transformer Oil Pump Flexible Separator Thermosiphon Filter Oil to Water Heat Exchanger
Description
Page
3 18 26 34 57 59 64 68 79 81 89 102 114 115 124 140 152 156 161 167 171 184 192 197 200
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 3 of 205
MUST READ
THE FOLLOWING CLAUSES IN THIS MANUAL ARE OF UTMOST IMPORTANCE AS REGARDS SAFETY AND HEALTH OF THE PERSONNEL AND EQUIPMENT ARE CONCERNED. HENCE, EVERY ONE INVOLVED IN THE ERECTION, COMMISSIONING, OPERATION OR MAINTENANCE OF THE EQUIPMENT SHOULD STUDY THE CONTENTS OF THESE CLAUSES CAREFULLY BEFORE TAKING UP ANY OF THE SAID ACTIVITIES. Clause1.2 on Pages 10 ~ 13 Clause 1.3 on Pages 14 ~ 17 Clause 2.3 on Page 20 Clause 3.0 on Pages 26 ~ 33 Clause 4.2 on Pages 38 ~ 39 Clauses 4.5 ~ 4.8 on Pages 40 ~ 44 Clause 4.2 on Page 56 Clause 6.0 on Page 51 : (Health & Safety matters) : (Dos & Donts) : (Lifting & Jacking) : (Receipt & Storage) : (Oil sampling & Filtering) : (Erection Precuations) : (Mixing of Transformer Oil) : (Commissioning)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 4 of 205
1.0
from one voltage to another. Shunt Reactors are used in high voltage systems to compensate capacitive generation from long lightly loaded overhead lines or extended cable systems and also for control of dynamic over voltages. When single pole reclosing is used on lines, the Neutral Grounding Reactor is used. Design, Construction, Installation, Operation and Maintenance also become more and more critical. and condition monitoring of the transformer/reactor, it can give the user trouble free service throughout the expected life of equipment. Hence, it is very essential that the personnel associated with the installation, operation or maintenance of the transformer are thorough with the instructions provided by the manufacturer. Manual contains general descriptions about Transformers/Reactor & specific details about the particular contract against which they are supplied. Also, it contains instructions regarding the safety aspects, erection, commissioning, operation, maintenance & trouble shooting of large capacity Power Transformers/reactor.
As the system voltage goes up, the techniques to be used for the
This
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 5 of 205
1.1
CONSTRUCTION The techniques used in the design and construction of high voltage
transformers/reactor varies from manufacturer to manufacturer. windings.
The active parts of the transformers/reactor consist of core and 1.1.1 CORE Transformer Core is manufactured from lamination of Cold Rolled
Grain Oriented Silicon Steel, which gives very low specific loss at operating flux densities. Joints of the laminations are designed such that the electromagnetic flux is always in the direction of grain orientation. The core clamping structure is designed such that it takes care of all the forces produced in the windings in the event of any short circuit. Shunt reactors are with three Gapped core main limbs. The core segments of main limb are of radial laminated configuration & core sections in each core packet are moulded in epoxy resin to prevent movement between individual laminations.The entire assembly of core packet is kept under postive pressure through rigid clamping structure provided for clamping of magnetic frame. NGR is an air cored reactor.
1.1.2
Windings Windings are made from paper insulated copper conductors which are transposed at regular intervals throughout the winding for ensuring equal flux linkage and current distribution between strands.
windings to ensure uniform distribution of impulse voltages. Insulation spacers in the winding are arranged such that oil is directed through the entire windings for ensuring proper cooling.
1.1.3
COOLING For ONAN/ONAF cooling, oil flows through the winding and external
cooler unit attached to the tank by thermo-syphonic effect. winding by oil pumps provided in the external cooler unit.
For OF AF/OD AF/ OF WF cooling, the oil is directed through the External cooler unit/units consists of pressed steel sheet radiators
mounted directly on the tank or separate cooler banks for air-cooled transformers and oil to water heat exchangers for water cooled transformers.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 6 of 205
1.1.4
TANK & COVER Tank and Cover are manufactured by welding steel plates and are
suitable for withstanding full vacuum and positive pressure test as per CBIP Manual. For large capacity power transformers, the tank will be of bell type construction. This is to avoid lifting of heavy core and windings, which requires very large capacity crane at site. The weight of upper tank will be much less in comparison with that of core & windings and can be lifted by using a small capacity crane. collection is avoided.
Construction of the tank and cover are such that pockets for water The tank and cover are designed such that these can be transported
by railways/road/water as per customer specification.
Note:
Transformer/reactor tank is provided with two earthing terminals. While earthing the cable box, busduct etc., it should be ensured that no closed loop is formed because of multiple earthing connections. Generator transformer busduct flange is sometime provided with isolating tube ( to be checked in busduct drawing provided) over the S.S bolt. In such cases busduct flange is to be earthed with adequate copper cable. To ensure single point earthing any auxiliary circuit armoured earth shield connection has to be put on isolating mode at the flange end ( like CT wire etc).
1.1.5
Wherever specified flexible separators or air cell if provided in the A smaller oil expansion vessel is provided for the On Load Tap
Changer.
Magnetic oil level gauge is fitted on the main conservator which can
give alarm / trip in the event of the oil level falling below the pre-set levels due to any reason.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 7 of 205
1.1.6
PRESSURE RELIEF DEVICE A device for avoiding high oil pressure build up inside the
transformer/reactor during fault conditions is fitted on top of the tank. The pressure relief device allows rapid release of excessive pressure that may be generated in the event of a serious fault. This device is fitted with an alarm/trip switch. provides rapid amplification of its actuating force and will reset automatically, as soon as the pressure inside the tank drops down to the pre-set pressure. the valve disc during the operation of the pressure relief device and is held in position by an 'O' ring in the pin bushing. This pin is clearly visible from ground level, which gives an indication that the device has operated.
A bright colour coded mechanical indicator pin in the cover moves with
rests on the valve disc. The relief device is provided with a shielded weatherproof alarm / trip and is operated by the movement of valve disc. For Small Capacity transformers, an explosion vent is provided with a diaphragm, which will break in the event of abnormal increase in internal pressure. Some times the explosion vent is provided with double diaphragm such that the outer one remains intact even after the inner one is ruptured. Rupturing of inside diaphragm can be checked by viewing through the oil level gauge provided in between the diaphragms.
1.1.7
GAS & OIL ACTUATED (BUCHHOLZ) RELAY Gas and oil actuated relay is fitted in the feed pipe from the tank to the
expansion vessel for collection of gas, if generated in the oil. The relay operates on the fact that almost every type of fault in an oil immersed transformer gives rise to generation of gas. This gas is collected in the body of the relay, and is used to close the alarm switch. In the event of any severe fault, the sudden increase in oil pressure causes an oil surge towards the expansion vessel and this is used to close the trip contacts. This oil surge will impinge on the flap fitted to the trip element causing it to rotate about its axis and thus bringing the switch to the closed circuit position, which in turn operates the tripping device.
In the event of serious oil loss from the transformer/reactor, both alarm
and trip elements operate in turn in the manner previously described for gas collection.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 8 of 205
Two petcocks are fitted at the top of the relay body, the outlets of which
are threaded to take a bleed pipe if required for collection of gas samples.
In the pipe connection between On Load Tap Changer and its oil
expansion vessel a single float Oil Surge Relay is fitted. This relay operates on the principle of oil surge impinging on a flap causing operation of the switch connected to the trip circuit. Gas actuated alarm switch is eliminated because the gas generated during normal tap changing operation will give unnecessary alarm.
1.1.8
SILICAGEL BREATHER Expansion and contraction of oil cause breathing action. The silicageldehydrating breather absorbs any humidity in the air breathed. An oil seal in the air intake prevents external moisture being absorbed when no breathing occurs. such that the air breathed must pass through it. The desiccant contains blue/orange crystals. When the silicagel is fully active, the blue/orange crystals will change to pink/blue-green as it absorbs moisture. When saturated with moisture and the charge contained should be replaced. The gel removed from the breather may be arranged for regeneration and preserved for future use. over a period of six months approximately. The factors, which influence the selection of size of the silicagel breather required for a particular transformer, depend on many factors like, the oil quantity in the transformer, the adsorption capacity of silicagel, the loading pattern and the atmospheric conditions prevailing at site. The loading pattern and the site conditions are difficult for the transformer manufacturer to assess. Hence, the selection of breather is based on certain assumptions and it is difficult to fix up a time schedule for the regeneration of silicagel. It is advisable to have a periodic inspection (say monthly) of the indicator so that the gel can be regenerated or replaced as soon it is saturated with moisture.
The size of the breather is chosen such that it can operate effectively
1.1.9
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 9 of 205
capillary is connected to the measuring bellow of the instrument and the other to a compensation bellow. The measuring system is filled with a liquid, which changes its volume with rising temperature. Inside the instrument is fitted with a heating resistance which is fed by a current proportionate to the current flowing through the transformer winding. The instrument is provided with a maximum temperature indicator. The heating resistance is fed by a current transformer associated to the loaded winding of the transformer. (The heating resistance is made out of the same material as that of the winding) The increase in the temperature of the resistance is proportionate to that of the winding. The sensor bulb of the instrument is located in the hottest oil of the transformer, therefore, the winding temperature indicates a temperature of hottest oil plus the winding temperature rise above hot oil i.e. the hot spot temperature. b)Direct measurement Sometime if asked in the specification, transformer winding top block(location of hot spot) is embeded with fibre optic sensor for direct maesurmnent of temeprature. The details of working principle is to be referred from specific catalouge provided within list of drawing.
1.1.10
OIL TEMPERATURE INDICATOR The oil temperature indicator consists of a sensor bulb, capillary tube
and a dial thermometer, the sensor bulb is fitted at the location of hottest oil. The sensor bulb and capillary tube are fitted with an evaporation liquid. The vapour pressure varies with temperature and is transmitted to a bourden tube inside the dial thermometer, which moves in accordance with the changes in pressure, which is proportional to the temperature.
1.1.11
BUSHINGS
bushings. Terminal bushings upto 36 kV class, 3150 Amps, are normally of plain porcelain and oil communicating type. Higher current rated bushings and bushings of 52 kV class and above will be of oil impregnated paper condenser type or resin impregenated type. In case of oil, the oil inside the condenser bushings will not be communicating with the oil inside the transformer. Oil level gauge is provided on the expansion chambers of the condenser bushings. Oil in the condenser bushing is hermetically sealed and it should not be disturbed in normal operation. Oil level may be checked regularly and any oil leakage should be reported to the bushing manufacturer for immediate attention.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 10 of 205
1.1.12
TAP CHANGER Tap changers of power transformer are specifically of two types1. 2. On Load Tap changer Off Circuit Tap changer
when the transformer is de-energised, but in the case of on load tap changers the tap changing takes place when the transformer is in operation. The tap changer can be designed for changing the taps. a. Manually b. Automatically & c. From remote The On load tap changer will be a self-contained unit housed in the main transformer tank. Since some amount of arcing takes place during the switching operations from one tap to the other, the oil inside the tap selector will deteriorate faster. Hence, this oil cannot be allowed to mix with the oil in the main transformer. On load tap changer is provided with a separate conservator and oil surge relay. For details of construction and maintenance, please refer to the OLTC supplier's manual attached with Specific Instructions at the end of this manual. For furnace transformer sometime Vacuum type OLTC is provided depending upon technological requirement.
In the case of off circuit tap changer, the tap changing takes place only
1.1.13
CONTROL & MONITORING SYSTEM Local control and monitoring of the cooler, tap changer and alarm and
trip indicators is carried out at the marshalling kiosk. Automatic control of the tap changer is carried out at the remote control panel.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 11 of 205
1.1.14
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 12 of 205
1.2
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 13 of 205
1.2.1
ELECTRICAL SAFETY
The following hazards are commonly associated with the installation, operation and maintenance of electrical equipment Existence of AC and DC voltage. Possible existence of toxic hazards associated with material used in the construction of electronic components, cleaning agent and solvents. Electric shock due to incorrect earthing, moisture on insulation, bad engineering or working practices. Fire or burn out due to incorrect setting or over load or protective devices, incorrect cables or fuses, insufficient ventilation or incorrect operating voltage. Short circuit flash over due to dust or moisture on insulation or short circuit on live conductors. No work should be done to transformer or its associated equipment unless it is disconnected from supply and all terminals have been solidly earthed. If the secondary of a current transformer is disconnected, a dangerously high voltage can be induced in the circuit. If the secondary circuit of a current transformer is to be disconnected it must be shorted by a link capable of carrying the rated current. Do not apply any voltage or even high voltage megger when the equipment is under vacuum.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 14 of 205
1.2.2 1.2.2.1
1.2.3
ENVIRONMENTAL HAZARDS DUE TO OIL SPILLAGE & FIRE CONSEQUENT TO FAILURE OF TRANSFORMER AT SITE
Oil spillage from Transformer tank, bushing, pipe joints etc. may cause the source of major fires. It is recommended that Transformer/reactor shall be inspected daily for the oil spillage. The general CBIP recommendations for the Transformer installation/reactor are: a. Soak pits b. Drain pits c. Barrier walls d. Fire detection system e. Fire hydrant system f. Fire mulsifyre system
1.2.3.1
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 15 of 205
1.2.3.2
CONTROL OF FIRE
It is necessary to check the healthiness of the Transformer/reactor fire protection system regularly so that the fire risk can be minimized There shall not be any oil leakage. During hot oil circulation in the Transformer/reactor, keep fire extinguisher ready near by. All the combustible materials shall be kept at a safe distance. Terminal connector, Fuses shall be checked against spark. Condition of Transformer oil shall be checked regularly Proper Housekeeping near Transformer may help to reduce the risk of fire. Proper fire fighting system as per CBIP recommendation shall be installed near Transformer. Regular inspection & maintenance to be done on the Fire fighting system.
1.2.3.3
Welding on oil filled Transformer/reactor shall be carried out if unavoidable, as per the instructions of the Manufacturer. Hot oil circulation shall be carried out only under the round the clock supervision to prevent chances of fire on lagging materials etc.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 16 of 205
1.3
1.3.1
DO'S
Insulating oil and insulation of windings and connections are inflammable. Watch for fire hazards. Before entering inside the Transformer/reactor, replace Nitrogen gas completely with air if it was transported with nitrogen gas inside. Make sure that nothing is kept inside the pockets before one enters inside the main unit. Also take off the wristwatches and shoes. List up all the tools and materials to be taken inside and check it after coming out to make sure that no tools are left inside. There must be a protective guard for lamp to be taken inside. Keep inspection covers open for supply of fresh air when some one is working inside. When one person is working inside, second person must be available out side for emergency help. Use rings spanners and tie them to the wrist of the person or some where outside the tank. Be careful during connections where bolted joints are involved so that nut, washers etc. are not dropped inside the tank. If it is required to weld some lugs or brackets etc., these should be welded to tank stiffeners taking all precautions to avoid fire hazards. De-energise the unit by circuit breakers and line switches while working on energised unit. Check the diaphragm of explosion vent and replace it if cracked.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 17 of 205
Attach the caution tags "DO NOT OPERATE THE SWITCHES" while working on units, which are energised. Make sure that the fire fighting equipment is available at the oil treatment equipment as well as workplace and adjacent to the transformer. Fire fighting equipment should be checked regularly and should have sufficient quantity of extinguishant. Transformer tank, control cabinets etc. as well as oil treatment equipment shall be connected with permanent earthing system of the station. Check and thoroughly investigate the transformer whenever any alarm or protective device is operated. Check air cell in conservator. Attend leakage on the bushings. Examine the bushings for dirt deposits and clean them periodically. Check the oil in transformer and OLTC for dielectric strength and moisture content and take suitable action for restoring quality. Check the oil level in oil cup and ensure air passages are free in breather. If oil is less make up the oil. If inspection covers are removed or any gasket joint is to be tightened, then tighten the bolts evenly to avoid uneven pressure. Check and clean the relay and alarm contacts. Check also their operation and accuracy and if required change the setting. Check the protection circuits periodically. Check the pointers of all gauges for their free movement. Clean the oil conservator thoroughly before erecting. Check the OTI and WTI pockets and replenish the oil if required. Gas filled storage of transformer at site should be limited to a maximum of 3 months. Check the door seal of the Marshalling box. Change the rubber lining if required.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 18 of 205
Ensure proper tightness of top terminal of condenser bushings to avoid entry of rainwater. Check oil level in condenser bushing, any discrepancy should be reported immediately to the manufacturer. Do jacking only at jacking pad. In case of bushings with Resin base insulation, care must be taken for the moisture free storage, until its erection.
1.3.2
DON'TS
Do not take any fibrous material such as cotton waste inside while repairing. Do not drop any tools / material in side. Do not stand on leads / cleats. Do not weld, braze or solder inside the tank. Do not weld any thing to the tank wall from outside without proper guidance/consent from the manufacturer. Do not weld any thing to the conservator vessel if Air cell bag is inside. Do not smoke near the transformer. Do not use fibrous material for cleaning as it can deteriorate the oil when mixed with it. Do not energise without thorough investigation of the transformer whenever any alarm of protection has operated. Do not re-energise the transformer/reactor unless the Buchholz gas is analysed. Do not re-energise the transformer without conducting all precommissioning checks. The results must be compared with factory test results. Do not handle the off circuit tap switch when the transformer is energised. Do not energise the transformer unless the off circuit tap switch handle is in locked position. Do not leave off circuit tap switch handle unlocked.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Do not use low capacity lifting transformer/reactor for jacking / slinging. Page 19 of 205 jacks / slings on
Do not change the setting of WTI and OTI alarm and trip frequently. Setting should be done as per manufacturer's instructions. Do not leave any connection loose. Do not meddle with the protection circuits. Do not leave marshalling box doors open, they must be locked. Do not switch off the heater in marshalling box except to be periodically cleaned. Do not allow unauthorised entry near the transformer. Do not close any valve in pump circuit for taking stand by pump and motor into circuit. Do not allow water pressure to exceed the oil pressure in oil to water heat exchangers. Do not mix transformer oils of different make/ base, unless oil is new and conforms fully to IS: 335. Do not continue with saturated (wet) silica gel, this should immediately be changed or reactivated. Do not store transformer in gas filled condition for more than three months after reaching site. If storage is required for longer duration, the main body should be filled up with oil. Do not leave tertiary terminals unprotected outside the tank. Do not allow WTI / OTI temperature to exceed 70 C during dry out of transformer and filter machine temperature beyond 75 C Do not parallel transformers, which do not fulfil the conditions for paralleling. Do not over load the transformers beyond limit specified in IS: 6600. Do not leave secondary terminals of any CT open. Do not measure insulation resistance by using megger when the transformer/reactor is under vacuum. Do not stand on any vessel, which is under vacuum.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 20 of 205
2.0 2.1
TRANSPORT, PACKING & DESPATCH GENERAL Depending on the restriction imposed by the weight and transport
dimensions, the transformer/reactor will be despatched either in oil filled or gas/dry air filled condition. pressurised with dry nitrogen gas to minimise the likelihood of condensation or moisture entering the tank.
maintain positive pressure during transportation and storage before erection. checked on daily basis and any loss of pressure must be made up
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 21 of 205
by feeding gas from the cylinder. For allowable range of pressure at various ambient temperatures, please refer to Fig. 2.I.
Accessories and cooler are despatched separately. All oil pipes and
chambers are despatched in sealed condition to avoid entry of water during transportation and storage.
2.2
PACKING When any internal part like tap changer, CT's etc. are removed from
the main body for transportation, they shall be despatched in tanks filled with oil or dry air gas or suitable measures are taken so that they do not absorb moisture. shall be carefully packed to avoid breakage in transit.
All fragile parts such as temperature indicators, oil level gauges etc. Air cell type conservator shall be despatched with air cell mounted
inside the conservator and inflated with air at a slightly positive pressure so that it remains fully tight inside the conservator. This is to avoid relative movement of air cell inside the conservator during transit and to avoid damages to air cell during handling.
All blanking plates, valves guards etc., which are used exclusively
for transportation are painted with a different colour shade than the transformer (normally post office red) and shall be preserved for future use.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 22 of 205
2.3.1
LIFTING & JACKING Transformers/reactor should be lifted only by using the lifting
bollards provided on the main body for the purpose. All the lifting bollards should be used simultaneously. Care should be taken to use the correct size of sling for lifting and the lifting angle should not exceed 60 . corresponding to the lifting angles are shown in Fig. 2.2
Lifting Angle
Slinging Angle
MULTIPLYING FACTOR FOR DIFFERENT LIFTING ANGLES Lifting Multiplying Angle Factor
SAFE LOAD OF WIRE ROPES Dia. of Safe Wire Load Rope mm kg.
0 20 40 60
6 12 16 20 24 28 32 36 40 44 56 64 70
600 1,300 2,300 3,500 5,000 7,000 9,000 11,000 14,000 17,000 24,500 33,500 40,000
2.3.2
JACKING For the purpose of jacking, only the jacking pads provided on the
tank are to be used. Capacity of Jacks should be at least 1.5 times the weight of transformer. Put sufficient wooden/steel packing below the jack to support the weight. Do not lift more than 30 mm at a time. Use all jacks simultaneously. Jacks should not be left in the loaded position for long time. Transformer/reactor should be handled only in the normal upright position.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 23 of 205
2.3.3
2.4
ROAD TRANSPORT Generally road transport is resorted to in case of smaller units and of
site where rail link is not available or where well developed road system exists. Multi-axle tractors driven low-platform trailers are used for transport. Prior to taking decision to transport the heavy consignment by road a route survey has to be conducted to confirm strength of bridges and the road worthiness and to identify constraints if any enroute. Weak bridges if any should be strengthened with the help of, Highways department. A pilot vehicle with all-necessary tools and tackles and trained staff should be run in front of the vehicle. Red flags and danger lamps should be exhibited on the consignment. Tightness of lashing should be verified at frequent intervals during movement.
