Anda di halaman 1dari 36

Quality Assurance system

certified by ÖQS
ÖNORM EN ISO 9001:2000
Reg.no. 366/0

Member
The TRI-
functional
pipe system
Austria Association for
PLASTIC PIPE RECYCLING

ARA licence no. 9087

Cold water | Compressed air | Cooling

A H A ! - 02.06.06
Handbook/06
Index KE KELIT´s Approvals
Quality targets Registration
Quality targets; approvals; registration 3
Drinking water supply (cold), operating conditions 4–5 1. Our quality targets are not confined
to the product.
Introduction – Compressed air; cooling 6–7
They include all areas covered by
Raw materials; oxygen diffusion barrier; NONOX procedure 8–9 ÖNORM EN ISO 9001: 2000
Testing on the basis of
Pipe types; service life 10 – 11 2. Suppliers and customers are ÖNORM B 5174
CX-Pipes; PE pipes; heat loss 12 – 13 integrated into the quality assurance
Test report: 18 886
system to ensure that mistakes are
The six methods of joining 14 – 15 prevented.
Installation Test for
3. Every employee is responsible impact resistance
Polyfusion welding, saddle fitting welding 16 –17 for the quality of his own work and
should be highly motivated to to – 30°C
Table welding machine 18 –19 continually assess his work. Test no. 19 149
Overhead welding machine 20 – 21
4. Customer satisfaction can only be
Butt welding machine 22 – 23 achieved by responding to the Test for
requirements of the customer and oxygen impermeability
E-uni socket welding 24 – 25 the market. Test no. 19199
Glycol brine pipelines, pressure loss in KEtrix® drinking water pipes 26 – 27 Test no. 19200
5. A responsible attitude to the Test no. 19222
Pipe sizing to DIN 1988 – the complementary pipe system 28 – 31 environment can be achieved by Test no. 19223
manufacturing long-life products by Test no. 19240
Pipe sizing - PN10; ALU-composite and PN16 32 – 33
environment-friendly processes. Test no. 19241
Compressed air technology; compressed air network 34 – 35
Pipe sizing graphs for compressed air systems 36 – 37
Expansion; force of expansion; compensation 38 – 39
Compensation for expansion in practice; pipe supports 40 – 41
Foodstuff approval
Pressure testing for drinking water 42 – 43
to ÖNORM B 5014/1
Pressure testing for chilled water and compressed air 44 – 45 Test no. 45.403

Installation guidelines 46 – 47
Product range 48 – 67
Permeability to water vapour
Agencies worldwide 70 – 71 to ASTM F 1249-90
KR. Karl Egger eh.

A H A ! - 02.06.06
Test report no. 45.565
Managing Director
Note: please read the chapters concerning installation and joint technology
before using KEtrix® for the first time

2 3
Drinking water Operating conditions The result
(cold) KEtrix® PN10 The KEtrix® pipe system with many
PN10 = 20°C /10 bar; 40°C /9 bar advantages for new building and
The problems renovation projects:

KE KELIT
● Range of pipes and fittings for cold
Corrosion
water applications: d20 - d160
● The concentration of ions is increasing. ● Pressure rating PN10 d20 - d160
The following ions are a particular risk Resistant to both internal and external
for metal materials: corrosion from all ions found in water
Chlorides: stainless steel and building materials
Sulphates: galvanised steel ● No crystallisation points for mineral

PN 10
Nitrates: copper deposits
● Even more problematic sources of Internal corrosion – Copper
● Secure joint technology which requires
water are being used for drinking no additional materials
water supplies ● Suitable for contact with potable water
● Acid rain lowers the pH value of surface Conforms to foodstuff regulations
water and spring water to below 7 ● Low pressure losses as a result of
(=neutral). External corrosive attacks smooth bore
from new building materials, insulating ● Low noise level
materials and installation techniques ● Low thermal conductivity
● Disinfectants (chlorine, ozone) are Comparison of λ-values
particularly aggressive on copper, KEtrix® 0.24 W/m°C
releasing poisonous copper ions into Copper 320.00 W / m°C
the water supply. ● Easy to install,
● High resistance to impact
Deposits ● Saves on labour costs
● Hard water leads to the formation of
The ● No demountable embedded joints
deposits on the inside walls of metal External corrosion –
solution ● System can be easily drained
materials . Galvanised Steel ● Stringent testing and monitoring

I n d u s t r i e - R o h r PN 10
The KEtrix® of quality
This results in: drinking water ● Long service life
pipe system ● Pre-insulated pipes can be located
● Higher friction losses
in the wall
● Reduced flow rate
Plastics are not
● Blockages
”replacement For hot water systems use
● Expensive repairs
materials”. the KELEN® pipe system
● Time-consuming renovation
When chosen and
● Acute supply problems
applied correctly they
often provide the

®
A secure supply of better solution for
a defined problem.
drinking water is an ”No more

A H A ! - 30.05.06
essential factor for Sometimes even the corrosion in the
only one.
a high quality of life Calcite deposits third millennium”
4 5
Compressed air
technology PN16 Cooling technology
Compressed air is now an integral
part of the manufacturing and
Chilled water Cooling systems
processing industries.
Pipe systems for chilled water cooling There are only a few types of plastic which
There are numerous tasks and the systems (from fan coil systems to ceiling are resistant to impact at low
solution is often simple. However, cooling systems) must be safe to use, temperatures, resistant to corrosion and
the quality of the piping and its flexible in design and quick to install. have a reasonable relationship of price
long term properties play a decisive to performance.
role in the safety and the costs. KEtrix® meets all these
requirements: CRYOLEN®, a polypropylene alloy
(POB = Polyolefine blend) meets these
● The highly secure welding joint requirements:
technology with a safety factor > 3
● High impact resistance at temperatures
The polyfusion welding ● NONOX® process ensures down to –30°C
technology assures clean, no oxygen diffusion
leak-free, secure and ● Resistant to glycol brines whatever
● Resistant to chemicals, aqueous the concentration
homogeneous joints.
solutions and water hammer,
Pressure rating: PN16 ● NONOX® process ensures
even at cold temperatures.
no oxygen diffusion
● Resistant to corrosion, even at points
Advantages where there is unwanted condensation ● Resistant to corrosion, even at points
Applications where there is unwanted condensation
● Complete fitting programme which and at temperatures around 0°C.
● Range: d 20 – d 125 has been adapted for each application
● Driving medium for tools such as All the necessary fittings and ● No pre-treatment (painting) of
drilling machines, hammer-drive adaptors ● The low weight and easy handling the pipes required
screws, grinding machines, means that many joints can be pre-
● High chemical resistance to manufactured in the workshop. ● Safe. In comparison to
pressure cylinders … compressor oils steel/copper/stainless steel a very
This saves time and costs
● Pneumatic control systems ● No corrosion. This ensures that quick welded joint
for machines ● KE KELIT pre-manufactures fitting
the quality of the compressed components which are required in
● Driving force for regulating fittings, air is maintained large numbers
Insulation
solenoid valves, shut-off devices, ● No energy loss caused by
valves … ● In most cases with cooling systems
leakage through dried seals
a specialist insulating contractor will
● Purification air at the workplace ● The smooth surface means there install the insulation with a suitable
are low friction losses and no and approved elastomer foam and
narrowing of the cross-section will ensure that it is sealed to stop
in the fitting. diffusion
As a result of the this and the
● Straight lengths of pipes are also
elasticity of the material there
available with polyurethane insulation
is a low noise transmission
(see pages 12 and 13)

A H A ! - 30.05.06
6 7
The raw materials Impermeability The NONOX® process
to oxygen
The polymer Metal thread fittings KE KELIT has developed a new
patented process:
KEtrix® is made of CRYOLEN® The molecular structure of the polymers
Polyolefine blend (POB). Special attention has been paid to the means that small amounts gases diffuse
choice and quality control of the metal The structure of the polymer alloy makes
A polypropylene alloy with excellent through the material at different rates.
threads. it possible to close the ”molecular pores”
properties.
by means of a ”redox” treatment.
The problem is well-known:
CRYOLEN® is a heterogeneous material O2 molecules can no longer diffuse
● Carbonated drinks should not lose
but for the purpose of testing is classified through the material.
as a type of PP-B in accordance with any CO2
ÖNORM B5174
● Many foods need to be protected The result
Density: 0.9 g/cm3 from the effects of O2
Melting point: ~ 140°C (fats, oils, milk cheese, meat…) KEtrix® pipes, which are made
Tensile strength: 40N/mm2 completely of plastic are
● On the other hand aromas should impermeable to oxygen when the
Elongation at tear: 800%
not escape wall thickness is a minimum
E-module (20°C): 1500 N/mm2 of 3,7 mm.
(coffee, jam, vegetables….)
Spec. heat: 2kJ/kg°C
Heat conductivity: 0.24 W/m°C ● Sheets act as water vapour barriers The material was tested to ÖNORM B5157
Spec. heat expansion: 0.14 mm/m°C Special quality properties: according to the zinc absorption method.
in buildings Pipes in water circulation
Impact resistance: – 30°C ● Dezincification resistant brass systems must not allow oxygen to
(MS 63, CZ 132) for all parts which diffuse through the pipe as this will Test reports by the TGM institute in Vienna
Remarkable properties transport water ensures a high showed the following results:
attack the metal components and
● Elastic despite high rigidity resistance to aggressive water. cause the following problems:
● Excellent chemical resistance ● A pore-free, chemically applied, – Corrosion (Iron, steel) Max. diffusion
for defined operating conditions nickel plating prevents stress crack – Incrustation defined by standard: 0.1 mg O2 /d . m3
corrosion. – Blockages Result for Ketrix: < 0.005 mg O2 /d . m3
● The raw materials conform to foodstuff
– Malfunctioning
regulations (LMG 1975) ● MS 58 brass with pore-free plating
– Expensive repairs
ÖN B5014 is used for metal components not in
● Colour: burgundy red contact with water
KEtrix® is unmistakeable ● The threads are designed to be In general these problems are solved
● Colour of the stripes: resistant to torsion and are suitable by using composite materials:
PN10 = blue for the building site.
PN16 = white ● Threads conform to DIN 2999 A combination of plastic material with
other materials which provide strength or
a barrier to oxygen diffusion E.g.
– EVOH to prevent O2 diffusion
Plastic threads – Fluorine polymers to prevent
Adaptor threads in sizes 1/2" and 3/4" are manufactured from H2O vapour
modified strong CRYOLEN® material (see list of parts). – PA to prevent diffusion of oils

A H A ! - 02.06.06
and fuels
Advantage: Socket side: easy to weld
– Metal to prevent the loss of aroma
Thread side: seal with PTFE tape!

