NUMERICALLY SUPERIOR
CSRH-Y
Energy indices
Energy indices ESEER and IPLV
Increasingly closer attention is being paid towards the power consumption of air-conditioning
equipment. Indices have been introduced that also consider usage in part load conditions when the
external air temperature is lower than the rated value and when the separation stages of the cooling
compressors are used.
The valuation index adopted in the United States is called IPLV (Integrated Part Load Value) and is
defined in the regulations issued by ARI (American Refrigeration Institute).
ARI Standard
where:
EER100%, EER75%, EER50% and EER25% are the efficiencies of the chiller in the various load conditions (100% - 75% - 50% and
25% respectively), calculated in the external air temperature conditions shown below.
The temperature of the water leaving the evaporator is considered constant at 6.7C in all load conditions, with a delta of
5C in the full load condition.
The multipliers 1, 42, 45 and 12 are the cooling performance coefficients in various load conditions statistically calculated by
ARI an the basis of surveys conducted, for various types of buildings and operating conditions, in 29 Amerian cities.
Evaporator temp. leaving
DeltaT full load
6,7C costante
5C
Load
Cond. water temp.
75%
23,9C
100%
29,4C
50%
18,3C
25%
18,3C
CSRH-Y
In Europe there is a proposal for EECCAC (Energy Efficiency and Certification of Central Air Conditioner)
Proposal EECCAC
Evaporator temp. leaving
DeltaT full load
Load
100%
Cond. water temp.
30C
6,7C
5C
75%
26C
50%
22C
25%
18C
Size
IPLV
ESEER
Size
IPLV
ESEER
Size
IPLV
ESEER
0401
6.18
5.95
1001
5.06
5.11
4802
7.35
7.24
0501
6.52
6.33
1201
7.43
7.24
5003
6.68
6.59
0551
6.51
6.35
1301
6.48
6.26
5203
7.27
7.19
0651
6.42
6.19
1351
7.36
7.16
5403
7.23
7.15
0751
6.62
6.42
1601
6.78
6.54
5414
7.42
7.33
0802
6.54
6.32
1801
7.43
7.24
5904
7.07
7.00
0851
6.70
6.51
2002
7.00
6.89
6404
6.87
6.82
0951
6.65
6.52
2402
7.39
7.28
6804
7.39
7.30
1002
6.73
6.62
2602
6.81
6.69
7204
7.32
7.24
1102
6.32
6.22
2702
7.50
7.39
7804
6.98
6.91
1302
6.81
6.68
3202
6.95
6.84
8404
6.58
6.53
1502
6.91
6.79
3602
7.41
7.31
9004
6.92
6.85
1702
6.86
6.74
4202
6.76
6.63
9604
7.26
7.17
1902
6.85
6.75
4502
7.06
6.94
CSRH-Y
Water-to-water chillers
Water-to-water chillers. The unit is supplied with anti-freeze oil and refrigerant and has been factory tested. On-site installation
therefore just involves making connections to the mains power and water supplies.
Unit charged with R134a refrigerant.
Screw compressors
Semi-hermetic screw-compressors with 2 five and six-lobe rotors. The five-lobe rotor is directly splined onto the 2-pole
motor (2,950 rpm) without the use of overgears. Compression occurs five times every motor turn and the gas therefore
discharges continuously without the typical throbbing common to reciprocating compressors. Leading-edge numerical control
machines were used to make the rotors and machine the bearing seats. Compressor cooling power is continuously modulated
from 100 to 50%. In addition to the standard no-load starting feature, the motors are fitted with electric starting devices
which limit the power absorbed during the compressor starting phase. A check valve on the coolant delivery line prevents
the rotor from reversing after stopping. Special maintenance-free bearings allow very long work cycles. Lubrication is
forced, without the use of an oil pump. The high efficiency built-in oil separator ensures the constant presence of oil in the
compressor. The rotors are dynamically balanced to ensure that the vibrations common to reciprocating compressors do
not occur. The lack of vibrations and the absence of delicate intake and delivery valves, in addition to very fine manufacturing
tolerances, sophisticated quality controls during the production process and a limited number of moving parts, guarantee
quiet and highly reliable operation. Each compressor is fitted with manual-reset motor thermal protection, delivery gas
temperature control, an oil level float, an oil level sight-glass and an electric resistance for heating the oil when the compressor
is stopped.