2.5
WATER TRANSPORT Special cares to be taken during manufacture, packing and despatch
of transformers which are to be shipped through high seas. Even if it is not specified by the purchaser the transformer should be applied with anti corrosive coating and packaging should be strong enough for possible rough handling enroute. Accessories should have polythene covering and should contain silicagel or any other suitable moisture absorbent.
2.6
SHIPMENT OF ACCESSORIES Accessories are packed and despatched separately. Items, which
are detached from the main body for transportation, are listed on the outline drawing. These will be transported in suitable crates. Crates containing fragile items should be marked 'FRAGILE' and handled carefully during loading on vehicle, shipment and unloading at site. Crates containing accessories, which should not be kept upside down like condenser bushings, control panel etc. should marked 'THIS SIDE UP' and should be handled as per manufacturer's instruction only.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 24 of 205
FIG. 2.3 2.7 SHIPMENT OF OIL Transformer oil is despatched to site in sealed steel drums or
tankers.
allow for expansion and contraction of oil due to variations in temperature. Drums should be stacked only in horizontal position with the oil. This will avoid collection of water on top of the drum, which may be sucked in by the vacuum created inside the drum due to the expansion and contraction of oil owing to changes in ambient temperature. Due to any reason, if the drums are kept in vertical position, drums should be covered with polythene or tarpaulin sheet to avoid risk of water getting collected on top and eventually leaking into the drums. Filter holes and air release holes shall be in one horizontal line. This will avoid breathing in of moist air. If there is any leakage of oil it can
FIG. - 2.4
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 25 of 205
easily be identified. When oil is transported in tankers, there should be storage tanks of sufficient capacity available at site. Such tanks should be fitted with dehydrating breathers.
2.8
IMPACT RECORDERS Impact recorders are attached to the main body of the transformer
during transportation to monitor the shock, which the transformer may be subjected to, during transportation. Impact Recorders are of two types, viz. Mechanical analogue type and electronic digital type. Both types of shock recorders have ability to record shock and impact from all directions. i. ii. iii. Lateral shock ('x' axis) Longitudinal shock ('y' axis) Vertical shock ('z' axis)
Typical sensitivity (rating) values of impact recorders are as follows: i. ii. Trucks trailer Truck trailers Smooth road Rough road 2g 6g
At the time of despatch of the transformer/reactor from the factory, the recorders should be switched 'ON' and the time set. The threshold limits above which the shocks are to be recorded are set and the recorder is activated. The threshold limits above which the shocks are to be recorded are determined and the Minishock is activated. During the transport journey, the acceleration is measured continuously and recorded together with the date and time, whenever the threshold is exceeded. The acceleration is measured continuously and recorded together with the date and time, whenever the threshold is exceeded along any of the direction. Care is required to see the battery condition to serve its full transport journey time. The mounting of the shock recorder should be rigid with its mounting support, to avoid erroneous result during the transport. After reaching the site, the shock recorder should be switched off and sent back to factory to download the data via. Suitable RS port, to its software platform.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 26 of 205
The result of shock recorder is analysed by manufacturer and customer is suitably reported for further action of clearance to charge the transformer. In case the transformer suffers serious shock during shipment, the core and coil will have to be subjected to thorough inspection before erection and commissioning. NOTE: Seperate transport instruction for Transformer/reactor is carried by the transporter to fulfill the conditon of constaints during the transport.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 27 of 205
3.0 3.1
STORAGE RECEIVING MAIN UNIT AND ACCESSORIES When a transformer/reactor arrives at site a careful external
inspection must be made of the unit, its cooling system and all sealed components, referring to the general arrangement drawing and the shipping list. missing items.
Inspect all packing cases and loose components for damage or Check whether the transformer/reactor has arrived at site with a
positive gas pressure in case of despatch without oil. In case of despatch of main body in oil filled condition, the oil level should be checked. One transport oil level gauge is welded near the top of the tank for indicating the level of oil in the tank. to gas leakage) it must be assumed that moisture has entered the tank and that the moisture will have to be driven out. In such cases the manufacturers advice must be sought. contents tally with the packing list if the packing case is damaged.
Confirm that case numbers match with the packing list. Check their IMPORTANT: If any scratches or damage to the paint is noticed on receipt of Main
body or Accessories, touchup painting should be done immediately over the damaged area. For procedures of touchup painting, refer to Clause 4.22: Touchup Painting at site.
3.1.1
REPORT OF DAMAGE PARTS ETC. If any damage is noticed, claim must be lodged with the insurance
agency and the matter must be reported promptly to the manufacturer. The report should contain sufficient details of damaged parts and extent of damage so that the cost of replacement /rectification can be worked out.
3.1.2
INSPECTION OF MAIN UNIT GAS FILLED After receipt of consignment at site, gas pressure inside the tank and
the temperature at the time of measurement should be recorded. The value obtained should be compared with the gas pressure versus temperature chart furnished in the instruction manual. (Refer fig. 2.1 of chapter 2)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 28 of 205
3.1.3
INSPECTION OF MAIN UNIT OIL FILLED Upon arrival at site, check oil level inside the tank. If a transparent oil
level gauge is not provided, the oil level can be measured by connecting a transparent hose between the bottom and top sampling valves.
Check for damages to valves etc. A sample of oil should be taken from the bottom of the tank and
tested for BDV and moisture content. If the values do not meet the relevant standards the matter should be taken up with the manufacturer.
3.2.1
UNLOADING OF MAIN UNIT In cases where the substations are having adequate crane facility;
the transformer is unloaded by crane. Alternatively, mobile cranes are used. Where no crane facility is available a trench is dug to a depth equal to height of the trailer platform and the transformer is slid to position. If this also is not possible the transformer is unloaded into a sleeper platform and gradually lowered to plinth level (Refer Figure 3.1 for guidance). The sleeper platform level is to be at a slightly higher level to allow for the increase in height of the trailer while the load is released due to the springs getting relaxed. Winches are to be used for putting the transformer/reactor into position.
Fig. 3.1
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 29 of 205
Lift the main body of the transformer/reactor with a mobile crane and wire ropes. The crane capacity must be at least 10% higher than the weight of consignment. Lifting angle of ropes should be limited to 30 deg. to vertical. Unloading must be done with maximum care, avoiding any jerking movements or dropping. Use only the lifting bollards/hooks for slinging while lifting. For lifting with hydraulic jacks, the transformer/reactor are provided with jacking pads dimensioned for lifting the complete transformer/reactor filled with oil. If the foundation of the transformer/reactor is not ready and if the transformer/reactor are to be unloaded temporarily, it should be done on levelled hard surface. Place at least 300 to 400 mm wooden sleepers to facilitate jacking.
3.2.2
PLACING IN POSITION
If foundation is ready and if rail link between unloading point/storage place is available, then the main body of the transformer/reactor must be moved on its own rollers to the foundation where the transformer/reactor is to be erected finally. If the transformer/reactor is not provided with rollers and if it is to be erected on its skid base (Note: 400 kV class shunt reactors are to be placed directly on plinth by default. Rollers are provided for the movement only), the transformer/reactor must be slid to its final position using greased steel plates to protect the plinth surface and make movement easier. The plates should form a continuous surface and it must clear the final jacking areas.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 30 of 205
The transformer/reactor must be pulled by using slings and winches as shown in Fig. - 3.2. Use only the specified haulage lugs for pulling. Pulling capacity of winches should be more than (Main body weight x 0.15/4) tons. Pulleys should have a capacity of (Main body weight x 0.15/2) tons. When jacking (e.g. to remove steel plates), position the jacks under specified jacking pads only. When jacking, ensure that all four jacks are operated simultaneously. Before lowering, clean all grease dirt etc. from the under base of the transformer/reactor.
3.2.3
UNPACKING AND INSPECTION OF ACCESSORIES Crates / packages are to be opened carefully so that the tools used
for opening do not cause damage to the contents.
Any damage or short shipment should be reported to the 3.3 3.3.1 STORAGE OF MAIN BODY GENERAL It is preferable to erect the transformer/reactor immediately on
receipt at site and fill with transformer oil. However, if it is not possible, the following precautions should be taken for storing the main body and accessories for longer duration: accessible for inspection.
The storage area should be adequate and should be easily The surface on which it should be stored is strong and levelled. Surrounding area of storage is not polluted and water does not
accumulate in the storage area.
Sufficient space is provided underneath for free flow of air and also
for lifting, jacking etc.
3.4
Filename
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 31 of 205
immediately after receipt. If oil can not be filled immediately after receipt of main body, it must be retained with dry air/gas filled at a positive pressure of 0.2 kg/ cm2 at about 20OC. (Please ref. Fig. 1 of Chapter 2 for Pressure Vs Temperature Chart). the receipt of main body at site.
The duration of gas filled storage should be limited to 3 months from If the pressure of gas inside drops due to leakage, the leakage point
may be detected by using soap water. The matter shall be reported to the manufacturer for immediate corrective action.
1. Cylinder Key. 2. Top sampling valve of transformer. 3. Gauge for reading gas pressure inside the transformer 4. Adapter. 5. Gauge to indicate gas pressure in the cylinder 6. Gas pressure regulator. 7. Gauge to indicate gas pressure from the regulator 8. Pneumatic pressure hose. 9. Hose clip. 10. Air/Gas cylinder.
FIG. 3.3 Should it not be possible to rectify the leak immediately, the
transformer/reactor must be covered by putting a tarpaulin sheet over the whole tank until remedial measures can be carried out. Gasket must not be tightened indiscriminately as this could result in loss of gasket property due to over compression. The arrangement for gas filled storage is shown in fig. - 3.1
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 32 of 205
basis and any pressure drop should be made up by opening the cylinder and operating the pressure regulator. The cylinder should be kept closed. Before deciding on loss of pressure, the pressure versus temperature chart (Fig. 2.1) shall be referred to. If the storage period at site is expected to be beyond 3 months, it is recommended to keep it filled with transformer oil.
3.5
OIL FILLED STORAGE If the gas pressure on arrival at site is found satisfactory, it can be
assumed that there is no leakage. Before filling oil, all the valves, which were detached during transport, should be fitted back and blanked. If possible, the main body shall be fitted with its own rollers and supported on rails and locked in position. Assemble conservator, pipe work and fix silicagel breather. Oil shall be filled upto the conservator corresponding to the ambient temperature. If the transformer/reactor foundation is not ready, it may be stored in any convenient location. In that case, oil shall be filled upto the level so as to immerse all the insulation parts in oil and the space above should filled with dry gas. Fix silicagel breather at any convenient point on the cover. If the main unit is received at site filled with oil, fit a silicagel breather on any opening on cover with a suitable pipe. Before filling oil inside the transformer/reactor, its BDV and moisture content should be measured. If values are not within limit specified, the oil should be filtered.
3.6
STORAGE OF OIL If the oil is received at site in tankers, it is necessary to provide an oil
storage tank of enough capacity to hold the oil for one transformer.
The oil storage tank should be equipped with valves for oil filling,
draining, sampling and filtration, oil level gauge, silicagel breather and a manhole on top cover. The inside of the tank should be painted with oil resistant paint / varnish. Before filling oil, the inside of the tank should be cleaned thoroughly. horizontal position as shown in Fig 3.2 and covered with tarpaulin sheet. Filter holes and air release holes shall be in one horizontal line. This will avoid breathing in of moist air. If there is any leakage of oil it can easily be identified.
TM1902_2012 Rev no. 05 Date 19/02/2012
Filename
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 33 of 205
Fig. 3.4 3.7 STORAGE OF ACCESSORIES The following points may be taken care of in order to keep
accessories in good condition without damage, rust and dust. received in good condition.
Check and confirm that all packing cases as per packing list are If erection work is not likely to commence immediately the boxes,
which are opened for inspection, should be repacked and the packing list retained for future reference and records. so as to allow free circulation of air underneath. Water should not collect in the storage area. There should be sufficient space for inspection, handling and transport.
All fragile items and instruments should be stored indoors. All crates should be kept as per the markings provided on the crates
by manufacturer. As a general rule, all control boxes such as RTCC Panel, Marshalling Box, Drive Mechanism etc. should be kept indoors in vertical position.
Crates should not be stacked one over the other. Strictly adhere to the specific storage instruction provided by the
manufacturer for specific items.
Filename
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Table- 1
Sr. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 Accessories Storage Position Position Location Precautions Special Instructions Inspection check
Page 34 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 35 of 205
4.0 4.1
Oil Purifier
1 No.
Vacuum Pump
1 Set
Flexible Oil Hoses: (of 3 m length) (of 10 m length) (of 10 m length) 5 Nos. 2 Nos. 2 Nos.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 36 of 205
Sr. No. 5
Qty. 2 Nos.
Specifications Flexible vacuum hoses of 75 mm diameter with flanged ends. The hoses shall be capable of withstanding full vacuum. Oil testing equipment shall be capable of checking break down voltage of transformer oil across 2.5 mm sphere gap 100 kV (min.). Vacuum gauge of Mc Leod type capable of measuring vacuum less than 0.01 torr
1 Set
Vacuum Gauge
2 Nos.
Compound Gauge
1 No.
a)
Megger
1 No.
b) c) 10 11
0 ~ 300 V AC range. 0 ~ 75 V AC range. 100 W Lamp of 100 V or less with sufficient length of flexible cable and bulb protector.
12
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 37 of 205
Sr. No. 13
Qty. 1 No.
14
Sufficient Nos. Slings and shackles of sufficient length to handle weight up to 25 tonnes. 40 m2 30 meters For temporary exposed parts covering of
15 16
17
Hose Nipple
2 Nos.
18 19 20 21 22
Methyl Ethyl Ketone / 10 litres For cleaning purpose. Carbon tetra chloride Rag Cotton cloths Unstarched Mill Cloth Knife Spanners 20 kgs. For cleaning purpose. 10 m. 2 Nos. 2 Sets For cleaning internal Parts. For cutting insulation parts. All standard sizes for both metric sizes up to 42 mm and BS to 1.
23 24
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 38 of 205
Sr. No. 25
Tool/ Equipment a) 3 Phase, 440 Volts, 50 Hz. Electric Power Supply for Operating the vacuum pump and filter machine b) Water Supply if Purifier is water cooled.
Qty.
Specifications
26 27
Pulling winches/ Pulleys Hydraulic/Mechanical Screw Jacks with Locking facility Measuring Tapes Spirit Level/Level tube (Plastic) Dry Air Generator (For Transformers of 400 kV class and above)
Please refer section 4.3. 50% of total weight of main body with oil. 10 meter long.
28 29 30
Capacity; 4~5 m3/hr. Dew Point 40O C Temperature 25 5OC, Outlet pressure 200 Aq.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 39 of 205
4.2
OIL SAMPLING AND FILTERING Oil should not be filled in the transformer directly from the drums or
transport container as there is a chance of precipitated water or sediments may also be pumped into the transformer along with the oil. Oil from the drums or transport container should be filled into the oil storage tank and oil parameters should be tested before it is filled into the transformer. If oil is received in drums, samples should be taken for testing from as many drums as shown in the Table -1 at random. Table -1 Selection of Samples from drums No. of Drums in a Batch 2 to 5 6 to 20 21 to 50 61 to 100 101 to 200 201 to 400 401 and more in fig.4.2 for testing. No. of Drums from which Samples to be taken 2 3 4 7 10 15 20
FIG. 4.2
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 40 of 205
If oil does not meet the specified criteria, oil should be filtered and While pumping oil from the barrels, the barrels may be tilted suitably
to ensure that complete oil is taken out from each barrel.
FIG. 4.3
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 41 of 205
4.5
ERECTION PRECAUTIONS
NOTE: PRECAUTIONS MUST BE TAKEN TO ENSURE THAT ALL N2 GAS / DRY AIR PRESSURE IN THE TRANSFORMER IS RELEASED BEFORE ANY ATTEMPT IS MADE TO REMOVE A COVER AND DRYNESS (DEW POINT) IS CHECKED BEFORE A N2 GAS/ DRYAIR CYLINDER IS USED.
opened at a time in order to minimise the ingress of moisture. The hand hole cover should be replaced as soon as the operation is completed.
Dry air of dew point 40OC or better must be fed through the inside
of tank when covers are removed in case of 400 kV and higher class of transformers to avoid direct contact of winding insulation with moist air outside.
completion of work. The exposure should not be allowed more than 16 hours at stretch.
and followed during the erection procedure. Transport block wherever called in the Transformer & Reactor is to be removed.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 42 of 205
4.6
ERECTION PROCEDURE
The following flow chart shows the installation procedure generally followed at site. PREPARATION FOR INSTALLATION . INSTALLATION OF MAIN BODY ON FOUNDATION . RECEIVING INSPECTION AND STORAGE . OIL RECEIVING AND FILTERING . ASSEMBLE BUSHING TURRET . ASSEMBLE LV BUSHING AND CABLE DUCT . ASSEMBLE COOLERS . ASSEMBLE CONSERVATOR . ASSEMBLE PRESSURE RELIEF DEVICE . ASSEMBLE HV BUSHINGS . ASSEMBLE ACCESSORIES . INTERNAL LEAD CONNECTIONS . FILL OIL UNDER VACUUM . CONTROL WIRING OIL LEAKAGE TEST . OIL FILLING UNDER VACUUM .
PAINTING (Ref. Cl. 4.22) . Note: The sequence in flow chart is general in nature and would need to be suitably modified to suit site/weather conditions by keeping the basic objectives.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 43 of 205
4.7
REPLACE DRY GAS WITH OIL After installing the transformer on the foundation dry gas in the
transformer should be replaced with treated oil.
Make sure that the hose and pipe interiors are cleaned in advance. Connect the oil pipes to the lower filter valve. Ref. fig. 4.4
Oil Storage Tank Transformer Dry Gas Filter Press Transparent Vinyl Hose (For oil level Indication)
FIG. 4.4 Attach a transparent vinyl hose to indicate the level of oil being filled
in the transformer.
Open the top filter valve or any other bolted covers on topmost point
on the transformer for releasing dry gas at the time of oil filling. valve on the oil storage tank. transformer winding. expansion of oil.
Open the bottom filter valve on the transformer and top air release Oil should be filled upto a level above the top insulation of A small gas space (approx. 5~10%) should be left above oil for During oil filling, if the filter press stops due to any reason, the top
filter valve and any other opening on the top of the transformer should be closed immediately to prevent air getting into the transformer.
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 44 of 205
While filling oil directly from the barrels, the barrels shall be tilted
suitably to ensure that complete oil is taken from the barrels.
After filling oil, if the storage is expected to be for a long period, dry
gas should be filled above the oil at a pressure of 0.1 ~ 0.2 kg/cm2.
Assembling work should start from the bottom of the tank so that
after initial oil filling, oil need not be drained again for assembling work.
4.8
Following each days work, transformer should be kept oil filled. For high voltage jobs of 400 kV and above, dry air having dew point
below -40 C should be purged inside the tank during internal assembling work.
Extreme care shall be taken against any foreign objects falling inside
the transformer tank during inside working.
Keep only one man hole open at a time and close it as soon as
possible.
Avoid inside working on rainy days. Earthwork near the transformer should be avoided when internal
assembly is in progress to avoid ingress of dust.
covers etc., keep a cloth below to avoid the scraped material falling into the transformer. person who is using the same.
Any tools taken inside should be tied by string or cotton tape to the No. of tools shall be counted and recorded before and after each
days work in order to ensure that no tools are left inside.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 45 of 205
tightening and under tightening of gaskets should be avoided as these may cause oil leakage and shortening of gasket life.
4.9
ERECTION OF PIPE WORK All items of pipe work are match marked. All joints are to be assembled with gasket only and without joining
compounds or grease.
Joints must be fully tightened only when the transformer has been
fully erected; by that stage the pipes can be centralised.
No pre determined torque values are applicable. No joint must be under excessive assembled load as subsequent
expansion or contraction could cause leaks.
Ensure that all accessories belong to the same unit. Indent No., Unit
No. and Serial numbers of each item are marked on each item. This is to avoid mismatching at site. E.g.: 670700002 / 4 / 209 shows: Sale Order No.: 670700002, Unit No.: 4 and Serial No. of item : 209
Serial numbers of all items, which are dismantled from the main
body and sent separately, are shown in "PART MARKING AND CABLE WIRING" drawing.
4.10
ERECTION OF COOLER BANK Generally for oil forced cooled transformers radiators will be
mounted in a separate cooler bank.
Since cooler headers are provided with butter fly type shut off valve,
oil from main body need not be drained for assembling cooler.
Filename
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 46 of 205
Check and ensure that level of all the foundations for cooler support
are in same level as that of the top surface of rails. Level difference should be compensated by putting shims if the level is lower and chipping the concrete foundation if the level is higher. General arrangement and Foundation Plan drawing. proper alignment.
Fix cooler header mounting frames as per dimensions shown in Mount cooler headers loosely. Final tightening to be done only after Top and bottom butterfly valves of all radiators should be in the
vertical line. This should be confirmed by a plumb.
Remove blanking plates from the butterfly valves. Tighten the cooler frame foundation bolt, and clamping bolts of
cooler headers and pipe connections.
While mounting the oil pump and oil flow indicators, care should be
taken to ensure the arrows indicating the oil flow direction are towards the transformer tank. weight is balanced.
While mounting radiators care should be taken to ensure that the Ensure that a fresh gasket is used while mounting the radiators. In case of separately mounted coolers, the oil pipes are provided
with expansion joints. Tack welded bars on expansion joints should be removed. arrangement drawing.
Fix the fan mounting frames and fans as indicated in the general Fan & mounting frame shall be connected to the earth grid. 4.11 CONSERVATOR Mount the conservator as shown in G.A. Drawing. Very often the small conservator for on load tap changer is attached
to the main conservator.