8 9
Pipe system Dimensions: as specified by Operating conditions as specified Operating pressure in relation to
ÖNORM B 5174 by ÖNORM: service life and temperature
TRI 02 PN10 Colour: Burgundy red. 3 co-extruded PN10: 20°C/10 bar
blue lines (90° apart) help the plumber From –30°C to +40°C/9 bar Temperature Pressure Service life
KEtrix® pipe SDR 11
Oxygen barrier above d40 to align pipe and fitting Safety factor: Taking into account the (°C) (bar) (years)
dxs Flow rate L/m Standard length: 4 m properties of the raw material ÖNORM 10 16,6 50
20 x 1,9 mm 0,21 Other lengths can be produced on request B5174 includes a safety factor of 20 13,9 50
25 x 2,3 mm 0,33 subject to minimum quantities (SF=1.25) in the operating conditions 30 11,5 50
32 x 2,9 mm 0,54 Resistance to impact: –30°C given on the right. 40 9,3 50
40 x 3,7 mm 0,83
50 x 4,6 mm 1,31
63 x 5,8 mm 2,07
® ®
75 x 6,8 mm 2,96 TRI 02 Industrie-Rohr 50 x4,6 PN 10 gepr. CRYOLEN KE KELIT
90 x 8,2 mm 4,25
110 x 10,0 mm 6,36
125 x 11,4 mm 8,20
160 x 14,6 mm 13,44

TRI 08 PN16 Dimensions: as specified by Operating conditions as specified Temperature Pressure Service life
KEtrix® pipe SDR 7,4 ÖNORM B 5174 by ÖNORM: (°C) (bar) (years)
Oxygen barrier above d32 Colour: Burgundy red. 3 co-extruded PN16: 20°C/16 bar 10 26,3 50
dxs Flow rate L/m blue lines (90° apart) help the From –30°C to +40°C/10 bar 20 22,0 50
20 x 2,8 mm 0,16 plumber to align pipe and fitting Safety factor: Taking into account the
30 18,2 50
25 x 3,5 mm 0,25 Standard length: 4 m properties of the raw material ÖNORM
32 x 4,4 mm 0,42 Other lengths can be produced on request B5174 includes a safety factor of 40 14,7 50
40 x 5,5 mm 0,66 subject to minimum quantities (SF=1.25) in the operating conditions 50 9,6 50
50 x 6,9 mm 1,03 Resistance to impact: – 30°C given on the right.
63 x 8,6 mm 1,65
75 x 10,3 mm 2,32
90 x 12,3 mm 3,36 TRI 08 ®
Industrie-Rohr 25 x 3,5 PN 16 gepr. CRYOLEN
®
KE KELIT
110 x 15,1 mm 5,00
125 x 17,1 mm 6,48
160 x 21,9 mm 10,60

TRI 01 PN16 Colour: medium pipe and protective Operating conditions as specified Temperature Pressure Service life
KEtrix® ALU composite pipe layer are burgundy red. by ÖNORM: (°C) (bar) (years)
Oxygen barrier Standard length: 4 m PN16: 20°C/16 bar 10 26,3 50
dxs Flow rate L/m A layer of aluminium is bonded to the From –30°C to +40°C/10 bar 20 22,0 50
20 x 2,3 mm 0,19 medium pipe by a coupling agent. Safety factor: As a result of the
30 18,2 50
25 x 2,8 mm 0,30 This bonding reduces the expansion aluminium layer a PN 12.5 medium pipe
32 x 3,6 mm 0,48 considerably. can withstand the same operating 40 14,7 50
conditions as a standard PN16 pipe.

A H A ! - 30.05.06
® ®
TRI 01 ALU-Stabil-Rohr 32 x 3,6 PN 16 gepr. CRYOLEN KE KELIT

10 11
KEtrix®-CX: Design KEtrix® PE: The thermal
The modern solution The pre-insulated dynamics of PUR
Protective jacket:
for the problem of Spiral pipe made of galvanised steel
pipe for below insulated pipes
expansion (0.6mm). The fold is on the inside, ground installations
Heat loss: QR (W/m)
so the outside surface is smooth Common application: There will always be a transfer of heat
OD 80 – 250 mm Underground cooling pipelines between two warm media (either heat
Common applications: gain or heat loss)
Insulation:
Pipes in the cellar, garages, risers, Design The formula below is used to make the
industrial pipes in buildings Polyurethane hard foam, Protective jacket calculation
closed cell, CFC-free, Smooth, black HDPE pipe
Function: compression-proof OD 90 – 225 mm π (t1 – t2)
The KEtrix® raw material has a very low QR =
Insulation thickness meets or Insulation: da di da
elasticity module compared to steel. ln med ln man ln man
exceeds the requirements PUR foam, CFC-free 1
+ dimed + damed + diman +
1
This means that the expansion can be of. ÖNORM M 7580 λ-value: 0.030 W/ m°C αi · dimed 2λmed 2λpur 2λman αa· daman
restrained to ”zero” using very little force
and at the same time provide excellent
insulation against heat loss or heat gain. QR for KEtrix® CX
Exposed pipes in buildings
Fittings: Heat loss at an ambient temp. t2 = 20°C
Pre-insulated elbows and tees are Medium pipe Spiral jacket t1 t1 t1
available on request. Medium pipe: mm mm –20°C 0°C 30°C
d20 – 32 ALU composite pipe PN16 d 20 80 4,6 2,3 1,1
In general only non-insulated fittings are d40 – 110 KEtrix® pipe d 25 80 5,4 2,7 1,3
used which are then insulated at a later d 32 80 6,7 3,3 1,7
Available in either PN10 or PN16 d 40 80 8,6 4,3 2,2
point by specialist companies. Length of pipe: 6 m d 50 100 8,8 4,4 2,2
d 63 125 9,0 4,5 2,3
Medium pipe: KEtrix® PE fittings d 75
d 90
160
180
8,3
9,1
4,2
4,5
2,1
2,3
KEtrix® Elbow d 110 200 10,4 5,2 2,6
The surface of the pipe is pre-treated to
d20 – d110, 90° and 45° d 125 225 10,7 5,3 2,7
enable bonding d 160 250 13,8 6,9 3,5
d20 – 32 ALU composite pipe PN16 KEtrix® Tees
d40 – 160 KEtrix® pipe d20 – d110
equal tee and reducer tees
Available in either PN10 or PN16 QR for KEtrix® PE
are in our product range
Takes into account reduction of losses as a
Advantages Lengths of pipes: 6 m (not in stock) result of installation 0.7m under the ground
Heat loss when the earth temperature t2 =8°C
● Practically no linear expansion Medium pipe Jacket pipe t1 t1 t1
of exposed KEtrix® CX pipes mm mm –20°C 0°C 30°C
d 20 90 3,1 0,9 2,4
● Pipes can be clamped without the d 25 90 3,6 1,0 2,8
need to remove insulation d 32 90 4,4 1,3 3,5
Important: d 40 110 4,5 1,3 3,5
● High mechanical strength protects The K2S socket ensures a water-proof d 50 110 5,7 1,6 4,5
Any remains of PUR foam on pipes which joint. Each individual socket contains
against damage d 63 125 6,5 1,9 5,1

A H A ! - 30.05.06
have been cut to size must be completely detailed installation instructions. d 75 160 5,9 1,7 4,6
● Excellent heat insulation provided removed mechanically before the fusion d 90 200 5,6 1,6 4,4
Please follow these instructions.
by evenly distributed PUR foam welding can be done! d 110 225 6,2 1,8 4,9

12 13
The six ways of All KEtrix® fittings d 20-125 meet
Text
3. Threaded adaptor fittings Advantages:
joining the pipes the requirements of pressure rating Sizes:
Text ● Wide range of fittings
PN20 and can be used with both d 20 x 1/ 2" – d 75 x 2 1/ 2" ● Female thread is a
A wide range of safe and secure fittings PN10 and PN16 pipes. The threads conform to straight thread
for joining the pipes is essential for a pipe DIN 2999 and are made of ● Male thread is tapered
system. dezincification resistant brass and roughened
KE KELIT has a comprehensive range of (MS63-CZ132). They are metal- ● Thread is firmly anchored
plated to protect against stress
fittings for each method of joining in the fitting.
corrosion cracking. Male and female
threads are available as both High resistance to twisting
straight and elbow fittings. strain
1. Polyfusion welding Advantages:
Principle: ● Pipe and fitting are made
Fusion welding occurs when of the same material.
4. Flange connection Advantages:
a large area of the outside of No additional materials Sizes: d 40 – d 160 ● Can be detached at
the pipe and the inside of the are required. The solution for flanged fittings any time
socket are welded together. ● Welded joints are not a Backing ring conforms to ● Plastic EPDM seal
weak point in the system pipe sizes ● Dimensions conform
● Pipe can only enter the d 20 – d 125: fusion welding to DIN 2501-PN16
fitting after they have been d 160: butt welding
heated on the welding
machine
(important safety feature) 5. Detachable union Advantages:
● The weld does not cause fittings ● Detachable fittings
a reduction in the flow at Sizes: ● Plastic EPDM fittings
A wide range of fittings the joint d 20 x 1/ 2" – d 90 x 3" ● TRI 57 fitting for
is available connecting to appliances
Sizes: d 20 – d 125 3 types:

2. Butt welding Advantages:


● Pipe and fitting are
made of the same TRI 55-POB TRI 56-POB TRI 57-POB
material.
No additional materials 6. Electrofusion Advantages:
are required. welding ● Repair socket for areas
● Welded joints are not a
Sizes: d 20 – d 110 which are difficult to reach
Principle: weak point in the system
KELIT E-uni-welding sockets ● Welding machine
After the end of the pipe has been cut ● The weld does not cause
can be considered for available at KE KELIT
flat the face of the pipe and fitting are a reduction in the flow
welding in confined spaces ● Each fitting is packaged
simultaneously heated to melting at the joint
individually.

A H A ! - 30.05.06
temperature. They are then pressed Size: d 160 Instruction sheet and
together under pressure until the cleaning tissue are
material has cooled. enclosed.
14 15
1. The pipes and fittings are joined by
KEtrix® polyfusion polyfusion welding at 260°C. The welding
Welding times
welding with machines and tools are self-regulating.
Just connect to the electricity supply (230V)
Pipe OD Heating time Adjustment time Cooling time
mm sec sec min
the hand welding and wait:
The red light indicates that the machine is 20 5
machine connected to the electricity supply. 25 7
4 2
When the green light goes out the welding
temperature has been reached. 32 8
Work can begin. 40 12 6 4
Measure the length of the pipe required 50 18
(including the length of pipe required to weld
into the sockets). 63 24
1.1 Before welding the ALU composite
75 30 8 6
pipe sufficient aluminium must be removed 90 40
by the peeler to allow the pipe to be welded 110 50
to the full depth of the socket. 10 8
125 60
Important: There should be no aluminium
in the welding area. Make a visual check
before welding! Welding KEtrix® saddle
The pipe can then be welded to the fittings in
1.1 the same way as the standard KEtrix® pipe. fittings
The welding procedure 1. The surface of the pipes and saddle
2. Ensure that the surface of the pipes are fittings should be free of grease,
clean and free of grease. clean and dry.
2.1 Measure the depth of the socket and
mark the insertion depth accordingly. 2. A hole is drilled in the pipe using a
2.2 The heating time (see table) begins when 24 mm saddle drill.
the full insertion depth of the pipe and the
whole of the socket in the fitting have been
pushed on to the welding tools.
2.1 2.3 The heating time varies according to the
pipe size (see table). Once the heating time
has elapsed push the pipe and fitting together 3. If the saddle fitting is being connected
smoothly and evenly without delay. The result to an ALU composite pipe use the peeling
is a homogenous and strong joint. tool to remove the aluminium layer.
2.4 Three lines on the pipe (90° apart) act
as a guide for making a straight joint. 3.1 A wide range of fittings are available
2.5 The position of the fitting can be adjusted in different sizes.
for a few seconds (see table) immediately
after the pipe and fitting have been joined. A
short time later (see table) the joint is capable 4. Once the heating time is over the saddle
2.2 2.4 of withstanding operating conditions.
fitting is immediately pushed into the pipe
3. The low weight and high flexibility of wall (do not twist!) and pressed for approx.
the material makes it possible to weld whole 30 sec. The melting of both the pipe wall
sections of the piping at the work bench. Take and the pipe surface ensures a strong
advantage of this and save a lot of time.

