SECTION 15441 CHILLED WATER PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. B. Drawings and general provisions of Contract, including Special Conditions and Division-1 Specification Sections, apply to work of this Section. The requirements specified in this section apply to all related sections in this Division. The requirements of all related sections, elsewhere in this division also apply to this section unless specified to the contrary.

1.2

DESCRIPTION OF WORK A. The work includes the providing of all labor, supervision, materials, equipment, accessories, services and tests necessary to complete, make ready and set to work for acceptance by the Owner, all centrifugal pumps in accordance with Drawings and Specifications.

1.3

QUALITY ASSURANCE A. Manufacturers: Firms regularly engaged in manufacture of centrifugal pumps of the types and materials, sizes and capacities required, whose products have been in satisfactory use in similar service for not less than 5 years as approved by the Engineer. Standards Compliance: Comply with requirements of applicable local codes and the standards outlined in section 15020. 1. Single Source Responsibility: manufacturer. Obtain all centrifugal pumps from a single

B.

1.4

SUBMITTALS A. Product Data: Submit manufacturer's product data, including printed technical literature, installation instructions and catalog cuts for each type of centrifugal pump furnished. Certified hydrostatic test and performance curves of each pump model indicating operating point.

B.

C. Shop drawings showing layout and connections as well as accessories.

Cleopatra Plaza Tower (Nasr City) Specifications

15441/1

Rev.0 March.2012

Crown Home Consultants

PART 2 - PRODUCTS 2.1 GENERAL A. Provide constant and variable speed motors, as noted in the schedule on the drawings, with motor sizes, in all cases, selected to be non-overloading over the entire performance range of the pump. The pump's brake horsepower at design speed may not, under any condition, exceed the nominal motor horsepower. Select the pumps to operate at or near their point of peak efficiency, thus allowing for operation at capacities of approximately 25% beyond design capacity. In addition, select the design impeller diameter so that the design capacity of each pump will not exceed 90% of the capacity obtainable with maximum impeller diameter at the design speed. The pump curve must be continuously rising from maximum capacity to the shut-off point. Hydrostatically test all pump casings at 1-1/2 times the design working pressure. Factory test all pumps at their rated speed, head, capacity, efficiency and brake horsepower, and at such conditions of head and capacity to properly establish the performance curve. Submit certified copies of the test report.

B.

C. D.

2.2

AXIALLY SPLIT CASE PUMPS A. Mounting feet cast integrally with the lower half casing single or multi-stage, centrifugal pump with motor, volute type, double suction, fully bronze fitted, with an impeller mounted between grease lubricated out-board bearings and with a flexible coupling connecting the motor and pump shafts. Casing construction: cast iron for working pressures to 1200 kPa flanged piping connections and replaceable bronze wearing rings. Impeller: statically and dynamically balanced, enclosed, double inlet, fabricated from cast bronze with wearing rings. Impeller removable without disturbing pipe connections or motor. Key impeller to shaft and fix in an axial position. Pump shaft bearings: heavy duty, grease lubricated ball bearings contained in a moisture and dust proof housing. Pump shaft: 416 stainless steel. Seals: mechanical seals type. Install an abrasive separator, in the seal piping with a sight type flow indicator, piped in accordance with the manufacturer's instructions.

B. C.

D. E. F. G. H. 2.3

Base plate: Channel steel with drip rim, sufficiently rigid to support the pump and driver. I. All pumps are vertical arrangement in line with the pipes . END SUCTION, FLEXIBLE COUPLED PUMPS
15441/2 Rev.0 March.2012