Magnetic oil level gauge shall be mounted after attaching the float to
the gauge. Check and confirm free movement of float arm and proper locking of float to the float arm.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 47 of 205
Mount all valves as shown in GA drawing on the conservator. Mount the connecting pipe with Buchholz relay from the main tank to
the conservator. Ensure direction of Buchholz Relay by the direction of arrow on Buchholz Relay towards conservator. conservator.
Mount connecting pipe with oil surge relay from OLTC to the Mount breather connecting pipes and silica gel breathers for the
main tank and OLTC conservators.
Set up the air cell in side the conservator. Care should be taken to
see that the hooks on air cell are properly engaged in the brackets provided in side the conservator.
Inflate the air cell at a pressure as shown in the instruction plate (DO
NOT APPLY EXCESS PRESSURE AS IT MAY DAMAGE THE AIR CELL) through the breather connection pipe. Follow the instructions given in the Instruction Plate fixed on the transformer.
Ensure that there is no leakage. The conservator with Air Cell is pressure tested and despatched
from the factory at a slightly positive pressure. Confirm that there is no oil leakage.
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 48 of 205
Keep air release valves open. Fix air filling adapter on breather pipe
and inflate the air cell at an air pressure indicated on the INSTRUCTION PLATE affixed on the transformer and hold air pressure. valve of the transformer.
Open the air release valves and start oil filling from the bottom filter Observe the air release valves and as soon as oil starts overflowing,
close the air release valves one by one. Stop oil filling when all air release valves are closed.
Remove the air filling adapter. Continue oil filling and observe the Magnetic Oil Level Gauge
(MOLG)
Stop the filling when the needle of MOLG shows the level
corresponding to the ambient temperature at the time of filling.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 49 of 205
Proceed as follows: Create a vacuum in separator. With the same source of vacuum, create a vacuum in the
conservator.
Open the oil filling valve of the transformer. Because of the vacuum
in the conservator, the oil level rises automatically. attained.
Stop the oil filling once the required volume in the conservator is While maintaining the conservator under vacuum, allow Dry Air or
Nitrogen gas to enter into the internal part of the separator. Then, the separator inflates by itself, and takes all the free space due to the fact that the conservator was not completely full. In particular, during the operation, the oil is going to rise to the top of the conservator. PLATE.
Inflate the separator at a maximum as shown in the INSTRUCTION Check on the vent-holes, and confirm that there is no more air in the
conservator or, if necessary, adjust the level. CAUTION: The above mentioned CAUTION regarding the opening of air release valves after completion of oil filling is applicable for this case also.
4.12
PRESSURE RELIEF DEVICE Mount PRD as per manufacturers leaflet and also the G.A. drawing
of Transformer.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 50 of 205
4.13
FIG. 4.5
METHOD OF LIFTING CONDENSER BUSHINGS FROM PACKING CASE AND MOUNTING ON THE TRANSFORMER AT
If oil is drained from the tank a continuous supply of dry air should be Dry air shall have a dew point of -40OC or better. Total exposure time should not exceed 8 hrs.
ensured while removing the blanking plates and fixing the bushing turrets and bushings.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: with dry air. PTRM1104 Page 51 of 205
At the end of each days work, blank off all openings and pressurise If weather is bad (rain, snow or fog) the tank should not be opened
unless adequate shelter is provided.
to the specific drawing and suppliers catalogue given in the instruction manual.
Ensure that a fresh gasket is used while mounting the bushing. Ensure that the air release pipe connections are oriented towards
the correct directions, as shown in the GA and part marking drawings.
Check for match markings on the mating flanges. Bushing shall be mounted in the order of B, A, C or B, C, A. While mounting the bushings, ensure that the oil level gauge is
oriented away from the transformer.
While lowering draw lead type condenser bushing the cable shall be
held tightly by using strong steel/plastic rope. Remember that dropping of cable can cause injury to the personnel and damage to the transformer. any are connected to the proper terminals on the terminal board.
Check and ensure that secondary terminal of turret mounted C.T. if Check and ensure that secondary leads of C.T's. mounted inside the
transformer are connected to the proper terminals in the terminal board.
If holes are not provided in the CT terminal box for fixing cable
glands, suitable holes shall be drilled and cable glands assembled.
Fix all air release pipes between bushing turrets and Buchholz relay
connecting pipe. Please refer to the part marking drawing for respective part numbers of air release pipes.
4.14
TEMPERATURE INDICATORS Sensing elements of oil and winding temperature indicators are to be
fitted on to the thermometer pockets welded on the top cover of the transformer.
should be cleaned thoroughly and filled with transformer oil upto a depth of half the pocket.
TM1902_2012 Rev no. 05 Date 19/02/2012
Filename
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 52 of 205
RTD (if provided and shown in GA drawing) sensor element and Fill oil in the pocket after cleaning. CT leads shall be connected on one side and sensor leads are taken
from the other side. room.
RTD instruments are mounted on the remote panel in the control 4.15 OLTC DRIVE MECHANISM In case of on load tap changing transformer, the OLTC driving
mechanism has to be mounted on the transformer. Please refer to the OLTC instruction manual supplied by the OLTC manufacturer.
Please ensure that tap postion as on OLTC top head cover (for all
poles) and of drive mechanism is in same tap postion, before connecting the coupling shafts.
Please check for the rotation lag in Raise & Lower direction, to be as
approximately same in number of revolutions.
Bring the tap position in DM to the tap position 1. Connect 3-phase supply with correct phase sequence. Check raise/lower operations. If direction is correct, check electrical
end stops at extreme positions.
Bring back the DM to the tap position 1. Different manufacturers of OLTC adopt different designs for the DM.
Some manufacturers adopt dry type gear box for the motor and some manufacturers adopt oil filled gear box. Oil, if required, shall be filled as per the manufacturer's instructions. only after ensuring that both are at the same tap position. Normally the transformer is despatched from the factory at rated Tap position. other extreme tap position and bring back to rated tap.
Operate the DM manually from rated tap to tap no. 1 and then to the
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 53 of 205
Verify the ratios on all taps using ratio meter or digital voltmeter. 4.16 CABLE BOX ASSEMBLY If cable box is provided, the assembly shall be carried out referring
to the cable box assembly drawing provided in the Instruction Manual. is inserted and bolted on to the cable box. the transformer tank.
Cable sealing ends shall be fitted on to the end of the cable before it Cable box assembly may be bolted to the disconnecting chamber on Flexible connections shall be made between bushings and cable box
bus bars through the Inspection Cover.
4.17
INSTRUCTIONS REGARDING USAGE OF GASKETS Gasket materials used are either Synthetic Rubber Bonded Cork
(SRBC) sheet or nitrile rubber.
Synthetic rubber bonded cork sheets once used should not be used Gasket seating surfaces should be smooth and free from scratches,
oil, grease, dirt etc.
Gasket should be properly located before tightening. Gasket joints are designed with 40~50% compression. Gasket joints should be tightened evenly with a diametrically
opposite sequence.
Full compression should not be achieved in one go. Over tightening will cause the gasket material to loose its properties
and under tightening may not prevent oil leakage.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 54 of 205
4.18
CHECKING LEAK RATE UNDER VACUUM Drain oil & create vacuum of 200 torr inside the tank, close the valve
between vacuum pump and tank and stop the pump and hold the vacuum. There should be no appreciable loss of vacuum over one minute.
If there is leak, find out the leak and rectify. Start the pump and open the valves and continue till a vacuum of 10
torr is achieved.
Close vacuums valve and stop the pump. There should not be an increase of pressure of more than 1 torr over
half an hour.
IF the rise in pressure is more, find out leak and rectify. If results are satisfactory, restart the vacuum pump open the valves
and continue pumping to obtain a vacuum of 1 torr or better and maintain this vacuum for more than 24 hrs. before and during subsequent oil filling operations.
4.19
INSULATION OF CORE AND FRAME TO TANK If the internal body earthing lead is brought out through low voltage
bushings, the megger values shall be measured using 2 kV megger and the values recorded.
4.20
OIL LEAKAGE TEST Oil leakage test is done after attaching the oil pipes, bushing,
radiators, conservator, relief device and all the instruments.
Remove the breathers and connect dry gas cylinder with pressure
gauge to the connecting pipes if conservator is not provided with air cell. If conservator is fitted with air cell, pressure shall be applied after connecting an equaliser pipe between the air release valve and breather connection pipe. Otherwise the air cell may get damaged.
Remove PRD and explosion vent if provided and blank the opening. Open all valves between conservator, main tank and OLTC. Fill oil in the transformer upto 1/3 rd of the conservator through oil
filter.
Apply a gas pressure above the oil such that the pressure at the
base of the tank is between 0.7 kg/cm to 1.0 kg/cm.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 55 of 205
Check for oil leakage at all bolted and welded joints by keeping the
pressure for 12 Hrs.
If any leakage is noticed, rectify the leak and continue the test. Break pressure and reassemble breathers, PRD, explosion vent etc. 4.21 VACUUM OIL INJECTION Oil injection shall be made under full vacuum (1.0 torr or better) for
transformers above 66kV. 380 mm Hg or better vacuum is required for transformers rated for 66kV and below. The vacuum shall preferably be measured by using McLeod Vacuum Gauge.
should be pulled from the oil filling hole on main conservator. If the conservator is fitted with air cell, pressure equalising connection is required to avoid damage to the air cell. compartment of OLTC simultaneously, an equaliser pipe (Refer GA drawing for item number & location) is supplied. This is to be fitted during evacuation and removed after vacuum oil filling.
Before starting vacuum, all bolted connections shall be checked. Radiator valves shall be kept open. A transparent vinyl hose shall be connected to the bottom sampling
valve (Refer Fig. 4.4) for indicating the oil level.
Full Vacuum shall be maintained for minimum 6 hours. Oil may be injected through the bottom filter valve until the level
reaches 35OC marking on the Magnetic Oil Level Gauge of the conservator. inside the transformer shall be limited to 300 mm. react with oil. broken.
Initial oil filling shall be done at a slow rate. Rise in oil level per hour Natural rubber hose shall not be used as sulphur in the rubber may Oil inlet valve shall be closed and after one hour the vacuum shall be Oil level indicating vinyl hose can be removed by closing the bottom
sampling valve.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: position. PTRM1104 Page 56 of 205
Vacuum gauges may be detached and breathers assembled in its Pressure equalising connection provided for explosion vent
diaphragm and OLTC diverter chamber shall be removed.
4.22
TOUCH UP PAINTING AT SITE Any damage to the painting of the transformer and accessories shall
be made good during/ after complete erection work.
If a welding has been done on the transformer at site, the paint film
Remove the rust by wire brush and emery paper #80 / #100. Wash away the oil, grease, dirt and dust by using suitable solvent
and dry it up.
After cleaning, stir the ready mixed rust resistant primer paint 'Yellow
Zinchromate' or 'Red Oxide' primer paint. Before applying the paint, confirm the correct viscosity.
Apply the paint uniformly by using a brush. drying time for the paint
is normally 4 hours.
After the first coat of paint is dried up, mix and stir the finish coat
paint to the desired viscosity and apply by brush uniformly. Drying time of finish coat paint is normally 6 hours.
(i) For brushing : 50 ~ 55 sec. (ii) For spraying : 20 ~ 25 sec. (iii) Pressure for spraying : 55 ~ 60 psi. (iv) Time gap between two coatings : 24 Hours. (v) Total dry film thickness after final coating: as per data sheet (80 ~ 100 microns if not specified)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 57 of 205
4.23
MIXING OF TRANSFORMER OIL Some times a need arises at site to top up a transformer with oil of a
different make.
New oil can be mixed with each other irrespective of the source or
degree of refinement if both the oils meet the same standard specification. oils or the other one is uninhibited.
Inhibited oils can be mixed only if the inhibitor used is same in either At any point of time, the percentage of new oil topped up shall be
limited to 10% of the total oil quantity.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 58 of 205
5.0 5.1
INSULATION DRY OUT AT SITE HOT OIL CIRCULATION Connect bottom filter valve of tank to inlet point of filter machine. Connect top filter valve of tank to outlet of vacuum filter machine and
start oil circulation.
The filter outlet temperature should be limited to 60 ~ 70OC. Continue filtration for 4 cycles. Oil circuit should include a vacuum chamber in which oil drawn from
the transformer is sprayed and the moisture and gases are released from the oil are extracted by the vacuum pump. being admitted to the vacuum chamber to remove impurities circulation equipment.
Oil drawn from transformer is passed through a filter press before A minimum capacity of 6000 litres per hour is recommended for the Cooler connection at inlet shall be kept closed to minimise loss of
temperature during circulation. Outlet valve shall be kept open to allow expansion of oil inside the cooler.
Coolers also shall be included in the hot oil circulation towards the
end of the process.
Drain the oil by simultaneously admitting dry air or nitrogen gas from
the top. This is to avoid winding insulation coming in contact with moisture.
Apply vacuum of 1.0 torr or better and maintain for 6 Hrs. Inject oil under vacuum upto a level of approximately half of the
conservator.
Start hot oil circulation again as explained earlier and continue for 4
cycles. Maintain temperature of 60 ~ 700 C.
Drain oil by feeding dry air or nitrogen gas as explained. Apply vacuum as explained Repeat vacuum/hot oil circulation cycle till required dryness is
obtained.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 59 of 205
FIG. 5.1 Variation of Insulation Resistance with Temperature Dryness of insulation is determined by measuring insulation
resistance of transformer winding.
Direct heating of transformer is not recommended for dry out at site. Oil samples shall be tested for moisture content, (Below 20/15/10 for
145/220/400 kV class respectively). Break down voltage (More than 60 kV at 2.5 mm gap). Resistivity ( 1012 ohm meter) before final oil filling. vacuum.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 60 of 205
COMMISSIONING POST ERECTION CHECKS INSPECTION AND MAINTENANCE LOG SHEET It is important that an inspection and maintenance log sheet be kept
regularly. The original of this log sheet should be kept along with the Instruction Manual for future reference and record. maintenance carried out.
The log should include dates and details of all inspections and Results of oil tests and insulation resistance together with the
temperatures at the time of measurement should also be recorded in the log sheet.
terminals of all current transformers are kept short-circuited. After test these shorting connections shall be removed.
6.1.2
PHYSICAL CHECKS Check oil levels in the level gauges of all condenser bushings. All air release plugs shall be loosened and closed after releasing
trapped air if any.
Check and confirm tightness of all fasteners. Check and confirm that valves are either open or closed as indicated
the valve schedule plate.
Check all bolted gasket joints and confirm that there is no oil leak. All blanking plates and spares including spare gasket should be
stored carefully for future use.
Check all cable terminations and ensure that cables are properly
connected and cable numbering ferrules are provided. bushing protection covers etc. are removed. and are without damage. Bushings are tightened. transportation purpose.
TM1902_2012 Rev no.
Check and ensure that all protective covers like valve guards, LV Check and confirm that all bushing porcelain are cleaned thoroughly Check & confirm that the test tap caps of all Condenser type Remove the cap provided at the bottom of silicagel breather for the
Filename 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 61 of 205
Arcing horns if provided are set to the specified gap All earthing connections are tightened properly. Anti condensation heaters are functioning correctly. Rating and connection diagram plates and other marking labels are
fitted properly.
All isolating switches are set at ON position. Cooler control switch is set to AUTO. All alarm circuits are reset. OLTC to Transformer equalising pipe shall be removed after oil filling
under vacuum and the opening shall be coverd by blanking plate supplied with the transformer.
6.2
INSULATION RESISTANCE CHECK Check and record insulation resistance between pair of windings and
windings and earth using 5 kV Motorised megger megger and record the values at 15, 60 & 600 seconds. (Polarisation Index.) and IR 60/ IR 15
Calculate the ratios of insulation resistances IR 600/ IR 60 Compare the values with factory test results. Check insulation resistance between core and frame to ground if the
earthing connection is brought out through bushings. equipment is under vacuum.
Do not apply any voltage or even high voltage megger when the 6.3 RATIO TESTS Connect 3-phase 415 volts supply between HV terminals and
measure the voltage ratios at all taps and record. measurement and reconnected after tests.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 62 of 205
6.4
VECTOR GROUP TESTS Connect 415 V, 3-phase supply to HV winding terminals. The
transformer shall be at rated tap.
6.5
MAGNETIC BALANCE TEST Single-phase 240 volts is applied across star HV winding and
voltage induced across the other phases are measured and compared with the factory test results. CAUTION: If there is a residual magnetism in the core, it can give erratic readings.
6.6
SHORT CIRCUIT IMPEDENCE LV terminals are shorted by using suitable cables. 3 phase 415 volts supply is connected to HV winding and HV
exciting current of all the phases and LV circulating currents of all the phases are measured and recorded. Measured current x Rated voltage
Percentage impedance = Rated current x Applied voltage x 100 Compare the results with factory test results. 6.8 WINDING RESISTANCE MEASUREMENT Note down the oil/winding temperature. If the measurements are
done after hot oil circulation; the oil/winding temperature may be different from the ambient temperature. Kelvin bridge.
Measure the resistance of all windings using a Whetstone Bridge or Convert the resistances to 75OC.
For copper windings:
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 63 of 205
R (75)
Compare the values with factory test results. 6.9 TAN DELTA AND CAPACITANCE Measure tan delta and capacitance of Condenser bushings of 52 kV
and above and compare with the factory test results (Refer to "INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE OF OIP CONDENSER BUSHINGS" provided elsewhwhere in this Manual).
Compare the values with factory test results. 6.10 OPERATION CHECKS 6.11
Check direction of rotation of pumps and fans. Check and confirm that flow indicators are mounted correctly. Check signalling circuits for pump fail/fans fail etc., and reset. Check setting of over load relays and reset.
BUCHHOLZ RELAY OPERATION Check inclination of Buchholz relay pipe. The slope should be in
upward direction, between 3 ~ 9O to horizontal towards the conservator. cylinder to the petcock on top of the Buchholz relay.
Connect a compressed air line (Pressure 4 kg/cm2) or a nitrogen Valve provided towards the tank side of buchoz pipe should be
closed. relay.
Open the petcock slowly and allow air to enter into the Buchholz Check the continuity of alarm contacts by using a multimeter. Record the volume of air in the Buchholz Relay at which the alarm
switch contact closes.
Close the air supply and release all the air by opening the other
petcock on the Buchholz relay.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 64 of 205
Open the petcock quickly and allow air full flow with surge. Record
the minimum pressure required to operate the surge contacts.
Release all the air trapped in the Buchholz relay. 6.12 WINDING TEMPERATURE INDICATOR CALIBRATION Rotate the indicator pointer slowly and confirm that the alarm signal
is received at the set temperature. at the set temperature.
Rotate the pointer slowly and confirm that the trip signal is received For set values of alarm and trip contacts, please refer to the
instruction manual.
Repeat the test for all winding temperature indicators if more than
one indicator is provided. insert in hot oil bath.
Remove the thermal sensing bulb from the transformer cover and Check the readings with clinical thermometer. Replace the sensing element in transformer pocket and check the
readings or remote winding temperatures if provided. supplier's catalogue.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 65 of 205
APPENDIX A
SL. No. 1
CHECK POINT
AVAILABILITY OF DOCUMENTATION Erection drawings including OGA Erection / Maintenance Manual Transport packing list
O.K.
REMARKS
RECEIPT OF TRANSFORMER Externally inspected damage (if any) Gas pressure on receipt (Where applicable) Oil level (in case of oil filled transformer) Unit correctly positioned
RECEIPT OF ACCESSORIES All materials stored correctly Packing Cases inspected, damage if any Marshalling box inspected, damage if any Control panels (RTCC)inspected damage if any
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
SL. No.
PTRM1104
CHECK NPOINT O.K
Page 66 of 205
NOT O.K. REMARKS
Materials received corresponded to Advise note Any shortages / wrong supply Materials comply with shipping specification Remark (if any)
ERECTION Transport rollers mounted Conservator mounted Buchholz relay and oil surge relay mounted (arrow marked should be towards conservator) Breather mounted and duly charged HV Bushings mounted LV Bushing mounted Tertiary Bushing mounted (if applicable) HV neutral Bushing mounted LV Neutral Bushing mounted Bushing installed at correct angles Diaphragm checked MOLG mounted Radiator mounted Fans mounted Pressure Relief valves mounted Alignment of all pipe work OLTC Conservator mounted Heat Exchangers assembled with pipe work Topping up of transformer oil Leakage observed after 24 hrs.(if any) Rating Diagram and identification plate fitted
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
Marshalling box aligned Control panel (RTCC) aligned Control panel (OLTC) aligned
PTRM1104
Page 67 of 205
OIL FILLING All bushing oil level Tap changer selector oil level Diverter switch oil level Auxiliary unit oil level Radiator, Headers oil filled Transformer / OLTC Conservator oil tight Complete transformer/reactor oil tight All air release plug vented Valves in service position All drain / filter valves blanked
MULTICORE CABLE All tray work adequately secured All cables adequately tied/clipped back to tray Cables glanded correctly WTIs and OTIs satisfactorily installed
BREATHERS Silica gel breather satisfactory Tap changer silica gel breather satisfactory Drycol breather correctly installed (if present)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
8 FANS Fans rotate freely & quickly Pumps installed for correct flow Flow indication visible 9 CONTROL PANELS Cable termination Cable glanding Control cabinet clean & tidy Heater supplied Locking arrangement 10 CLEANING & TOUCH UP PAINTING OF COMPLETE TRANSFORMER
PTRM1104
Page 68 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 APPENDIX -B PRE-COMMISSIONING CHECKS & TEST RESULTS Customer: ______________________ EQUIPMENT DETAILS: (Rating, Ratio*, Maker's Ref., Sl. No., Year etc.) ___________________________________________________________________ Vector Group*: -------------------------- Amps. (H/I/L) ---------------------------------------------Tapping Range: --------------------% Impedance at Normal tap --------------------------Wdg. --------------------------Site:______________________________ Page 69 of 205
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
CHECK POINTS Direction & mounting angle of O.S.R. & Buchholz relay Dryness of silica gel, seal removal & oil level in bottom cup Oil level in Main conservator. Oil level in OLTC conservator. Oil filled in OTI / WTI pockets. Earthing of Main tank, cooler bank, neutral, fans, pumps, etc Absence of oil seepages / leakages. Bushing -their oil levels & test cap covering. Explosion vent & rupture pin setting. Touch up painting & washing. Overall clearances. Atmoseal commissioned (top gauge glass to show full oil ) Sagging of radiator / pipes Tightness of bushing top seal Distortion in expansion bellows / removal of transit support Jumpers connected to bushing
1. One person should be able to disconnect & reconnect the jumper (without additional help for pulling / matching of jumpers) 2. Jumper should not sag below the bushing terminal level NOTE : Recommended connection is vertical jumper connection.