CSRH-Y
Refrigerant circuit
Basic model
Unit without heat recovery.
CSRH-Y
Accessories (Option)
Acoustic box
Rubber isolators
Compressor suction valve
Increased evaporator insulation.
Cu/Ni condensers
Flanges on evaporator (if not standard)
Evaporator water flow switch (supplied separately)
Pressure valve for water from wells (14/30C)
Microprocessor
Microprocessor
W3000
Multi-language menu
OPT
Communication protocol
OPT
OPT
OPT
OPT
Par.
OPT
OPT
OPT
OPT
OPT
OPT
Connection to sequencier
OPT
Remote keyboard
OPT
Standard
OPT
Available on request
Par.
CSRH 2402 - D - EX - ST - LN - Y
o~WuWoQMT==vWoNPQ~==wWoQNM~
oOO===~
_Wp~~==ikWi=k==piWp=i=k
r===~=
b=~=
e~=W=aWm~~==oWq~
`==
t~=====
CSRH-Y
0401 0501
0551
Performance
Cooling capacity
Power input
Evaporator water flow
Evaporater water pressure drop
Condenser water flow
Condenser water pressure drop
Microprocessor
kW
kW
m3/h
kPa
m3/h
kPa
99.1
19.8
17.1
23.0
20.4
40.7
121.6
25.2
20.9
22.8
25.1
65.8
148.5
29.1
25.6
18.4
30.5
54.4
168.0
33.5
28.9
23.5
34.5
55.1
Cooling capacity
Power input
Desuperheater heating capacit
CSRH-D-Y Evaporator water flow
(1)(2)(5) Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
Microprocessor
kW
kW
kW
m3/h
kPa
m3/h
kPa
102.9
19.1
17.7
17.7
24.8
3.0
26.4
126.1
24.3
22.5
21.7
24.5
3.9
3.0
154.0
28.1
26.0
26.5
19.8
4.6
2.4
174.3
32.4
29.9
30.0
25.3
5.2
3.2
202.4
40.2
34.8
22.8
41.7
64.9
W3000
194.7 210.0
36.2 38.9
33.5 36.0
33.5 36.1
31.6 24.6
5.8 6.2
2.5 27.5
Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
CSRH-R-Y
Evaporator water pressure drop
(1)(6)
Heat recovery water flow
Heat recovery water pressure drop
Microprocessor
kW
kW
kW
m3/h
kPa
m3/h
kPa
88.3
23.7
110.6
15.2
18.2
19.2
55.4
108.6
30.0
136.8
18.7
18.2
23.7
42.7
131.7
35.4
164.9
22.7
14.4
28.7
62.1
149.5
40.2
187.2
25.7
18.6
32.6
54.2
167.8
44.7
209.9
28.9
23.5
36.5
49.2
CSRH-Y
(1)(2)
187.6
37.5
32.3
29.3
38.6
55.9
225.4
44.1
38.8
28.3
46.2
66.1
252.1
50.3
43.4
53.7
51.8
48.4
247.4
49.3
42.6
51.7
50.9
67.3
285.8
57.0
49.2
69.0
58.8
50.9
339.7
67.3
58.5
59.8
69.8
56.5
233.9
42.6
39.4
40.3
30.5
6.8
3.5
261.5
48.6
44.9
45.0
57.8
7.8
2.5
256.7
47.6
44.0
44.2
55.6
7.6
3.0
296.5
55.0
50.8
51.1
74.3
8.9
2.3
352.4
64.9
60.1
60.7
64.4
10.5
3.2
199.8
52.9
249.5
34.4
22.2
43.4
57.5
224.3
59.9
280.6
38.6
42.5
48.7
52.1
220.6
58.8
275.9
38.0
41.1
47.9
43.4
254.2
69.4
319.4
43.8
54.6
55.5
58.2
302.0
80.6
377.8
52.0
47.3
65.6
55.2
1
1
1
1
2
2
2
2
2
2
W3000
180.0
48.2
225.3
31.0
18.0
39.2
57.5
W3000
