Selection guide

TeSys contactors

Applications

Equipment based on standard contactors

Equipment requiring low consumption contactors which can be switched directly from solid state outputs

Rated operational current

AC-3 AC-1

6A 12 A

6...16 A 20 A

9150 A 25200 A

115800 A

7501800 A

6...12 A 20 A

925 A 2040 A

2001600 A 8002750 A

Rated operational voltage

690 V

690 V

690 V

1000 V

1000 V

690 V

690 V

Number of poles

2 or 3

3 or 4

3 or 4

2, 3 or 4

14

3 or 4

Contactor type references

LC1 SK LP1 SK

LC1 K LC7 K LP1 K

LC1 D

LC1 F

LC1 B

LP4 K

LC1 D

Pages

5/4 and 5/5

5/42 and 5/43

5/92 and 5/93

5/11

5/44 and 5/45

5/2

Equipment requiring magnetic latching contactors

Motors, resistive circuits, rotor short-circuiting devices, electro lifting magnets, hoisting, mines, c motors, high operating rates. Variable composition bar mounted contactors.

Induction heating, heating of metal or of a metal part in a channel or crucible furnace by induction of a.c. currents. Contactors for induction heating applications

Applications conforming to NATO specifications and references. Shockproof contactors

Protection of reversing variable speed controllers for d.c. motors. Fast acting contactors.

1501800 A 2502750 A

80...1800 A 802750 A

8016 300 A

12630 A 25850 A

1000 V

a 1000 V c 440 or 1500 V 16

3000 V

690 V or 1000 V

a 1000 V c 1050 V 2 or 4

14

18

3 or 4

CR1 F CR1 B

CVp

CEp CSp CG p

LC1 DpG LP1 DpG LC1 FGppp

CR3 pB

5/218 to 5/227

5/194 and 5/195

Please consult your Regional Sales Office

5/3

Selection guide

TeSys contactors
TeSys d

Applications

All types of automation system

Rated operational current le max. AC-3 (Ue y 440 V) le AC-1 ( y 60 C) 9A 20/25 A 12 A 18 A 25/32 A 25 A 25/40 A 32 A 50 A 38 A

Rated operational voltage

690 V

Number of poles

3 or 4

3 or 4

3 or 4

3 or 4

Rated operational power in AC-3

5
Auxiliary contacts

220/240 380/400 415/440 500 V 660/690 1000 V

V V V V

2.2 kW 4 kW 4 kW 5.5 kW 5.5 kW

3 kW 5.5 kW 5.5 kW 7.5 kW 7.5 kW

4 kW 7.5 kW 9 kW 10 kW 10 kW

5.5 kW 11 kW 11 kW 15 kW 15 kW

7.5 kW 15 kW 15 kW 18.5 kW 18.5 kW

9 kW 18.5 kW 18.5 kW 18.5 kW 18.5 kW

1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks common to the whole range, comprising up to 4 N/C or N/O instantaneous, up to 1 N/O + 1 N/ C time delay and up to 2 N/O or 2 N/C protected contacts and 2 screen continuity terminals

Thermal overload relays manual-auto compatible

Class 10 A Class 20

0.1010 A 2.510 A

0.1013 A 2.513 A

0.1018 A 2.518 A

0.1032 A 2.532 A

0.1038 A

0.1038 A

Suppressor modules (c and low consumption contactors have built-in suppression as standard)