STATUS OK NOT OK
REMARKS
16
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 70 of 205
A. MARSHALLING BOX (Sl. No. & Rating : _____________________________) STATUS CHECK POINTS OK 1 W.T.I. (Sl.No., Make & Model) a. Transit lock release. b. Switch settings & operation. c. Connections. d. Ambient reading. e. Heater shunt shorting link. f. Matching with repeaters. g. Power supply & current converter 2 O.T.I (Sl. No., Make & Model) a. Transit lock release b. Switch setting & operation. c. Connections. d. Ambient reading. e. Matching with repeaters. 3 4 5 6 7 8 Space heater & Thermostat settings. Cabling, Glanding, Termination etc. Earthing & Touch up painting. Stand by supply change over operation Timer settings. Closure of openings & tidiness. NOT OK REMARKS
B. FANS: (Model, RPM, KW / HP ) ____________________________________ 1 2 3 Glanding & Earthing. Mounting & Terminal cover condition. Direction & Smoothness of operation : a. Manual -Local. b. Manual Remote
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 71 of 205
c. Auto & Stand by operation 4 5 6 7 Overload setting Starting current Running current Megger values STATUS CHECK POINTS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Alignment of all shafts & Drive Mechanism Oil fill in gear box (Where reqd.) Mechanical end limits of D.M. Coupling Position & rotation lag. Manual operation. Local electrical operation. Electrical end limit operation. Remote electrical operation. Tightness of external shaft coupling Bending of lock washer. Fitment of window & shaft covers. Cabling, Termination, Glanding etc. Space heater & thermostat setting. Continuity check during transition by voltage application. Earthing. TPI counter reading CCU for TPI OK NOT OK REMARKS
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 72 of 205
D. R.T.C.C.: (Sl. No. & Rating): _________________________________________ 1 2 3 4 5 6 Installation & Earthing. Cabling, Glanding, Termination etc. Setting of Timers. Functioning of Indication Lamps. Functioning of Hooter / Buzzers. Annunciation / Relay Checks: a. b. c. d. e. f. g. Make & Model 7 8 9 10 Tap position indicator. W.T.I. Repeater. O.T.I. Repeater. O.L.T.C. Operations : a. Individual : b. As Master : c. As Follower : 11 12 13 Emergency Trip. Out of step & MP Timer operation. Operation of A.V.R. & L.D.C.
E. Operation of Pumps, NRV, Flow Indicators: 1 2 3 4 Direction of pump operation. Manual operation. Auto operation. Stand-by changeover.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: 6 7 8 9 10 11 PTRM1104 Page 73 of 205
Non Return Valve operation. Overload setting Starting current Running current Stability of alarm & trip contacts of Buchholz relay during oil pump starting by manual / Auto mode Megger value (500 V / 1000 V Megger )
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: S I T E T E S T R E S U L T S: NOTE: Instruments provided by Customer will normally he used for the tests after ascertaining their operation in the applicable ranges. A. Insulation Resistance: Range, Make, kV rating & Type of tester: _________________________________ 1 2 Top oil Temperature: Megger Values: 60 Sec. H.V. to L.V.: H.V. to T.V.: L.V. to T.V.: CORE to TANK ( By 1000 V Megger ) CORE to FRAME ( By 1000 V Megger ) B. Current Transformers: C. TAN DELTA & CAPACITANCE TEST OF BUSHINGS: C. T. DETAILS 600 Sec. H.V. To Earth T.V. To Earth L.V. To Earth 60 Sec. 600 Sec. PTRM1104 PART 2 Page 74 of 205
CHECK POINT Continuity Approx. Ratio Polarity (Only for REF / DIFFL. C.T) Saturation check only for PS class C.T's
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 75 of 205
C. TAN DELTA & CAPACITANCE TEST OF BUSHINGS: a. Atmospheric condition & temperature: b. Equipment used for test: c. Bushing position on test: Bushing Sl. No. Make Rating A / V Tan delta Capacitance Megger value
NOTE: Please ensure that the bushings are absolutely clean. Atmosphere should be dry & bushing should be in vertical or mounted on transformer during testing. Test tap should be cleaned with CTC & dried out using a hot air dryer (60 C) if need be. Short the terminals of other bushings & connect to earth. Arcing horns & line terminals to be removed. D. SHORT CIRCUIT TEST ON TRANSFORMER: Method of testing: Tap Position FIRST NORMAL LAST REMARKS: Value of short circuit current should be observed on other taps for any abnormality & abnormalities if any may be recorded. E. PHASING CHECK ON MULTI-RUN OF CABLES (HV & LV): Ensure absence of cross connections by physical inspection, and continuity check. PHASING CHECK BEFORE PARALLELING: Current in Amps HV LV IV NEUTRAL
O
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 76 of 205
F.
Ensure absence of cross connections by physical inspection and by measurement of voltage across corresponding phases on the LV By applying low voltage on HV. Approximate Voltage Ratio*: Apply single phase 240 or 440 volts on each HV line lead and N or pair of HV line leads and Measure LV voltage on all taps in all phases. HV Volts (applied) 1U-1V 1U-1N 1V-1W 1V-1N 1W-1U LV1 Volts 2U-2V 2V-2W 2V-2N 2W -2U 2W -2N LV2 / Tertiary 3U-3V 3W-3N 3V-3W 3V-3N 3W-3U 3W-3N
Tap No.
1W-1N 2U-2N
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 77 of 205
G. MAGNETIC BALANCE: (For star winding only) AT NORMAL TAP POSITION VOLTAGE ACROSS
TAP No.
1U-1N
1V-1N
1W-1N
2U-2N
2V-2N
2W-2N
H. EXCITATION WITH REDUCED VOLTAGE: 1. For LV winding of up to 1.1 KV class, apply single phase, 2 wire, 415 volts from HV side (Keeping neutrals isolated) on each leg. 2. For L.V. winding of class higher than 1.1 KV, apply single phase, 2 wire, 415 volts from LV side (Keeping neutrals isolated) on each leg. Tap No Applied Volts ( V ) Measured current (A) 1U-1V 1V-1W 1W-1U 1U 1V 1W
I. OIL BREAKDOWN VALUES: (Average of six readings with 2.5 mm gap) (a) Main tank top oil sample : ______________________________ (b) Main tank bottom oil sample : ______________________________ (c) O.L.T. C. oil sample: ______________________________ J. VECTOR GROUP CHECK: Short terminals 1U to 2U and apply 3 phase, 3 wire 415 volts supply across 1U-1V-1W and measure voltage across terminals and confirm the group STAR -STAR CONNECTION 1V -2V : 1V -2W : 1W -2W : 1W -2V : STAR -DELTA CONNECTION
1V -2V : 1V -2W : 1W -2W : 1W -2V : 1U -1V : 1V -1W : 1W -1U : (Signature & Name): _____________ (Signature & Name): _______________ AREVA ENGINEER CUSTOMER'S ENGINEER
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 78 of 205
PART 3
PRE-COMMISSIONING CHECKS To be carried out after transformer/Reactor is connected to lines & before energisation
CHECK POINTS 1 2 3 4 Clearances in air (refer O.G.A.) Arcing horn gap set (refer O.G.A.) Tightness of bushing lugs, cable / line connections, terminals, etc. Simulation of Alarm & Trip circuits (verify breaker / Master trip operation by initiating operating contacts of) a. Buchholtz relay b. Winding temperature indicator c. Oil temperature indicator d Oil surge relay e. Pressure relief device / vent switch f. M.O.L.G. g. Oil / Water flow indicators / D.P.G. h. Sudden pressure relay I. Over current relay j. Earth fault relay k. Differential relay l. Inter tripping relay m. Others Air venting from: a. Bushings b. Radiators, headers, couplings c. Buchholtz relay d. O.L.T.C. cover / head e. Main tank cover / Thermosyphon f. Disconnecting chamber a. H.V. Lightening Arrester counter reading b. L.V. Lightening Arrester counter reading STATUS O.K. NOT OK REMARK S
6.
Transformer successfully energised on __________ at _______ Hrs on Tap No. ___ Load & is operating satisfactorily. Transformer put on _______ Amps. / MVA load on _______ at _______ Hrs and is operating satisfactorily. Signature : ____________________ Signature: _________________ (AREVA ENGINEER) (CUSTOMER'S ENGINEER) Name : _________________ Name: _____________________ Designation: __________________ Designation: _________________
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 DATA REGARDING ACCESSORIES: 1 H.V.BUSHINGS: Make: Rating: Sl. No.: 2 L.V.BUSHINGS: Make: Rating: Sl. No.: 3 O.L.T.C. DETAILS: Make: Type: Sl. No.: 4 FACIA DETAILS: Make: Sl. No.: Model: No. of windows : Voltage: 5 PRESSURE RELIEF DEVICE: Make: Sl.No: Pressure Setting: Name of Service Engineer: Signature: Date: Page 79 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 80 of 205
7.0
Excessive vibration if any on any part of the transformer shall be Transformer shall be observed for any abnormality. If any gas is collected inside the Buchholz relay, it shall be analysed
for its combustibility. If gas is not combustible, it indicates air trapped inside the transformer.
All instruments should be checked for any abnormal indication. Check winding temperature and oil temperature readings at least
once in every shift. remote indicators.
Check and confirm that tap position indicators is same in local and Check and confirm that none of the alarms are indicated. Ensure that cooler power supply isolator is ON. Ensure that cooler control is in AUTO. Ensure that pumps and fans are running smoothly as temperature
dictates. If the temperature is below the ON setting neither the pump nor fan should be running.
hours and confirming that everything is normal, the transformer shall be taken on load. indicators.
Observe the rise in temperature of oil and winding temperature While temperature is rising, confirm that fans and pumps are
switched on automatically at the preset temperatures. switched off at preset temperature.
While temperature is falling, observe that the pumps and fans are
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: 7.1 PTRM1104 Page 81 of 205
ROUTINE / PERIODIC INSPECTION SCHEDULE FOR TRANSFORMER & REACTOR Items to be inspected Load current Terminal Voltage Ambient Temperature Winding Temperature Oil Temperature Tap position Air cell conservator Oil level in Conservator Oil level in Bushings Oil level in OLTC Conservator Oil level in breather cup Connections Dust deposits & physical damages to bushings Air passage & colour of silica gel in breather Cable boxes, gasket joints, gauges etc. Dielectric strength of transformer oil Moisture content of transformer oil Dissolved gas analysis of transformer oil Resistivity of transformer oil Insulation resistance of windings Tan delta & Capacitance of condenser bushings Operation of relays and their circuit Surface paint Frequency Hourly Hourly Hourly Hourly Hourly Daily Daily Daily Daily Daily Daily Monthly Monthly Quarterly Quarterly Half yearly Half yearly Half yearly Half yearly Yearly Yearly Yearly 2 ~ 3 Years**
S. No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Note: ** Duration of surface repainting depends on the level of pollution prevailing at site. If pollution level is high, a frequent repainting schedule may have to be worked out. Lifting of core and windings are not recommended as a routine inspection. Core and coils are to be inspected only if such an inspection is warranted by test results of dissolved gas analysis, any abnormality in performance or for suspected internal damages due to external short circuit.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 82 of 205
8.0
8.1 8.1.1
Oil Sampling
Oil sample should be tested for the following and results recorded: -
Electric Strength
mm gap, the oil must be filtered to improve the characteristics. For line end OLTC diverter chamber, oil filtration is recommended when the BDV is 40 kV at 2.5 mm gap. For neutral end OLTC diverter chamber, oil filtration is recommended when the BDV is less than 30 kV at 2.5 mm gap.
8.1.2
Moisture Content For transformers of 400 kV and above class, if the moisture content is
found to have increased beyond 20 ppm oil should be filtered. For transformers of voltage class up to 245 kV, if the moisture content is found to have increased beyond 25 ppm oil should be filtered.
8.1.3
Filename
Acidity
TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 83 of 205
It the acidity is increased beyond 0.5 mg KOH/g, than the oil needs
filtration. After draining the oil completely from the transformer/Reactor, core, winding, insulation and interior of tank should be washed by hot oil jet. The oil being used for washing of internal body also must be drained completely. Refilling of oil in transformer/reactor should be done under vacuum.
8.2
Sampling procedure Special care in oil sampling is required for Delta connected transformer
and autotransformers.
8.2.1
Tools required
Spanner set Thermometer Steel sampling bottles with polyethylene cone caps. Silicon rubber tubing 10 mm bore - 1 m long. Clean synthetic sponge. Polyethylene sheet - 1 m square Clean cloths Self adhesive labels
8.2.2
Procedure The sampling bottles shall be labelled and marked with information like
source of sample, date and time & sample temperature. Sample bottle shall not be opened before it is needed for testing. Sampling point should be cleaned by using sponge. Blanking plate of sampling valve shall be removed by using spanner. Clean the silicon rubber tubing thoroughly and fit to sampling point nipple. Rinse the bottle in oil stream and reduce the rate of oil flow to 1 litre/minute. Put the end of rubber tubing to sampling bottle and fill the bottle from bottom.
No air bubble shall be introduced into the bottle. The bottle is allowed to overflow before it is closed. Measure and record the temperature of oil sample as soon as it is
taken. Put back and tighten the blanking plate. Remove all tools, excess oil container and oil sample from the area.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 84 of 205
Arrange for testing oil sample at laboratory. 8.3 8.3.1 8.3.2 WINDING TEMPERATURE INDICATOR TESTS Tools and materials
Hot oil bath (with heating facility) Secondary injection test set Multimeter Clinical thermometer Keys of marshalling box.
Procedures The purpose of this check is to confirm that the winding temperatures
Indicators are functioning accurately. The transformer shall be isolated and earthed. Rotate the indicator pointers slowly to the alarm set value and confirm from the control room that the alarm signal has been received. Rotate the pointer still further and confirm from the control room that trip signal is received.
8.3.3
Calibration Remove the thermal sensing bulbs from the transformer and insert it
into the hot oil bath. Check the winding temperature readings up and down the scale at intervals of 5 C. Confirm from control room that remote temperature readings are tallying with the local readings. Replace the sensing element into the transformer pocket. For any adjustment, see the manufacturer's catalogue.
8.3.4 8.3.5
SECONDARY INJECTION TESTS ONAN Rating Set the cooler supply isolator of OFF position. Connect the secondary injection test set across the heater coil
terminals. Inject current and check the resultant gradient for ONAN rating.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 85 of 205
8.3.6 8.4
OFAF Rating
In order to carry out these tests the pump must be running. Set the cooler isolator to ON position. Set the cooler switch to fans and pumps. Check and confirm that the pump is running. Inject current in the heater coil and check the gradient for OFAF rating. Disconnect. Set the cooler control switch to AUTO.
BUCHHOLZ RELAY FUNCTIONAL TEST Tools and Materials Required. Multimeter Nitrogen cylinder with regulator and pressure gauge or air supply (4
kg/cm) Bucket 10 mm polythene tube, 10 meters.
8.4.1
Filename
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 86 of 205
8.5
TAPCHANGER OPERATION Regular inspection of tap changing equipment is not required because
mechanical operation of tap changer does not involve significant contact wear. It is sufficient to operate the tap changer through the whole range of tap selector positions twice a year. The purpose of this check is to ensure correct mechanical operation of tap changer. Transformer shall be isolated and earthed. Note the tap position. Operate the tap changer through operating handle through entire range of tap positions. Return to the original tap position. Set the local selector switch to LOCAL. Press RAISE button and release. Check and confirm the tap position indication has changed and that limit switch stops the tap changing at preset tap. Repeat. Press the LOWER button and release. Check and confirm that limit switch has operated and tap position indication has changed. Repeat till the tap position has returned to the original value. Set the local selector switch to REMOTE.
8.6
8.6.1
8.6.2
Procedure Remove the blanking plate from filter valves and connect the oil inlet
hose to top filter valve and oil outlet hose to the bottom filter valve. Open the filter valves and start circulation of hot oil. Oil temperature shall be 55 C to 70 C. Circulate the oil for 4 full passes. Re sample and arrange to test.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 87 of 205
Continue until oil condition is acceptable. 8.7 CORRECTIVE MAINTENANCE All flange gaskets must be renewed wherever joints are dismantled. Cleanliness of gasket surfaces and correct compression (40 % ~ 50%
approx.) of gasket must be ensured during reassembling.
8.8 8.8.1
8.8.2
Procedure
Transformer is isolated and earthed. Close the isolating valves on either side of pump Disconnect the motor supply wires Remove the drain plug of the pump and drain oil from the pump. Remove the clamping bolts and remove the pump Blank off the isolating valve. For re-fixing the pump, remove the blanking plates. Fix new gaskets. Replace and tighten the clamping bolts. Open the isolating valves on cooler side. Open air release plug and close when oil starts flowing out. Open the isolating valve on transformer tank side.
8.9 8.9.1
8.9.2
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 88 of 205
Set the cooler supply isolator of OFF. Close the inlet and outlet valves if radiator is mounted on a separate
8.10 8.10.1
cooler tank. Close the top and bottom isolating valves of radiator. Open the top air release plug. Remove the bottom drain plug and drain the oil to oil container under gravity. Sling the radiator with jib crane. Remove the radiator clamping bolts. Remove radiator. Blank off the radiator and header openings. Close the air release and drain plugs. For Re fitting the Radiator. Remove the blanking plates. Fix new gaskets. Assemble the radiator and tighten the clamping bolts. Open the top header air release plug. Open the bottom radiator isolating valve. If the radiator is on a separate cooler bank, oil shall be filled into the radiator bank through the bottom header valve by using the filter machine. If the radiator is tank mounted, the oil from the oil tank should be pumped into the tank by using the filter machine. Close the air release plug on top as soon as oil starts flowing through the air release plug. Shut down the oil filter machine Open top header isolating valve. In case of separate cooler banks, air should be released through the top common header air release plugs.
REMOVING AND RE FITTING FAN & MOTOR Tools and materials Forklift truck to take weight of fan and motor assembly.
8.10.2
Procedure
The transformer is to be isolated and earthed. Set cooler supply isolator to OFF and lock the marshalling box. Disconnect the fan motor supply wires. Support the weight of fan and motor assembly by using fork lift truck.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 89 of 205
Unbolt fan and motor form fan mounting frame. Lower the fan from the fan-mounting frame. 8.10.3 Re fitting Fan and Motor Assemble the fan and motor in position and tighten clamping bolts. Re connect the power supply wires. Unlock marshalling box and set cooler supply isolator to ON.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 90 of 205
9.0
TROUBLE SHOOTING
Following table shows some of the symptoms, possible causes and remedies in case of abnormal situations: If the abnormality is of a major nature, the manufacturer should be contacted at the address given else where in this Manual. When the matter is referred to the manufacturer it shall contain the following: Transformer Rating. Voltage Rating. Manufacturers Indent No. / Serial No. Year of Manufacture. Date / Time of failure. Brief description of the problem. Checks done and their results.
9.1
High ambient temperature Insufficient cooling Low oil level Deterioration/ sludge formation of oil. Short circuited core Electrical Troubles/ Winding Failure Lightning, short circuit, Overload Oil of low dielectric strength.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 91 of 205
Testing of oil
Measurement of Tan delta of Windings Analysis of gas collected in Buchholtz Relay Dissolved Gas Analysis
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 92 of 205
9.3
PROTECTIVE DEVICES
No. 1 DETECTIVE DEVICE Pressure Relief Device DESCRIPTION
When the internal pressure increases beyond the preset value of PRD it operates. This may also happen if the breather connection is choked. Judgment based on the inspection of other protective relays is essential Differential Relay This relay detects the internal defects by comparing the input current and the output current of the transformer. If it functions simultaneously it indicates internal fault. Please note that this relay sometimes operates due to in rush current when transformer is energised and this is not an internal fault. Oil Temperature This thermometer gives Alarm when the temperature Indicator/ Winding rises beyond the set value. Over loading, insufficient Temperature cooling because of contamination of fan impellers, Indicator Alarm stoppage of fans/pumps etc. are to be checked. Over Current These are intended for detecting faults in power system Relay/ Earth Fault associated with the transformer. A fault in the Relay transformer results in operation of these relays. This is accompanied by actuation of protective devices of the transformer. Identification of fault should therefore be made on the basis of a thorough analysis of these functions. Voltmeter/ If a sudden change in voltage or current is noted when Ammeter there is no abnormality in the power system or an unbalance of voltage or current is noted between phases, the reasons should be investigated. Human Sense Human sense can play an important role in detection of faults. a) Discoloration or odour of insulating oil. If pieces of insulating materials or copper are found in oil, an internal fault can be suspected. b) Abnormal noise or vibration.