A H A ! - 31.05.06
homogenous joint. After approx. 10 minutes
4. The pipes should be insulated according the joint can be subjected to operating
to the relevant national standards. conditions.

16 17
Table welding See pages 14 and 15 for welding The welding procedure: 1.
times and instructions on preparing
machine pipes and fittings for welding. 1. Fix the fitting in the clamp and the
fitting holder. Ensure that the face of
the fitting is flat against the clamp.
1. Screw the required heating elements 4. Set the pipe diameter switch to the 1.1 Put the pipe in the pipe clamp.
to the welding plate. The length of the required size. This switch regulates the Do not tighten the clamp.
heating plate varies according to the size length of the pipe that will be welded into
of the pipe and the section of pipe to be the socket. 1.2 Hold down the spacing button
and move the sliding blocks together using
welded.
the hand wheel until the pipe is touching
5. Spacing button
the fitting or the sliding blocks can no
2. One side of the fitting clamps can Press the button to fix the distance
longer move.
be used for small pipe sizes (d20-40). between the two sliding blocks which will
For larger sizes (d50-d90) the clamps enable the appropriate section of pipe 1.3 Release the spacing button.
should be turned around. and the complete socket of the fitting to Only now fix the pipe in the clamp.
be heated on the welding elements. 2.
2. Move the sliding blocks apart and
3. The same principle applies for the
pull down the welding plate.
pipe clamps. Note: The machine is available in
two sizes: 2.1 Move the sliding blocks together until
Type 1: d20 – 90 mm they are stopped by the lock.
Type 2: d25 – 125 mm 2.2 When the heating time has elapsed
move the sliding blocks apart briskly and
remove the welding plate.

Heating element 3. Push the sliding blocks together


Fitting clamp briskly until the pipe diameter switch
catches.
Welding plate
Fitting holder 3.1 Never cool the welded joint abruptly.
After a while loosen the clamp and the
finished joint can be removed from the 3.
Lock machine.
3.2 Once the cooling time has elapsed
the joint can be subjected to operating
Pipe clamp conditions.

Pipe OD Heating time Adjusting time Cooling time


mm sec sec min
20 5
4 2
25 7
32 8
40 12 6 4
50 18
Spacing button 63 24
75 30 8 6
90 40

A H A ! - 31.05.06
Pipe diameter switch Hand wheel 110 50
10 8
125 60

18 19
Overhead welding It is recommended to use the 1. Fix the pipe clamps to a pipe that has 1.
overhead welding machine for already been installed. The machine will 1.1 1.3
machine exposed piping in confined areas hang at the end of the pipe.
(d50 – d110) 1.1 To provide extra support the pipe
should be clamped close to a pipe bracket
1.2 A pole can be placed under the centre
of gravity to support the machine if
necessary.
Adjustable 1.3 The pipe should protrude far enough
pipe clamps out of the pipe clamp to ensure that the
(d50 – d110) Adjustable pipe can be fully welded into the socket of 1.2
are mounted on fitting clamps the fitting but also allow enough space for
sliding blocks (d50 – d110) the welding plate. 2. min. 100 mm
are fixed The space between the pipe and the
to the machine fitting when the sliding block has
been completely rolled back should
be approx. 100 to 150 mm.

2. Put the fitting in the clamp and support


the fitting with the fixing elbow. The fitting
must have sufficient room to move sideways
so that the whole of the socket can be 3.
welded.

3. Put the welding plate between the pipe


and fitting. Turn the hand wheel to move
3.1
the pipe and fitting. Heat the pipe and
fitting.

3.1 When the heating time is over remove


the welding plate and push the pipe and
fitting together briskly to weld the joint.
Hand wheel 3.2 When the cooling time is over the joint
for moving the can be subjected to operating conditions.
sliding block on Elbow for
the pipe side supporting
Hand wheel for Hand wheel for the fitting
fixing the pipes fixing the fitting
Pipe OD Heating time Adjusting time Cooling time
mm sec sec min
50 18 6 4
Centre of gravity
63 24
is marked below the machine

A H A ! - 31.05.06
75 30 8 6
90 40
110 50 10 8
20 21
Butt welding machine Welding plate 1. Loosen the screws and fit the required
reducers in the clamps.
for KEtrix® pipes 1.1 The end of the pipes should protrude
The table below is valid for the KELIT butt from the clamps by no more than 30 mm.
welding machine WZ115.
2. Put the surface cutter between the pipe
If you use other welding machines ends. Move the pipes together and remove
then follow the operating instructions the oxide layer on the welding surface by
for that machine. cutting away 0.2mm of the surface. Ensure
that the ends of the pipes are vertically

Time to build up pressure


parallel to each other (maximum deviation:

Max. change-over time

Welding pressure
Heating pressure
Joining pressure

Height of bead 0.3 mm). The maximum deviation

Heating time

Cooling time
horizontally is 0.5 mm.
SDR series

Surface cutter
Pipe

3. The welding procedure


dxs bar mm bar sec sec sec bar min (see table on the left for welding criteria)
160 x 14,6 11 27 1,0 3 277 8 13 27 24 3.1 Before welding begins read off the
160 x 21,9 7,4 38 1,5 4 359 10 19 38 34
IMPORTANT:
manometer the pressure required to bring
The pipes cannot be touched and must be
the pipes together. This pressure must be
Hydraulic welded immediately.
added to the joining pressure given in
control unit; If this is impossible and the welding has
the table.
Plug connection to be done later then the welding surface
for welding plate 3.2 Insert the heating element (temp: has to be cleaned and any grease
and surface approx. 210°C). Press the pipe ends on the removed.
cutter heating element and apply the pressure
as defined in 3.1 until a bead forms around
the complete circumference of the pipe.
During the heating time the pressure
must be reduced to the heating pressure.
Once the heating time is over move the
sliding blocks apart rapidly and remove the
heating element. m
30m
3.3 The change over time (time between
removing the heating element and welding
the pipes) should be as short as possible.
3.4 The welding pressure should be
built up as smoothly as possible during the
time given in the table
(minimum: 0.15 N/mm2). Never cool the joint abruptly.
3.5 The welding pressure must be If the weld has been done correctly a
maintained during the cooling time. double bead should be visible around the
whole circumference of the pipe.

A H A ! - 01.06.06
30 mm

Pipe clamps

22 23
KELIT E-Uni 6. The operating instructions are
6.
located in the cover of the E-socket 6.1
Welding socket welding machine. Please read them
before switching on the machine.
Connect to the electricity supply Ein
Schweißvorgang
läuft
6.3
Schweißbeginn
1. 4. (230V +/-10%, 50 Hertz). Schweißvorgang
Schweißvorgang
bendet
falsch 6.4
angeschlossen Rückstellung
Schweißmuffe

ffen-230V -4A-1
000W-50Hz 6.5
Ensure that the cable is TOP 110 Elektro-Schweißmu

completely unrolled to avoid 6.6


inductive loss of voltage.
6.1 Turn on the main switch. The 6.2
light next to ”Power” will switch on.
1. Cut the KEtrix® pipe at 4. Remove any grease from the end of 6.2 Connect the welding cable to
right angles. the pipes and the electrofusion sockets the socket. The light next to
in the areas where the weld is going to ”Sleeve connected” will switch on.
2. be made. This should be done with the
cleaning tissue (soaked in isopropyl 6.3 Press the ”start” button. The
alcohol) which is supplied with the light next to ”welding in process”
E-socket. will switch on. 6.5 Press the ”Reset” button before
No oil-based solvents (e.g. paint thinner) The welding machine calculates the each new weld.
should be used to clean the socket. welding time automatically.
6.6 If there is a defect ”Incorrect
5. 6.4 When the welding time is over welding” and ”Welding over” will
the machine will switch off and the light up. Establish the cause and if
2. Scrape the surface of the KEtrix® light next to ”Welding over” will necessary wait for one hour for the E-
pipe with a suitable tool, e.g. a blade come on. Check whether the orange socket to cool down, press the ”reset”
(DO NOT use sandpaper). tracers have emerged from the sockets button and start again with the
to show that the weld has been procedure in point 6.
A thin layer must be removed from the successfully completed.
pipe. At the same time the diameter should
not be reduced below its nominal value. 5. By cutting out the buffer in the middle 7. Ensure that the electrofusion
of the socket the e-socket can be pushed socket is axial to the pipe and is not 8.
completely over the pipe. subjected to stress or strain during
3. 5.1 welding.
8. Ensure that no moisture is present 7.
either inside or outside the welding
zone during welding.
9. Ensure that the weld is not
subjected to stress, impact, moisture 9.
or any other strain during the cooling
3. Alu peelers are available for removing 5.1 In order to guarantee the central period (allow at least 10 minutes for
the aluminium layer from the Alu pipes position of the weld, mark the welding cooling).

A H A ! - 20.06.06
(please note that more aluminium has to depth of the socket on the pipe. For pipes 10. Wait for at least one hour before 10.
be removed from an electrofusion socket which are being installed horizontally try pressure testing or subjecting to
than for a standard socket). to ensure that the tracers point upwards. operating conditions
24 25
Pipe sizing for glycol The viscosity of glycol water fluids is much For other cooling brine solutions
higher than water. The pressure losses (e.g. potassium formate or acetate with
brine solutions must be adjusted by the factors in the corrosion inhibitors)
following charts and as a result the the data will vary according to the product.
The KEtrix® pipe system is resistant to required pipe sizes are larger Please follow the instructions given by the
water/glycol fluids. Standard products (see pages 32 and 33). manufacturer.
contain inhibited ethylene glycol or
propylene glycol (for foodstuff). Relative pressure loss in comparison to water (+10°C) when there is turbulent flow
The following charts can be used for sizing Ethylene glycol-water fluids Propylene glycol-water fluids
Ethylene glycol-water fluids Faktor
the pipes. 3,0
Propylene glycol-water fluids
2,5
100% (V/V) 100% (V/V)

Anti-freezing 80 2,0 80
of ethylene glycol -water fluids of propylene glycol- water fluids
52 47
(crystallisation point according to DIN 51 782) (crystallisation point according to DIN 51 782) 44
1,5
38
±0 34
25
20 1,0
0 = Water 0 = Water
fluid -10 fluid
0,5
-20 ±0 +20 40 60 80°C -20 ±0 +20 40 60 80°C
-20
bursting effect bursting effect
Pressure loss in Calculation of the pressure loss (Z)
below the anti- below the anti-
freezing point freezing point for the standard fittings:
(solid) no
-30 (solid) no KEtrix® drinking 2
bursting bursting Z=ζ· v
effect
-40
effect water pipes 2
(frazil ice) (frazil ice)
Fitting Symbol Coefficient
The total pressure loss (∆p) of the KEtrix® ζ
-50 pipe system is calculated by multiplying
0 10 20 30 40 50 60 0 10 20 30 40 50 60
the friction loss (R) by the length of the Elbowl 90° 1,3
% (V/V) % (V/V)
piping (l) plus the sum (∑) of the friction Elbow 45° 0,4
loss for the individual fittings (Z). Tee-flow
Specific heat
0,3
Ethylene glycol-water fluids kj Propylene glycol-water fluids
4,4
Total pressure loss ∆p Tee-flow
Water Water ∆p = (l . R + ∑ Z) in Pa separation 1,3
0 4,2 0
4,0 16 Tee-
20 25 The choice of pipe size for the water
34 3,8 38 reverse flow 1,5
47 supply is dependent on the following
44 3,6
factors: Reducer 0,4
57
52 3,4 ● The available water pressure Stop valve
60
3,2
80
● Geodetic difference in height d20 10,0
3,0 ● Pressure losses through system components d25 G 8,5
80
● Minimum flow pressure through faucets
2,8 d32 8,5
100% (V/V) ● Pressure losses in the pipes
100% (V/V) 2,6 ● The individual pressure losses of the fittings Slanted seat valve
Boiling point Boiling point