Varistor Diode RC circuit Bidirectional peak limiting diode Relay Relay + override function Solid state a or c 3-pole a 4-pole c 4-pole

p p p

p p p

p p p

p p p

p p p

p p p

Interfaces

p p p

p p p

p p p

p p p

p p p

p p p

Contactor type references

LC1 D09 LC1 DT20/ LC1 D098 LC2 D09 LC2 D09 LC2 DT20 LC2 DT20
5/58 to 5/61 5/62 to 5/65

LC1 D12 LC1 DT25/ LC1 D128 LC2 D12 LC2 D12 LC2 DT25 LC2 DT25

LC1 D18 LC1 DT32/ LC1 D188 LC2 D18 LC2 D18 LC2 DT32 LC2 DT32

LC1 D25 LC1 DT40/ LC1 D258 LC2 D25 LC2 D25 LC2 DT40 LC2 DT40

LC1 D32 LC2 D32 LC2 D32

LC1 D38 LC2 D38 LC2 D38

Reversing contactor type references

a 3-pole c 3-pole a 4-pole c 4-pole

Pages

Contactors Reversing contactors

5/42

5 5

40 A 60 A

50 A 80 A

65 A

80 A 125 A

95 A

115 A 200 A

150 A

1000 V on a supply, 690 V on c supply

11 kW 18.5 kW 22 kW 22 kW 30 kW 22 kW

15 kW 22 kW 25/30 kW 30 kW 33 kW 30 kW

18.5 kW 30 kW 37 kW 37 kW 37 kW 37 kW

22 37 45 55 45 45

kW kW kW kW kW kW

25 45 45 55 45 45

kW kW kW kW kW kW

30 55 59 75 80 75

kW kW kW kW kW kW

40 kW 75 kW 80 kW 90 kW 100 kW 90 kW

1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks common to the whole range, comprising up to 4 N/C or N/O instantaneous, up to 1 N/O + 1 N/C time delay and up to 2 N/O or 2 N/C protected contacts and 2 screen continuity terminals

1750 A 1740 A

1770 A 1765 A

1780 A 1770 A

17104 A 1780 A

17104 A

60150 A 60150 A

60150 A 60150 A

p p p p

p p p p

p p p p

p p p p

p p p p

p p p p

p p p p

p p p p

p p

p p

p p p

p p p

p p p

p p p

p p p

p p p

p p p

p p p

p p p

p p p

p p

LC1 D40 LC1 D40 LP1 D40 LC2 D40 LC2 D40

LC1 D50 LC2 D50

LC1 D65 LC1 D65 LP1 D65 LC2 D65 LC2 D65

LC1 D80 LC1 D80 LP1 D80 LC2 D80 LC2 D80

LC1 D95 LC2 D95

LC1 D115 LC1 D115 LC1 D115 LC2 D115 LC2 D115

LC1 D150 LC2 D150

5/43

Selection guide

TeSys contactors
TeSys d, low consumption

Applications

Automation systems

Rated operational current le max. AC-3 (Ue y 440 V) le AC-1 ( y 60 C) 9A 20/25 A 12 A 20/25 A 18 A 25/32 A

Rated operational voltage

690 V

Number of poles

3 or 4

3 or 4

3 or 4

Rated operational power in AC-3

220/240 V 380/400 V 415/440 V

2.2 kW 4 kW 4 kW 5.5 kW 5.5 kW

3 kW 5.5 kW 5.5 kW 7.5 kW 7.5 kW

4 kW 7.5 kW 9 kW 10 kW 10 kW

500 V 660/690 V

Coil consumption Operating ranges

2.4 W (100 mA - 24 V) 0.71.25 Uc

Operating time at 20 C and at Uc

Closing Opening

70 ms 25 ms

Auxiliary contact blocks

1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks common to the whole range, comprising up to 2 N/C or 2 N/O instantaneous standard contacts Built-in suppression as standard, by bi-directional peak limiting diode

Interference suppression

Contactor type 3-pole 4-pole Reversing contactor type 3-pole 4-pole Pages Contactors Reversing contactors

LC1 D09 LC1 DT20/D098

LC1 D12 LC1 DT25/D128

LC1D18 LC1 DT32/D188

LC2 D09 LC2 DT20


5/58 to 5/61 5/62 to 5/65

LC2 D12 LC2 DT25

LC2 D18 LC2 DT32

5/44

5 5

25 A 25/40 A

32 A 50 A

38 A 50 A

3 or 4

5.5 kW 11 kW 11 kW 15 kW 15 kW

7.5 kW 15 kW 15 kW 18.5 kW 18.5 kW

9 kW 18.5 kW 18.5 kW 18.5 kW 18.5 kW

2.4 W (100 mA - 24 V) 0.71.25 Uc

70 ms 25 ms

1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks common to the whole range, comprising up to 2 N/C or 2 N/O instantaneous standard contacts Built-in suppression as standard, by bi-directional peak limiting diode

