ISA 20.50 Rev.1 PROJECT UNIT P.O. ITEM CONTRACT MFR SERIAL Fluid Flow rate Inlet Pressure Outlet Pressure Inlet Temperature Inlet Density
Viscosity/ Spec Heats Ratio
of 78-TV-801
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
SPECIAL / ACCESSORIES
CONDENSATE Units kg/h bara bara 0 C kg/m3 cP bara bara Max Flow 2400.00 3.50 1.00 138.70 927.29 0.20 3.484 221.1 6.22 FLASH % dBA Norm Flow Min Flow 2126.00 350.00 4.00 4.50 1.00 1.00 87.00 84.00 967.45 0.33 0.63 221.1 1.51 CAVIT 75/ 969.43 0.34 0.56 221.1 0.23 CAVIT 75/ 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 *Type *Mfr & Model *Size On/Off
Spring Action Open/Close PNEUMATIC (Spring & Diaphragm)
Shut-Off
SERVICE CONDITIONS
Required Cv
75/
In Pipe Line Size & Schedule Out Pipe Line Insulation *Type *Size *Max Press / Temp *Mfr. & Model *Body/Bonnet Matl *Liner material/ID *End Connection In *End Connection Out *Flg Face Finish *End Ext/Matl *Flow Direction *Type of Bonnet *Lub & Iso Valve *Packing Material *Packing Type 1
2" #150 RF 2" #150 RF 30mm Rock Wool 100 Globe ANSI Class 150 0 5 barg / 260 C FISHER 1" GX +ACT. CS 1.0619 / A216 Gr. WCC 1" #150 RF 1" #150 RF RF Up BOLTED/ EXTENSION TYPE Lub
FISHER GX integrated GX/225 CLOSE 6barg 4barg 4 barg 2-6 barg NAMUR NO FAIL OPEN
ACTUATOR
Max 6 barg *Bench range Actuator Orientation Handwheel Type Air Failure Valve
Min
POSITIONER
Input Signal 4-20mA dc (Pt to Pt) Type ELECTROPNEUMATIC/Hart Communicator Mfr. & Model EMERSON DVC 6030 On Incr. Signal Output Incr/DecrHC TYPE (*) Guages Bypass Cam Characteristics ATEX Exd (explosion proof) IIC T6 IP66 Type Mfr. & Model Contacts/Rating Actuation Points Mfr. & Model Set Pressure Filter Quantity
*Type *Size *Characteristics *Balanced/Unbalanced *Rated Cv *Plug/Ball/Disc Material *Seat Material *Cage/Guide Material *Stem Material EQ PERCENTAGE
UNBALAN PORT GUIDED PLUG 14mm
TRIM
6.9
FL /XT S31603
0.9
AIR SET
SWITCHES
83 84 85 86 Rev. 0 1 2
TESTS
Date
Orig PS
App
PStylianopoulos
Page 1 of 2
ISA20.50 Rev.1
ISA 20.50 Rev.1 PROJECT UNIT P.O. ITEM CONTRACT MFR SERIAL Fluid Flow rate Inlet Pressure Outlet Pressure Inlet Temperature Inlet Density
Viscosity/ Spec Heats Ratio
of 78-TV-801
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44
SPECIAL / ACCESSORIES
STEAM Units kg/h bara bara 0 C kg/m3 k Max Flow Norm Flow Min Flow 2400.00 2126.00 350.00 3.50 4.00 4.50 3.00 3.50 4.00 158.00 158.00 158.00 1.81 1.35 2.08 1.35 2.35 1.36 Shut-Off
SERVICE CONDITIONS
Required Cv % dBA
102.03
82.88
12.55
75/
75/
In Pipe Line Size & Schedule Out Pipe Line Insulation *Type *Size *Max Press / Temp *Mfr. & Model *Body/Bonnet Matl *Liner material/ID *End Connection In *End Connection Out *Flg Face Finish *End Ext/Matl *Flow Direction *Type of Bonnet *Lub & Iso Valve *Packing Material *Packing Type 4
FISHER GX integrated GX/225 CLOSE 6barg 4barg 4 barg 2-6 barg NAMUR NO FAIL OPEN
ACTUATOR
Globe ANSI Class 150 0 5 barg / 260 C FISHER 4" GX +ACT. CS 1.0619 / A216 Gr. WCC 6" #150 RF 6" #150 RF RF
Max
6 barg
Min
*Type *Size *Characteristics *Balanced/Unbalanced *Rated Cv *Plug/Ball/Disc Material *Seat Material *Cage/Guide Material *Stem Material EQ PERCENTAGE
UNBALAN PORT GUIDED PLUG 90mm
POSITIONER
Input Signal 4-20mA dc (Pt to Pt) Type ELECTROPNEUMATIC/Hart Communicator Mfr. & Model EMERSON DVC 6030 On Incr. Signal Output Incr/DecrHC TYPE (*) Guages Bypass Cam Characteristics ATEX Exd (explosion proof) IIC T6 IP66 Type Mfr. & Model Contacts/Rating Actuation Points Mfr. & Model Set Pressure Filter Quantity
TRIM
112
FL /XT S31603
0.67
AIR SET
SWITCHES
83 84 85 86 Rev. 0 1 2
TESTS
Date
Orig PS
App
PStylianopoulos
Page 2 of 2