Anda di halaman 1dari 13

Crown Home Consultants

SECTION 15160 STORM DRAINAGE PIPING PART 1 1.1 GENERAL

SUMMARY A. Section includes pipe, pipe fittings, connections and equipment for storm water piping systems. This Section also includes roof and floor-drains, cleanouts, interceptors, catch basins and sump pumps. Related Sections: 1. Building Services Piping: (Optional short phrase). 2. Concrete Forms and Accessories: Execution requirements for placement of inserts and sleeves specified by this section. 3. Cast-in-Place Concrete: Execution requirements for placement of concrete specified by this section. 4. Paints and Coatings: Execution requirements for painting material specified by this section. 5. Mechanical Identification: Product requirements for pipe identification for placement by this section. 6. Wiring Devices: Execution requirements for electric connections to equipment specified by this section. 7. Motors: Product requirements for motors for placement by this section.

B.

1.2

REFERENCES A. B. C. D. E. F. G. H. STM A74 - Cast Iron Soil Pipe and Fittings. ASME B16.23 (American Society of Mechanical Engineers) - Cast Copper Alloy Solder Joint Drainage Fittings DWV ASME B16.29 (American Society of Mechanical Engineers) - Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings - DWV. ASME B31.9 (American Society of Mechanical Engineers) - Building Services Piping. ASTM B32 - Solder Metal. ASTM B306 - Copper Drainage Tube (DWV). ASTM C14 - Concrete Sewer, Storm Drain, and Culvert Pipe (ASTM C14M Concrete Sewer, Storm Drain, and Culvert Pipe). ASTM C425 - Compression Joints for Vitrified Clay Pipe and Fittings.
15160/1
Rev.0 March.2012

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

I.

ASTM C443 - Joints for Circular Concrete Sewer and Culvert Pipe, Using Rubber Gaskets (ASTM C443M - Joints for Circular Concrete Sewer and Culvert Pipe, Using Rubber Gaskets) ASTM C564 - Rubber Gaskets for Cast Iron Soil Pipe and Fittings. ASTM C700 - Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated. ASTM D2235 - Solvent Cement for Acrylonitrile - Butadiene - Styrene (ABS) Plastic Pipe and Fittings. ASTM D2665 - Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings ASTM D2751 - Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings ASTM D2855 - Making Solvent-Cemented Joints with Poly (Vinyl Chloride) (PVC) Pipe and Fittings. ASTM D3034 - Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings. ASTM F477 - Elastomeric Seals (Gaskets) for Joining Plastic Pipe. CISPI 301 - (Cast Iron Soil Pipe Institute) Cast Iron Soil Pipe and Fittings for Hub less Cast Iron Sanitary Systems. ASTM F708 - Design and Installation of Rigid Pipe Hangers. ASME A112.21.1 (American Society of Mechanical Engineers) - Floor Drains. ASME A112.21.2 (American Society of Mechanical Engineers) - Roof Drains. Pipe Hangers and Supports - Fabrication and Installation Practices. ASTM C478/C478M Pre-cast Reinforced Concrete Sections UL 1479 (Underwriters Laboratories, Inc.) - Fire Tests of Through-Penetration Fire stops.

J. K. L. M. N. O. P. Q. R. S. T. U. V. W. 1.3

SUBMITTALS A. B. C. Submittal Procedures: Submittal procedures. Shop Drawings: Indicate dimensions, weights, and placement of openings and holes for sump-pumps, catch basins and manholes. Product Data: Submit data on pipe materials, fittings, and accessories. Submit manufacturers catalog information. Submit component sizes, rough-in requirements, service sizes, and finishes. Submit pump type, capacity, and certified pump curves showing pump performance characteristics with pump and system
15160/2
Rev.0 March.2012

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

operating point plotted. Include NPSH curve when applicable. Include electrical characteristics and connection requirements. D. E. 1.4 Manufacturer's Installation Instructions: Submit installation instructions for material and equipment. Manufacturer's Certificate: Certify products meet or exceed specified requirements.

CLOSEOUT SUBMITTALS A. B. C. Execution Requirements: Closeout procedures. Project Record Documents: Record actual locations of equipment and clean-outs. Operation and Maintenance Data: Submit spare parts lists, exploded assembly views for pumps and equipment.

1.5

QUALIFICATIONS A. Manufacturer: Company specializing in manufacturing products specified in this section with minimum three years experience, and with sump pump service facilities within 100 miles of Project. Installer: Company specializing in performing Work of this section with minimum three years experience

B. 1.6

PRE-INSTALLATION MEETING A. B. Administrative Requirements: Pre installation meeting. Convene minimum one week prior to commencing Work of this section.