LC1 D25 LC1 DT40/D258

LC1 D32

LC1 D38

LC2 D25 LC2 DT40

LC2 D32

LC2 D38

5/45

Characteristics

TeSys contactors
TeSys d

Contactor type

LC1

D09D18 D25D38 D40 DT20 and DT25 DT32 and DT40 690 1000

D50D95

D115 and D150

Environment
Rated insulation voltage (Ui) Conforming to IEC 60947-4-1, V overvoltage category III, degree of pollution: 3 Conforming to UL, CSA V Conforming to IEC 60947 kV

600 6 8

Rated impulse withstand voltage (Uimp) Conforming to standards

Product certifications

IEC 60947-1, 60947-4-1, NFC 63-110, VDE 0660, BS 5424, JEM 1038. EN 60947-1, EN 60947-4-1. GL, DNV, PTB, RINA UL, CSA Complies with SNCF, Sichere Trennung recommendations Conforming to VDE 0106 part 101 and A1 (draft 2/89) Conforming to VDE 0106 and IEC 60529 Power connection Coil connection Conforming to IEC 60068 Storage Operation Permissible C C C m V 400

Separation insulation

Degree of protection (1) (front face only)

Protection against direct finger contact IP 2X Protection against direct finger contact IP 2X TH - 60+ 80 - 5+ 60 - 40+ 70, for operation at Uc 3000 a /c

Protective treatment Ambient air temperature around the device

Maximum operating altitude Operating positions (2)

Without derating Without derating in the following positions

30

30

180

Positions that are not permissible

For c contactors LC1 D09 to D38

Flame resistance

Conforming to UL 94 Conforming to IEC 60695-2-1 Contactor open Contactor closed Contactor open Contactor closed

V1 960 10 gn 15 gn 2 gn 4 gn 8 gn 15 gn 8 gn 10 gn 8 gn 10 gn 6 gn 15 gn

Shock resistance (3) 1/2 sine wave = 11 ms Vibration resistance (3) 5300 Hz

4 gn

4 gn

90

90

3 gn

180
4 gn

(1) Protection provided for the cabling c.s.a.'s indicated on the next page and for connection by cable. (2) For other operating positions, please consult your Regional Sales Office. (3) Without change of contact states, in the most unfavourable direction (coil energised at Ue).

Selection : pages 5/160 to 5/191

References : pages 5/58 to 5/61

Dimensions : pages 5/82 to 5/85

Schemes : pages 5/86 and 5/87

5/46

Characteristics (continued)

TeSys contactors
TeSys d

Contactor type

LC1

D09 and D12 D18 (3P) DT20 and DT25

D25 (3P)

D32 D38 D18 and D25 D40 (4P) DT32 and DT40

D50 and D80 and D115 and D150 D65 D95

Power circuit connections


Connection by cable
Tightening torque Screw clamp terminals Connector 2 inputs 1.510 1.56 16 14 1.56 1.56 N 2 6 2.5 2.510 2.510 110 1.56 1.510 2.510 N 2 6 2.5 2.510 2.510 2.510 2.510 2.516 2.516 N 2 6 1.8 Screw clamp terminals 2.525 2.516 2.525 2.510 2.525 2.516 6 8 5 Connector 1 input 2.525 2.516 2.525 2.510 2.525 2.516 6 8 5 450 425 450 416 450 425 6 8 4 9 Connector 2 inputs 10120 10120 + 1050 10120 10120 + 1050 10120 10120 + 1050 4 12

