Anda di halaman 1dari 4

Product Brief 2010

Energy Varistors SIOV-E


for the Protection of Power Distribution Systems
SIOV metal oxide varistors in the E series are designed to be used as active elements in gapless surge arresters for protection of medium and high voltage AC power utility distribution systems against overvoltages. Glass collar passivation makes this series suitable for a broad range of arrester designs such as porcelain housed arresters, or polymer housed arresters with a hollow insulator as well as for molded polymer arresters. The broad range of diameters supports the different class requirements according IEC and ANSI. Construction Glass passivated collar Flame-sprayed termination for pressure contact Features Disk diameter of 32 to 99 mm Disk height up to 44 mm Stackable for higher voltage ratings Based on IEC 60099-4 and ANSI/IEEE C62.11 Arrester blocks for distribution class Arrester blocks for station class

www.epcos.com

Energy Varistors SIOV-E: Distribution Class

Technical data

Distribution Class

Type Ordering code Dimensions Diameter Height Arresters classification Suggested usage in gapless arrester constructions based on IEC 60099-4 Line discharge class Suggested usage in gapless arrester constructions based on IEC 60099-4 Characteristics Suggested rated voltage (max.) Continuous operating voltage (max.) Reference current Reference voltage (min.) Residual voltage at In Ur Uc Iref Uref Ures h

E32VR302 B72232 E0302R026

E32VR602 B72232 E0602R026

E41NR302E B72241 E0302R026

E41NR502E B72241 E0502R026

E42VR302 B72242 E0302R018

E42VR402 B72242 E0402R018

34 1 19.75 0.6

34 1 39.5 0.6

41.9 0.7 19.5 0.6

41.9 0.7 29.4 0.6

43 1 19.75 0.6

43 1 26.3 0.6

mm mm

10

10

10

10

kA

3 2.45 1 3.15 7.85 ... 8.55 5 65 150 0.18 100 32

6 4.9 1 6.3 15.75 ... 17.05 5 65 150 0.35 200 32

3 2.45 2 2.75 7.35 ... 8.25 10 100 400 0.27 150 32

5 4.1 2 4.6 12.25 ... 13.75 10 100 400 0.45 225 32

3 2.45 2 3 7.85 ... 9.05 10 100 250 0.25 160 32

4 3.25 2 4 10.55 ... 12.15 10 100 250 0.33 210 32

kV kV mA kV kV kA kA A W g pcs.

Nominal discharge current In (8/20 s) High current impulse (4/10 s)1 Long duration current impulse (2 ms) Max. resistive power Pc dissipation at Uc Approx. weight/pcs. Packing unit
1

Secondary insulation required for E32/E41 types

Marking
Collar Metallization EPCOS Type Ures classification
Explanation example for type E42VR302 Pc Resistive power dissipation at maximum continous operating voltage and 25 C in 10-2 W e.g. P 09 = Pc = 9 10-2 W = 0.09 W Ures (In) Measured residual voltage at nominal discharge current In = 10 kA in kV e.g. 7.91 = 7.91 kV Ures (In) Residual voltage is classified in classification 100 V steps and identified by a letter e.g. A

Pc 25 C

Ures Lot number

For further information please contact your EPCOS sales office.

EPCOS AG 2010

Energy Varistors SIOV-E: Station Class

Technical data

Dimensions Diameter Height Arresters classification Suggested usage in gapless arrester constructions based on IEC 60099-4 Line discharge class Suggested usage in gapless arrester constructions based on IEC 60099-4 Characteristics Suggested rated voltage (max.) Continuous operating voltage (max.) Reference current Reference voltage (min.) Residual voltage at In Ur Uc Iref Uref Ures 0.385 x Ures Ures / 3.2 2 0.385 x Ures 10.65 ... 12.55 10 100 680 0.26 310 18 0.385 x Ures Ures/ 3.2 2 0.385 x Ures 12.65 ... 14.25 10 100 680 0.3 350 18 0.415 x Ures Ures/ 3.0 3 0.415 x Ures 12.15 ... 13.75 10 100 1000 0.4 550 16 kV kV mA kV kV kA kA A W g pcs. 2 2 3 10 10 10 kA h 48 1 30.5 0.6 48 1 35.4 0.6 59.7 1 35.4 0.6 mm mm