A H A ! - 21.06.06
2,4 ● Type, number and simultaneous use of d20 3,5
Anti-freezing Anti-freezing the draw-off points
2,2 d25 S 2,5
-40 -20 0 +20 40 60 80 100 120 140 160°C -40 -20 0 +20 40 60 80 100 120 140 160°C ● Flow velocity d32 – 63 2,0
26 27
Guidelines for 3. Use of total flow rate / peak 6. Minimum flow pressure and design flow rate for typical
flow rate Draw-off points and appliances
pipe sizing The design flow rate of all draw-off Minimum Type of draw-off fitting or Design flow rate
(DIN 1988/3) points shall be included in the design
flow
Pressure
appliance Mixed water*) Cold water only
of water supply system, adding the flow V̇R V̇R V̇R
Bar cold l/s hot l/s l/s
rate of the draw-off points for which
1. Determine the design flow rate continuous use is to be assumed to the Taps KEtrix KELEN KEtrix
0,5 without jet regulator DN 15 – – 0,30
and minimum flow pressure for peak flow rate of the draw-off points 0,5 DN 20 – – 0,50
all the draw-off fittings. (continuous use being defined as use 0,5 DN 25 – – 1,00
The design flow rate VR is derived from lasting more than 15 minutes) 1,0 with jet regulator DN 10 – – 0.15
the draw-off fitting flow rate. The table Assumptions regarding simultaneous 1,0 DN 15 – – 0,15
below gives guideline values for the demand are to be based on the type 1,0 Shower
of building or its occupation (e.g. heads DN 15 0,10 0,10 0,20
design flow rate of common types of
residential building or communal 1,0 Flushing valves
fittings and appliances. for urinals DN 15 – – 0,30
The design flow rate VR may be facility).
1,0 Domestic
determined as a mean value using the Normally it may be assumed that not Dishwasher DN 15 – – 0,15
following equation: all draw-off fittings are fully open at 1,0 Domestic
the same time. washing machine DN 15 – – 0,25
The conversion curves for the different Mixing valves for
V̇R = V̇min + V̇max applications are shown on pages 30 1,0 showers DN 15 0,15 0,15 –
2 and 31. 1,0 baths DN 15 0,15 0,15 –
1,0 kitchen sinks DN 15 0,07 0,07 –
1,0 wash basins DN 15 0,07 0,07 –
1,0 sitz baths DN 15 0,07 0,07 –
2. Determine total flow rates and 4. Determination of diameter 1,0 Mixing valves DN 20 0,30 0,30 –
assign to pipe runs Determine the pipe size, pressure loss 0,5 Flushing cistern
The design flow rates for all draw-off and flow velocity (see pressure loss DIN 19 542 DN 15 – – 0,13
points shall be added, starting at the charts on pages 30 and 31) *The values specified are based on a temperature Note:
draw-off point furthest from the water of 15°C for cold water and 60°C for hot water ● For any outlets or apparatus not included
above or similar to the above with a
main and ending at the water main, different flow rate please follow the
and the total flow rates so obtained 5. Evaluation of head loss in terms manufacturers instructions regarding the
assigned to the pipe runs considered, of available pressure 7. Maximum flow velocity sizing of the pipes.
each run extending from the fitting The head loss shall be almost equal to according to DIN 1988
where the total flow rate or pipe ● For the purpose of pipe sizing it is assumed
but not greater than the available total Maximum design that there will be no reduction in the
diameter changes until the next fitting. head loss flow velocity for a
internal diameter caused by incrustation
Type of pipe run given pipe run
since the surface structure of the pipe is
≤ 15 min >15 min
At the junction of the cold water m/s m/s amorphous and the surface roughness of
the pipe is minimal (0.007).
pipe feeding the water heater with Service pipes 2 2
the pipe branches off, the total Supply mains:
flow rate comprises that of the Pipe runs with low
cold and hot water side.
head loss in-line valves The partner system
(ζ < 2.5 ) 5 2
In-line valves For hot water systems use the
with greater
KELEN® pipe system in either

A H A ! - 23.06.06
loss factor 2.5 2
PN16 or PN20 pressure rating,
made of grey PP-R material.

28 29
Excerpt from Excerpt from
DIN 1988/3 DIN 1988/3
Peak flow rate V̇S as function of total flow rate ∑ V̇R Peak flow rate V̇S as function of total flow rate ∑ V̇R
30 30 30 30

20 Residential buildings 20 20 Hotels 20


15 15 15 15
Office buildings Department stores G H
10
E 10 10 10
Schools Hospitals I
Peak flow rate V̇S in l/s

Peak flow rate V̇S in l/s


7 7 7 7

5
C B 5 5 5
4 4 4 4
3
D 3 3 3

2 2 2 2
1,5
B 1,5 1,5
K 1,5

1
A
1 1 F 1

0,7 0,7 0,7 0,7


0,5 0,5 0,5 0,5
0,4 0,4 0,4 0,4
0,3 0,3 0,3 0,3

0,2 0,2 0,2 0,2


0,15 0,15 0,15 0,15

0,1 0,1 0,1 0,1


0,1 0,15 0,2 0,3 0,4 0,5 0,7 1 1,5 2 3 4 5 7 10 15 20 30 40 50 70 100 150 200 300 400 500 0,1 0,15 0,2 0,3 0,4 0,5 0,7 1 1,5 2 3 4 5 7 10 15 20 30 40 50 70 100 150 200 300 400 500

Total flow rate ∑ V̇R in l/s Total flow rate ∑ V̇R in l/s

Calculating the peak flow rate V̇S Calculating the peak flow rate V̇S
Type of building Curve Application: Curve Application: Type of building Curve Application: Curve Application:
∑ V̇R ≤ 20 l/s ∑ V̇R > 20 l/s ∑V̇R ≤ 20 l/s ∑V̇R > 20 l/s
Residential
buildings A B V̇S =1,7. (∑ V̇R)0,21 – 0,7 in l/s Hotels F G V̇S =1,08 . (∑ V̇R)0,5 – 1,83 in l/s

Office V̇S = 0,682 . (∑ V̇R) – 0,14 in l/s


0,45
Department
A C V̇S = 0,4 . (∑ V̇R)0,54 + 0,48 in l/s F V̇S = 0,698 . (∑ V̇R)0,5 – 0,12 in l/s H V̇S = 4,3 . (∑ V̇R)0,27– 6,65 in l/s
buildings stores

Schools D V̇S = 4,4 . (∑ V̇R)0,27 – 3,41 in l/s E V̇S = -22,5 . (∑ V̇R)– 0,5+11,5 in l/s Hospitals F I V̇S = 0,25 . (∑ V̇R)0,65 + 1,25 in l/s

Residential buildings Special case Hotels, department stores, hospitals Other special buildings,
An additional wash basin, sitz bath, WC, If the system is equipped with draw-off If the system is equipped with draw- commercial and industrial
urinal, and shower unit (in addition to the fittings with a design flow rate of off fittings with a design flow rate of premises
bath tub) need not be allowed for in V̇R ≥ 0,5 l/s then, where the total flow V̇R ≥ 0,5 l/s then where the total flow Particular considerations must be given
determining the total flow rate if it may rate is between 0,5 l/s and rate is ≤ 1,0 l/s the peak flow rate shall to the extent to which simultaneous
be assumed that the level of simultaneous 1,0 l/s the peak flow rate shall be be deemed to be equal to the total flow demand is to be assumed for water
use will not be increased by the use of deemed to be equal to the total flow rate. rate. If the total flow rate is >1,0 l/s supply systems on commercial and trade
their appliances. If the total flow rate is ≥ 1,0 l/s curve and ≤ 20 l/s curve K (equation: V̇S premises. The total flow rate is
B shall be used. =(∑V̇R)0,366 in l/s) is used for calculating determined in consultation with the
Schools operator of the system.
the peak flow rate.

A H A ! - 23.06.06
The peak flow rate is deemed to be
equal to the design flow rate where
∑VR ≤ 1,5 l/s
30 31
Pipe sizing and The pressure losses for water (10°C) are Pipe sizing and The pressure losses for water (10°C) are
calculated according to the ”Nikuradse” calculated according to the ”Nikuradse”
pressure losses formula: pressure losses formula:
for the KEtrix® R = 9,87161 . 10 7 . ṁ1,75580 . di -4,80112 for the KEtrix® R = 9,87161 . 10 7 . ṁ1,75580 . di -4,80112
pipe system PN10 Surface roughness: 0,007 mm pipe system PN16 Surface roughness: 0,007 mm
R = pressure loss [mbar/m] If glycol brines are the medium then the R = pressure loss [mbar/m] If glycol brines are the medium then the
ṁ = mass flow [l/s] extra factors described on pages 26 and ṁ = mass flow [l/s] extra factors described on pages 26 and
di = pipe inside diameter [mm] 27 must also be accounted for. di = pipe inside diameter [mm] 27 must also be accounted for.
1 mbar = 100 Pa 1 mbar = 100 Pa

KEtrix® pipe system PN10, d20 – 160 KEtrix® pipe system PN16, d 20 – 160

0,3
KEtrix® ALU pipe d20 – 32 KEtrix® ALU pipe PN16, d 20 – 32
180 180
AL AL AL

Flow rate l/h


Ud 200 U 200

0,5
Ud

Flow rate l/h


25 20 d2
x2 x2 250 0x 250
,8 ,3 2,3
AL 300 AL 300

0,8
Ud U d2
32 400 5x 400
x3 2,8

1,0
,6 AL
500 500
Ud
600 32 600

1,5
700 x3 700
d2 ,6
0x 800 800
1,9

2,0
0,3
900 900
1.000 1.000

2,5
d2
5x

3,0
2,3 1.500 1.500
d2
d3 2.000 0x 2.000
2x 2,8
2,9
2.500 2.500
d2
3.000 5x 3.000
3,5
4.000 4.000
d3
5.000 2x 5.000
4,4
6.000 6.000
7.000 d4 7.000
8.000 0x 8.000
9.000 5,5 9.000
d4 10.000 10.000
0,3

0x d5
3,7 0x
15.000
6,9 15.000
d5
0x d6
4,6 20.000 3x 20.000
8,6
d6 25.000 d7 25.000
3x 30.000
5x 30.000
0,5

5,8 10
d9 ,3
d7 40.000 0x 40.000
5x 12
6,8
0,8

Flo 50.000 ,3 50.000


d9 d1
w 0x Flo 10
1,0

60.000 60.000
ve 8,2 70.000 w d1 x1 70.000
loc d1 ve 25 5,1
ity 10
80.000
loc x1 80.000
90.000
ity 90.000
1,5

m/ x1 100.000
7,1 100.000
d1 0,0 m/
s 25 d1
2,0

x1
1,4
s 60
x2
150.000 1,9 150.000
2,5

d1
60
3,0

200.000 200.000
x1
Pressure loss 4,6
250.000 Pressure loss 250.000
280.000 280.000