Flexible cable without cable end

1 conductor 2 conductors Flexible cable 1 conductor with cable end 2 conductors Solid cable 1 conductor without cable end 2 conductors Screwdriver Philips Flat screwdriver Key for hexagonal headed screw Tightening torque

mm 2 mm 2 mm 2 mm 2 mm 2 mm 2

N.m

14 14 14 12.5 14 14 N 2 6 1.7

1.56 1.56 16 14 1.56 1.56 N 2 6 1.7

Spring terminal connections (1)


Flexible cable without cable end 1 conductor 2 conductors mm 2 mm 2 2.5 (4: DT25) 2.5 (except DT25) 8 M3.5 N 2 6 1.7 4 4 4 4 4 4 10

Connection by bars or lugs


Bar cross-section Lug external of screw Screwdriver mm mm 8 M3.5 N 2 6 1.7 10 M4 N 2 6 2.5 10 M4 N 2 6 2.5 8 (2) M3.5 N 2 6 1.8 13 M5 N 2 8 5 16 M6 N 3 8 5 3 x 16 17 M6 8 10 9 5 x 25 25 M8 13 12

Philips Flat screwdriver Key for hexagonal headed screw N.m Tightening torque

Control circuit connections


Connection via cable (tightening via screw clamps)
Flexible cable without cable end Flexible cable with cable end Solid cable without cable end Screwdriver Tightening torque 1 conductor 2 conductors 1 conductor 2 conductors 1 conductor 2 conductors Philips Flat screwdriver mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 14 14 14 12.5 14 14 N 2 6 1.7 14 14 14 12.5 14 14 N 2 6 1.7 14 14 14 12.5 14 14 N 2 6 1.7 14 14 14 12.5 14 14 N 2 6 1.7 14 14 14 12.5 14 14 N 2 6 1.7 14 14 12.5 12.5 14 14 N 2 6 1.2 14 14 12.5 12.5 14 14 N 2 6 1.2 14 14 12.5 12.5 14 14 N 2 6 1.2 12.5 12.5 12.5 12.5 12.5 12.5 N 2 6 1.2

N.m

Spring terminal connections (1)


Flexible cable without cable end 1 conductor 2 conductors mm 2 mm 2 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5

Connection by bars or lugs


Lug external of screw Screwdriver Tightening torque mm mm Philips Flat screwdriver N.m 8 M3.5 N 2 6 1.7 8 M3.5 N 2 6 1.7 8 M3.5 N 2 6 1.7 8 M3.5 N 2 6 1.7 8 M3.5 N 2 6 1.7 8 M3.5 N 2 6 1.2 8 M3.5 N 2 6 1.2 8 M3.5 N 2 6 1.2 8 M3.5 N 2 6 1.2

(1) If cable ends are used, choose the next size down (example: for 2.5 mm2, use 1.5 mm2 ) and square crimp the cable ends using a special tool. (2) To connect cables with a c.s.a. > 4mm2 and up to 10 mm2, it is essential to use special connectors, sold in bags of 100 (reference: LAD 96180).

Selection : pages 5/160 to 5/191

References : pages 5/58 to 5/61

Dimensions : pages 5/82 to 5/85

Schemes : pages 5/86 and 5/87

5/47

Characteristics (continued)

TeSys contactors
TeSys d

Contactor type

LC1

D09 (3P) A A V Hz A 9 25 (1) 690

DT20 D098

D12 (3P) 12 25 (1) 690

DT25 D128

D18 (3P) 18 32 (1) 690

DT32 D188

D25 (3P) 25 40 (1) 690

DT40 D258

Pole characteristics
Rated operational current (Ie) (Ue y 440 V) In AC-3, y 60 C In AC-1, y 60 C Rated operational voltage (Ue) Up to Of the operating current y 60 C Conforming to IEC 60947 Conforming to IEC 60947 For 1 s For 10 s For 1 min For 10 min Without thermal type 1 overload relay, gG fuse type 2 With thermal overload relay At Ith and 50 Hz AC-3 AC-1 A A A A A A A m W W 20 25 32 40