1.7

DELIVERY, STORAGE, AND HANDLING A. B. Product Requirements: Product storage and handling requirements. Protect piping systems from entry of foreign materials by temporary covers, completing sections of the work, and isolating parts of completed system.

1.8

ENVIRONMENTAL REQUIREMENTS A. B. Product Requirements. Do not install underground piping when bedding is wet or frozen.

1.9

FIELD MEASUREMENTS A. Verify field measurements prior to fabrication.


15160/3
Rev.0 March.2012

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

1.10

WARRANTY A. B. Execution Requirements: Product warranties and product bonds. Furnish five year manufacturer warranty for storm drainage piping.

1.11

EXTRA MATERIALS A. B. Execution Requirements: Spare parts and maintenance products. Furnish two sets of pump seals PRODUCTS

PART 2
2.1

STORM WATER PIPING, BURIED BEYOND 5 FEET OF BUILDING A. Cast Iron Pipe: ASTM A74 extra heavy service weight. 1. Fittings: Cast iron. 2. Joints: ASTM C564, neoprene gasket system or lead and oakum. Copper Tube: ASTM B306 DWV. 1. Fittings: ASME B16.23, cast bronze, or ASME B16.29 wrought copper. 2. Joints: ASTM B32, solder, Grade 50B. Concrete Pipe: ASTM C14 (ASTM C14M). 1. Fittings: Concrete. 2. Joints: ASTM C443 (ASTM C443M), rubber gaskets. PVC Pipe: STM D3034 SDR 35. 1. Fittings: PVC. 2. Joints: ASTM F477, elastomeric gaskets. PVC Pipe: ASTM D2665 or ASTM D3034. 1. Fittings: PVC. 2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

B.

C.

D.

E.

2.2

STORM WATER PIPING, BURIED WITHIN 5 FEET OF BUILDING A. Cast Iron Pipe: ASTM A74 service weight. 1. Fittings: Cast iron. 2. Joints: ASTM C564, neoprene gasket system or lead and oakum. Cast Iron Pipe: CISPI 301, hub less, service weight. 1. Fittings: Cast iron. 2. Joints: Neoprene gaskets and stainless steel clamp-and-shield assemblies. Copper Tube: ASTM B306, DWV.
15160/4
Rev.0 March.2012

B.

C.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

1. 2.
D.

Fittings: ASME B16.23, cast bronze, or ASME B16.29 wrought copper. Joints: ASTM B32, solder, Grade 50B.

Concrete Pipe: ASTM C14(ASTM C14M). 1. Fittings: Concrete. 2. Joints: ASTM C443(ASTM C443M), rubber gaskets. ABS Pipe: ASTM D2680 or ASTM D2751. 1. Fittings: ABS. 2. Joints: ASTM D2235, solvent weld. PVC Pipe: ASTM D2665 or ASTM D3034. 1. Fittings: PVC. 2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement. PVC Pipe: ASTM D2665, ASTM D3034, or ASTM F679. 1. Fittings: PVC. 2. Joints: ASTM F477, elastomeric gaskets.

E.

F.

G.

2.3

STORM WATER PIPING, ABOVE GRADE A. Cast Iron Pipe: ASTM A74 extra heavy weight. 1. Fittings: Cast iron. 2. Joints: ASTM C564, neoprene gasket system or lead and oakum. Cast Iron Pipe: CISPI 301, hub less, service weight. 1. Fittings: Cast iron. 2. Joints: Neoprene gaskets and stainless steel clamp-and-shield assemblies. Copper Tube: ASTM B306, DWV. 1. Fittings: ASME B16.23, cast bronze, or ASME B16.29 wrought copper. 2. Joints: ASTM B32, solder, Grade 50B. Aluminum DWV Pipe: CAN-3 B281. 1. Fittings: Cast iron. 2. Joints: ASTM C564, thermoplastic rubber coupling and stainless steel clamps. ABS Pipe: ASTM D2680 or ASTM D2751. 1. Fittings: ABS. 2. Joints: ASTM D2235, solvent weld. PVC Pipe: ASTM D2665 or ASTM D3034. 1. Fittings: PVC. 2. Joints: ASTM D2855, solvent weld with ASTM D2564 solvent cement.

B.

C.

D.

E.

F.