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

A. Base mounted single stage, centrifugal pump with motor, volute type, end suction, fully bronze fitted, horizontally split case design with an impeller mounted between grease lubricated out-board bearings and with a flexible coupling connecting the motor and pump shafts. B. Casing construction: cast iron for working pressures to 1,200 KPa with ANSI B16.1, flanged piping connections and replaceable bronze wearing rings. C. Impeller: statically and dynamically balanced, closed, single inlet, fabricated from cast bronze. Impeller removable without disturbing pipe connections or motor. D. Pump shaft bearings: heavy duty grease lubricated ball bearings contained in a moisture and dust proof housing. E. Pump shaft: 416 stainless steel, include 420 stainless steel shaft sleeve (minimum 500 Brinell hardness) with stuffing box. F. Seals: mechanical seals for closed systems and stuffing boxes with seal cage for open systems (condenser water) within allowable suction pressure limits. G. 2.4 Install a polyurethane abrasive separator, in the seal piping with a sight type flow indicator, piped in accordance with the manufacturer's instructions.

END SUCTION, CLOSE COUPLED PUMPS A. Base mounted single stage, centrifugal pump with motor, volute type, end suction, fully bronze fitted, vertically split case design, grease lubricated close coupled motor and pump shafts. Temperature and pressure rating: 121C continuous water temperature and 1,200 KPa working pressure. B. Casing construction: cast iron for working pressures to 1,200 psig with 861 KPa flanged piping connections and replaceable bronze wearing rings. C. Impeller: statically and dynamically balanced, closed, single inlet, fabricated from cast bronze. Impeller removable without disturbing pipe connections. D. Pump shaft: S.A.E. 1045 carbon steel, with renewable bronze sleeve. E. Seals: mechanical seals. F. Motor Bearings: Grease-lubricated ball bearings.

2.5

IN-LINE CIRCULATORS

Cleopatra Plaza Tower (Nasr City) Specifications

15441/3

Rev.0 March.2012

Crown Home Consultants

A. Single stage, centrifugal pump with motor, volute type, single suction in-line, fully bronze fitted, radially split case design, oil lubricated bearings with a flexible coupling connecting the motor and pump shafts. B. Casing construction: cast iron with companion flanged piping connections. C. Impeller: statically and dynamically balanced, closed, fabricated from cast bronze. Impeller removable without disturbing pipe connections. D. Pump shaft bearings: oil lubricated sleeve bearings. E. Pump shaft: ground and polished steel, with bronze sleeve. F. Seals: mechanical seals. 2.6 MAINTENANCE MATERIAL A. Furnish spare parts for each pump as follows: Set of two mechanical seals/pumps Set of two bearings/pumps Set of casing gaskets/pumps (number as required) PART 3 - EXECUTION 3.1 INSPECTION A. Examine area and condition under which centrifugal pumps are to be installed. Notify the Engineer in writing of conditions detrimental to proper completion of the work. Do not proceed with the work until unsatisfactory conditions have been corrected.

3.2

INSTALLATION A. Furnish and install centrifugal pumps of the types, sizes, capacities, and arrangements indicated on the drawings and specified herein. B. Assemble flexibly coupled pumps with their motor drivers on heavy duty fabricated structural steel baseplates, which include sheet metal coupling guards and drain troughs with tapped drain connection piped to waste. Coordinate drain piping routing and requirements with other trades. C. Install base-mounted pumps on concrete foundations. For flexibly coupled pumps, support the pump base plate on tapered steel wedges to provide a gap of 20mm to 40mm under baseplate for non-shrink grout. Adjust the wedges until the shafts of the pump and motor are level. Grout the base to the concrete foundation with non-shrink grouts tighten the foundation bolts and after the grout has set, align the pump and motor shafts. After alignment is correct, fill the base plate completely with nonshrink grout, and pitch to drain. After the grout has cured, fully tighten the foundation bolts. D. The pumps are to be aligned in the field utilizing a dial indicator. Alignment accuracy must be plus or minus .05mm or the more stringent requirements of the manufacturer.

Cleopatra Plaza Tower (Nasr City) Specifications

15441/4

Rev.0 March.2012

Crown Home Consultants

E. Install air vent cocks at the high point of the pump casings, extended outside of any insulation and valved drains at the low points of the casing. Include integral pressure gauge tappings on the suction and discharge of the pumps.

END OF SECTION 15441