Frequency limits Conventional thermal current (Ith) Rated making capacity (440 V) Rated breaking capacity (440 V) Permissible short time rating No current flowing for preceding 15 minutes with y 40 C Protection by fuses against short-circuits (U y 690 V) Average impedance per pole Power dissipation per pole for the above operational currents

25400 25 (1) 20 250 250

25400 25 (1) 25 250 250

25400 32 (1) 32 300 300

25400 40 (1) 40 450 450

210 210 240 380 105 105 145 240 61 61 84 120 30 30 40 50 25 40 50 63 20 25 35 40 See pages 6/16 and 6/17, for aM or gG fuse ratings corresponding to the associated thermal overload relay 2.5 2.5 2.5 2 0.20 0.36 0.8 1.25 1.56 1.56 2.5 3.2

Control circuit characteristics, a.c. supply


Rated control circuit voltage (Uc) Control voltage limits 50 or 60 Hz coils 50/60 Hz coils 50/60 Hz V 12690

Operational Drop-out Operational

Drop-out a 50 Hz Inrush 50 Hz coil Cos 50/60 Hz coil Sealed 50 Hz coil Cos 50/60 Hz coil a 60 Hz Inrush 60 Hz coil Cos 50/60 Hz coil Sealed 60 Hz coil Cos 50/60 Hz coil Heat dissipation 50/60 Hz Operating time Closing "C" (2) Opening "O" Mechanical durability 50 or 60 Hz coil in millions of operating cycles 50/60 Hz coil on 50 Hz Average consumption at 20 C and at Uc Maximum operating rate at ambient temperature y 60 C In operating cycles per hour

VA VA VA VA VA VA VA VA W ms ms

0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 60 C 0.30.6 Uc at 60 C 0.75 70 0.3 7 0.75 70 0.3 7.5 23 1222 419 15 3600

(1) Versions with spring terminal connections: 16 A for LC1 D093 and LC1 D123 (20 A possible with 2 x 2.5 mm 2 cables in parallel), 25 A for LC1 D183 to LC1 D323 (32 A possible for LC1 D183 connected with 2 x 4 mm2 cables in parallel; 40 A possible for LC1 D253 and LC1 D323 connected with 2 x 4 mm2 cables in parallel). (2) The closing time "C" is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time "O" is measured from the moment the coil supply is switched off to the moment the main poles separate.

Selection : pages 5/160 to 5/191

References : pages 5/58 to 5/61

Dimensions : pages 5/82 to 5/85

Schemes : pages 5/86 and 5/87

5/48

D32

D38

D40

D50

D65

D80

D95

D115

D150

32 50 (1) 690 25400 50 550 550

38 50 690 25400 50 550 550

40 60 1000 25400 60 800 800

50 80 1000 25400 80 900 900

65 80 1000 25400 80 1000 1000

80 125 1000 25400 125 1100 1100

95 125 1000 25400 125 1100 1100

115 200 1000 25400 200 1260 1100 1100 950 550 250 250 200

150 200 1000 25400 200 1660 1400 1400 1200 580 250 315 250

430 430 720 260 310 320 138 150 165 60 60 72 63 63 80 63 63 80 See pages 24514/2 and 24514/3, for aM or gG fuse 2 2 5 2 3 5 1.5 2.4 5.4

810 900 990 1100 400 520 640 800 208 260 320 400 84 110 135 135 100 160 200 200 100 125 160 160 ratings corresponding to the associated thermal overload relay 1.5 3.7 9.6 1 4.2 6.4 0.8 5.1 12.5 0.8 7.2 12.5

0.6 7.9 24

0.6 13.5 24

12690

24660

24500

0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 60 C 0.30.6 Uc at 60 C 0.75 70 0.3 7 0.75 70 0.3 7.5 23 1222 419 15 3600