9.4
9.5
Filename
PUMPS
TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
SYMPTOM Pump Motor over heats
PTRM1104
POSSIBLE CAUSE Impeller binding Insulation failure of Motor Winding Two phase operation Motor bearings worn Impeller damaged Pump bearing bushes or rings worn. Valve not fully open Impeller damaged or worn Speed too low
Page 93 of 205
REMEDY Remove the pump and investigate the problem. Remove the pump and investigate the problem. Check power supply. Remove pump and investigate the reason Remove pump and investigate the reason Remove pump and investigate the reason Open the valve fully. Remove pump and investigate the reason Check electric supply.
9.6
FANS
SYMPTOM Fan motor overheats Fan vibrating POSSIBLE CAUSE Motor bearing worn Two phase operation Fan blades out of balance and noisy Mounting bolts loose REMEDY Remove the fan and investigate reason. Check electric supply Balance the fan or replace Check and tighten fasteners.
9.7
BUCHHOLZ RELAY
SYMPTOM Rate of gas evolution NONE Electrical response of relay POSSIBLE CAUSE Identity Class of fault of gas Oil surge Sudden vaporisation of oil at 260~400OC Boiling of water in exceptional cases Inference REMEDY
Faulty operation of oil pump Large masses of metal heated Eg.: Earth fault, short circuit not causing insulation failure. Simultaneous occurrence of a heat producing fault and entry of water into the tank.
RAPID
Filename
Rev no.
05
Date
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
repeats after releasing gas Trip and alarm mechanism operates Hydrogen
PTRM1104
fault
Page 94 of 205
circulating pump.
MEDIUM
Alarm operates and repeats within minutes or hours after each release of gas
SLOW
Alarm operates
Hydrogen
Local, very high current, hot spot not involving insulation, arc over between metal parts of Terminal gear or terminal to tank. Thermal Local hot spots due to decomposition very high current faults of oil and in contact with solid insulation. insulation Eg. Insulation failure followed by arc between insulated conductors and earth, short circuited turn etc. Air leaks or Fracture of tank pipe or leakage due to Buchholz relay casing mechanical or faulty oil circulating fault. pumps Local hot spots not Thermal decomposition involving insulation, faulty joint/ contacts, of oil above core faults causing 400OC burning, an incipient fault not involving solid insulation Eg. Core not properly earthed Local hotspots in contact with solid insulation. Low power Thermal arc between insulated decomposition conductors and earth, of oil and solid core faults. Faulty insulation. joints/ contact. Any incipient fault involving solid insulation Presence of Release of entrapped air due to air during early life of mechanical transformer of fault or transformer, crack in physical tank, pipe or relay absorption casing, faulty oil pump. Decomposition Low current arcing not of oil only involving solid
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 95 of 205
insulation, gassing caused by high electrical stress, corona discharge Decomposition Low energy arcing of oil and solid involving insulation decomposition of solid insulation, creepage through solid insulation, oxidation of insulation Low oil level Oil level falling below the level of Buchholtz relay due to oil leakage
Alarm operated
N. A.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 96 of 205
Table 9.1: DIELECTRIC STRENGTH OF INSULATING OIL (12.5 mm dia. Spheres, 2.5 mm gap) No. 1 2 3 Nominal Voltage Of Transformer Dielectric Strength of Insulating Oil (kV) 145 kV class and above 72.5 kV class to less than 145 kV Less than 72.5 kV class More than 50 More than 40 More than 30
Table 9.2: ACID CONTENT OF INSULATING OIL (BY NEUTRALISATION) No. 1 2 3 Judgment Good Replace or do filtration Replace immediately Acid Content of Oil (mg KOH/g) Less than 0.2 0.3 ~ 0.5 Above 0.5
Table 9.3: RESISTIVITY OF INSULATING OIL No. 1 2 3 Judgment Good Fair Poor Resistivity of Oil at 90OC ( -cm) More than 0.1x1012 1x1011 to 0.1x1012 Less than 0.1x1011 Table 9.4: WATER CONTENT No. Nominal Voltage of Transformer 1 2 400 kV Class & above Upto 245 kV Class Water Content (ppm) Less than 20. Less than 25.
Table 9.5: DIELECTRIC DISSIPATION FACTOR No. Nominal Voltage of Transformer 1 2 145 kV Class & above Below 145 kV Class At 90OC, 40 ~ 60 Hz 0.2 Max. 1.0 Max
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 97 of 205
9.8
Table 9.6 "Normal" Values of Dissolved Key Gas Concentration Limits in oil of Power Transformers in Service [Parts per Million ppm]. (Ref. FIST 3-30MM : October 2000) Status H2 CH4 C2H2 C2H4 C2H6 CO CO2* TDCG** Condition 1 100 120 35 50 65 350 2500 720 Condition 2 101~ 121~ 36~ 51~ 66~ 351~ 2500~ 721~ 700 400 50 100 100 570 4000 1920 Condition 3 701~ 401~ 51~ 101~ 101~ 571~ 4001~ 1921~ 1800 1000 80 200 150 1400 10000 4630 Condition 4 >1800 >1000 >80 >200 >150 >1400 >10000 >4630
MM
Ref.: FIST 3-30 (Transformer Maintenance; Facilities, Instructions, Standards and Techniques by United States Department of the Interior Bureau of Reclamation, Denver, Colorado). CO2 is not considered in the calculations for TDCG, because it is not a combustible gas TDCG means Total Dissolved Combustible Gas.
* **
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 98 of 205
Condition - 1
Total Dissolved Combustible Gas (TDCG) and any individual combustible gas below this level indicate normal operation of the transformer/Reactor. If any gas exceeds the specified level, it needs investigation.
Condition - 2
TDCG and any individual combustible gas in this range indicate greater than normal combustible gas level. A fault may be present. Further monitoring is required. Refer Table 9.7 for recommended sampling frequency and actions.
Condition - 3
TDCG and any individual combustible gas in this range indicate a high level of decomposition of cellulose insulation and / or oil. Refer Table 9.7 for recommended sampling frequency and actions.
Condition - 4
TDCG and any individual combustible gas in this range indicate excessive decomposition of cellulose insulation and / or oil. Continued operation could result in failure of the transformer. Refer Table 9.7 for recommended sampling frequency and actions.
Note:
A sudden increase in key gases and the rate of gas generation are more important in evaluating a transformer/Reactor than the amount of gas.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 99 of 205
Table 9.7
Action based on Dissolved Combustible Gas concentration.
Conditions TDCG Level or Highest Individual Gas (Ref. Table 9.5) 720 ppm of TDCG or highest condition based on individual gas from Table 9.5 TDCG Generation Rates (ppm / day) < 10 10 ~ 30 > 30 < 10 10 ~ 30 > 30 < 10 10 ~ 30 > 30 Condition 4 < 10 10 ~ 30 > 30 Sampling Intervals and Operating Actions for Gas Generation Rates Sampling Interval Annually/ 6 Monthly for EHV Trf. Quarterly Monthly Quarterly Monthly Monthly Monthly Weekly Weekly Weekly Daily Daily Exercise caution. Analyse individual gases to find cause. Determine load dependence. Exercise caution. Analyse individual gases to find cause. Determine load dependence. Exercise caution. Analyse individual gases to find cause. Plan outage. Contact manufacturer for advice. Exercise caution. Analyse individual gases to find cause. Plan outage. Contact manufacturer for advice. Consider removal from service. Contact manufacturer for advice Operating Procedures Continue normal operation
Condition 1
Condition 2
Condition 3
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 100 of 205
Table 9.8 Transformer Fault Types and the gases they produce.
Key Gases H2, possible trace of CH4 and C2H6, possible CO H2, CH4 (CO if discharges involve paper insulation). Possible trace of C2H6. Possible Faults Partial discharge (Corona) Possible Findings Weakened insulation from ageing and electrical stress. Pinhole puncture in paper insulation with carbon and carbon tracking. Possible carbon particles in oil. Loose grounding of metal objects. Metal fusion, (poor contacts in tap changer or lead connections). Weakened insulation, from ageing and electrical stress. Carbonised oil. Paper over heating/ destruction if it is in the arc path. Discoloration of paper insulation. Overloading or cooling problem. Bad connections. Stray current path and/or stray magnetic flux. Paper insulation destroyed. Oil heavily carbonised. Same as above with metal discoloration. Arcing may have caused a thermal fault.
H2, CH4, C2H6, C2H4 and C2H2 present in large amounts. If C2H2 is being generated, it indicates continuance of arcing. CO will be present if paper is being heated.
H2, CO.
Thermal faults less than 3000C in an area close to paper insulation (Paper is being heated)
H2, CO, CH4, C2H6 and C2H4 All the above gases and acetylene in large amounts.
Thermal fault between 3000 C and 7000 C High energy electrical arcing 7000 C and above.
Note: Transformers are so complex that it is impossible to put all causes into a chart. Several other reasons like high current surges due to faults down stream, static electric discharges, multiple core earthing, sustained operation under over load, over/under voltage etc. may also be seen.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 101 of 205
Dissolved Gas Analysis using Key-gas Ratios (Ref. CIGRE Report 15.01.01: October 1999)
Key ratio No. 1: (INDICATION: DISCHARGE) C2H2 (acetylene /ethane) : >1 indicates fault C2H6 Key ratio No. 2: (INDICATION: PARTIAL DISCHARGE) H2 (hydrogen /methane) : >10 indicates problem CH4 Key ratio No. 3: (INDICATION: THERMAL FAULT) C2H4 (ethylene /ethane) : >1 indicates thermal fault C2H6 Key ratio No. 4: (INDICATION: CELLULOSE DEGRADATION) CO2 (carbon dioxide /carbon monoxide) : >10 indicates thermal CO over heating >3 indicates electrical fault Key ratio No. 5: (INDICATION: INTANK TAPCHANGER) C2H2 (acetylene /hydrogen) : >2 & C2H2 >30 ppm indicates possibility H2 Note: Ratios are to be calculated only if the concentrations of both the gases are above the detection levels. of tap changer oil leaking into main tank
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 102 of 205
FLOW CHART FOR FAILURE INVESTIGATION Ref.: IEEE Std. C 57. 125 - 1991
SELECTED TESTS ANALYSIS OF DATA ROUTINE TESTS SHOW DEVIATION FROM PAST
MONITOR
YES PROBLEM
NO RETURN TO SERVICE
YES
DAMAGE IS OBVIOUS
NO
YES
SELECTED TESTS
SCRAP
YES
PROBLEM FOUND
NO
NO
FURTHER TESTING
FIELD REPAIR
YES
NO
NO
YES
TEARDOWN-TABLE 10 ANALYZE-SECTION 6
FIG. 9
NOTE: For further details please refer to IEEE Std. C. 57. 125 - 1991
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 103 of 205
10.0
NATIONAL AND INTERNATIONAL STANDARDS APPLICABLE TO POWER TRANSFORMER AND ALLIED PRODUCTS. INDIAN NATIONAL STANDARDS. POWER TRANSFORMERS:
IS 1866 : 2000 Code of Practice for Maintenance and Supervision of Insulating Oil in Equipment. IS 1885 (Part 38) : 1993 Electrical Vocabulary - Transformers and Reactors. IS 2026 ( Part 1) : 1977 Power Transformers - General. IS 2026 (Part 2 ) : 1977 Power Transformers - Temperature rise IS 2026 (Part 3 ) : 1981 Power Transformers - Insulation level and dielectric tests. IS 2026 (Part4) : 1977 Power Transformer - Terminal marking, Tapping & Connections IS 2026 ( Part5) : 1994 Transformer / Reactor bushing minimum external clearance in air IS 6600 : 1972 Guide for loading of oil immersed
10.1
10.1.1
transformers. IS 10561 IS 11171 IS 10028(Part1) : 1983 Application guide for power transformers. : 1985 Dry type transformers. : 1985 Code of practice for selection installation & maintenance of transformers- Selection IS 10028 (Part 2) : 1981 " IS 10028 (Part 3) : 1981 " " " Installation Maintenance
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 104 of 205
10.1.2
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS 8603 (Part 1) PTRM1104 : 1977 Dimensions bushings for for use Page 105 of 205 porcelain in transformer polluted
heavily
atmosphere 12/17.5 kV Bushings. IS 8603 (Part 2) : 1977 Dimensions bushings for for use porcelain in transformer polluted
heavily
atmosphere 24 kV Bushings. IS 8603 (Part 3) : 1977 Dimensions bushings for for use porcelain in transformer polluted
heavily
atmosphere 36 kV Bushings. IS 8603 (Part 4) IS 12676 : 2003 52 kV Bushing. for oil impregnated paper
: 1989 Dimensions
insulated condenser bushings. IS 13305 : 1992 Permissible limits of visual defects for insulating porcelains for electrical circuits. IS 13312 : 1992 Dimensions of porcelain oil filed transformer bushings (rated 52 kV) in medium polluted atmospheres. IS 15137 : 2002 Metal Connecting Lugs for Porcelain Transformer Bushings - Specification IS 1573 : 1986 Electroplated coatings of zinc on iron & steel IS 2629 : 1985 Recommended practice for hot dip
galvanising of iron and steel. IS 2633 : 1986 Methods for testing uniformity of coating of zinc coated articles. IS 4759 IS 3401
Filename TM1902_2012
: 1996 Hot dip zinc coating on structural steel. : 1992 Silica gel
Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS 3588 IS 3637 IS 3639 PTRM1104 Page 106 of 205
: 1987 Electric Axial flow fans. : 1966 Gas operated relays. : 1966 Fittings & accessories for power Transformers
: 1980 Cork Composition Sheet - Plain cork : 1980 Cork Composition Sheet - Cork & Rubber. : 1970 Electric power connectors. : 1988 Oil to water heat exchanger for
Conductors for transformer winding. IS 8468 IS 8478 IS 104 : 1977 On load tap Changers. : 1977 Application guide for on load tap Changers. : 1979 Ready mixed paint, brushing, zinc chrome, priming. IS 2074 : 1992 Ready mixed paint, air drying, red oxide zinc chrome, priming. IS 2932 : 1993 Enamel, synthetic, exterior (a) IS 13213 IS 13238 undercoating, (b) finishing.
: 1991 Polyurethane full gloss enamel. : 1991 Epoxy based zinc phosphate primer (two pack).
IS 1554 (Part 1)
: 1988 PVC insulated (heavy duty) electric cables for working voltages upto and including 1100 V.
IS 1554 (Part 2)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS 9147 PTRM1104 Page 107 of 205
1S 9700 IS 12943
: 1991 Activated alumina. : 1990 Brass Glands for PVC Cables. Low voltage Switch Gear and Control Gear General rules.
IS 4257 (Part 1)
: 1981 Dimensions
for
clamping
arrangements
10.1.3
INSTRUMENT TRANSFORMERS
IS 1885 (Part28) : 1993 Electro Technical Vocabulary Instrument Transformers. IS 2705 (Part1) IS 2705 (Part2) IS 2705 (Part3) IS 2705 (Part4) : 1992 Current Transformers - General. : 1992 Current Transformers - Measuring. : 1992 Current Transformers - Protective. : 1992 Current Transformers Protective Current transformers for special purpose application. IS 3156 (Part1) IS 3156 (Part2) IS 3156 (Part3) IS 3156 (Part4) IS 4146 : 1992 Voltage transformer - General. : 1992 Measuring Voltage transformers. : 1992 Protective Voltage transformers. : 1992 Capacitive Voltage transformers. : 1983 Application guide for Voltage transformers. IS 4201 : 1983 Application guide for Current transformers.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS: 5547 PTRM1104 Page 108 of 205
10.1.4
TRANSFORMER BUSHING
IS 1885 (Part54) : 1993 Electro Technical Vocabulary - Insulators. IS 2099 : 1986 Bushings for alternating Voltages above 1000 V. IS 3347(Part 1to8) Dimension bushings. IS 4257 (Part 1) : 1981 Dimension for Clamping arrangements for bushing 12 kV to 36 kV. IS 5621 : 1980 Hollow porcelains for use in electrical equipment. IS 8263 : 1976 Methods for radio interference test on high Voltage insulators. IS 8603 (Part1~3): 1977 Dimension for porcelain transformer for porcelain transformer
bushings for heavily polluted atmospheres 12, 24 & 36 kV. IS 8603 (Part 4) IS 8704 : 2003 52 kV Bushing
IS 12676
: 1989 Dimensions
for
oil
impregnated
paper
respect of pollution Conditions. IS 13305 : 1992 Permissible limits for Visual defects for
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS 13312 PTRM1104 : 1992 Dimensions of Page 109 of 205 porcelain oil filled
transformer bushing (rated 52 kV) for medium polluted atmosphere. IS 15137 : 2002 Metal Connecting Lugs for Porcelain Transformer Bushings - Specification
10.1.5
REACTORS
IS 5553 (Part 1) IS 5553 (Part 2) IS 5553 (Part 3) : 1989 Reactors - General. : 1990 Shunt Reactors. : 1990 Current limiting reactors and neutral
earthing reactors. IS 5553( Part 6) : 1990 Earthing transformers (Neutral Couplers) IS 5553( Par 8) : 1990 Smoothing Reactors
10.1.6
IS 1448 (Part 10) : 1970 Method for test for petroleum and its products cloud point and pour point. IS 1448 (Part 16) : 1990 Density of crude petroleum and liquid petroleum products by Hydrometer method. IS 1448 (Part 21) : 1992 Petroleum and its Products - Flash point by Pensky Martens Apparatus. IS 1448(Part 25) : 1976 Determination of Kinematic and Dynamic Viscosity. IS 1866 : 2000 Code of practice for maintenance and supervision of insulating oils in
equipment.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IS 2362 PTRM1104 Page 110 of 205
IS 6103
: 1971 Method of test for specific resistance (resistivity) of electrical insulating liquids.
IS 6104
: 1971 Method of test for interfacial tension oil against water by ring method.
of
IS 6262
: 1971 Method of test for power factor and dielectric constant of electrical liquids. insulating
IS 6792
IS 6855 IS 9434
: 2003 Method of sampling for liquid dielectrics. : 1992 Guide for sampling and analysis of free and dissolved gases and oil from oil filled electrical equipment.
IS 10593
: 1992 Methods of evaluating the analysis of gases in oil filled electrical equipment.
IS 12177
: 1987 Methods of test for oxidative ageing of electrical insulating petroleum oils by open beaker method.
IS 13567
: 1992 Determination of water in insulating liquids and in oil impregnated paper & press board by automatic Coulometric Karl Fisher
Titration - Method of Test. IS 13631 : 1993 Method of test for detection & determination of antioxidant additives in insulating oils. IS 12463
Filename TM1902_2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 111 of 205
10.1.7
: 1974 : 1976
IS 2165 (Part2)
IS 3716
guide
for
insulation
co-
IS 6209
: 1982 Methods
for
partial
discharge
measurements. IS 8690 : 1977 Application guide for measuring devices for high voltage testing. IS 2551 IS 8923 IS 12776 : 1982 Danger notice plates. : 1978 warning symbol for dangerous voltages. : 2002 Galvanised Specification. strand for earthing -
10.2
IEC STANDARDS
IEC 60071-1 (2006) Insulation co-ordination; Definitions, principles and rules. IEC 60071-2 (1996) Insulation co-ordination; Application guide.
05 Date 19/02/2012
Filename
TM1902_2012
Rev no.
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 112 of 205
Power transformers; General. Power transformers; Temperature rise. Power transformers; Insulation levels,
dielectric tests and external clearances in air. IEC 600764 (2002) Power transformers; Guide to the lightning impulse and switching impulse testing. IEC 600765 (2006) Power transformers; Ability to withstand short circuit. IEC 600767 (2005) Power transformers; Loading guide for oil immersed power transformers. IEC 600768 (1997) IEC 6007610 (2005) Power transformers; Application guide. Power transformers; Determination of
sound levels Application Guide. IEC 6007610-1 (2005) Power transformers; Determination of
sound levels. IEC 6007611 (2004) IEC 6007614 (2004) Power transformers; Dry type transformers. Power transformers; Design & Application of liquid immersed power transformers using high temperature insulation materials. IEC 60137 (2003) Insulating bushings for alternating voltages above 1000 V IEC 60156 (1995) Method for determination of the electric strength for insulating oils. IEC 60044-1 (2003) IEC 60044-2 (2003) IEC 60044-5 (2004) IEC 60044- 6 (1992) Current Transformers. Inductive Voltage Transformers. Capacitor Voltage Transformers. Protective Current Transformer for transient performance.
TM1902_2012 Rev no. 05
Filename
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 113 of 205
Tap changers; Application Guide Tests on indoor and outdoor post insulators greater than 1000 volts.
High
Voltage
Test
techniques:
Partial
discharge measurements. IEC 60289 (1988) IEC 60296 (2003) Reactors. Fluids for electro-technical applications unused mineral insulating oils for
transformer and switch gear. IEC 60310 (2004) Railway applications Traction
Transformers and inductors. IEC 60422 (2005) Mineral insulating oil in electrical equipment - Supervision and maintenance guide. IEC 60445 (2006) Identification of equipment terminals and termination of certain designated conductors including general rules for an alpha numeric system. IEC 60475 (1974) IEC 60529 (2001) Method of sampling liquid dielectric. Degrees of protection provided by enclosures (IP Codes). IEC 60554 (Part 1 ~ 3) Specification for cellulosic papers for electrical purposes. IEC 60567 (2005) Guide for the sampling of gases and of oil from oil filled electrical equipment and for the analysis of free and dissolved Gases.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: IEC 60599 (1999) PTRM1104 Page 114 of 205
electrical equipment in service. IEC 60616 (1978) Terminal and tapping marking for power transformers. IEC 60628 (1985) Gassing of insulating liquids under electrical stresses and ionisation. IEC 60905 (1987) Loading guide for dry type Power
Transformer. IEC 60947 (Part 1 to 7) IEC 61378-1 (1997) Low voltage switchgear and control gear. Converter Transformer for industrial application. IEC 61378-2 (2001) Converter Transformer for HV DC application. IEC 61639 (1996) Direct Connection and gas between insulated power metal
transformer
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 115 of 205
TRANSFORMER ACCESSORIES
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 116 of 205
TEMPERATURE INDICATOR
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 117 of 205
2.