A H A ! - 23.06.06
20

25
30

40

4000
5000
6000
50
60
70
80
90
100

150

200

250
300

400
500
600
700
800
900
1000

1500

2000

2500
3000

7000
8000
9000
10000
10

4000
5000
6000
15

20

25
30

40
50
60
70
80
90
100

150

200

250
300

400
500
600
700
800
900
1000

1500

2000

2500
3000

Pa/m Pa/m

1 1,5 2 3 4 5 6 7 8 10 15 20 30 40 50 60 80 100 150 200 300 400 500 600 mm/WS 2 3 4 5 6 7 8 10 15 20 30 40 50 60 80 100 150 200 300 400 600 800 1000 mm/WS

32 33
Compressed air The compressed air The main pipeline
The sum of the required supply to all of
technology PN16 network PN16 the distributor pipes
The distributor pipelines
The long-term advantage of compressed If the compressed air is to be supplied
The quality of air technology is dependent on two factors: centrally a pipe network will be required
The distributor pipelines transport the
compressed air from the main pipeline to
compressed air ● Compressed air to supply the air to the individual units. the connecting pipeline. If possible this
The compressed air can be divided into ● Compressed air network In order to operate efficiently the network pipeline should be a circulation pipeline.
different quality categories which can be has to fulfil the following requirements:
classified according to the application. The advantage of a circulation pipeline
The pressure dew point ● Sufficient volume flow compared to a direct pipeline:
Class Pressure dew point
As a result of the compression of the air the 1 – 70° C – for each unit A circulation pipeline is a closed circuit.
water content in the compressed air rises 2 – 40° C ● Required working pressure It is possible to shut off sections of the
greatly. Drying the air reduces the formation 3 – 20° C – for each unit pipe network without disrupting the supply
of condensation inside the system to the 4 + 3° C of compressed air in other parts of the
minimum possible. The pressure dew point ● Quality of the compressed air
5 + 7° C
is the temperature at which the water within 6 + 10° C – to ensure that system operates network. This will increase the economic
the compressed air starts to condense and is smoothly efficiency and operational security of the
categorised in different classifications. Max. Max.
● Pressure loss system. In a circulation pipeline the
size of particle concentration of particle
The solids – as low as possible compressed air has less distance to travel
Class mikro/m mg/m3
Solid impurities found in the air are also 1 0,1 0,1 ● Operational liability than in a direct pipeline system. This
present in compressed air and must be 2 1 1 – maintenance and repairs should will mean a lower pressure drop; ∆p.
reduced by filtration. The particle sizes and 3 5 5 not shut down the whole network In a circulation pipeline the size of
concentrations are specified in different 4 15 8
5 40 10
● Safety requirements the pipe is calculated with half the
classifications.
– to prevent accidents flow volume of a direct pipeline.
The oil concentration Oil concentration
Compressors require at least some lubricating Class mg/m3 Connecting pipeline
The connecting pipelines branch off from
oil for the working process. Depending on
the application various procedures must be
1
2
0,01
0,1
The pipe network the distributing pipelines. Since the outlets
undertaken to remove this oil from the 3 1 are all operated at different pressures a
compressed air. The oil concentration is also 4 5 Option: Direct pipeline
Connecting pipeline monitor unit including a pressure regulator
divided into different categories 5 25 7 is usually installed by the outlet.
Direct pipeline
The type of flow
Laminar flow Conclusion:
The laminar flow is an evenly The flow velocity of 5
distributed flow 3
compressed air in pipelines
Vmax
● Low pressure loss is usually 2 – 3 m/sec and
● Low heat transfer should not exceed 20 m/sec 4 2
Main pipeline 6
in order to avoid noise and Option: Circulation pipeline
turbulent flow. Connecting
pipeline 7
1
Turbulent flow 1 = Compressor
The turbulent flow is an uneven 2 = Shut-off valve
flow. Small whirls are formed 3 = Compressed air tank
Vmax 4 = Steam trap

A H A ! - 26.06.06
in the flow current 5 = Safety valve
● High pressure loss 6 = Compressed air dryer
● High heat transfer 7 = Compressed air connections
Circulation pipeline
34 35
Pipe sizing for Requirement for compressed air
for tools
Pipe sizing of PN16
compressed air The volume flow must account for the pipes by using the graph
requirements of all the tools and
systems PN16 appliances. It is easier and quicker to calculate the Example: Main pipeline
Machine and tool manufacturers can pipe size by using the nomograph V̇ = flow volume: 13 l/s
For economic reasons it is important to provide information about the air below. The determining factors are the p = operating pressure: 8 bar
calculate the pipe sizes accurately. requirements for their appliances. same for both methods of calculating l = fluidic pipe length: 150 m
Any calculation factors for simultaneous the pipe size. ∆p = pressure drop: 0,04 bar
The main factors affecting the size of the use are to be specified by the consultant
pipe are as follows: Pipe size PN16: d 40
or operator since there are no empirical
values that can be considered a basis for
● V̇ = Total volume flow [l/s] calculation. Length of the pipeline l [m]
● l = Fluidic pipe length [m]) 1 2 5 10 20 50 100 200 500 1000 2000
The equivalent pipe lengths of the Air requirement for compressed air tools 0,8
First of all read off the point where the 0,9
elbows, fittings or other units must Blow-out gun approx. 2-8 l/s flow volumeV̇ and operating pressure p
1

be added. Colour spray-hobby approx. 2-4 l/s meet. Then follow the arrows as shown 1,5
● p = operating pressure [bar] Colour spray-professional in the example below.
is dependant on the cut-in pressure approx. 3-6 l/s 20 2

of the compressor Impact screw driver-hobby


3
● ∆p = pressure drop [bar] approx. 4-6 l/s
The max. pressure drop in the Impact screw driver-professional 25 4

individual sections of piping should approx. 5-8 l/s 5

not exceed the following: Right angle grinder approx. 5-8 l/s 6
32 7
Eccentric grinder approx. 3-5 l/s 8

Pipe OD PN16 d [mm]


Main pipeline: ≤ 0,04 bar
Drill approx. 4-6 l/s 9
10
Distributing pipeline: ≤ 0,04 bar Nibbler approx. 2-5 l/s

[l/s]
Circulation pipeline: ≤ 0,04 bar 40
15
Connecting pipeline: ≤ 0,03 bar
The total pressure loss in the complete Equivalent pipe lengths 20

Flow volume
network should be ≤ 0,1 bar. An important factor when calculating the 50
sizes of the pipes is the length of the pipes. 30
Elbows, valves and other fittings greatly 40
Calculation of the inside diameter increase the flow resistance in the pipes 63 50
of the pipe and must be accounted for. 60
To make the calculation easier the flow 70
The required inside diameter (di) can be 75 80
calculated using the following formula: resistance in the various fittings is 90
100
converted into the equivalent pipe lengths.
450 x V̇ 1,85 x l 0,2
The table below shows the equivalent pipe
90
di = 150
∆p x p length for the fittings in different sizes:
200
110

Equivalent pipe lengths in m for compressed air systems 300


Size d20 d25 d32 d40 d50 d63 d75 d90 d110 d125 125 400
Elbow 90° 0,8 0,9 1,2 1,5 1,9 2,5 3,0 3,5 4,3 5,2 500
Elbow 45° 0,2 0,3 0,3 0,4 0,5 0,7 0,8 1,0 1,2 1,3 600
700
0,9 1,2 1,5 1,8 2,3 2,9 3,4 4,1 5,1 6,3 800
Tee 900

A H A ! - 27.06.06
1000

0,03
0,04
0,05
Reducer 0 0 0 0,1 0,1 0,1 0,1 0,1 0,2 0,2 0,002 0,01 0,1 0,2 0,5 1 2 4 6 10 15

Ball valve 0,1 0,1 0,1 0,2 0,2 0,3 0,3 0,4 0,5 – Pressure loss ∆p [bar] Operating pressure p [bar]
36 37
Expansion behaviour Expansion arm for Force of heat Practical solutions for
of KETRIX pipes exposed piping expansion compensating
Compensation must be made for the The force of linear expansion is different
expansion
Linear heat expansion of KEtrix® pipes under heat for each material. The specific force of
The following methods can be used to
conditions. heat expansion is calculated according to
expansion the following formula:
control the linear expansion and the force
Even if the rise in temperature is only for of expansion.
Under heat conditions all materials a short time sufficient compensation must Ft = E · A · α · ∆ t
● Piping that is embedded in the
increase in volume and/or length be made for this temperature difference. 1000
floor or the wall is prevented
according to the following formula: Compensation is always made between a E = E-module of KEtrix® [N/mm2] from expansion by frictional
fixed point and a change in direction of A = Cross sectional surface force. No extra measures are
Calculation of the linear expansion: the piping (expansion arm). area of pipe [mm2] required.
α = Coefficient of expansion [mm/mC°]
∆ l = l · ∆t · Calculation of the expansion arm: ∆ t = Difference between temperature ● Every change in temperature will
at time of installation and exert a force.
l = length [m] MS = 22 · d · ∆ l operating > temperature [°C]
∆ t = difference between temperature F t = force of expansion [N] An expansion force will occur when
22 = coefficient for KEtrix®
at time of installation and ∆l = change in length [mm] the temperature rises.
operating temperature [°C] The force of heat expansion A force of contraction will occur when
d = outside diameter of pipe [mm] (or cooling contraction) is dependant
α = coefficient of expansion MS = Minimum length of the the temperature falls.
on the dimension of the pipe and
[mm/m°C] expansion arm [mm] ● Suppliers of pipe clamps and brackets
the change of temperature but not
∆ l = expansion [mm] Length of pipe which branches know the properties of the materials
on the length of piping.
off at 90° from the main pipe to and offer a range of solutions.
The linear expansion is determined the next fixed point. An important factor is the rigidity of the
by the length of the pipe, the material (E-module). ● Pipe channels may be used to increase
Example: the stability of the pipe.
increase in temperature and the The E-module of Cryolen (like any other
A d50 pipe runs over a length of 15 m.
coefficient of expansion. plastic) is dependent on the temperature The expansion is reduced to the same
∆ t = 18 °C.
It is not determined by the diameter Question: How long does the expansion (see graph below) value as steel pipes.
of the pipe. arm have to be to compensate for the > Temperature < E-module ● Compensation must be made for
expansion? < Temperature > E-module expansion of exposed piping.
Coefficients ∆ l = 15 · 18 · 0,14 The force of heat expansion is therefore
● Think of the option of using
an important criteria when planning an
of expansion ∆ l = 37,8 mm expansion installation. KEtrix®-CX pipes. The expansion of
exposed piping is effectively restricted
Steel α = 0,012 mm/m°C MS = 22 · 50 · 37,8 E-module of cryolen and they provide excellent insulation
2300
Copper α = 0,016 mm/m°C MS = 956 mm expansion arm 2200 against heat gain and heat loss.
KELOX® α = 0,025 mm/m°C 2100
● The expansion can be minimised by
Length of piping l 2000
KEtrix® ALU α = 0,030 mm/m°C 1900 installing the Ketrix ALU pipes
1800
KEtrix® α = 0,140 mm/m°C 1700
(d20 – 32). This pipe reduces the
E-module in N/mm2

PEX α = 0,175 mm/m°C 1600 expansion by approx. 75%.