0.851.1 Uc at 55 C 0.30.6 Uc at 55 C 0.81.1 Uc on 50 Hz and 0.851.1 Uc on 60 Hz at 55 C 0.30.6 Uc at 55 C 200 0.75 245 20 0.3 26 220 0.75 245 22 0.3 26 610 2026 2026 812 812 16 16 6 6 3600 3600

2026 812 16 6 3600

2035 620 10 4 3600

2035 620 10 4 3600

0.851.1 Uc at 55 C 0.30.5 Uc at 55 C 0.81.15 Uc on 50/60 Hz at 55 C 0.30.5 Uc at 55 C 300 0.8 0.9 280350 280350 22 0.3 0.9 218 218 300 0.8 0.9 280350 280350 22 0.3 0.9 218 218 38 34.5 2050 2035 620 4075 8 8 8 2400 1200

5/49

Characteristics (continued)

TeSys contactors
TeSys d

Contactor type

LC1 D09D38 LC1 DT20DT40 c Conforming to IEC 60947-1 Conforming to UL, CSA Operational Standard coil Wide range coil Drop-out c Inrush Sealed Closing Opening "C" "O" V V V 12440 690 600 0.71.25 Uc at 60 C

LC1 or LP1 D40D65 12440

LC1 or LP1 D80 LC1 D95

LC1 D115 and LC1 D150 24440

d.c. control circuit characteristics


Rated control circuit voltage (Uc) Rated insulation voltage Control voltage limits

0.851.1 Uc at 55 C 0.751.2 Uc at 55 C

0.751.2 Uc at 55 C 0.150.4 Uc at 55 C 270 to 365 2.45.1

Average consumption at 20 C and at Uc Average operating time at Uc (1)

W W

0.10.25 Uc at 60 C 0.10.3 Uc at 55 C 5.4 22 22 5.4 22 22

Time constant L/R (L/R) Mechanical durability at Uc In millions of operating cycles Maximum operating rate In operating cycles per hour at ambient temperature y 60 C

ms 63 15 % 85110 95130 2035 ms 20 20 % 2035 2035 4075 Nota : The arcing time depends on the circuit switched by the poles. For all normal 3-phase applications, the arcing time is less than 10 ms. The load is isolated from the supply after a time equal to the sum of the opening time and the arcing time. ms 28 65 75 25 30 3600 20 3600 20 3600 8 1200

Low consumption control circuit characteristics


Rated insulation voltage Maximum voltage Conforming to IEC 60947-1 Conforming to UL, CSA Of the control circuit on c Wide range coil (0.71.25 Uc) Closing Opening Operational Drop-out ms In millions of operating cycles At ambient temperature y 60 C Inrush Sealed "C" "O" V V 690 600 250 2.4 2.4 77 15 % 25 20% 0.7 to 1.25 Uc 0.10.3 Uc 40 30 3600

Average consumption d.c. at 20 C and at Uc Operating time (1) at Uc and at 20 C Voltage limits ( y 60 C) of the control circuit Time constant L/R (L/R) Mechanical durability Maximum operating rate

W W ms ms

ops/h

(1) The operating times depend on the type of contactor electromagnet and its control mode. The closing time "C" is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time "O" is measured from the moment the coil supply is switched off to the moment the main poles separate.

Selection : pages 5/160 to 5/191

References : pages 5/58 to 5/61

Dimensions : pages 5/82 to 5/85

Schemes : pages 5/86 and 5/87

5/50

Characteristics (continued)

TeSys contactors
TeSys d

Characteristics of auxiliary contacts incorporated in the contactor


Mechanically linked contacts Conforming to IEC60947-5-1 Mirror contact Conforming to IEC60947-4-1 Rated operational voltage (Ue) Up to Rated insulation voltage (Ui) Conforming to IEC 60947-1 Conforming to UL, CSA Conventional For ambient temperature thermal current (Ith) y 60 C Frequency of the operational current Minimum switching capacity U min = 108 I min Short-circuit protection Conforming to IEC 60947-5-1 Rated making capacity Conforming to IEC 60947-5-1, I rms Short-time rating Permissible for 1s 500 ms 100 ms Insulation resistance Non-overlap time Operational power of contacts conforming to IEC 60947-5-1 Each contactor has 2 N/O and N/C contacts mechanically linked on the same movable contact holder The N/C contact on each contactor represents the state of the power contacts and can be connected to a PREVENTA safety module 690 690 600 10 25400 17 5 gG fuse: 10 A a: 140, c: 250 100 120 140 > 10

