Anda di halaman 1dari 7

Control Theory

Page 1 of 7

CONTROL ACTIONS
Two step control action
This can be defined as 'the action of a controller whose output changes from one state to another due to a variation in its input' One example of this control is that of a float operated filling v/v say for a cistern. In normal condition the output of the float is nil and no water passes through the valve, should the water level drop the float detects this and operates the valve to change to its second state which is open and water flows. When the level reestablishes then the float controls the valve to return to its primary state which is closed. In this way the float is controlling the water level by changing the valve between two different states. A more realistic system is shown below.

The system works as follows; the level drops until the lower float is uncovered, the controller detects this and opens the filling valve, the filling v/v remains open until the top float is covered and then the controller shuts the valve The distance between the floats is termed the 'Overlap' i.e. the distance between the high and low controlling values ( on some systems this can be altered by altering the high or low set point of the controller, in the above system this would mean altering the position of the floats ) If there where any delays or lags in the sensing side, say the float switch was a little sticky or the filling v/v was slow to fully open then the level would fall below rise above the low and high set points respectively. This is termed 'Overshoot', it can be seen if the controller 'response to change' time was speeded up so the overshoot could be reduced. The system may be represented in block form as follows;

The measuring unit signal ( in this case an electrical on/off ) is the Measured value on which the controller operates. The signal is being 'fed back' to the controller hence to measured value is Feed back for the controller; i.e. the controller can see the direct results of its action. Feed forward signals are sometimes used on systems which have an inherently high

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 2 of 7

Process Lag; an example of this may be on a Marine Diesel engine jacket fresh water cooling system where part of the control is that the inlet temperature to the engine is monitored and fed forward to the controllers, should the temperature at inlet rise then consequently the outlet temperature must also rise. As the rise has already been detected then the controller can start increasing the sea water cooling to the jacket water coolers even though no temperature rise on the outlet from the engine may have been detected. This type of control, as it takes no account of what is happening to the process ( is the engine running and hence requires the extra cooling or is it stopped ) is not very accurate and normally ( and as in this case ) required Feedback to improve it.

The actions of controllers having variable output

Proportional control action


This where the change in output signal from a controller is proportional to the change in input signal The control can be summed up in the following; Output = Constant x Deviation Output - this is the output from the controller and goes to the control element ( say the filling v/v on the previous example i.e. the piece of equipment that actually alters the process. Constant- This is the 'Gain' of the controller, as the output varies with the deviation, the amount it varies can be altered. Say if the deviation changes by one unit the output changes by one unit, hence the gain is one. If the output varied by two for the same one change in deviation then the gain would be two. Similarly if the change in output was one half a unit for a one unit change in input then the gain would be half. Another way used to describe Gain is 'Proportional band', here a gain of one is described as a proportional band (Pb)of 100%. For a gain of two the Pb is 50%, and for a gain of a half the Pb is 200%, hence it can be seen that the magnitude of the Pb is opposite to the gain. Deviation- This is the difference between the set point of the controller and the measured value. If the set point was one unit and the measured value was two units the deviation would be one unit.

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 3 of 7

Deviation = Set point - Measured value The important think to remember is that the narrower the Proportional band the higher the gain and hence the higher the output varies for a change in deviation, this has the effect of making the controller control the process quicker by operating the controlling element more for smaller variations measured value. This has the negative effect as will be seen of making the system unstable

OFFSET
For a proportional controller to work there must be an deviation, if the deviation is zero then the controller output to the controlling element is zero. For the example of the tank and filling v/v obviously this is not possible, with the water constantly flowing out of the manual outlet v/v then the filling valve ( or controlling element ) must always be some degree open. If the level is at the level of the set point then the output is nil, the filling v/v is shut and the level drops, deviation occurs and the filling v/v opens. with this it can be seen that the system is not stable; what would happen in reality is the level would change ( say the level was low and was now rising) until it reached a point close to the set point where the deviation multiplied by the gain would give an output signal to the filling v/v such that the flow of water in to the tank equalled the flow of water out of the tank. This deviation is called 'offset' Therefore a proportional only controller when in equilibrium must have offset The amount of offset will be determined by the Gain, for the tank system if the gain is high the deviation can be small for a larger output The offset will increase for increased loads on the system i.e. if the outlet v/v on the example where to be opened further obviously the filling v/v would have to be opened further, and hence the deviation ( offset ) to give the required output would have to be greater. For the system above all the control would be positive as the filling v/v would only be open if the level was low and hence the offset would always be positive, when the level rose above the set point, say caused by Lags leading to Overshoots or the filling v/v leaking slightly the deviation would be negative and the output zero.

Proportional action and instability (Hunting)


As the gain increases so the output increases for smaller and smaller changes in deviation, eventually the response starts to look similar to that of a two step controller with the control valve flying from full open to full shut with the slightest deviation from the set point. This would be o.k. if the system was devoid of all Lags, with lags however, particularly between the controller and controlling element, there is a tendency for 'over shoot'.