d 50 mm 1500
1400
FP MS 1300 The force of expansion can be
This means that when heated 1200
KEtrix® will expand more than 1100 calculated for every installation.
1000 However, in general the force is

A H A ! - 27.06.06
metal materials if the expansion 900
is unhindered. 0 10 20 30 40 50 just a fraction of the force which
Medium temperature [tm] in °C occurs with metal materials.
FP
38 39
Installing KEtrix Guidelines for Condensation
In order to prevent corrosion or
Installing the pipes in the shaft distance between disruptions in the operation of the system
In practice the main risers can expand and contract pipe support points attention must be paid to any
laterally in the shaft between two floors if a fixed condensation that is formed:
point is located next to the pipe that branches ● The distances between the support a) by effective air drying
off from the main pipe. The distance between two fixed points given below (in cm) prevent (zeolite, silica gel ….)
points should not exceed 3 m. Other methods can be KELEN pipes from sagging when they
used to accommodate expansion such as an expansion b) by a water trap before the
are filled with water and there are NO connections to the apparatus
arm in the pipe branching off from the riser. pipe channels.
c) by installing a ”swan´s neck”
● Pipes containing compressed air are joint to the connecting pipeline.
subject to much greater changes in
length than pipes filled with water c)
Exposed piping when the temperature fluctuates as
Preventing expansion by mechanical restraint the medium has no cooling effect.
d20 – d50 Longer runs can be split up into
In order to achieve this stability all of the pipes must expansion zones and the fixed points
be supported by pipe channels and all of the brackets located accordingly.
must be fastened tightly to the pipe to make them
fixed points. In addition the channels are fixed to the Suppliers of pipe clamps and brackets
pipe (e.g. using cable ties)*. know the properties of the materials
This method reduces the and offer a range of solutions.
linear expansion to the same max. 180 cm
amount as steel.
Size KEtrix® PN10 KEtrix® PN16
Up to size d32 KEtrix Alu
0°C 20°C 30°C 0°C 20°C 40°C
pipes are usually preferred. *Pipe channels in sizes d20, d25
d20 80 75 65 85 80 70
and d32 are self-locking.
d20 ALU 130 120 115 130 120 110
d25 85 80 75 90 85 80
d25 ALU 140 130 125 140 130 120
Expansion loops d32 105 95 85 110 100 90
d63 – d160 d32 ALU 150 140 135 150 140 130
All changes in the direction of the pipe can be used to d40 115 105 100 120 110 105
accommodate the linear expansion. In some cases an d50 130 120 115 135 125 120
expansion loop will be necessary. d63 145 135 125 150 140 130
The fixed points are arranged d75 175 165 155 180 170 160
so that the piping is divided d90 195 185 175 200 190 180
into sections and the MS d110 205 195 180 210 200 185
expansion force can be guided SP SP
d125 215 210 195 220 215 200
in the desired direction.
See page 38 for the d160 240 235 215 245 240 220

A H A ! - 27.06.06
calculation of the length FP FP
minimum (mm) For sizes d20 – 32 we recommend the use of pipe channels. If pipe channels are used
of the expansion arm. . 2 ∆l + 150 then we recommend a maximum distance of 180 cm between the support points

40 41
Pressure testing b) Preliminary testing Drinking water – Pressure test report
for drinking water The test pressure is equal to the maximum
operating pressure of the system plus 5
systems bar (minimum: 15 bar). The test pressure Location:
must be built up over a period of 30
KE KELIT recommends pressure testing to minutes. Within the 30 minutes the Project:
DIN 1988/2 for plastic pipes as stated pressure should be re-adjusted 2 times
below. (each time 10 minutes apart). After a Length of piping: d 20 _____ m Length of piping: d 75 _____ m
As a result of the material properties of further period of 30 minutes under Length of piping: d 25 _____ m Length of piping: d 90 _____ m
plastic pipes the pipe will expand during pressure testing there should be no leaks
Length of piping: d 32 _____ m Length of piping: d 110 ____ m
the pressure testing. The pressure testing and the drop in pressure should not
exceed 0,6 bar. Length of piping: d 40 _____ m Length of piping: d 125 ____ m
is split into a preliminary test and a main
test. The preliminary test is sufficient for Length of piping: d 50 _____ m Length of piping: d 160 ____ m
small sections of the piping such as c) Main testing
Length of piping: d 63 _____ m
connecting pipes and distributing pipes The main testing should be carried out
in the wet rooms. immediately after the preliminary testing. Test: Yes No
The duration of the test is 2 hours. The
a) Preparation drop in pressure between the end of the Visual check:
preliminary testing and the end of the 2
1. After the pipes have been installed hour main test must not exceed 0,2 bar. Test pressure: ___ bar (minimum: 15 bar)
and before they are concealed the
piping is filled with water and any air After the pressure testing has been
Preliminary test:
removed. completed we recommend issuing a
Testing time = 60 min.
2. If possible the pump should be placed confirmed report. ___ bar (max. pressure drop: ≤ 0,6 bar)
Pressure after 1 hour:
at the lowest point in the system
3. The manometer should be capable Please note:
Main test:
of reading changes in pressure of ● Fluctuations in the temperature
Testing time = 120 min.
0,1 bar and should be placed at the may alter the test pressure ___ bar (max. pressure drop: ≤ 0,2 bar)
Pressure after 2 hours
lowest point of the section of piping ● Every pressure test is an
being tested. assessment of the current state Location of highest outlet: ___ m above the manometer
of the system and is no
guarantee against any mistakes Ambient temperature: ___ ° C
made during installation.
The piping is free of leaks:

Complaints:

Confirmation

Person in charge:

Date: Time: from to

A H A ! - 29.06.06
Client:
signature/stamp
42 43
Pressure test report for chilled water system Pressure test report for compressed air systems
Since there are no specific standards for testing chilled water pipe systems the pressure This test report is based on TRB 522 (technical rules for compressed air reservoirs).
testing follows the guidelines of standard DIN 18380 or ÖNORM B 8131 for pressure All pipes are to be closed off with metal stoppers, caps and blank flanges.
testing of radiator systems. Welded joints must have been completed at least one hour before the test.
All pipe joints must be subjected to a visual check.
Location: ……………………………………………………………..
Location:……………………………………………………………
Project: ………………………………………………………………
Project: ………………………………………………………………
Operating pressure: ……………………………………………………
Operating pressure:………………………………………………………
Pressure test
Testing for leakages by gas pipe device (water head manometer)
The testing pressure for the pipe system should be equal to 1,3 times the operating
pressure and should also be a minimum of 1 bar above the operating pressure at each
of the points in the system being tested. The manometer should be capable of reading The test pressure is 110mbar (1,1 m head of water)
changes in pressure of 0,1 bar and should be placed, if possible, at the lowest point of The testing time is a minimum of 30 minutes for up to 100 litres volume. For every
the section of piping being tested. extra 100 litres of volume add 10 minutes to the testing time (see page 8 for volume).
After the testing pressure has been obtained time must be allowed for temperature
equalisation. Afterwards the pressure must be returned to the testing pressure to Wait for approx. 15 minutes to allow for temperature equalization and for the air to
compensate for any drop in pressure which has occurred in the meantime. settle. The testing time can then begin.
All equipment and faucets which are not suited for the testing pressure should be Test pressure ...... mbar
removed from the system before testing. The system is filled with filtered water and
the air completely removed. During the test there should be a visual check of each pipe Volume ...... litre
joint. Ambient temperature ...... °C
The testing pressure must be maintained for 2 hours and should not drop by more than Testing time ...... minutes
0,2 bar. There should be no leakages.
The compressed air pipeline was tested as one complete system in different sections
Calculated test pressure: ...... bar During the testing time there was NO drop in pressure.

Testing time: ...... hours Strength testing at higher pressure


The strength test immediately follows the leakage test. The test pressure should be
During the time of the test there was never a drop in pressure ≥ 0,2 bar. 1,1 times the maximum operating temperature. Two times during the following
30 minutes the pressure should be re-set at the testing pressure to compensate for any
The system contains the following anti-freeze agent: …………………………… drop in pressure. After that the testing pressure should be held constant for 30 minutes.
Test pressure: ...... bar
For safety reasons the system was therefore emptied completely.
During the testing time the drop in pressure did not exceed ≥ 0,1 bar.

Confirmation Confirmation

Person in charge: ……………………………………………………… Person in charge: ………………………………………………………

Date: ………………… Time: from ……………… to ………………… Date: ………………… Time: from ……………… to …………………

A H A ! - 27.06.06
Customer: …………………………………………………………… Customer: ……………………………………………………………
Signature / stamp Signature / stamp
44 45
Summary of 4. 7. 11.
Any corrections to the Avoid using heat to
the instruction alignment of pipe and bend the pipes
Pipelines must be
clearly marked in
guidelines fitting up to a (it is possible to bend accordance with
maximum of 5° must the cold pipe to a existing standards
be made during the welding procedure. radius of 12 x d). If the pipe has to be (DIN 2403) to make aware of any
Any later adjustments would damage the heated then only use hot air (max. dangers and prevent accidents.
1. joint (see pages 17, 19 and 21 for the 140°C). Never heat the pipe with a naked
The KEtrix® pipe permissible time for adjustments). flame! On request KE KELIT can make an
system is made of offer for manufacturing butt welded
plastic and needs to be elbows up to 30° in various lengths for
treated carefully to size d50 mm and above.
12.
In order to qualify
prevent shocks and impact on the pipe 5. for guarantee cover
during transportation, storage and Do NOT screw any each installation must
installation. threaded pipes or any use KEtrix® system
cast iron fittings into
the female threads of
8. parts only.
Try to make the joints
the metal moulded fittings.
2. Only join to faucets and components with
for standard sections
Protect the pipes, of piping at the work
straight threads, The threaded joints can
fittings and opponents be sealed by the usual methods (hemp,
bench before they are 13.
from lengthy exposure installed. This saves time and increases In order to install the
paste, tape)
to direct UV radiation the safety of the system. KEtrix® pipe
Do not over-screw the threads.
from the sun. successfully a minimal
The usual time required for storage and amount of
installation will have no effect on the expenditure is required for tools.
material as it is stabilised against UV rays 6. 15
20
25
9. For your own security we recommend
but the material is not resistant to long- The expansion of Once the system has that you use and maintain the tried and
term UV exposure KEtrix® pipes is 10 30 been installed it trusted tools.
bar
clearly defined and 5 35 should be subjected to
0
must be accounted for pressure testing.
in the design and installation of the system. You can copy pages 43 – 45 of the
3. Please refer to pages 38-40 regarding catalogue to make a test report. 14.
Follow the installation the methods of accommodating the If you are in doubt
guidelines for the expansion of exposed piping. do not hesitate to
different methods of
Pipes containing compressed air are subject consult our
joining the pipes
technicians.
(see pages 16 – 25). to much greater changes in length than
°C 10. There is not always a perfect solution but
The welding times are based on an pipes filled with water when the The KEtrix® pipe
temperature fluctuates as the medium we can always help
ambient temperature of 20°C. p system is designed for
If the ambient temperature falls below has no cooling effect. Longer runs can be the applications
0°C the heating times may alter slightly. split up into expansion zones and the described in this
fixed points located accordingly. handbook. Extra stress on the system caused