V V V A Hz V mA

A A A A M

1 million operating cycles 3 million operating cycles 10 million operating cycles

Guaranteed between ms 1.5 on energisation and on de-energisation N/C and N/O contacts a.c. supply, categories AC-14 and AC-15 d.c. supply, category DC-13 Electrical durability (valid for up to 3600 operating cycles/hour) Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet: on an inductive load such as the coil of an electromagnet, making current (cos 0.7) = 10 times the power broken without economy resistor, the time constant increasing with the (cos 0.4). load. V 24 48 115 230 400 440 600 V 24 48 125 250 440 VA 60 120 280 560 960 1050 1440 W 96 76 76 76 44 VA 16 32 80 160 280 300 420 W 48 38 38 32 VA 4 8 20 40 70 80 100 W 14 12 12 AC-15 DC-13
Millions of operating cycles Millions of operating cycles

10 8 7 6 5 4 3 2

10 8 7 6 5 4 3 2

24 V 48 V 125 V

250 V 1 0,8 0,7 0,6 0,5 0,4 0,3 0,2 440 V

1 0,8 0,7 0,6 0,5 0,4 0,3 0,2

0,1 0,1

0,2

0,3 0,4 0,6 0,8 1 0,5 0,7 0,9

4 5

6 7

8 10 9

0,1 0,1

0,2

0,3 0,4 0,6 0,8 1 0,5 0,7 0,9

4 5

6 7

8 10 9

Current broken in A

Current broken in A

Selection : pages 5/160 to 5/191

References : pages 5/58 to 5/61

Dimensions : pages 5/82 to 5/85

Schemes : pages 5/86 and 5/87

5/51

Characteristics

TeSys contactors
Auxiliary contact blocks without dust and damp protected contacts for TeSys d contactors

Contact block type

LAD N or LAD C

LAD T and LAD S

LAD R

LAD 8

Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature around the device Maximum operating altitude Connection by cable Conforming to IEC 60068 Conforming to VDE 0106 Storage Operation Permissible for operation at Uc Without derating Phillips N 2 and 6 mm Flexible or solid cable with or without cable end Flexible or solid cable without cable end C C C m mm2 IEC 60947-5-1, NF C 63-140, VDE 0660, BS 4794, EN 60947-5-1 UL, CSA TH Protection against direct finger contact IP 2X - 60+ 80 - 5+ 60 - 40+ 70 3000 Min: 1 x 1, max: 2 x 2.5

Spring terminal connections

mm2

Max. 2 x 2.5

Instantaneous and time delay contact characteristics


Number of contacts Rated operational voltage (Ue) Rated insulation voltage (Ui) Conventional thermal current (Ith) Frequency of the operational current Minimum switching capacity Short-circuit protection Rated making capacity Short-time rating Up to V 1, 2 or 4 690 690 600 10 25400 17 5 10 a : 140 ; c: 250 100 120 140 > 10 1.5 (on energisation and on de-energisation) 1.5 30 See page 5/54 - 40+ 70 2 % + 15 % 0.25 % per C 5 - 40+ 70 2 % + 15 % 0.25 % per C 5 30 2 2 2

V Conforming to IEC 60947-5-1 V Conforming to UL, CSA For ambient temperature y 60 C A Hz U min I min Conforming to IEC 60947-5-1 and VDE 0660. gG fuse I rms Conforming to IEC 60947-5-1 Permissible for 1s 500 ms 100 ms V mA A A A A A M ms ms C