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 4 of 7

This can occur with reduced gain when the process lags are increased, for systems with a very large lags even small changes in gain can seriously effect the stability of a system and especially its ability to resist step ( or rapid ) load changes. For smaller values of gain the system can be set up to have minimum of hunt and be self stabilizing .

Split range control( negative and positive offset)


A system could be designed to control both the outlet valves and inlet valves (this is what is seen on the feed water system level control with the spill and filling being controlled from the one controller) ; here the controller would be set up so that when the level is at the set point its output is mid range ( say for a controller operating in the 3 to 15 psi range this would be 9 psi) The control valves would be set up so that one, say the filling v/v would go from close at 9.5 psi to open at 15 psi, and the spill v/v would go from close at 8.5 psi to open at 3 psi. The 1 psi in the middle is called the 'Deadband' and is there to ensure both v/vs are not open at the same time.( The v/v acting to open with increasing input signal is called 'Direct Acting' and the v/v closing with increasing pressure is called 'Reverse Acting')

It can be seen that there can now be an offset in the positive i.e. water being used and hence the make up v/v has to be open and in the negative i.e. there is too much water entering the system and the spill v/v's have to be opened. Offset is not a desired result of the control of a system, however for proportional only controllers this is a direct consequence. That is why for all controllers performing important functions; including the make up/spill system controller above other types of controlling action are added to remove the offset

Other types of controlling action

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 5 of 7

Integral action ( and the removal of offset )


Integral action is defined as the action of a controller whose output signal changes at a rate proportional to the input(deviation from the set point) signal. What this means is that if a controller has a constant deviation then the integral action controller will increase its output continuously until it reaches maximum (often referred to as 'Saturation') If the deviation is zero the integral action controller is zero If the deviation is small the rate the controller output increases by is small If the deviation is great then the integral action controller will rapidly increase its output. Integral action is included in proportional controllers to remove the inherent offset of the proportional action, the offset is the deviation the integral action requires to alter the output Integral action time The amount of integral action, or how fast the integral action increases or decreases the output for one unit of deviation is expressed as the time taken to repeat the proportional action after a stepped change in input. Rate of increase of output = Deviation x Integral action time What this means is say the load changes in the simple filling system example by the manual v/v being opened and the level suddenly dropping by a foot, the proportional action will see this load change and give a stepped change in output i.e. if the foot drop in water level equals a change in input signal to the controller of one unit away from the set point, the controller will give a stepped change in output equating to the gain (which is say two ) times the deviation ( one unit) which equals a change in output of two units. Whilst all this has been going on the integral part of the controller has seen the deviation and has decided to increase the rate of output by an amount equal to the deviation multiplied by the integral action time. The time taken for the output to increase by a further two units ( remembering that this was how much the proportional action changed the output) is the integral action time and is measured in seconds. The shorter the integral action time ( less seconds ) the more rapidly the integral part of the controller will increase the output; The longer the integral action time the slower the integral action will increase the output.

A common way of expressing integral action is in 'Repeats per minute', integral action time is seconds per repeat, hence if the IAT is 10 ( seconds per repeat ), this would equate to 10/60 minutes per repeat, or more simply 1/6 mins. The repeats per minute is therefore 6.

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 6 of 7

Integral action and stability The introduction of integral action into a controller introduces an extra time lag, remembering the diagram showing that the integral action will take time to increase the output to a stepped load change, whereas the proportional action will give a stepped change. Lags introduce instability, hence it would more difficult to find settings which give a stable output. Integral action is always used with proportional action

Derivative action
The definition of this is the action of a controller whose output is proportional to the rate of change of input. That is to say for the filling system if the level was falling slowly the output of the controller would be small. If the level was flying down at a great rate of knots then the derivative controller would give a high output. It is quite obvious that the derivative action takes no account of the deviation from the set point but is only interested in the rate of change of deviation and hence; Derivative action by itself cannot be used for control. The purpose of adding derivative action to a controller is to increase the responses that deviation is removes as quickly as possible. That is to say if the level in our filling system is falling the proportional action will increase the filling at a the same rate, however as with seen, if there is a lag in the system particularly between the controller and controlling element; then there is a possibility of instability and a hunt. If we where at the point where the water level was just starting to fall less rapidly but not at the point where it was actually starting to rise, all the proportional and integral action see is a large deviation and so keep the water v/v wide open, the derivative action, however, sees this slowing down of the drop in water level, its output is dependent on the rate of change and hence reduces, and so the output from the controller reduces. The introduction of derivative action introduces a stabilizing effect into a control system Derivative action time Output = Derivative action x rate of change of input Derivative action [coefficient]- This is described as the time the proportional action takes to repeat the derivative action after a ramped ( or constant rate of change) input. The units are seconds.

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Control Theory

Page 7 of 7

file://C:\Documents and Settings\DINESH\My Documents\Read\engines tech\www.marin...

8/25/2006

Anda mungkin juga menyukai