SCOPE OF SUPPLY
OTI & TI: Instrument with specified Range, Number of control switches, length of capillary and sensing bulb. WTI: Same as 2.1 but fitted with specified thermal image device. TRANSMITTER (OPTIONAL): A precision potentiometer is mounted inside the case of OTI or WTI (2.1 or 2.2) to transmit the measured temperature to remote point(s). REPEATER (OPTIONAL): Analogue indicator supplied separately for remote indication of the temperature measured by OTI or WTI (2.1 or 2.2)
3.
OPERATION
The instrument operates as OTI when its sensing bulb is mounted in an oil filled pocket located in the hottest oil of an oil immersed transformer. The instrument operates as TI when its sensing bulb is exposed to the medium adjacent to the windings of a dry type transformer. When a proportionate load current of the transformer is passed through the thermal image device, the instrument operates as a WTI integrating the simulated temperature rise of the thermal image device and the top oil temperature measured by the sensing bulb. Remote indication of the temperature measured by the OTI or WTI is provided by connecting the transmitter to the repeater either directly or through a resistance transducer (resistance to current converter).
4.
CONSTRUCTION
LIQUID-FILLED SYSTEM (Refer Fig. 1): A sensing bulb (25), a measuring bellows (2) and a small bore capillary tube (24) connecting the two, form the measuring system. A second bellows (16-compensating bellows)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 118 of 205
connected with a second capillary (24) running parallel to the first capillary and terminated at the head of the bulb from the temperature compensating system. Both the systems are completely filled with the same liquid (other than mercury). The two bellows are linked to a compensating lever (15) in such a manner that the effect of ambient temperature changes on the capillary line and measuring bellows is compensated. The movement of the measuring bellows is related only to the temperature being measured by the sensing bulb. This movement is amplified by the link and lever mechanism (6), which directly drives the rotating disc (21) carrying the control switches. The same mechanism moves, through rack and pinion a separately mounted indicating pointer (Fig. 2, 11) over a calibrated dial. Head compensation is provided by sealing both the systems under initial pressure, which is greater than the possible head pressure due to differences in the elevation between the bulb and indicator. MAXIMUM POINTER (RED COLOURED) located on the indicator lid, is resettable from outside the case by a screw driver blade. Unscrew and remove black cap to reach the screw driver-slot. CAUTION: Never use the switch testing knob for setting the maximum pointer. If used, the switch contacts will close and initiate the external control circuits when the instrument is in operation. SWITCH TESTING KNOB: It is fitted on the indicator lid to check mercury switches setting and potentiometer operation. This knob when rotated moves the indicating pointer, switch mechanism and potentiometer wiper together and facilitates testing these circuits without opening the lid. Rotate the knob slowly and steadily for an accurate check. Never allow the knob to spring back suddenly or quickly, as this will cause damage. THERMAL IMAGE DEVICE (Refer Fig. 1): A heater coil (3-Bellows Heater) is fitted around the measuring bellow (2) and supplied from a current transformer in the load circuit of transformer. The heater coil simulates hotspot temperature of the winding over top oil temperature for a given load. The measuring bellows reacts to this simulated temperature rise in addition to the top oil temperature measured by the sensing bulb and the instrument functions as a WTI displaying the hottest spot temperature of the winding. An adjustable shunt resistor (17-calibrating shunt) is provided for shunting portion of the current through the heater coil to obtain precise thermal image.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 119 of 205
FIG. 1
INDICATOR (LID & DIAL REMOVED)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 120 of 205
REMOTE INDICATION (OPTIONAL): Refer Fig. 1, A precision potentiometer (20) is mounted inside the indicator to function as a transmitter for remote indication of the temperature measured by the OTI/WTI. Technical Data of the transmitter and repeater along with details of adjustments are given in the relevant data sheet supplied with each indicator. ELECTRICAL CONNECTION: All internal electrical connection are wired to the terminal block (Fig. 1, 14) mounted inside the indicator case. A wiring diagram is fixed inside the case of each indicator. Switches are identified by markings S1, S2, S3 and S4 on them. Terminal Nos. wired to each circuit are detailed below.
WIRED TO S1 Alarm S2 Trip S3 Cooler Control 1 S4 Cooler Control 2 Bellows, Heater & Shunt Potentiometer-Min., Wiper, Max
5.
PRE-INSTALLATION TESTING
EQUIPMENT: 1. Controlled constant temperature bath with continuously stirred liquid. 2. Certified Standard Thermometer. 3. A continuity test circuit. 4. High voltage breakdown tester. 5. A constant current source. Note: Calibration baths are generally suitable for use only in workshop. If required for use in the field, they should be used under cover and in a non hazardous environment.
PRE-CONDITIONING: Before commencing any tests check the following: 1. The instrument is as per purchaser specification.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 121 of 205
2. The instrument is not damaged in any way and any such damage is rectified before testing. 3. The instrument is mounted correctly. (Refer 6.1) 3. The shipping stop (22 - Fig. 1) is removed.
OTI CALIBRATION: Place the sensing bulb of the temperature indicator under test in the well-stirred constant temperature bath. Allow 5 minutes settling time before taking readings. Check the reading near to but not less than minimum value of the indicator scale. For increasing values of temperature, repeat the procedure to obtain at least two further readings the highest value being near to but not greater than the maximum scale value of the indicator. The readings should agree with the standard thermometer within 1.5% f.s.d. (Maximum scale value). Otherwise following adjustments should be made.
ZERO ADJUSTMENT: Use this adjustment for correcting readings near minimum scale value. Referring to Fig. 1, firmly hold the tongue adjuster (50 by a 2BA spanner and slacken the lock nut (4) with a second 2BA spanner. To move the indicting pointer (19) up or down the scale, turn the tongue adjuster (5) by a small amount anticlockwise or clockwise respectively. Retighten the lock nut holding firmly the tongue adjuster. Do not twist the measuring bellows while carrying out this adjustment as this may cause damage to the linkage/bellows.
SPAN ADJUSTMENT: Use this adjustment for correcting reading near the maximum scale value. Referring to Fig. 1, slacken the shoulder screw (7) half a turn but do not remove the same. Turn the range adjuster screw (8) anticlockwise or clockwise to increase or decrease respectively the sweep of the pointer. Make the adjustment in small increments and carefully. Half a turn in either direction may correspond to approximately 0.5 reading. After adjustment, retighten the shoulder screw.
Ensure that the lock nut (4) and shoulder screw (7) are properly tightened after the above adjustments. Repeat the tests in cold and hot bath until the accuracy limit of 1.5% f. s. d. is achieved.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 122 of 205
WTI CALIBRATION: During Calibration, keep the instrument lid fixed in position. Place the sensing bulb in the continuously stirred oil bath, the temperature of which is maintained at the specified value. Allow 5 minutes setting time and apply the specified current to the bellows heater and calibrating shunt network. The current must remain switched on at specified value for at least 40 minutes before taking reading. To achieve the readings within the accuracy limits or to reset the temperature rise to a different value, the following adjustments should be made.
GRADIENT ADJUSTMENT: After opening the instrument lid, carefully remove the dial. Withdraw the calibrating shunt (17-Fig. 1) after removing the nut and retaining washer. One adjustable centre band and two fixed bands at the ends are provided in the shunt. One supply lead is connected to the centre band and the other lead to the lower band on the shunt. Slacken the screw in the retaining clip of the centre band. To reduce the temperature rise, move the centre band nearer to the lower band, to increase the temperature rise reverse the procedure. Retighten the screw on the centre band after adjustment. Replace the shunt, dial and lid. Repeat the calibration, check after adjustments until the accuracy limits achieved. SWITCH SETTING: The switch settings are adjustable as indicated below: Indicator Scale Range Switch setting adjustable Switch differential (close to to close between open) adjustable between 0 - 120 C 20 - 120 C 30 - 120 C 0 - 150 C 0 - 240 C 40 C and 120 C 50 C and 120 C 50 C and 120 C 45 C and 150 C 80 C and 240 C 6 C and 80 C 6 C and 90 C 6 C and 100 C 7.5 C and 105 C 12 C and 160 C
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 123 of 205
NOTE: Unless specified otherwise, the instruments are supplied with minimum switch differential. Connect across the switch contacts the continuity test circuit and check the correct operation of the switches at their set points to make (close) and break (open) contacts. The switches should operate at set point within 2.5% of switch setting arm pointer (10-Fig. 1) indication, otherwise the following adjustment should be made. SWITCH ADJUSTMENTS: Referring to Fig. 1 slacken switch setting screw (11) on each switch setting arm (10). Move the left hand arm pointer over the switch scale (9) to the required temperature for making (closing) contact and right hand arm pointer to the required temperature for breaking (opening) contact. Retighten both switch setting screws. By closing the left hand arm pointer to the right hand arm pointer minimum differential is obtained. A builtin stop automatically sets the minimum differential. While slackening and tightening the setting screw, steady the disc with the other hand to prevent undue strain on the mechanism. The indicating pointer can be moved with a finger in a clockwise direction to check the operation of the switches at set points. By moving the pointer slowly and steadily, an accurate check is obtained. Never allow the pointer to spring back suddenly or quickly and also force the pointer in an anticlockwise direction. By doing so the measuring bellows is likely to be damaged. An alternative procedure is to check the switch operation while calibrating the instruments for temperature readings.
INSTALLATION
MOUNTING: Mount the instrument in a vertical position. Otherwise errors, particularly in the horizontal plane, will upset the zero setting of the mercury switches. Place a sprit level on the top of the indicator case to ensure correct positioning and operation of the mercury switches. If vibration exists at the mounting position, mount the indicator on a nonvibrating structure. Suitable anti-vibration mountings are supplied. Do not use these mountings during transport. CAPILLARY LINE: Do not stretch hard twist or bend the capillary to a radius less than 75 mm. Continuously support the capillary by suitable clips at intervals of 300 to 450 mm. Allow necessary slack at the bulb and for
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 124 of 205
mounting and removing the bulb without sharp bend at the joint. Wind in spiral (minimum dia. 150 mm) the possible excess length of capillary close to the indicator or the bulb.
7.
8.
MAINTENANCE
Normally no maintenance is required for the temperature indicator. However, adjustment or replacement of switches and resetting of the maximum pointer may become necessary.
9.
REPAIRS
If a mercury switch is damaged in anyway, it may be unclipped from the switch carrier and the leads removed with a hot soldering iron. After resoldering the leads to a new switch and locating back the switch in the clip, the switch should be re-balanced. This is done by making the switch to topple in its carrier at the instant when the mercury flows toward or away from the electrodes. By sliding the switch a little in the appropriate direction in the clip, correct topping is achieved. After correctly balancing the switch, check the operation at preset temperature. If necessary re-zero the switch scale by slackening the switch zeroing screw (12-Fig. 1) at the top of the switch scale and rotating the scale to required position. Retighten the screw after adjustment. If the bellows, bulb or capillary are damaged, repairs can be done only at the manufacturer's factory.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 125 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 126 of 205
CONTENTS
I. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. General Applications Advantages Construction Functional Test Electrical Connection Installation and Maintenance Basic Characteristics Function Operating Characteristics Relays for use in areas of Seismic Disturbances Specifications of Relays Overall Dimensional drawing Dimensions and ratings
PREFACE
The ever increasing demand for electrical energy goes together with the demand for more and more efficient and reliable "protection devices'' for power, distribution and supply facilities. In the field of power supply, transformers represent key installations that demand effective protection to ensure the constant availability of electrical energy. One of the most essential devices to protect a transformer is a Buchholz relay. For more than 20 years, Buchholz relays have been manufactured in India. They are made by an experienced staff of skilled workers, highly qualified technicians and engineers ensuring a high degree of precision and quality. A wide range of type corresponding to the BIS & International Standards are available to meet the many requirements of manufacturers and users of transformers.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 127 of 205
1.
GENERAL
Power Transformers are considered to be a highly reliable type of equipment, yet, in order to ensure the continuity of service that modern conditions demand, protective devices are required. The purpose of such devices is to disconnect faulty apparatus before large-scale damage is caused by a fault to the apparatus or to other connected apparatus. Such devices generally respond to a change in the current or pressure arising from the faults and are used for either signalling or tripping the circuits. Protective devices in the ideal case must be sensitive to all faults, simple in operation, robust for service and economically feasible. Considering liquid immersed transformers, a near-ideal 'protective device' is available in the form of Gas and Oil relay described here. The relay operates on the well-known fact that almost every type of electric fault in a `liquid immersed transformer' gives rise to gas. This gas is collected in the body of the relay and is used in some way or other to close the alarm or the tripping circuit The principle of the Gas and Oil relay was first successfully demonstrated and utilised by 'Buchholz' many years back. In a series of experiments carried out extensively in Germany it was proved that the Relay is capable of bringing to light incipient fault thereby preventing further spreading of the fault and extensive damage and thus saving expensive and protracted repairs. So successful is the principle of this Relay that despite the continued search for better protective devices in other electrical fields the Gas-and-Oil Relay is still on its own in providing protection against a variety of faults.
2.
APPLICATIONS
Double element relays can be used in detecting minor faults in a transformer. The alarm element will operate, after a specified volume of gas has collected to give an alarm indication. Examples of incipient faults are a) Broken-down core bolt insulation
b) Shorted laminations c) Bad contacts d) Overheating of part of windings. The alarm element will also operate in the event of oil leakage, or if air gets into the oil system.
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 128 of 205
The trip element will be operated by an oil surge in the event of more serious fault such as a) b) c) d) Earth faults Winding short circuits Puncture of bushings Short circuit between phases
The trip element will also be operated if a rapid loss of oil occurs. Single element relays can be used to detect either incipient or major faults in oil filled potential transformers, reactors, capacitors etc. A special single element relay is available for the protection of on load tap-change equipment.
3.
ADVANTAGES
a) b) Castings treated against porosity through a special process. Unique internal design of 'housing' prevents false air traps on top of the relay. Well-designed internal layout gives clear view of colour of gas inside the relay through glass window for fault analysis. Bucket type float design with inherent ability to withstand vacuum treatment of transformers. Built in test facility for checking continuity of both Alarm and Trip circuits. Antivibration custom-built mercury switches give high stability against mechanical shocks and vibrations. g) ISI Mark of quality on every relay
c)
d)
e)
f)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 129 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 130 of 205
4.
CONSTRUCTION
The Buchholz relay essentially consists of enclosure 1 i.e. an oil tight container and an inserted assembly 2 comprising of two pivoted elements fitted with switches (Refer fig. above). The enclosure is provided with inlet 1.1 and outlet 1.2 for the liquid. To allow connection of pipes, the enclosure openings can be designed with pipe thread or flange. The front inspection glass is provided with a graduation (100 to 300 cm) to allow readings the accumulated volume of gas and observe colour of gas for fault analysis. For checking the function of the inserted assembly a Test Key (1.3) is provided. There is also a visual indication on the scale (1.4) of service and Test/Locking position, in the form of movement of red indicator on the reading scale. This allows the testing of the alarm and Trip circuits before installation and even when the transformer is in service. Just above the inspection glass an arrow shows the specified direction of flow of the insulation liquid to the conservator. Enclosure 1 and its inserted Assembly cover are made out of Cast Iron.
5.
5.1
FUNCTIONAL TEST
Testing the relay Function with the test key. A test system is provided in the Buchholz relay that allows the functional test of the upper and lower switching system. To test the relay function loosen the nut (1.5) on the Test Key (1.3) and rotate the key with a screwdriver in the Anticlockwise direction till the SLOT on the TEST. Key points towards the T/L position. Both the alarm (upper switching system) and Trip (lower switching system) will show continuity. On bringing the SLOT on the Test Key to S (service) position by rotating the
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 131 of 205
'key' clockwise the Alarm and Trip circuits will not show continuity. The circuits will be actuated to 'ON' position only when there will be a fault in the transformer. Repeat the functional test each time a relay is started or maintenance completed. 5.2 Testing the relay Function with the Test Pump. Screw the test pump/Air bottle to the test cock. Open the test cock and pump air gently into the Buchholz relay until the upper switching system operates. For operating the lower switching system air has to be pumped suddenly with a jerk which will in turn operated the lower switching system.
6.
ELECTRICAL CONNECTION
To allow installation of the 'signal wire' open the terminal box cover comprising of the nameplate and the instruction sticker on the backside. Then pass the wire through one of the two-conduit screwings (1.6) into the terminal box. By using either one or the other openings, facility is given for the cable to enter the terminal box from the left or right. The upper two studs are terminals for the Alarm switching circuit and are denoted by A. Likewise the lower two studs are terminals or the Trip switching circuit and are denoted by T.
7.
7.1
INSTALLATION
Installation in to pipeline. For installing the relay into pipeline proceed as follows: See that the Buchholz relay is positioned with the arrow pointing towards the conservator, the connection box is in the Y plane (vertical) and to Test cock. (1.7) and air vent cock (1.8) are at the top. Mount the Buchholz relay as close as possible to the tank in the pipeline between transformer and conservator.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 132 of 205
Keep pipe bends as wide as possible between transformer and conservator. Make sure pipe ascends to the conservator at angle between three degree to seven degrees.
See that the relay enclosure is not subjected to stress. If necessary, use expansion compensators. Ensure that he slot on the Test Key remains in the T/L (Test/Locking) position during storage or loose transportation of the relay.
- Ensure that the slot on the Test Key remains in the 'S' (Service) position and the Test Key Bolt is Tightened just before commissioning of the relay. 7.2 Filling with insulation Liquid To fill the Buchholz relay, proceed as described below: 7.3 Remove the protective acorn nut (1.9) from the air vent cock. Open the air vent cock to let air escape until insulation liquid emerges. Shut the air vent cock. Check liquid level in conservator.
Maintenance The Buchholz relays are not sensitive to external influences. No servicing is needed during operation. On routine inspections of the protection equipment, test the function of the Buchholz relay as described earlier and check the alarm and trip devices connected to them.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 133 of 205
8.
Basic Characteristics
The Gas and Oil relay provide protection against a number of internal faults but it also is able to indicate in several cases the type of fault. This is possible because the gas collected in relay can, from its colour, odour and composition, indicate where the fault may be and what its nature is. By examining the gases collected it is possible to infer the nature of fault. Thus : a. If the gas is colourless and odourless or with only a faint odour of oil, the gas is air trapped in the oil or the insulation. b. If the gas is Greyish White with sharp and penetrating odour and noninflammable it is due to overheated or faulty insulation (fuller board etc.)
c. If the gas is yellowish in colour and inflammable it may be due to surface leakage on material like wood. d. lf the gas is dark Grey and inflammable it may be due to a flashover in oil or due to excessive overheating of the oil caused by a fault in the winding or the core. On the operation of the alarm if investigation of the collected gas does not indicate a serious fault it is possible to leave the transformer in service till it is convenient to carry out a through inspection. This occurrence is possible on a newly commissioned transformer due to air trapped in the oil or the insulation. On repeated and frequent alarm signals the transformer should be taken out of service for thorough check up.
9.
FUNCTION
The function of a double element relay will be described here. During normal operation of a transformer the Buchholz relay is completely filled with oil. Buoyancy and the moment due to counter weights keep the floats in their original top positions.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 134 of 205
In the event some fault in the interior of the transformer tank gas bubbles are produced and accumulate in the Buchholz relay on the way to the conservator. In consequence, the oil level in the relay enclosure drops which in turn lowers the upper bucket. This causes the mercury switch/Reed switch to operate an alarm signal. The lower bucket does not change its position, because when the gas reaches the upper inside wall of the pipe it can escape into the conservator. Hence, minor fault in the transformer tank will not trigger the lower switching assembly and will not trip the transformer. In case the liquid continues to drop due to loss of oil, the lower also goes down. In consequence lower switching system operates if the level of oil goes below the bottom level of the pipe connected to the relay. The lower bucket, does not change its position, because when the gas reaches the upper inside wall of the pipe it can escape into the conservator. Hence, minor fault in the transformer tank will not trigger the lower switching assembly and will not trip the transformer. In case the liquid continues to drop due to loss of oil, the lower also goes down. In consequence lower switching system operates if the level of oil goes below the bottom level of the pipe connected to the relay. Alternately in the event the liquid flow exceeds a specific value (which is continuously adjustable, by means of a flap) the lower bucket is forced down, thus triggering the lower switching system to operate. As the liquid flow rate decreases or the level of the liquid rises the bucket returns to its original position. The single element relay has only one operating element and it responds to either gas collection or oil surges. The method of operation is similar to that described for double element relay. Single element relays are suitable for the protection of oil filled reactors, capacitors and potential transformers. The single element oil Surge relay has been specifically designed for use with on load tap change equipment and it will bypass normal amounts of gas which are generated by tap change operations and will only respond to oil surges and loss of oil.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 135 of 205
10.
OPERATING CHARACTERISTICS
Relays of the double element type are made in three sizes. The sizes are distinguished by the numerical prefix 1, 2 or 3. This refers to the diameter of the bore of the oil pipe connecting the transformer to the conservator tank. They are referred to as Type GOR 1, GOR 2 and GOR 3, where the Alphabets indicate 'Gas and Oil Operated Relay' and the number refers to the pipe bore diameter as 25, 50 and 80 mm. respectively. The implications of the various Type Nos. and their operating conditions can be listed as follows: TYPE NO. GOR 1 GOR 2 Double element Mercury switch type Buchholz Relays Normally open type. SPECIAL OPERATING CONDITIONS.