Insulation resistance Non-overlap time Guaranteed between N/C and N/O contacts Overlap time Guaranteed between N/C and N/O contacts on LAD C22 Time delay Ambient air temperature for (LAD T, R and S contact blocks) operation Accuracy only valid for setting Repeat accuracy range indicated on the front face Drift up to 0.5 million operating cycles Drift depending on ambient air temperature Mechanical durability In millions of operating cycles Operational power of contacts

References : pages 5/69 and 5/70

Dimensions : pages 5/82 and 5/83

Schemes : pages 5/86 and 5/87

5/52

Characteristics (continued)

TeSys contactors
Auxiliary contact blocks with dust and damp protected contacts for TeSys d contactors

Contact block type

LA1 DX

LA1 DZ Protected

LA1 DY Non protected

Environment
Conforming to standards Product certifications Protective treatment Degree of protection Ambient air temperature Connection Conforming to IEC 60068 Conforming to VDE 0106 Storage and operation Phillips N 2 and 6 mm Flexible or solid cable with or without cable end C mm 2 IEC 60947-5-1, VDE 0660 UL, CSA TH Protection against direct finger contact IP 2X - 25+ 70 Min: 1 x 1, max: 2 x 2.5

Number of contacts

Contact characteristics
Rated operational voltage (Ue) Rated insulation voltage (Ui) Conventional thermal current (Ith) Maximum operational current (Ie) Frequency of the operational current Minimum switching capacity Short-circuit protection Rated making capacity Short-time rating Up to Conforming to IEC 60947-5-1 Conforming to UL, CSA For ambient temperature y 40 C V V V A mA Hz U min I min Conforming to IEC 609475-1 gG fuse Conforming to IEC 60947 5-1, I rms Permissible for 1s 500 ms 100 ms V mA A A A A A M 50 250 500 17 4 > 10 50 250 500 17 4 > 10 690 690 600 10 25400 17 5 10 a: 140; c: 250 100 120 140 > 10 24 250 50 3 0.3 > 10 5 Gold - Single break with crossed bars

Insulation resistance Mechanical durability Materials and technology used for dust and damp protected contacts In millions of operating cycles

5 5 30 Silver - Single break Silver - Single break

References : page 5/69

Dimensions : pages 5/82 and 5/83

Schemes : pages 5/86 and 5/87

5/53

Characteristics (continued)

TeSys contactors
Auxiliary contact blocks with dust and damp protected contacts for TeSys d contactors

Rated operational power of contacts (conforming to IEC 60947-5-1)


a.c. supply, categories AC-14 and AC-15
Electrical durability (valid for up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet: making current (cos 0.7) = 10 times the power broken (cos 0.4). V VA VA VA 24 60 16 4 48 120 32 8 115 280 80 20 230 560 160 40 400 960 280 70 440 1050 300 80 600 1440 420 100

1 million operating cycles 3 million operating cycles 10 million operating cycles


Millions of operating cycles

10 8 7 6 5 4 3 2

1 0,8 0,7 0,6 0,5 0,4 0,3 0,2

0,1 0,1 0,2 0,3 0,4 0,5

0,6 0,8 1 0,7 0,9

4 5

6 7

8 10 9

Current broken in A

d.c. supply, category DC 13


Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load. V W W W 24 120 70 25 48 90 50 18 125 75 38 14 250 68 33 12 440 61 28 10

1 million operating cycles 3 million operating cycles 10 million operating cycles


Millions of operating cycles

10 8 7 6 5 4 3 2 250 V

24 V 48 V 125 V

1 0,8 0,7 0,6 0,5 0,4 0,3 0,2

440 V

0,1 0,1 0,2 0,3 0,4 0,5 0,6 0,8 1 0,7 0,9 2 3 4 5 6 7 8 10 9

Current broken in A

References : pages 5/69 and 5/70

Dimensions : pages 5/82 and 5/83

Schemes : pages 5/86 and 5/87

5/54