A H A ! - 27.06.06
Suppliers of pipe clamps and brackets by higher temperatures or pressure could
know the properties of the materials and reduce the service life and security of the
offer a range of solutions. system.
46 47
Product range TRI 02 KEtrix® pipe PN10
for chilled water and cooling; d s di L wight V
The KEtrix® pipe system is constantly impermeable to oxygen: mm mm mm m kg/m l/m
being extended and updated to meet the d40 and above 20 1,9 16,2 4 0,11 0,21
requirements of the industry. 25 2,3 20,4 4 0,16 0,33
32 2,9 26,2 4 0,26 0,54
Please refer to the current KEtrix® price 40 3,7 32,6 4 0,41 0,83
list for the complete product range. 50 4,6 40,8 4 0,64 1,31
63 5,8 51,4 4 1,01 2,07
The abbreviated references (e.g. TRI02 75 6,8 61,4 4 1,41 2,96
=PN10 pipe or TRI30 = tee) simplify the 90 8,2 73,6 4 2,03 4,25
administration. Please refer to the TRI 110 10,0 90,0 4 3,01 6,36
numbers when you place your order. 125 11,4 102,2 4 3,91 8,20

L
160 14,6 145,4 4 6,38 13,44

s di
d

TRI 01 KEtrix® Alu composite pipe PN16 TRI 08 KEtrix® pipe PN16
for chilled water, cooling d s di L wight V for chilled water, cooling and d s di L wight V
and compressed air; mm mm mm m kg/m l/m compressed air; mm mm mm m kg/m l/m
20 2,3 15,4 4 0,18 0,19 impermeable to oxygen: 20 2,8 14,4 4 0,15 0,16
Oxygen barrier d32 and above
25 2,8 19,4 4 0,27 0,30 25 3,5 18,0 4 0,23 0,25
32 3,6 24,8 4 0,39 0,48 32 4,4 23,2 4 0,37 0,42
40 5,5 29,0 4 0,58 0,66
50 6,9 36,2 4 0,90 1,03
63 8,6 45,8 4 1,41 1,65
75 10,3 54,4 4 2,01 2,32
90 12,3 65,4 4 2,87 3,36
110 15,1 79,8 4 4,30 5,00
125 17,1 90,8 4 5,53 6,48

L
L

s di s di

A H A ! - 27.06.06
d d

48 49
Polyfusion welding fittings TRI 26 Elbow 90° (male/female)
TRI 10 Socket d/di z t z1 t1 AD VP
mm mm mm mm mm mm Pcs
di z t AD BL VP 20 11 15 33 15 29 10
mm mm mm mm mm Pcs
20 1,5 15 29 33 10 25 16 20 42 20 36 10
25 1,5 20 36 43 10 32 20 24 42 22 43 5
32 1,5 24 46 51 10
40 1,5 27 54 57 5 z1
t1
50 2 28 68 60 2
63 2 29 85 62 1 d
75 2,5 30 101 65 1 z
di AD
90 3 34 121 74 1 t
110 5,5 37 145 85 1
z t di
125 10 40 165 90 1 AD
BL
TRI 27 Elbow 45° (male/female)
TRI 20 Elbow 90° d/di z t z1 t1 AD VP
mm mm mm mm mm mm Pcs
di z t AD VP 20 11 16 31 16 29 10
mm mm mm mm Pcs
25 18 20 33 20 36 10
20 11 15 29 10
25 16 20 36 10
32 20 24 46 10
40 25 27 54 5
z1
50 30 28 68 2 z
t z t
63 36 29 85 1 t1
75 41 30 102 1
AD di 90 50 34 122 1
110 58 37 145 1 di d
AD
125 84 40 165 1

TRI 70 Elbow 45° TRI 30 Equal tee


di z t AD VP di z t AD BL VP
mm mm mm mm Pcs mm mm mm mm mm Pcs
20 12 15 29 10 20 11 15 29 52 10
25 13 20 36 10 25 16 20 36 68 10
32 15 24 46 10 32 20 24 46 84 5
40 19 27 53 5 40 25 27 54 94 5
z 50 23 28 68 2 50 30 28 68 112 2
t
63 32 29 85 1 BL 63 36 29 85 128 1
75 37 30 101 1 z t 75 41 30 102 142 1
90 48 34 122 1 90 50 34 122 166 1
di
AD 110 53 37 137 1 di AD 110 58 37 145 195 1

A H A ! - 27.06.06
125 62 40 165 1 125 84 40 165 248 1

50 51
TRI 35 Reducer tee TRI 41 Reducer (male/female)
di di1 z t z1 t1 AD BL VP d di z t BL AD VP
mm mm mm mm mm mm mm mm Pcs mm mm mm mm mm mm Pcs
25 20 16 20 16 15 36 68 10 25 20 23 15 38 29 10
32 20 20 24 26 15 46 84 5 32 20 27 15 42 29 10
32 25 20 24 22 20 46 84 5 32 25 27 20 47 36 10
40 20 25 27 27 15 54 94 5 40 20 29 15 44 29 5
40 25 25 27 24 20 54 94 5 40 25 28 20 48 36 5
40 32 25 27 26 24 54 94 5 40 32 36 24 60 45 5
50 20 30 28 32 15 68 112 2 50 32 65 20 85 45 2
50 25 30 28 28 20 68 112 2 50 40 56 24 80 53 2
50 32 30 28 30 24 68 112 2 63 40 61 24 85 53 1
50 40 30 28 29 27 68 112 2 63 50 61 24 85 68 1
63 25 36 29 40 20 85 128 1 75 50 66 28 94 68 1
63 32 36 29 36 24 85 128 1 75 63 65 29 94 84 1
63 40 36 29 37 27 85 128 1 90 63 66 29 95 84 1
63 50 36 29 36 28 85 128 1 90 75 66 29 95 101 1
75 32 41 30 42 24 102 142 1 110 63 57 29 86 85 1
BL 75 40 41 30 41 27 102 142 1 110 75 61 29 90 101 1
t z 75 50 41 30 40 28 102 142 1 110 90 61 32 93 119 1
75 63 41 30 39 29 102 142 1 125 110 75 37 112 145 1
d di AD
AD di 90 63 50 34 54 29 122 166 1
z1
90 75 50 34 50 30 122 166 1
t1 110 63 58 37 70 29 145 195 1 z t
di1 110 75 58 37 68 30 145 195 1 BL
110 90 58 37 65 34 145 195 1
125 75 84 40 74 30 165 248 1
125 90 84 40 72 34 165 248 1
125 110 84 40 73 37 165 248 1

TRI 36 Reducer tee TRI 47 Saddle fitting


di di1 di2 z t z1 t1 z2 t2 AD BL VP d di t AD BH VP
mm mm mm mm mm mm mm mm mm mm mm Pcs mm mm mm mm mm Pcs
20 25 20 16 15 16 20 16 15 36 68 10 40 20 15 36 29 5
25 20 20 16 20 18 15 18 15 36 68 10 40 25 20 36 29 5
25 25 20 16 20 16 20 18 15 46 84 10 50 20 15 36 29 5
32 20 25 20 24 26 15 22 20 46 84 5 50 25 20 36 29 5
32 25 20 20 24 22 20 26 15 46 84 5 63 20 15 36 29 5
32 25 25 20 24 22 20 22 20 46 84 5 63 25 20 36 29 5
BL 32 32 20 20 24 20 24 26 15 46 84 5 75 20 15 36 29 5
t z z2 t2 32 32 25 20 24 20 24 22 20 46 84 5 d 75 25 20 36 29 5
AD di 90 20 15 36 29 5
AD di di2
z1 90 25 20 36 29 5
110 20 15 36 29 5

A H A ! - 27.06.06
t1 t 110 25 20 36 29 5
di1 BH

52 53
TRI 60 End cap TRI 83 HA Partition wall fitting 90° (female)
di z t AD BL VP di IG AG z t t1 K BL SW VP
mm mm mm mm mm Pcs mm Zoll mm mm mm mm mm mm mm Pcs
20 8 16 29 24 10 20 1/2" M 28x1,5 13 15 50 43 98 30 5
25 9 21 36 30 10
32 11 25 46 36 10
40 13 25 53 38 5 di
AD di 50 15 28 67 43 5
t
63 19 30 84 49 5
75 21 31 100 52 1 z
t z 90 26 36 120 62 1 K SW AG IG
BL 110 41 37 145 78 1
DO NOT join to any threaded t1
BL
pipes or cast iron fittings

TRI 83 Wall bracket 90° (female) TRI 83 SP Flush box fitting 90° (female)
di IG z z1 t AD BL VP di IG AG z t t1 K BL SW VP
mm Zoll mm mm mm mm mm Pcs mm Zoll mm mm mm mm mm mm mm Pcs
20 1/2" 13 21 15 41,5 48,5 10 20 1/2" M 28x1,5 13 15 15 43 63 30 5
20 3/4" 17 26 15 46 57 10
25 1/2" 17 26 20 46 57 10
di
di 25 3/4" 17 26 20 46 57 10
t
t
z
z K SW AG IG
AD IG

z1 DO NOT join to any threaded DO NOT join to any threaded t1


BL
BL pipes or cast iron fittings pipes or cast iron fittings

TRI 11 Male adaptor


di AG z t AD BL SW VP
mm Zoll mm mm mm mm mm Pcs
20 1/2" 44 15 45 60 - 10
20 3/4" 44 15 45 60 - 10
25 1/2" 40 20 45 60 - 10
25 3/4" 40 20 45 60 - 10
32 1" 59 24 60 83 39 5
40 11/4" 60 27 76 87 39 2
50 11/2" 66 28 82 92 52 1
63 2" 80 29 97 107 64 1
SW AG di AD 75 21/2" 90 30 123 120 80 1

A H A ! - 27.06.06
z t
Please check the current price list for
BL the availability of plastic thread fittings

54 55
TRI 13 Female adaptor TRI 31 Tee with male thread
di IG z t AD BL SW VP di AG z t z1 AD BL SW VP
mm Zoll mm mm mm mm mm Pcs mm Zoll mm mm mm mm mm mm Pcs
20 1/2" 18 15 45 45 - 10 20 1/2" 13 15 49 29 54 - 10
20 3/4" 18 15 45 45 - 10 20 1/2"BF 13 15 49 29 54 - 10
25 1/2" 16 20 45 45 - 10 25 3/4" 17 20 60 36 66 - 10
25 3/4" 16 20 45 45 - 10 32 1" 20 24 78 46 86 39 5
32 1" 22 24 60 68 39 5
z1
40 11/4" 26 27 76 71 48 2
50 11/2" 28 28 82 71 56 1
SW IG di AD 63 2" 38 29 97 86 70 1 SW AG z BL
75 21/2" 44 30 123 96 88 1 t
z t di
BL AD

DO NOT join to any threaded Please check the current price list for TRI 33 Tee with female thread
pipes or cast iron fittings the availability of plastic thread fittings di IG z t z1 AD BL SW VP
mm Zoll mm mm mm mm mm mm Pcs
TRI 21 Elbow adaptor 90° (male) 20 1/2" 13 15 23 30 56 - 10
di AG z t z1 AD SW VP 20 1/2"BF 13 15 23 30 56 - 10
mm Zoll mm mm mm mm mm Pcs
25 3/4" 17 20 32 37 66 - 10
20 1/2" 13 15 49 42 - 10
32 1" 20 24 42 46 84 39 5
25 3/4" 17 20 52 46 - 10
32 1" 20 24 61 61 39 5 z1
z1

SW IG BL
AD SW AG z
z
Please check the current price t
t
list for the availability of plastic DO NOT join to any threaded di
thread fittings di pipes or cast iron fittings AD