GOR 3 SR 1 25 mm. Single element Mercury switch type Surge relay suitable for OLTC 25 mm. Single element Mercury switch type for Gas volume Alarm suitable for reactors, capacitors, potential and distribution transformers. Double element Mercury Switch type Buchholz relays. Made as per UNEL-UTE-DIN-BS standards normally open type.
SR 1/V
GOR 1E GOR 2E
The symbol /VO following their type markings indicate that the relays contain Reed switches and normally open type
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 136 of 205
The symbol /S following their type markings of all relays mentioned indicate that the relays are suitable for Silicon Oil normally used in Electro static precipitator transformers. All relays mentioned above are normally open types. Normally closed type relays can also be supplied on request.
11.
The outward appearance of these relays are exactly the same as those with mercury switches but they are distinguished from them by the symbol /VO following their type marking. The latter V (for vibration) indicates that the relay contains reed switches and the latter O that the contacts are normally open. Thus a Type GOR 2/VO signifies a 50 mm. (pipe size). Double float relay with normally open Reed Switches. OPERATION In the double element relay, collection of gas causes the oil level within the relay to fall. This in turn causes the upper element to rotate on its pivots, bringing the magnet it carries into a position where it operates the Alarm Switch. An oil surge through the relay will cause the lower element to rotate about its pivots and its magnet into a position so as to operate the tripping switch. CONNECTIONS The terminal box and the terminals are the same as that of mercury switch type relays. In the reed switch relays, each reed switch is protected by, an inductor in series. These inductors are intended to protect the reed switch contacts from the effects of capacitive loads, such as are imposed by long leads or pilot cables, and must not be removed from relays in service.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 137 of 205
Protection of reed switch contacts against the effects of inductive loads, such as those imposed by contactors and Electro-Magnetic relays, is achieved by means of a diode wired across each load. This diode must be rated with forward current at least as high as the steady load current and connected observing polarity so as to absorb the back e.m.f.. These diodes are not provided with the relay. The Mounting position and Testing on site procedure are same as that of 'Mercury Switch type' Buchholz relay. OPERATING CHARACTERISTICS All double element relays are adjusted so that their performances lie within the limits given in table 14. In addition the Reed Switch Relay is capable of withstanding shocks of up to 4g. Such shocks will not of themselves cause the relay to operate.
SWITCH DATA:
TYPE ---------------------------------------------------------- Normally Open CONTACT RATlNG ------------------------ 250VA A.C. (r.m.s.) or D.C. max. SWITCHING CURRENT --------------------------------- 5A A C or D.C. max. SWITCHING VOLTAGE --------------------------------------- 300 V D.C. max. ----------------------------- 240 Volts A.C. (r.m.s.) max. BREAKDOWN VOLTAGE --------------------------------- 650 Volts D.C. min. INITIAL CONTACT RESISTANCE ------------------------- 70 milli-ohms max. RESONANT FREQUENCY ------------------------------- greater then 700 Hz. ACTUATING TIME (Including Bounce) -------------- 2 milli-seconds (Typical) THESE SWITCHES HAVE RHODIUM CONTACT, LOCATED MIDWAY ALONG THE LENGTH OF THEIR GLASS TUBES, THE TUBES CONTAIN AN ATMOSPHERE OF NITROGEN. PROTECTION OF REED SWITCH CONTACTS:
THE EFFECTS OF CAPACTIVE LOADS SUCH AS ARE IMPOSED BY LONG LEADS, ARE SUPPRESSED BY MEANS OF SMALL INDUCTORS
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 138 of 205
MOUNTED WITHIN THE RELAY AND WIRED ONE IN SERIES WITH EACH SWITCH. THE EFFECTS OF INDUCTIVE LOADS SUCH AS ARE IMPOSED BY CONTACTORS AND E.M. RELAYS ARE SUPPRESSED BY MEANS OF A DIODE WIRED ACROSS EACH LOAD. DIODE TO BE RATED WITH FORWARD CURRENT AT LEAST AS HIGH AS STEADY LOAD CURRENT AND CONNECTED SO AS TO ABSORB BACK e.m.f.. ARRANGEMENT OF TERMINALS AND MEANS OF PROTECTION FOR REED SWITCH CONTACT.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 139 of 205
12.
SPECIFICATION OF RELAYS
Parameter Contact System Type of contact Switching voltage Switching Current Switching Capacity Frequency Limiting temp of insulation liquid Gas volume alarm Insulating liquid flow Rating Mercury switch Make Contact 220V AC/DC 5 Amp AC/2 Amp DC 1000 W/VA 50 HZ + 120 C 100 cm to 300 cm 65 cm/sec to 160 cm./sec. (depending on size) 8 KG/cm for 1 minute 400 cm/sec. 0.01 inches peak to peak at frequency of 100 cycle/sec. Continuously adjustable Optional make or break 12 V to 250V AC/DC 0.05 to 5 Amp 1 W/VA to 1000 W/VA 0 to 60 HZ 140 C for two hrs. Tolerance
Relay casing tested at Max. Permissible flow rate of insulating liquid Vibration sensitivity
Assembled relays are pressure tested with transformer oil at 3kg/cm for 60 minutes. Electrical circuits are tested at 2000 volts R.M.S. for one minute. Insulation resistance measured at 500 volts is not less than 10 Megaohms in air.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 140 of 205
IMPORTANT The various part of a relay including the body, form one complete calibrated unit and must not be inter changed with those of other relays. We strongly recommend that relay should not be taken apart, and under no circumstances should any alteration be made to the angle of the flap on the trip element. This has been correctly adjusted during manufacturing.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 141 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 142 of 205
CONTENTS
1. 2. 3. 4. 5. 6. 7. 8. 9.
Design and construction Packing and storage Unpacking and handling Checks before installation Installation Checks after installation Periodical check and maintenance Unmounting and packing Safety
These instructions are crucial for the proper handling, installation, operation & maintenance of Oil Impregnated Paper Condenser Bushings and these should be in the possession of those who are responsible for the above activities.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 143 of 205
INSTRUCTIONS FOR INSTALLATION, OPERATION AND MAINTENANCE OF OIP CONDENSER BUSHINGS 1. DESIGN AND CONSTRUCTION
The general constructional details of the bushing, intended for oil-air application are shown in Fig. 1. The active part of the bushing consists of an Oil Impregnated Paper (OIP) core (1) manufactured from superior grade Kraft insulating paper with condenser graded layers for field control, wound under tension on central tube / conductor (2). The innermost condenser layer is electrically connected to the central tube / conductor (2) and the outermost layer is electrically connected to the fixing flange (3) through a test tap (11). The core is dried under heat and vacuum and then impregnated with superior grade of insulating oil. Porcelain insulators (4&5) on the upper and lower sides of the bushing, oil resistant high quality rubber gaskets & O rings (6) are held together with the central tube by means of a set of powerful springs (7). The fixing flange (3) is provided with a test tap (11) for the measurement of Capacitance and Tan delta, air releasing screw (10) to release the air trapped in the transformer during topping up of oil or can be connected to Buchholz relay, name plate giving the product details, handle / eyebolt for lifting and space for ring type CT's on the oil end of the bushing. At the oil end, an epoxy coated stress shield or base plate (15) is provided to control the high stresses in oil inside the transformer. A detachable bottom arc shield is provided for bushing rated 245 kV and above. The intervening space between the core and the porcelain insulators is filled with specially treated mineral oil under vacuum. A Prismatic (upto 300kV) or magnetic (upto 400 kV) Oil sight glass (14) is provided on the expansion bowl (8). A top terminal (12) is provided to connect to the over head line. Arcing horns (16, 17) are provided on request. (Ref. Fig. 3). Test Tap: - (Refer Fig. 2) The test tap (11) is provided for the measurement of Capacitance, Tan delta and Insulation Resistance (IR) values of the bushing. It is connected with a copper lead to the last condenser foil of the core directly. During normal service this test tap is electrically connected to the mounting flange through test tap cover. The threaded test tap cover must be fixed properly (Fig 2a) before putting into service.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 144 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 145 of 205
2.
3.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 146 of 205
open the top cover of the wooden case and inspect the bushings thoroughly for any transit damage. Ensure all the accessories are received in good condition and report, in case found to be missing. Note: Any damage or shortages should be reported immediately. Bushing should be handled only with mechanical lifting arrangements, such as the illustrated in Fig. 5. When bushings are taken out of the packing case, they must not be allowed to rest on the lower part of the bushing. The operation is best carried out two lifting gears and two ropes as shown in Fig. 6. One rope is slung around the lower end of the metallic flange and let directly to the hook of the first crane and the other passed around the shell, between two sheds and then led to the hook of the second crane. The bushing is raised sufficiently in the same inclination angle as in the packing case with hoists and then lowered at the flange end. When positioning the bushing upright (Fig. 7), care should be taken to avoid any shocks, jerks or scratch to the oil end porcelain and bottom stress shield. On no account the bushing should be balanced on rope, passed around the porcelain at its centre of gravity.
4.
i)
ii)
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 147 of 205
iv)
Measure and record the IR values of the bushing with a 2.5 kV meggar. The recommended values are:
4000 Meg ohms (Min) between oil end terminal or top and test tap.
1500 Meg ohms (Min) between test tap and flange with 1 kV meggar. The IR values may vary due to the atmospheric condition (humidity), surface cleanliness of the porcelains, dryness of test tap etc. In such cases, preheating of porcelains, terminals test tap etc., with hot air is recommended. This is only an indicative test, however, the healthiness of the bushings can be known only after measurement of Tan delta & capacitance values. v) Capacitance and Tan delta values of the bushing should be measured between the top terminal and test tap at 2 kV to 10 kV (Maximum). The measurement should be preferably carried out indoors with RH not exceeding 60% and at ambient temperature, with the facilities and procedure as described as described below:
Necessary screened connecting leads. Place the bushing vertically on suitable stand. Remove the threaded test tap cover. Insert a plug / clip into the central stud of the test tap and connect to the Schering Bridge through a screened cable. The flange body should be grounded. Connect the high voltage supply to the top terminal. Measure the capacitance & tan delta value of bushing upto a maximum of 10 kV. Note:
The voltage applied on the bushing should be limited to 10 kV, when the bottom end is not immersed in oil. Utmost care should be taken to avoid any contact with the bushing during testing as this may result in fatal injury to the personnel. The test tap should be dry, free from any moisture condensation and dirt deposition. The threaded test tap cover should be fixed back to the test tap, immediately after the test.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 148 of 205
Factory test values of tan delta and capacitance are indicated in the test report of individual bushing at working voltages. However, site values may vary, as they do not resemble factory test conditions. The site values recorded at the time of commissioning should be taken as the reference values for comparison with future measurements. The bushing can be commissioned, if tan delta value measured is less than or equal to 0.007, and capacitance value as per the factory test value with maximum variation of 10%. If higher values are obtained, please contact ALSTOM, Customer Service Department giving full details of testing arrangement, for further advice. Note: The bushing should be kept vertical or mounted on transformer for a minimum period of 24 hours before application of voltage.
5.
INSTALLATION:
Please refer to Fig. 8 The bushing is suitable for installation for a maximum angle of 30 degrees from vertical. During the lowering of the bushing into the transformer, extreme care should be taken to prevent the lower porcelain hitting the wall of the tank. The bushing should be so mounted on the transformer that the oil sight glass is visible from the ground level. Ensure the visibility of the oil level to the naked eye. Maximum stress experienced by the bushing is at the bottom stress shield during testing. Hence sufficient care should be taken to avoid any flashover from the stress shield to the wall of the turret. The flashover voltage depends on the clearance maintained in oil between the stress shield and turret, oil quality, surface smoothness, presence of barriers,
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 149 of 205
shape of the stress shield and turret etc. The recommended size of the turret to be maintained for various voltage class of bushings is given in the manufacturers booklet / respective drawings. BUSHING WITH DRAW LEAD CONNECTION: Please refer to Fig. 9. Each bushing is supplied with a top terminal (12), cable bolt (9), cable bolt pin and a gasket placed separately in the packing case. Drill a hole of suitable diameter based on the size of the flexible transformer cable at the bottom end of the cable bolt and braze the cable into it. Insert an M8 bolt at the upper end of the cable bolt and tie a wire or a fish cord on to it. Clean the gasket seating surface on top face of the transformer and place the gasket in position. Lift the bushing above the transformer turret and clean the bottom end of the bushing. Lower the bushing slowly into the transformer, simultaneously pull the transformer cable brazed with cable bolt through the central tube with the help of the fish cord. Secure the cable bolt to the central tube with the cable bolt pin. Remove the fish cord. Bolt the bushing into position taking care to correctly position the gasket joint. Ensure the threads on the terminal and the cable bolt are clean. Tighten the terminal to the cable bolt ensuring full thread engagement for proper current transfer. Sometimes the cable bolt is supplied along with the brazed flexible lead upto the flange seat with a half connector at bottom end. In such cases the flexible lead from the transformer winding should be brazed to the other half connector and should be fastened with the draw lead connector of the bushing using bolts and nuts.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 150 of 205
BUSHING WITH DRAW-ROD CONNECTIONS: Please refer to Fig. 10 Bushings of higher current ratings are provided with draw rod type arrangement with a half overlap bolted joint at the flange seat. Remove the draw rod through the bushing tube or take it out from the packing case. Clean the outer surface and braze the transformer cable to the lower half connector. Clamp the upper and lower half connectors together with bolts and nuts. Follow the installation instructions as described for draw lead type of bushing. BUSHING WITH SOLID STEM: Refer to Fig.11 In solid stem type of bushings, the central conductor forms the current carrying part. Mount the bushing on the turret and connections should be made to the top and bottom terminals individually. The transformer cable termination should be connected to the bottom terminal with bolts & nuts, through the viewing port of the transformer. The top terminal should be fixed directly to the central conductor.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 151 of 205
6.
The threaded test tap cover should be fixed back to the test tap immediately after the test. The bushing should be kept vertical mounted on the transformer for a minimum of 24 hours before energisation.
CAUTION: THE TEST TAP WILL ALWAYS BE EARTHED AS LONG AS THE THREADED CAP IS FIXED (Fig. 2a). HENCE THE CAP SHOULD NEVER BE KEPT OPEN.
7.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 152 of 205
8.
9.
SAFETY:
Understanding the procedures and instructions are a must while handling bushings. Also, all applicable safety procedures such as regional or local safety rules and regulations must be followed. Safe working practices and good judgement are essential by the personnel while installing, testing, maintaining or disposing the bushings. CAUTION: FAILURE TO FOLLOW THE INSTRUCTIONS MIGHT RESULT IN FATAL INJURY TO PERSONNEL OR DAMAGES TO PROPERTY INCLUDING TRANSFORMER AND ITS ALLIED EQUIPMENT.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 153 of 205
SILICAGEL BREATHER
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 154 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 155 of 205
TYPE 1
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 156 of 205
SILICAGEL BREATHER
TYPE 2
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 157 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 158 of 205
SIDE VIEW
FRONT VIEW
MATL.
Brass Cast Al. Cast Al. Cast Al. Glass Brass
Sr. No.
7. 8. 9. 10. 11. 12.
DESCRIPTION
Bolts 'B'-6 Nos.- M6 Base with Mtg. Holes Limit stoppers Gear with lever Float Arm 9.5 p tube Check Nut
MATL.
M.S. Cast. Al. Brass Brass Brass Brass
Fig. 1
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 159 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 160 of 205
CALIBRATION
The standard calibration of dial is Empty, 1/4, 1/2, 3/4, Full. Calibration of marks Empty & Full is done after leaving 65 mm from bottom and top of conservator to avoid striking of float to conservator wall. Different calibrations are done to suit customer's needs.
MOUNTING
In fig. 2, indicator is shown mounted by keeping dial and mounting pad in vertical position. However, indicator can be mounted in titled position towards ground (max 30 ) for easy viewing by fixing mounting pad at desired angle. The position of indicator on the conservator can be selected to suit site condition. Float mechanism passes through the hole in pad (see Fig. 2).
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 161 of 205
SPECIFICATIONS
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. Operating Liquid Working Temperature Working Pressure Environment Size Weight Mounting Specifications Float Travel Electrical witch Contact Rating Switch Setting : : : : : : : : : : : Transformer Oil to IS: 335 0 to 100 C of Oil 0 to 4 kg/cm For Indoor & Outdoor use See Fig. 2 & 3 6.6 Kg. with Float & Float-arm See Fig. 2 & 3 Float moves in right angle plane to seating face (See Fig.2) One SPST Mercury Switch 5 Amps 240 V.AC. 50 Hz. 1.2 Amps 240 V.DC. Normally Open Closes when oil level drops to Empty level. Switch opens automatically when oil level rises. 12. 13. 14. Dial Size Dial Position Conservator dia : : : 250 mm dia. Vertical or Inclined Available for use in range of 600 to 1500 mm dia.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 162 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 163 of 205
GLOSSARY OF TERMS
PRV : Pressure Relief Valve Tank : Tank in which transformer winding & oil etc. are housed. Figures : Figures in brackets in write-up refer to part list of Drg. CD-601-R-3
1.
APPLICATION:
This PRV is designed to be used on Power Transformer. When pressure in the tank rises above predetermined safe limit this valve operates and performs following functions. G Allows the pressure to drop by instantaneously opening a port of about 150 mm diameter. G Gives visual indication of valve operation by rising a flag. G Operates a micro switch. This switch has 1 NO and 1 NC contacts (Four terminals). Hence switch can be effectively used in control circuit.
2. 3. 4.
SPECIFlCATIONS:
See Drg. No. CS-601-R-3.
TESTS:
Tests are carried out as per test certificate attached to this leaflet.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 164 of 205
The diaphragm restores its position as soon as pressure in the tank drops below set limit. The lift of the diaphragm is utilised to operate flag ( 10) and micro switch ( 11) with the help of rod (8). The flag and switch remain operated until they are reset manually.
5.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 165 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 166 of 205
6.
7.
INSTALLATION
Each valve should be cleaned from inside (tank side) with compressed air jet. All particles should be removed from tank side. While cleaning, care should be taken that the jet does not attack the switch and the flag mechanism. The PRV should be installed considering the following aspects. The indicating flag (10) is easily seen from distance, The valve is accessible for manual resetting and for routine manual checking. While installing remove dirt and clean the mounting surface, remove all traces of oil, grease. The rubber gasket supplied with the valve should be properly cleaned & be located properly in the recess carefully. All the bolts should be tightened evenly so that equal pressure is exerted on gasket and base. Connect control circuits to terminal plate provided in the switch box through cable gland (14). As per wiring diagram (ref. fig. 1 drg. CS-601-R-3), check the operation of flag and switch by lifting operating rod (8) and confirm that both controls operate as required. The PRV can be put to service.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 167 of 205
8.
9.
GENERAL NOTES:
Store the valve on its base duly packed in polythene bag to ensure that dirt or other solid particles do not enter the valve port from tank side. Do not remove the protection cover on flag box and switch box when it is stored. Keep the flat gasket (2) duly tied to the valve. Remove it only when it is to be installed. This gasket should be kept dry. After installation of valve on transformer, test periodically the functioning of switch operation and flag operation by lifting the operating rod manually. This will ensure the switch operation and flag operation when valve opens due to rise in pressure inside the tank. It is not possible to change the operating pressure at site. The valve gaskets are of entirely different nature for synthetic liquid and transformer oil. Hence use proper valve for liquid as described on product label.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 168 of 205
EXHAUST FAN
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 169 of 205
COOLING FANS
GENERAL
Exhaust type cooling fans used on transformers are designed to operate outdoors in all weather conditions. Generally the following sizes of fans are used.
MOTORS
The fans are powered by totally enclosed, squirrel cage induction motors. The motors are adequately rated to give reliable service for many years.
IMPELLER
The impeller is designed to give maximum volume at minimum noise level with minimum power consumption. For reducing vibrations, special shoes made of rubber are provided at fixing points of fan lugs.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 170 of 205
MOUNTING
1. The arm is secured by the resilient mounting caps, which are placed over the rubber sockets and secured to the diaphragm with 8 screws, nuts and washers provided. The lock washers should be fitted under the heads of the screws. Rubber sockets fitted to arms. To be fitted so that flat side will come in contact with the diaphragm. Arms to be secured to motor by the 4 screws in motor carton. NOTE: Lock washers are supplied and should be fitted. 4. Setscrew in blade should engage in dimple nearest the end of the shaft. After blade is fitted, see that split pin 5 is replaced in end of shaft.
2. 3.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 171 of 205
CONSTRUCTIONAL DETAILS
No. 1 2 3 4 5 6 7 8 9 10 11 12 13
PART NAME TERMINAL BLOCK BALL BEARING STATOR WINDING EARTH SCREW ROTOR STAMPING STATOR STAMPING RESILIENT CAP RUBBER SLEEVE BACK COVER FIXING SCREW BACK COVER FAN FIXING BOLT WING CH. HD. SCREW
No. 14 15 16 17 18 19 20 21 22 23 24 25
PART NAME WING FIXING BOLT SPLIT PIN SHAFT HUB FIXING BOLT HUB BALL BEARING LUBRICATOR SCREW MOUNTING ARM MOTOR FIXING BOLT DIE CAST AL. ROTOR CH. HD. SCREW DIAPHRAGM
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 172 of 205
FLOW INDICATORS
FLOW INDICATORS
Filename TM1902_2012 Rev no. 05 Date 19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 173 of 205
FUNCTION
Flow indicators included in this catalogue are mainly designed as a safety device looking to the need of an electrical signal on failure of forced circulation of liquid in pipeline. They perform following functions: 1. 2. Indicate the rate of full flow in proper direction in specified pipe. Operate one or two mercury switches when rate of flow drops near to 70% of specified full flow. These switches can be used to initiate precautionary systems or safety devices.