Cleopatra Plaza Tower (Nasr City) Specifications

15160/5

Rev.0 March.2012

Crown Home Consultants

2.4

PIPE HANGERS AND SUPPORTS A.


B. C.

Drain, Waste, and Vent: Conform to ASME B31.9, ASTM F708, MSS SP58, MSS SP69 and MSS SP89. Hangers for Pipe Sizes 1/2 to 1-1/2 inch malleable iron or Carbon steel, adjustable swivel, split ring. Hangers for Pipe Sizes 2 inches and Over: Carbon steel, adjustable, clevis. Multiple or Trapeze Hangers: Steel channels with welded spacers and hanger rods. Wall Support for Pipe Sizes to 3 inches Cast iron hook. Wall Support for Pipe Sizes over 3 inches welded steel bracket and wrought steel clamp. Vertical Support: Steel riser clamp. Floor Support: Cast iron adjustable pipe saddle, lock nut, nipple, floor flange, and concrete pier or steel support. Copper Pipe Support: Carbon-steel, copper-plated adjustable ring.

D.
E. F.

G. H. I. 2.5

FIRE STOP SYSTEMS A. General Purpose Fire Stopping Sealant: Water based non-slumping, premixed sealant with in tumescent properties, rated for 3 hours in accordance with ASTM E814 and UL 1479. General Purpose Vibration Resistant Fire Stopping Sealant: Silicone based, nonslumping, premixed sealant with in tumescent properties, vibration and moisture resistant, rated for 3 hours in accordance with ASTM E814 and UL 1479. DWV Plastic Pipe Systems Fire Stopping Sealant: Silicone based, premixed sealant with in tumescent properties, vibration and moisture resistant, and rated for 3 hours in accordance with ASTM E814 and UL 1479 with metal collars.

B.

C.

2.6

EXTERIOR FLOOR DRAINS A. Manufacturers: 1. Jason 2. Terain Or approved equal Floor Drain (FD-1): ANSI A112.21.1; galvanized cast iron two piece body with double drainage flange, weep holes, reversible clamping collar, and round, adjustable nickel-bronze strainer.
15160/6
Rev.0 March.2012

B.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

C.

Floor Drain (FD-6): Lacquered or Galvanized cast iron two piece body with drainage flange, heavy duty grate 6 inches wide, 12 inches long, dome strainer, end plates with gaskets.

2.7

EXTERIOR PLANTER DRAINS A. B. C. ANSI A112.21.2; galvanized cast iron body with sump. Strainer: Removable [polyethylene ,cast metal ,cast aluminum ,cast bronze ,cast iron dome with stainless steel or bronze screen. Accessories: Membrane flange and membrane clamp with integral gravel stops.

2.8

CLEANOUTS A. B. C. Exterior Surfaced Areas (CO-1): Round or Square cast nickel bronze access frame and non-skid cover. Exterior Unsurfaced Areas (CO-2): Line type with lacquered cast iron body and round epoxy coated cover with gasket. Interior Finished Floor Areas (CO-3): Galvanized cast iron body with anchor flange, [reversible clamping collar, threaded top assembly, and round scored cover with gasket in service areas and round or square depressed cover with gasket to accept floor finish in finished floor areas. Interior Finished Wall Areas (CO-4): Line type with lacquered cast iron body and round epoxy coated cover with gasket, and round stainless steel access cover secured with machine screw. Interior Unfinished Accessible Areas (CO-5): Caulked or threaded type. Provide bolted stack cleanouts on vertical rainwater leaders.

D.

E. 2.9

SUMPS A. Manufacturers: 1. Terain 2. Jason Or approved equal Sump: Precast concrete specified in Section 03400 Precast concrete Epoxy coated fabricated steel, Glass fiber reinforced encased with 8 inches concrete with required openings and drainage fittings.

B.

2.10

SEDIMENT INTERCEPTORS A. Manufacturers: 1. Terain


15160/7
Rev.0 March.2012

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

2. B. 2.11

Jason Approved or equal

Sediment Interceptor: Epoxy coated cast iron ,Stainless steel ,Precast concrete body and secured cover with removable stainless steel sediment bucket.

CATCH BASINS A. Manufacturers: 1. Jason 2. Terain Approved or equal Barrel: ASTM C478(ASTM C478M); precast concrete sections laid on cast-inplace reinforced concrete foundation pad, 36 inches or 48 inches diameter with precast concrete top.

B.

2.12

MANHOLES
A.

