Electrical Energy Meter with integrated M-Bus interface EEM230-D-M

Electrical energy meter with an integrated M-Bus interface allow direct reading of all relevant data, such as energy (total and partial), current, voltage, active and reactive power.

Main features:

Single-phase energy meter, 230VAC 50Hz Direct measurement up to 32A Display of active power, voltage and current M-Bus interface to query the data Reactive power available through interface  Up to 250 meter can be connected to the M-Bus interface 7-digit display Lead seal possible with cap as accessory  Accuracy class B according to EN50470-3, accuracy class 1 according to IEC62053-21

Order Number
Standard Version: MID Version:

EEM230-D-M EEM230-D-M-MID

Technical data
Precision class Operating voltage B according to EN50470-3, 1 according to IEC62053-21 230 VAC, 50Hz Tolerance 20%/ +15 % Iref = 5A, Imax = 32A

Mounting
Mounting Terminal connections main circuit Terminal connections control circuit Insulation characteristics On 35mm rail, according to EN60715TH35 Conductor cross-section max. 6mm2, screwdriver pozidrive no. 1, slot no.1 torque: 1.2 Nm Conductor cross-section max. 2.5mm2, screwdriver pozidrive no. 0, slot no.1 torque: 0.5 Nm 4kV/50Hz test according to VDE0435 for energy meter part 6kV 1.2/50s surge voltage according to IEC255-4 2kV/50Hz test according to VDE0435 for Interface Device protection class II 25+55C 30+85C 95% at 25+40C, without condensation Surge voltage according to IEC61000-4-5 at main circuit, 4kV at M-Bus interface, 1kV Burst voltage according to IEC61000-4-4, at main circuit 4kV at M-Bus interface 1kV ESD according to IEC61000-4-2, contact 8kV, air 15kV

Reference/ measurement current Starting/minimum Ist = 20mA, Imin = 0.25A current Power consumption Active 0.4W per phase Counting range 00000.0099999.99 100000.0999999.9 Display LCD backlit, digits 5 mm high Pulses per kWh LC-Display 2000 Imp./kWh

Ambient temperature Storage temperature Relative humidity EMC/interference immunity

Dimension diagram

Display elements, direct measurement

Indicates the total consumption Indicates the partial consumption. This value can be reset P (kW) Indicates the instantaneous power U (V) Indicates the voltage I (A) Indicates the current 2000pulses/kWh Pulsates according to the amount of used power. Error indication (Line 1L/2L inverted) pulsating with 600/600ms
T total (kWh) T part (kWh)

2|

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

Menu to display the value on LCD

Start

T total

Total consumption

Tpart.

> 3s

> 3s

Partial consumption

Instantaneous power

> 3s

Voltage

> 2s

Current

20s

Back to Start

Back to Start

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

|3

Wirings Diagram
M-Bus

L1

Technical data M-Bus


Bus System Bus length Transmission rates Response time: (system response) M-Bus According to M-Bus specification 300, 2400, 9600 Bd. The transmission rate is automatically detected Write: up to 60 ms Read: up to 60 ms

Data transfer:
When reading out the values, all values are transferred in a telegram It supports the following telegrams (see p. 6 for more detailed information):
Initialisation SND_NKE Response: 0xE5 Reading meter REQ_UD2 Response: RSP_UD Changing primary address SND_UD Response: 0xE5 Reset Tpart SND_UD Response: 0xE5 The device does not respond to unknown queries The transmission rate is automatically detected The device has a voltage monitor. In the case of a power failure, all the registers are saved in the EEPROM.

Change the M-Bus address direct on device


In the menu, go for U Push long ( 3 sec) MBUS-ADR Push short M-Bus address +1, push long M-Bus address +10 Once the desired address is selected wait, to validate, till the root menu to come back

4|

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

Value information field (VIF) Provides information on multiplier and the unit of the following data block Value information field extension (VIFE) Detailed information on multiplier and the unit of the following data block Data information field (DIF) Specifies how the data should be interpreted by the master in terms of length and encoding Data information field extension (DIFE) Provides information on the tariff or subunits of the following data block Reading meter Query: Response: REQ_UD2 RSP_UD (see Telegram structure)

Telegram structure
0x68 02 0x04 0xFF 0xFF 0x38 ACC Epa 0x01 0x01 0x38 STAT 0x02 I Pr 0x68 0 0xFD 0x02 CSum 0x08 0 0xC9 0xAC 0x16 PAdr 0x8c 0xFF 0xFF 0x72 0x10 0x01 0x01 ID 0x04 V P 0xEE Eto 0x02 0x82 0x21 0x8c 0xFD 0x40 DEV 0x11 0xDB 0xAC