APPLICATION
Consider the case of furnace transformer in which one Flow Indicator can be mounted on suitable member of oil circulating pipe and one on water circulating pipe of heat exchanger. The pointer of respective Flow Indictor will indicate whether desired rate of flow is maintained or not and switch will operate if the flow drops near to 70% to initiate precautionary system. For similar purpose it can be used on liquid circulating pipes in chemical processes, heavy-duty bearings, compressors, etc.
MOUNTING
To introduce these Flow Indicators in a pipe line a `T-Mounting is necessary. In this catalogue we have tabulated dimensions of 'T-Mounting' for range of size from 40 mm (1.5") to 250 mm (10") N.B. Pipes. But customer can always specify if his requirement is different than the tables on page 8.
pointer and a cam. The pointer is set to read the specified rate of full flow and the cam is set to operate one or two mercury switches when flow drops near to 70%.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 174 of 205
A return spring is used which acts in the opposite direction of flow. Hence any steady position of pointer is the result of equilibrium of force due to impinging liquid on vane, spring tension & weight of vane. The pointer does not remain steady for unsteady flows. The size and shape of vane and tension on return spring is adjusted to suit specified full flow. The vane occupies very small area out of full cross section of pipe at NO-FLOW position. At full flow it becomes almost parallel to flow. Hence there is practically no head-loss across Flow Indicator.
DIAL MARKING
The spread of flow indicating portion of dial is only about 70 . Hence it is not possible to print more markings. Usually PUMP ON-PUMP OFF or FULL FLOW-NO FLOW type of limit markings is printed. Intermediate markings such as ALARM. TRIP is also printed if required. Besides, specifications such as value of full flow, liquid, pipe size and direction of flow are also printed. The background of dial is white. Direction indicating arrow is in red colour and all other markings in black colour.
SWITCHES
One or two mercury switches of SPST type are provided. The contact position can be set to No or NC at full flow. If required, switch can be changed from NO to NC or vice versa at site. In case of single switch, it is set to operate near 70% when flow is falling. In case of two switches, both are mounted on same plate. Hence both operate at same rate of flow. But in order to satisfy design requirements, one switch can be set to operate near 80% and the other near 70% or one near 70% and the other near 60%. It is not possible to set a switch to operate at lower value than 60%. Even when both switches are set to operate at lower value than 60%. Even when both switches are set to operate at same rate of flow, some switching differentiate is observed due to use of mercury as switching element, We can modify setting suitably if switching requirements are clearly specified.
WIRING
Leads from mercury switch/switches are brought into a terminal box positioned at the bottom of indicator. A two-way or four-way terminal strip is provided. Terminals are accessible for wiring after removing cover. A hole with conduit threads is provided for fixing cable gland to box. Terminals are marked. Wiring should be done as per respective wiring diagrams.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 175 of 205
SETTING
Full Flow- Each indicator is set in water-flowing condition. Pipe size, pipe position, direction of flow is maintained. By adjusting a valve in pipeline, the specified rate of full flow is established, then the pointer is set to read the full flow mark. This method of setting gives very accurate results as it is based on equilibrium of vane at full flow. In case of liquids other than water, proportional rate of flow of water is maintained for setting. Switch - After setting of pointer at full flow, switches are set in the sequence ordered by customer. Flow is reduced to check operation of switch & increased to check automatic resetting. The rate of flow at which switching occurs is approximate. The switch position is kept adjustable to compensate difference in pipe gradient at site.
TESTING
Static Pressure: At 7 kg/cm. Flow: Indicator is mounted on pipe. Water is allowed to flow in specified direction. Rate of flow is checked when pointer reads full flow. For Liquids other than water proportional rate of flow of water is checked. Switch: Switch operation is checked by reducing and increasing flow in pipeline. Contact rating: Switches are tested in laboratory at 5A.24OV.AC Dielectric strength: Live terminals are checked at 2 kV with body. A test Certificate is provided with each instrument.
DESIGN FEATURES
1. 2. 3. 4. 5. 6. Switch contacts are not affected by dust, humidity or corrosive atmosphere. Switches can be serviced without need of stopping flow. Causes negligible head-loss. Low maintenance cost. Robust construction & trouble free service. Does not get damaged due to excess flow or reverse flow.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 176 of 205
Fig. 1
1 2 3 4 5 6 7 8 9 10 -
SCHEMATIC
Item Description
Pointer & Dial Mercury Switch Switch Operating Cam Return Spring Vane Shaft Vane Main Pipe Driving Magnet Non-magnetic Wall Follower Magnet
Fig. 2
1 2 3 4 5 -
WORKING POSITIONS
Item Description
Main Pipe T - Mounting Connecting Flanges Flow Indicator Flange of indicator
NOTES: I. Flow indicators are not interchangeable for different liquids, pipe dia., direction of flow or rate of full flow. Hence they should be ordered separately. The rate of full flow is not adjustable. The switch operation point is not adjustable.
2. 3.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 177 of 205
Fig. 4
Hardware for indicator
(Supplied at extra cost) M 12 x 65 Bolts, Nuts - Nos. Washer & Suitable gasket.
Accessories
(Supplied at extra cost if agreed) T-Mounting, Weldable connection, Flanges, hardware.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 178 of 205
Material of Construction
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 179 of 205
Fig. 5
Details of vane orientation common to Series 4021 & 4022
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 180 of 205
Accessories
(Supplied at extra cost if agreed) T-Mounting, Weldable connection, flanges, hardware.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 181 of 205
Fig. 8
Wiring Diagram
For Series 4031
Fig. 9
Hardware for indicator
(Supplied at extra cost) M 12 x 65 Bolts, Nuts - Nos. Washer & Suitable gasket.
Accessories
(Supplied at extra cost if agreed) T-Mounting, Weldable connection, flanges, hardware.
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 182 of 205
mercury switches are provided. Proportionately, number of terminals, size of switchbox and size of terminal box differ, After suitable series is selected, requirement should be specified as per 'How to Order' column on Page 3 of this catalogue. Because each indicator is set to suit requirement specified by customer. Common specifications of Series 4031 & 4032 working: Principal of working, switch operation and other details as explained on page 2 & 3 of this catalogue.
Material of Construction
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 183 of 205
Fig. 10
Details of vane orientation common to Series 4031 & 4032
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no:
(Actual Supply may not be exactly same)
PTRM1104
Fig. 11
Wiring Diagram
For Series 4032
Accessories
(Supplied at extra cost if agreed) T-Mounting, Weldable connection, flanges, hardware.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 185 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 186 of 205
3. 4. 5.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: 6. 7. PTRM1104 Page 187 of 205
Ensure that the electrical supply available is suitable for data given on the pump rating plate. Care should be taken that the valves are in the 'open' position, when the pump set is operated, because the pump works correctly only when all valves are fully opened. The oil filled pump will produce Pressure even with the valves closed, but there is no circulation, there will be oil churning inside the pump set and the pump motor might also get overheated.
INSTALLATION Before mounting on pipeline check the following: 1. 2. 3. Remove the terminal box cover (8), and check the insulation resistance of the set with a meggar to ensure minimum resistance of 10 meg-ohms. Remove end covers and check for free rotation of the rotor. Ensure that Impeller (5) and locking screw (19) with washer are in their proper position. Connect the supply terminals and ensure rotation of impeller as per 'Arrow Mark' on the Impeller Housing i.e. anti-clockwise rotation when looking through the impeller housing opening.
NOTE: In case of wrong direction of rotation of impeller, there will be no discharge. OPERATION After installation on the pipe circuit, start filling the system with clean transformer oil until it completely fills the pump unit, Release all air by the air vent plug initial continuous air free oil seeps out. It is important that no air is trapped in the pump. It is always a good practice to allow the pump to run for about 30 minutes before energising the transformer, to ensure that any air not removed by venting has been pumped out. MAINTENANCE Check periodically the behaviour regarding leakage, vibration, noise, and current/power consumption of the pump set. In case the pump is to be removed, allow the unit to cool and drain the oil completely from the set and replace the end covers. Store as prior installation. Dismantling of Pump and Motor may be carried out as detailed on Page 201. TROUBLE SHOOTING Trouble 1) Reduced or No delivery : Checks a) Casing Suction Pipe not filled with liquid b) Discharge head too high. c) Wrong direction of rotation. d) Air not vented out.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 188 of 205
: : :
a) Wrong direction of rotation. b) No oil in the pump. a) Shaft bent. b) No free movement of rotating element. a) Hydraulic Noise: Cavitation, wrong direction of rotation b) Mechanical Noise : Bearing worn-out. a) Supply failure. b) Defective Phase. c) Loose Contacts. d) Rotor Mechanically locked.
DISMANTLING OF PUMP AND MOTOR Please refer Exploded view: 1. Remove Allen Cap Head Screw (19) and Washer (12). 2. Remove Impeller (5) by gently wrenching outwards with preferably a screw driver. 3. Remove Key (20) 4. Remove End shield fixing screws (21). 5. Lightly tap end shield (2) & (5) with a wooden/nylon mallet until it dismantles from bearing housing. 6. Remove Pre-loading washer (18). 7. Remove shaft with rotor (4). 8. Remove bearings (11) using a bearing puller. 9. In case required, the terminal arrangement, oil flow indicator (7) and plugs (13) may be dismantled in the same order as shown. For re-assembly follow reverse procedure.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 189 of 205
No.
1 2 3 4 5 6 7 8 9 10 11
DESCRIPTION
STATOR CASE WITH WINDING ENDSHIELD (ODE) ENDSHIELD (DE) SHAFT WITH ROTOR I MPELLER TERMINAL BOX OIL FLOW INDICATOR TERMINAL COVER TERMINAL BOARD SQUARE RING BALL BEARING SKF 6306
QTY. No.
1 1 1 1 1 1 1 1 1 1 1 12 13 14 15 16 17 18 19 20 21 22
DESCRIPTION
IMPELLER WASHER AIR VENT PLUG & DRAIN PLUG AIR VENT & DRAIN PLUG WASHE TERMINAL BOX GASKET TERMINAL COVER GASKET OIL FLOW INDICATOR WASHER PRE LOADING WASHER HEX SOCKET HEAD CAP SCREW PARALLEL KEY (OER) ENDSHIELD FIXING SCREW PLAIN WASHER
QTY. No.
1 2 2 2 1 1 1 1 1 16 32 23 24 25 26 27 28 29 30 31
DESCRIPTION
LOCK WASHER ENDSHIELD FIXING NUT TERMINAL BOARD FIXING SCREW TERMINAL BOX FIXING SCREW TERMINAL COVER FIXING SCREW PLAIN WASHER NUT FOR TERMINAL STUD LOCK WASHER PLAIN WASHER
QTY.
16 16 4 4 4 4 6 6 12
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 190 of 205
CONSTRUCTIONAL FEATURES
TYPE OF PUMP
P
285
D
150
Wt. kg.
IL - 5A
IL - 3A
345 200
25
20
502
425
380
305
240
210
270
240
295
240
23
23
65.0
41.0
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 191 of 205
SPECIFICATIONS
MOTOR STATOR ROTOR BEARING COOLING PERFORMANCE : : : : : : 4.3 HP and 7.5 HP 3 Phase, 50 Hz, Induction Type Squirrel Cage Type Ball Type, Lubricated by transformer oil itself. By circulating transformer oil itself. To IS: 325-1996; 3 Phase Induction Motor
PUMPS
CASING IMPELLER SEALING RINGS FRAME : Cast Iron : Cast Aluminium/Bronzed keyed to the shaft : Neoprene rubber : Cast Iron totally enclosed integral part of the pump
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 192 of 205
PARTICULARS OF DUTY AND DIMENSIONS 4.3 HP DISCHARGE TOTAL HEAD PIPE SIZE Inlet/Outlet (l.p.m.) (m) (mm) : : : 1190 11.00 100/100 7.5 HP 1880 11.00 150/150
Overall D HB
460 220 125 290 195 360 71 525 227 152 360 210 410 91
Fig.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 193 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 194 of 205
FLEXIBLE SEPARATOR
1. INTRODUCTION
Flexible separator (Air Cell) is provided inside the conservator of power transformers for avoiding direct contact of air with the transformer oil. Air Cell provides a permanent, flexible and non porous barrier between the atmosphere and the transformer oil without affecting the operational function of the system. The basic construction of the separator is a highly resistant fabric coated externally to resist transformer oil and internally to Ozone and weather resistant. Flexible separators offer the following advantages :-
Protection against water vapour and gases. Suppression of any gas bubble formation in oil. Compensation of large volume changes. 2. DESCRIPTION
Flexible separator is fitted inside a cylindrical conservator. Oil being outside, the separator is in direct contact with atmosphere. This type of mounting makes it possible to compensate for the oil volume displacements due to temperature variations.
3.
CHARACTERISTICS OF MATERIAL
Flexible separators are made from coated fabric consisting of :
Mass
Textile reinforcement i.e. highly resistant polyamide fabric. External coating chemically resistant to transformer oils Inner coating resistant to Ozone and all weather conditions. 1400 140 g/m Poly acrylonitrile butadiene Polyamide > 300 daN / 5 cm.
Major characteristics of materials are listed below: Coating Textile reinforcement Breaking Strength before immersion in oil
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 195 of 205
4.
INSTALLATION PROCEDURE
1 Connection to the inside of Air Cell 2 Connection to the inside of Conservator 3 Magnetic Oil Level Gauge
Fig. 1
Fig. 2
Fig. 3
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 196 of 205
5.
FILLING PROCEDURE WITHOUT VACUUM IN CONSERVATOR The conservator with Air Cell is pressure tested and despatched from the
Fix three numbers air release valves on the conservator. inflate the air cell at an air pressure indicated on the INSTRUCTION PLATE affixed on the transformer and hold air pressure.
Keep air release valves open. Fix air filling adapter on breather pipe and
DO NOT APPLY EXCESS AIR PRESSURE AS IT MAY DAMAGE THE AIR CELL. Open air release valves and start oil filling from the bottom of the
conservator.
Observe the air release valves and as soon as oil starts overflowing, close
the air release valves one by one. Stop oil filling when all air release valves are closed.
Remove the air filling adapter. Continue oil filling and observe the Magnetic Oil Level Gauge (MOLG) Stop the filling when the needle of MOLG shows the level corresponding to
the ambient temperature at the time of filling.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 197 of 205
CAUTION: Do not open any of the air release valves after completion of oil filling. If air release valve is opened, air will enter and oil level will drop. The plain oil level gauge on the end cover of the conservator should indicate full oil level always. If air enters the conservator, it can be seen by a fall in the oil level in plain oil level gauge. The plain oil level gauge should be monitored on regular basis.
Proceed as follows:
Create a vacuum in separator. With the same source of vacuum, create a vacuum in the conservator. Open the oil filling valve of the transformer. Because of the vacuum in the conservator, the oil level rises automatically. Stop the oil filling once the required volume in the conservator is attained. While maintaining the conservator under vacuum, allow Dry Air or Nitrogen gas to enter into the internal part of the separator. Then, the separator inflates by itself, and takes all the free space due to the fact that the conservator was not completely full. In particular, during the operation, the oil is going to rise to the top of the conservator. Inflate the separator at a maximum as shown in the INSTRUCTION PLATE. Check on the vent-holes, and confirm that there is no more air in the conservator or, if necessary, adjust the level.
The above mentioned CAUTION regarding the opening of air release valve after completion of oil filling, remains valid for this case also.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 198 of 205
THERMOSIPHON FILTER
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 199 of 205
POWER TRANSFORMERS
1. INTRODUCTION
Thermosiphon filter is provided on large capacity, oil filled Power Transformers for keeping the moisture level of insulating oil at a very low level. At the time of initial erection and commissioning of transformer, most of the moisture present in the oil is removed by hot oil circulation. The moisture absorption of oil is eliminated by directing the air breathed in by the transformer during its operation through silica gel desiccant. Air cell in conservator avoids direct contact of oil with air and thereby eliminating the chance of moisture absorption. However, it is a well known fact that water is released to the oil from the paper insulation due to ageing process. Thermosiphon filter helps in removing this moisture from oil. When the transformer is on load, the thermosiphonic action of liquid causes circulation of oil through the filter. The adsorbent filled in the Thermosiphon filter adsorbs moisture and keeps the oil dry.
2.
CONSTRUCTION
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 200 of 205
Typical arrangement of the Thermosiphon filter is as shown in the figure. Thermosiphon filters are provided with isolating valves at top and bottom to enable its removal for maintenance purposes.
3.
MAINTENANCE
Thermosiphon filters do not require any routine maintenance. Oil samples shall be tested periodically and the values of resistivity and tan delta shall be compared with the values given in the Operation & Maintenance Manual. If the results are within the limits, reactivation of the adsorbent needs to be done only as part of the annual maintenance. If there is a rapid deterioration in the values, reactivation of the adsorbent should be done immediately.
4.
MONITORING
The periodicity of oil testing and acceptance criteria is explained in the Instruction Manual of the Transformer. However, the same is reproduced here for your ready reference. a) b) c) Periodicity of measurement(Resistivity & Tandelta) : Quarterly Resistivity at 90OC : 0.1x 1012 cm Tandelta at 90OC :1% (Ref. IS - 1866: 2000)
5.
REGENERATION OF ADSORBANT
Regeneration of adsorbent can be done by circulation of hot gas at a temperature of 180 to 250O C. To confirm proper regeneration, the dew point of the purged gas may be measured and it should be less than 70O C. For regeneration of adsorbent, dry nitrogen gas is preferred. A continuous stream of gas is to be maintained during heating and gas pressure is not important.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 201 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 202 of 205
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 203 of 205
OPERATION AND MAINTENANCE INSTRUCTIONS FOR OIL TO WATER HEAT EXCHANGERS (SHELL & TUBE TYPE) 1. INTRODUCTION:
In transformer oil cooler, the hot oil from the transformer is passed through the shell, which comes in contact with the external surface of the tubes, which is constantly cooled by the incoming cooling water flowing inside the tubes. Heat transfer takes place due to temperature difference between the oil and cooling water flowing through tubes resulting in cooling of the oil.
2.
DESCRIPTION:
The transformer oil cooler is a shell and tube type oil cooler. It is also known as lantern ring type oil cooler. The hot oil passes through the shell, and cooling water passes through tubes, tubes are secured to the tube sheet by expansion. Baffle plates have been provided to support the tube. The baffles are held in position by tie rod and spacers. Baffles have thermal significance in that the shell side fluid is made to flow to and fro across the bundle from one end of the exchanger to the other end. The flow induced vibration is avoided by proper spacing of the baffles. Separation of shell and tube side fluids at the floating head is obtained by means of packing rings (o rings) installed between outside of the floating tube sheet and recesses in the rear head flanges. The shell and tube fluids have their own packing rings (o rings), which are separated, by a lantern ring provided with weep holes for leak detection. Leakage at the packing will not cause mixing of the shell side and tube side fluids within the exchanger itself. Channel side has been provided with pass partition arrangement so as to have the flow of cooling water inside the tubes in each section. The inside surface of channel except tube sheet have been coated with epoxy paint to prevent corrosion of carbon steel material. Zinc anodes are provided to reduce the galvanic corrosion.
3.
HYDRO TESTING:
The equipment shall be subjected to hot oil test on shell side and hydro test on tube side to a pressure of 1 times of the design pressure to check for leaks. Before conducting hydraulic test for new unit or one that has been out of service for sometime or for unit that has been opened, carry out a thorough internal and external inspection to ensure: All foreign materials have been removed Pressure gauges have been correctly calibrated Vent on high point of unit (air vent) if installed is left open
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 204 of 205
4.
OPERATING INSTRUCTIONS:
Inspect the transformer oil cooler and ensure that the external surfaces and channels are free of dirt and ensure the readiness of cooling water supply on the tube side.
5.
START UP PROCEDURE:
The start up of the oil cooler in a system consists of putting into service various equipment in a definite logical operating sequence. Open the vent and drain valve on the channel side of the oil cooler. Establish cooling water flow through channel and tubes When water flows through the vent and drain close the same. Open the oil side vent & drain and adopt the same procedure as that of tube side Temperature of oil shall be raised gradually with specified flow rate.
6.
7.
8.
CLEANING METHODS:
The bundle assembly is taken out and the internal and external surface of the tubes are cleaned by smooth wire mesh or cleaning agent. After cleaning, the bundle is inserted and the gasket and o ring are replaced with new ones and the equipment is tested hydraulically before setting the unit under operation.
9.
PRESERVATION
When the transformer oil cooler is out of service, preservation by
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.
ERECTION, COMMISSIONING, OPERATION AND MAINTENANCE MANUAL FOR TRANSFORMER & REACTOR Document no: PTRM1104 Page 205 of 205
proper methods is essential to prevent corrosion. It is recommended that during short duration of operational interruptions as a preventive measure against stand still corrosion, a continuous flow of cooling water through tubes is to be maintained. If this is not possible then it is necessary to clean the tubes to remove dirt, impurities etc. And fill with suitable clean water to retain in same condition. In case of longer shut down, the shell side of the oil cooler is to be drained and rinsed with oil. Dry all internal surfaces of oil cooler by using hot air. Blank all open nozzles to avoid ingress of dust. Clean the tube side to remove dirt, impurities etc., and fill with suitable clean water and retain in that condition.
9.1
preservative air should be less than 20% with reference to 20 C. The effectiveness of the measure taken is to be checked at regular intervals.
P.S.: The above instructions are applicable for single tube Heat Exchangers.
Filename
TM1902_2012
Rev no.
05
Date
19/02/2012
ALSTOM Confidential Information. Must not be disclosed, copied or used for Manufacturing, Tendering or for any other purpose without prior written permission.