Formed Bottom Manholes: ASTM C478 (ASTM C478M); concrete masonry units or reinforced precast concrete sections lay on cast-in-place reinforced concrete foundation pad as specified in Section 03300. 1. Size: diameter. 2. Cover: Standard cast iron with minimum sized pick hole, and frame. Use heavy-duty cover and frame in vehicular traffic areas. 3. Steps: 3/4 inch diameter galvanized steel or aluminum on 16 inch centers.

2.13

SUMP PUMPS A. Manufacturers: 1. Jason 2. Flycot Approved or equal Pump Type: Vertical centrifugal, direct connected, duplex arrangement. Casing: Cast iron volute with radial clearance around impeller, inlet strainer, slide away couplings. Impeller: Cast iron; bronze; open non-clog, closed, keyed to corrosion resistant alloy steel, stainless steel shaft. Support: Cast iron pedestal motor support on steel floor plate with gas tight gaskets. Bearings: Forced grease, Oil lubricated bronze sleeve spaced maximum 48 inches and grease lubricated ball thrust at floor plate.
15160/8
Rev.0 March.2012

B. C. D. E.
F.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

G. H. I.

Drive: Flexible coupling to vertical, solid shaft ball bearing electric motor. Sump: Steel cover plate [with steel curb frame for grouting into concrete sump on steel sump basin with inspection opening and cover, and alarm fittings. Controls (Simplex): Float switch with float rod , stops, and corrosion resistant float, and separate pressure switch high level alarm with transformer, alarm bell and stand-pipe. Controls (Duplex): Float operated mechanical alternator with float rod, stops, and corrosion resistant float to alternate operation of pumps. Cut-in second pump on rising level or lead pump failure. Furnish separate pressure switch high level alarm with transformer, alarm bell, and stand pipe ,and extra set of wired terminals for remote alarm circuit] [and emergency float switch with float rod, stops, and corrosion resistant float to operate both pumps on failure of alternator.

J.

2.14

SUBMERSIBLE SUMP PUMPS A. Manufacturers: 1. Flycot 2. Jason Approved or equal Pump Type: Completely submersible, vertical, centrifugal. Casing: Cast iron , Bronze pump body and oil filled motor chamber. Impeller: Cast iron ,Bronze; closed, stainless steel or corrosion resistant alloy steel shaft. Bearings: Ball bearings. Sump: Fiberglass basin with steel cover plate Accessories: Oil resistant cord and plug with three-prong connector for connection to electric wiring system including grounding connector. Servicing: Slide-away coupling consisting of discharge elbow secure to sump floor, movable bracket, guide pipe system, lifting chain and chain hooks. Controls: Integral diaphragm, mercury switch type level controls with separate, liquid-level, and control high level alarm. Controls: Motor control panel containing across-the-line electric motor starters with ambient compensated quick trip overloads in each phase with manual trip button and reset button, circuit breaker, control transformer, electro-mechanical alternator, hand-off-automatic selector switches, pilot lights, high water alarm pilot light, reset button and alarm horn. Furnish mercury switch liquid level controls,
15160/9
Rev.0 March.2012

B. C. D. E. F. G. H. I. J.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

steel shell switch encased in polyurethane foam with cast iron weight for pump on (each pump), pump off (common), and alarm. PART 3 3.1 EXECUTION

EXAMINATION A. B. Administrative Requirements: Coordination and project conditions. Verify excavations are to required grade, dry, and not over-excavated.

3.2

PREPARATION A. B. C. Ream pipe and tube ends. Remove burrs. Bevel plain end ferrous pipe. Remove scale and dirt, on inside and outside, before assembly. Prepare piping connections to equipment with flanges or unions.

3.3

INSTALLATION A. Extend cleanouts to finished floor or wall surface. Lubricate threaded cleanout plugs with mixture of graphite and linseed oil. Provide clearance at cleanout for snaking drainage system. Encase exterior cleanouts in concrete flush with grade. Install floor cleanouts at elevation to accommodate finished floor. Install non-conducting dielectric connections wherever jointing dissimilar metals. Route piping in orderly manner and maintain gradient. Route parallel and perpendicular to walls. Install piping to maintain headroom. Group piping to conserve space. Group piping whenever practical at common elevations. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment. Provide clearance in hangers and from structure and other equipment for installation of insulation and access to valves and fittings. Provide access where valves and fittings are not exposed. Coordinate size and location of access doors with Section 08310.

B. C. D. E. F. G. H. I. J.

Cleopatra Plaza Tower (Nasr City) Specifications

15160/10

Rev.0 March.2012

Crown Home Consultants

K.