Nominal discharge current In (8/20 s) High current impulse (4/10 s) Long duration current impulse (2 ms) Max. resistive power Pc dissipation at Uc Approx. weight/pcs. Packing unit

Marking
Collar Metallization EPCOS Type Ures classification
Explanation example for type E58NR133E Pc Resistive power dissipation at maximum continous operating voltage and 25 C in 10-2 W e.g. P 09 = Pc = 9 10-2 W = 0.09 W Ures (In) Measured residual voltage at nominal discharge current In = 10 kA in kV e.g. 12.19 = 12.19 kV Ures (In) Residual voltage is classified in classification 100 V steps and identified by a letter e.g. A

Pc 25 C

Ures Lot number

EPCOS AG 2010

For further information please contact your EPCOS sales office.

Station Class

Type Ordering code

E48NR113E B72248 E0113S072

E48NR133E B72248 E0133S072

E58NR133E B72258 E0133S072

Energy Varistors SIOV-E: Station Class

Technical data

Station Class

Type Ordering code Dimensions Diameter Height Arresters classification Suggested usage in gapless arrester constructions based on IEC 60099-4 Line discharge class Suggested usage in gapless arrester constructions based on IEC 60099-4 Characteristics Suggested rated voltage (max.) Ur Continuous operating Uc voltage (max.) Reference current Iref Reference voltage (min.) Uref Measured residual Ures (10 kA) voltage Residual voltage at In Ures Nominal discharge current In (8/20 s) High current impulse (4/10 s) Long duration current impulse (2 ms) Max. resistive power Pc dissipation at Uc Approx. weight/pcs. Packing unit h

E70NR133E B72270 E0133S072

E78SR392E B72278 E0392S003

E78SR123E B72278 E0123S003

E99SR113E B72299 E0113S003

70 1 35.4 0.6

78 1 14.5 0.6

78 1 44 0.6

98.8 1.2 44 0.6

mm mm

20

20

20

kA

0.425 x Ures (10 kA) Ures (10 kA)/2.9 5 Ures (10 kA)/2.9 11.85 13.45 12.65 ... 14.55 20 100 1500 0.5 760 5

0.423 x Ures (10 kA) Ures (10 kA)/2.9 5 0.423 x Ures (10 kA) 3.55 4.15 3.83 ... 4.52 20 100 1500 0.35 390 15

0.431 x Ures (10 kA) Ures (10 kA)/2.9 5 0.431 x Ures (10 kA) 10.65 12.35 11.50 ... 13.45 20 100 1500 0.95 1180 5

0.444 x Ures (10 kA) Ures (10 kA)/2.9 5 0.444 x Ures (10 kA) 10.35 12.05 11.10 ... 13.00 20 100 2100 1.5 1890 4

kV kV mA kV kV kV kA kA A W g pcs.

Marking
Collar Metallization EPCOS Type Ures classification

Pc 25 C

Ures Lot number

Explanation example for type E99SR113E Pc Resistive power dissipation at maximum continous operating voltage and 25 C in 10-2 W, e.g. P 89 = Pc = 89 10-2 W = 0.89 W Ures (10 kA) Measured residual voltage at discharge current I = 10 kA in kV, e.g. 10.64 = 10.64 kV Ures (10 kA) Residual voltage is classified in 100 V steps and identified classification by a letter, e.g. C

Important information: Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical requirements that are often placed on our products. We expressly point out that these statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. It is incumbent on the customer to check and decide whether a product is suitable for use in a particular application. This publication is only a brief product survey which may be changed from time to time. Our products are described in detail in our data sheets. The Important notes (www.epcos.com/ImportantNotes) and the product-specific Cautions and warnings must be observed. All relevant information is available through our sales offices.

EPCOS AG 2010 Corporate Center Edition 08/2010 Ordering No. EPC : 62008-7600 Printed in Germany PB 0810.5