TRI 23 Elbow adaptor 90° (female) TRI 33 HA Tee with female threads for partition walls
di IG z t z1 AD SW VP di IG AG z t t1 AD BL SW VP
mm Zoll mm mm mm mm mm Pcs mm Zoll mm mm mm mm mm mm mm Pcs
20 1/2" 13 15 21 42 - 10 20 1/2"BF M28x1,5 13 15 50 29 99 30 10
25 3/4" 17 20 21 46 - 10
32 1" 20 24 38 61 39 5

z1
S W AG IG
Please check z
the current
AD SW IG t
z price list for the

A H A ! - 27.06.06
availability of t1 di
DO NOT join to any threaded t plastic thread DO NOT join to any threaded
AD
pipes or cast iron fittings fittings pipes or cast iron fittings BL
di
56 57
TRI 43 Saddle fitting (female) TRI 55 Union (plastic-metal)
d IG AD BH VP d AG z t z1 BL SW SW1 VP
mm Zoll mm mm Pcs mm Zoll mm mm mm mm mm mm Pcs
20 1/2" 42 17 33 75 36 23 5
40 1/2" 36 29 5
25 3/4" 49 20 40 89 46 30 5
50 1/2" 36 29 5
63 1/2" 36 29 5 32 1" 55 26 44 99 52 37 3
40 5/4" 85 50 52 137 66 45 2
75 1/2" 36 29 5
50 6/4" 85 50 58 143 70 55 1
90 1/2" 36 29 5
110 1/2" 36 29 5 63 2" 85 50 65 150 86 66 1
d 75 2 1/2" 90 50 68 158 108 80 1
BL
AD IG z1 z
90 3" 90 50 73 163 122 94 1
DO NOT join to any threaded
pipes or cast iron fittings t
BH SW1 AG d SW

TRI 51 P Plastic ball valve PN10


di z t AD BL BH VP TRI 56 Union (plastic-plastic)
mm mm mm mm mm mm Pcs d z t BL SW VP
20 25 15 52 80 80 1 mm mm mm mm mm Pcs
25 27 20 64 94 88 1 20 42 17 84 36 5
32 27 24 70 102 100 1 25 49 20 98 46 5
40 33 27 85 120 125 1 32 55 26 110 52 3
50 43 28 98 142 145 1 40 85 50 170 66 2
63 56 29 114 170 160 1 50 85 50 170 70 1
75 88 30 160 236 210 1 63 85 50 170 86 1
90 112 34 188 292 260 1 BL 75 90 50 180 108 1
110 113 37 188 300 260 1 z z 90 90 50 180 122 1
t
d d SW
BH CAREFUL!
AD Not suited for compressed air
di (a PN16 rated valve is required)
Not suited for minus temperatures TRI 57 Union with female thread
(PVC valve required)
t z z t d IG z t BL SW VP
mm Zoll mm mm mm mm Pcs
BL
20 1" 44 17 53 36 5
TRI 51 V Extension for TRI 51P 25 5/4" 50 20 60 46 5
d L AD VP 32 6/4" 56 26 67 52 3
mm mm mm Pcs 40 2" 87 50 103 66 2
20 130 - 300 34 1 50 2 1/4" 87 50 103 70 1
L 63 2 3/4" 87 50 103 86 1
25-32 130 - 300 34 1 BL
z 75 3 1/4" 93 50 114 108 1
40 130 - 300 34 1 t
d 50-63 130 - 300 34 1 90 3 3/4" 93 50 115 122 1
130 - 300 34 1

A H A ! - 27.06.06
75 SW IG d
90-110 130 - 300 34 1
AD

58 59
K17 E-UNI welding socket Butt welding fittings
di
mm
z
mm
t
mm
AD
mm
BL
mm
VP
Pcs
TRI 20 ST Elbow 90° PN10
20 1,5 26 48 55 1 d z BL VP
mm mm mm Pcs
25 1,5 26 54 55 1 160 215 290 1
32 1,5 25 62 53 1
BL
includes cleaning tissue 40 1,5 25 70 53 1 z
50 1,5 25 80 53 1
63 1,5 30 94 63 1 d

di AD
75 2 33 107 70 1
90 2 36 121 76 1
110 2,5 41 143 87 1
z t
BL TRI 70 ST Elbow 45° PN10
d z VP
mm mm Pcs
160 172 1

TRI 18 Backing ring PN10


z
di DN z t BL AD VP
mm mm mm mm mm Pcs
40 32 8 22 30 61 1
50 40 10 25 35 74 1 d

63 50 10 30 40 90 1
75 65 10 30 40 106 1
90 80 10 32 42 125 1 TRI 30 ST Equal tee PN10
110 100 14 36 50 150 1 d z z1 BL BH VP
AD di mm mm mm mm mm Pcs
125 100 15 40 55 162 1
160 215 215 430 300 1
BL
z
z t
BL d
BH
z1

K19 PP flange with steel insert d


d DN LK d1 Nr.of BL AD VP
mm mm mm Holes mm mm Pcs TRI 35 ST Reducer tee PN10
40 32 100 18 4 16 140 1 d d1 z z1 BL BH VP
50 40 110 18 4 18 150 1 mm mm mm mm mm mm Pcs
63 50 125 18 4 18 165 1 160 90 215 190 430 260 1
75 65 145 18 4 18 185 1 160 110 215 200 430 280 1
90 80 160 18 8 18 200 1 BL
d1 110 100 180 18 8 18 220 1 z

BL 125 100 180 18 8 18 220 1


d

A H A ! - 27.06.06
BH
d z1
LK Dimensions conform
AD to DIN 2501 PN16 d1

60 61
TRI 41ST Reducer PN10 Accessories
d d1 BL VP K19 A Flange seal set
mm mm mm Pcs
160 125 225 1 d No. of VP
mm holes Pcs
40 4 1
50 4 1
63 4 1
d1 d 75 4 1
90 8 1
110 8 1
BL
1 set consisting of screws, bolts, 125 8 1
washers and EPDM seal 160 8 1
TRI 18 ST Welding neck PN10
d AD BL VP
mm mm mm Pcs K86 L Perforated plate
160 212 202 1 BL BH ST VP
mm mm mm Pcs
2000 60 3 1

ST
AD d

BH
Steel plate for securing fittings
in all positions. BL
BL

K19 ST PP Flange with steel insert K86 D pegs for K86 L


VP
d DN LK d1 Nr.of BL AD VP Pcs
mm mm mm mm Holes mm mm Pcs
10
160 150 240 22 8 24 285 1
Includes sound insulating
discs and screws.
d1

BL Dimensions conform
d to DIN 2501 PN10
LK
AD
K88 Pipe channel
di s L VP
mm mm mm Pcs
20 0,6 2000 20
L 25 0,6 2000 20
32 0,6 2000 20
40 0,6 2000 10
50 0,8 2000 10
di s 63 0,8 2000 10
75 0,8 2000 10

A H A ! - 27.06.06
Galvanised steel –
d20, d25 and d32 have clips 90 0,8 2000 10
to lock the pipe into the channel 110 0,9 2000 10

62 63
Tools WZ138 Bending tool for K86L
WZ100 Welding set for bending the perforated plate K86 L.
Pipe welding machine ncludes case, table clamp
and floor rest
Heating elements: d 20 – 32 mm,
Pipe cutters: d 16 – 40 mm.

WZ110 Pipe welding machine WZ129 Timer


Pipe welding machine. Includes case, For setting and checking the
heating elements d20-90 or d25 – d125 welding times of d20 – 110 pipes.
Pipe cutters: d20-75, d50 – d140
Special gloves and pipe rests
Packaged in transport crate

d20-90 machine
d25-125 machine

WZ122 Welding tools


WZ115 Butt welding machine d VP
mm Pcs
Hydraulic butt welding machine 230 Volt, 20 1
1000 Watt. 32 1
Includes plane cutter, welding plate 40 1
d40 – 160 welding inserts. 50 1
Packaged in transport crate. 63 1
75 1
90 1
110 1
Heating elements 125 1

WZ120 Overhead welding machine WZ130 Pipe cutter


For making polyfusion joints in areas that cannot d VP
be accessed with the table welding machine. mm Pcs
Can be used for the pipe types TRI 02 and 16 – 40 1
TRI 08. Replacement blade 1
Includes hand welding machine (1200 Watt)
d50 – 110 welding tools, d16 – 75 and

A H A ! - 27.06.06
d50 – 140 pipe cutters, timer and special
gloves. Packaged in transport crate.
Weight of machine: approx. 12 kilos
64 65
WZ135 Wheel pipe cutter WZ150 Alu peeler
d VP d VP
mm Pcs mm Pcs
16 – 75 1 20 1
50 – 140 1 25 1
Replacement wheel: small 1 32 1
Replacement wheel: large 1
For peeling Alu composite pipes TRI01 before
welding. Remove the screw to extend the peeling
area if the pipe is going to be welded to an
E-UNI socket K17.
WZ140 E-socket welding machine Peeler can be connected to a drill.
d VP
mm Pcs
20 – 110 1 WZ125 Drill for saddle fittings
d VP
mm Pcs
24 1

For welding the E-UNI welding socket K17.


Hand scraper included.

WZ145 Pipe scraper WZ124 Welding tools for saddle fittings


Hand scraper d VP
mm Pcs
d VP
mm Pcs 40x20/25 1
20 – 125 1 50x20/25 1
63x20/25 1
75x20/25 1
Pipe shaver for small sizes: 90x20/25 1
d VP 110x20/25 1
mm Pcs
20 – 63 1

Pipe shaver for large sizes:


d VP
mm Pcs
75 – 110 1
ø 75 – 110

A H A ! - 27.06.06
For shaving of the pipes before
electrofusion welding

66 67
68
69

A H A ! - 29.06.06
Innovative Pipe Systemes Innovative Pipe Systemes

Partners worldwide ”There is hardly anything in this world that It is imprudent to pay too much but it is
somebody cannot do a little bit worse and worse to pay too little. When you pay too
sell at a lower price. People who are only little, sometimes you lose everything since
dictated by price are easy prey for such the object you have bought cannot fulfil
machinations. the task it has been set. According to the
law of the economy it is not possible to
acquire high value with little money.

Accept the lowest offer and you take the


risk that you may need to incur extra
costs. If this is the case then you also have
enough money to pay for something
better.”
(K. Ruskin English social reformer 1819-1900)

Project references and satisfied


customers are the primary
benchmark for real quality.

Please note that for technical printing


reasons the numbers are written according
to the common practice in the German-
speaking countries (i.e. the number and
the decimals are separated by a comma). KE KELIT
Kunststoffwerk GesmbH.
Full technical back-up and support for the
KEtrix® pipe system is provided by A-4017 Linz, Ignaz-Mayer-Straße 17
KE KELIT®-Austria/ Europe. Austria – Europe
The network of sales partners, subsidiaries Tel. +43/73 2/77 92 06-0
Fax +43/73 2/77 92 06-118 The technical contents in this brochure are for your information and consultation. We are not liable for the

A H A ! - 03.05.06
and agents is constantly being expanded. contents. The application and installation of the products should be adapted to the individual requirements of
Please ask at the Austrian headquarters e-mail: office@kekelit.com each project. KE KELIT is constantly improving its products and retains the right to make technical changes
for the current status. www.kekelit.com in the course of these improvements. We are not liable for printing and spelling errors. KE KELIT 06/06 engl.

70 71

Anda mungkin juga menyukai