Establish elevations of buried piping outside building to provide not less than ft of cover. Install piping penetrating roofed areas to maintain integrity of roof assembly. Where pipe support members are welded to structural building framing, scrape, brush clean, and apply one coat of zinc rich primer to welding. Prepare exposed, unfinished pipe, fittings, supports, and accessories ready for finish painting. Refer to Section 09910. Excavate and backfill in accordance with Section 02315. Install bell and spigot pipe with bell end upstream. Sleeve pipes passing through partitions, walls and floors. Inserts: 1. Provide inserts for placement in concrete forms. 2. Provide inserts for suspending hangers from reinforced concrete slabs and sides of reinforced concrete beams. 3. Provide hooked rod to concrete reinforcement section for inserts carrying pipe over 4 inches 4. Where concrete slabs form finished ceiling, locate inserts flush with slab surface. 5. Where inserts are omitted, drill through concrete slab from below and provide through-bolt with recessed square steel plate and nut above flush with top of slab. Pipe Hangers and Supports: 1. Install in accordance with ASME B31.9 ,ASTM F708 and MSS SP89. 2. Support horizontal piping as scheduled. 3. Install hangers to provide minimum 1/2 inch space between finished covering and adjacent work. 4. Place hangers within 12 inches of each horizontal elbow. 5. Use hangers with 1-1/2 inch minimum vertical adjustment. Design hangers for pipe movement without disengagement of supported pipe. 6. Support vertical piping at every floor. Support riser piping independently of connected horizontal piping. 7. Where installing several pipes in parallel and at same elevation, provide multiple pipe hangers or trapeze hangers. 8. Provide copper plated hangers and supports for copper piping, sheet lead packing between hanger and support and piping. 9. Prime coat exposed steel hangers and supports. Hangers and supports located in crawl spaces, pipe shafts, and suspended ceiling spaces are not considered exposed.
15160/11
Rev.0 March.2012

L. M. N. O. P. Q. R.

S.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

10. 11. T. Pumps:


1.

Provide hangers adjacent to motor driven equipment with vibration isolation; refer to Section Support cast iron drainage piping at every joint. Provide shaft length allowing sump pumps to be located minimum 24 inches below lowest invert into sump pit and minimum 6 inches clearance from bottom of sump pit. Provide air cock and drain connection on horizontal pump casings. Provide line sized isolating valve and strainer on suction and line sized soft seated check valve and balancing valve on discharge. Decrease from line size with long radius reducing elbows or reducers. Support piping adjacent to pump independently of pump casings. Install supports under elbows on pump suction and discharge line sizes 4 inches and over. Provide pumps operating at specified system fluid temperatures without vapor binding and cavitations, non-overloading, in parallel or individual operation, and operating within 25 percent of midpoint of published maximum efficiency curve. Align and verify alignment of base mounted pumps prior to start-up.

2. 3.

4.

5.

6. 3.4

ERECTION TOLERANCES A. B. Quality Requirements: Tolerances. Establish invert elevations, slopes for drainage to inch per foot minimum. Maintain gradients.

3.5

SCHEDULES

METAL-PIPE HANGER SPACING:


A.

Pipe size: 1/2 to 1-1/4 inches 1. Maximum hanger spacing: 6.5 ft 2. Hanger rod diameter: 3/8 inches Pipe size: 1-1/2 to 2 inches 1. Maximum hanger spacing: 10 ft 2. Hanger rod diameter: 3/8 inch Pipe size: 2-1/2 to 3 inches 1. Maximum hanger spacing: 10 ft
15160/12
Rev.0 March.2012

B.

C.

Cleopatra Plaza Tower (Nasr City) Specifications

Crown Home Consultants

2. D.

Hanger rod diameter: 1/2 inch

Pipe size: 4 to 6 inches 1. Maximum hanger spacing: 10 ft 2. Hanger rod diameter: 5/8 inch Pipe size: 8 to 12 inches 1. Maximum hanger spacing: 14 ft 2. Hanger rod diameter: 7/8 inch Pipe size: 14 inches and Over 1. Maximum hanger spacing: 20 ft 2. Hanger rod diameter: 1 inch PLASTIC-PIPE HANGER SPACING: 1. 2. All Sizes: Maximum hanger spacing: 6 ft Hanger rod diameter: 38/inch END OF SECTION 15160

E.

F.

Cleopatra Plaza Tower (Nasr City) Specifications