Variable at 1, 2 or 4 bytes Byte 23 - 26 30 - 33 39 - 40 46 - 47 52 - 53 59 - 60 Content Eto=x Epa=x V=x I=x P=x Pr=x Type 4 b. BCD 4 b. BCD 2b. Integer 2b. Integer 2b. Integer 2b. Integer Description Energy total Energy partial Voltage Current Power Reactive Power

Unit with multiplier I U Pactive Preactive E (Current) (Voltage) (Power) (Reactive Power) (Consumption) 0.1 [ A ] 1 [V] 0.01 [ kW ] 0.01 [ kVAR ] 0.01 [ kWh ]

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

|5

Telegram structure (detailed)


Byte 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 0x01 0x02 0x04 0x08 0x10 18 19 20 21 22 23 24 25 26 27 28 29 0 0 0x8C 0x10 0x04 Eto_4 Eto_3 Eto_2 Eto_1 0x8C 0x11 0x04 DIF DIFE VIF = 0.01 kWh T1 total Value 0x68 0x38 0x38 0x68 0x08 x 0x72 x x x x 0xEE 0x21 x 02 x Description Start L_Read L_Read Start C Primary address CI ID1 (LSB) ID2 ID3 ID4 (MSB) MAN1 MAN2 DEV (Typ - Version) MED (Electric) ACC STAT Application_busy Any_Application_Error Power_low Permanent_Error Temporary_Error SIG1 SIG2 DIF DIFE VIF = 0.01 kWh Byte 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 Value Epa_4 Epa_3 Epa_2 Epa_1 0x02 0xFD 0xC9 0xFF 0x01 V_2 V_1 0x02 0xFD 0xDB 0xFF 0x01 I_2 I_1 0x02 0xAC 0xFF 0x01 P_2 P_1 0x82 0x40 0xAC 0xFF 0x01 Pr_2 Pr_1 CS 0x16 DIF VIF VIFE = 1V VIFE VIFE Voltage DIF VIF VIFE = 0.1 A VIFE VIFE Current DIF VIF = 0.01kW VIFE VIFE Power DIF DIFE VIF = 0.01kVAR VIFE VIFE Reactive power Checksum Stop T1 Partial Description

6|

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

Initialisation
Query: SND-NKE Telegram structure (brief) 0x10 0x40 Padr CSum 0x16 Response: 0xE5

Reset ACC (application reset)


Query: SND-UD Telegram structure (brief) 0x68 0x50 0x03 CSum 0x03 0x16 0x68 0x53 Padr Response: 0xE5

Telegram structure (detailed) Byte 1 2 3 4 5 0x16 Value 0x10 0x40 Description Start Send or reply, reset Primary address Checksum Stop

Telegram structure (detailed)


Byte 1 2 3 4 5 6 7 8 9 0x16 0x50 Value 0x68 0x03 0x03 0x68 0x53 Description Start Field length Field length Start C Primary address CI Checksum Stop

Changing primary address


Query: SND_UD (Byte 6 = actual M-Bus address; Byte 10 = new address) Response: 0xE5 Telegram structure (brief) 0x68 0x51 0x06 0x01 0x06 0x7A 0x68 New A 0x53 CSum Padr 0x16

Reset Tpart (Application reset with subcode)


Query: SND_UD (Reset Counter: 0x01 = T1Part) Response: 0xE5

Telegram structure (brief) 0x68 0x50 0x04 0x01 0x04 CSum 0x68 0x16 0x53 Padr

Telegram structure (detailed) Byte 1 2 3 4 5 6 7 8 9 10 11 12 0x16 0x51 0x01 0x7A Value 0x68 0x06 0x06 0x68 0x53 Description Start Field length Field length Start C Primary address CI DIF VIF New address Checksum Stop

Telegram structure (detailed) Byte 1 2 3 4 5 6 7 8 9 10 0x16 0x50 0x01 Value 0x68 0x04 0x04 0x68 0x53 Description Start Field length Field length Start C Primary address CI Reset Counter T1Part Checksum Stop

Data sheetSingle-phase Electrical Energy Meter with integrated M-Bus interface

|7

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Rolle, Z.A. La Pice 16, Switzerland by its Authorized Representative:

Saia-Burgess Controls Ltd Bahnhofstrasse 18 CH-3280 Murten/Schweiz Phone Fax +41 (0)26 672 72 72 +41 (0)26 672 74 99

Subject to change without notice. Printed in Switzerland P+P26/587EN01 / 05.2013