Compressors
Number of compressors
Number of circuits
Minimum resource step
n
n
1
1
1
1
50% 50%
1
1
1
1
1
1
50%
50%
50%
30
31
33
15
29
30
32
15
2
2
25% 50%
50%
25% 25%
25%
Charge
kg
kg
kg
kg
19
19
20
9
21
22
23
9
31
33
34
15
kg
kg
kg
800
830
850
840
890
940
1160
1210
1250
dB(A)
91
92
94
94
94
94
94
94
95
97
97
dB(A)
74
75
77
77
77
77
77
77
78
80
80
CSRH-Y
R134a
CSRH-D-Y R134a
CSRH-R-Y R134a
Oil
42
44
46
18
36
37
39
15
51
53
56
15
43
45
47
18
51
54
56
30
54
56
59
30
Operating weight
CSRH-Y
CSRH-D-Y
CSRH-R-Y
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 C
(6) Recovery water (in/out) 40/45 C
CSRH-Y
SIZE
1702
1902
1001
1201
1301
1351
1601
1801
2002
Performance
CSRH-Y
(1)(2)
Cooling capacity
Power input
Evaporator water flow
Evaporater water pressure drop
Condenser water flow
Condenser water pressure drop
Microprocessor
kW
kW
m3/h
kPa
m3/h
kPa
387.7 448.0 509.6 265.4 323.2 366.3 412.7 483.1 546.2 524.7
76.5 87.7 101.5 52.4 61.9 70.7 77.3 91.8 105.9 102.2
66.7 77.1 87.7 45.7 55.6 63.1 71.1 83.2 94.0 90.3
53.9 72.0 38.5 54.9 54.2 48.1 61.1 34.6 44.2 37.5
79.6 91.9 104.8 54.5 66.1 75.0 84.1 98.6 111.8 107.5
59.5 65.3 49.4 38.3 56.3 59.0 65.8 62.3 66.4 37.3
CSRH-D-Y
(1)(2)(5)
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water flow
Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
Microprocessor
kW
kW
kW
m3/h
kPa
m3/h
kPa
W3000
402.3 464.8 528.7 275.3 335.3 380.0 428.2 501.2 566.7 544.4
73.7 84.6 97.9 50.5 59.8 68.2 74.6 88.6 102.2 98.7
68.2 78.3 90.6 46.7 55.3 63.1 69.0 81.9 94.5 91.3
69.3 80.0 91.0 47.4 57.7 65.4 73.7 86.3 97.6 93.7
58.0 77.5 41.4 59.1 58.3 51.8 65.8 37.2 47.6 40.4
11.8 13.6 15.7
8.1
9.7
11.0 12.0 14.2 16.4 15.9
2.6
3.5
2.5
12.2 17.2 14.9 17.8 17.5 23.3 11.7
CSRH-R-Y
(1)(6)
Cooling capacity
kW
Power input
kW
Heat recovery capacity
kW
Evaporator water flow
m3/h
Evaporator water pressure drop
kPa
Heat recovery water flow
m3/h
Heat recovery water pressure drop kPa
Microprocessor
W3000
346.0 397.1 453.1 245.4 289.8 326.4 369.2 429.7 489.8 466.6
91.0 105.1 120.8 64.3 75.9 83.9 93.4 110.0 129.8 121.4
431.5 496.0 566.6 305.9 361.2 405.3 457.0 533.1 611.9 580.7
59.6 68.4 78.0 42.3 49.9 56.2 63.6 74.0 84.3 80.3
42.9 56.6 30.4 47.0 43.6 38.2 48.9 27.4 35.6 29.7
75.0 86.1 98.5 53.2 62.7 70.5 79.5 92.6 106.3 100.9
52.0 56.8 53.0 72.3 70.9 73.4 75.7 77.2 89.9 65.2
W3000
Compressors
Number of compressors
Number of circuits
Minimum resource step
2
2
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
2
2
25%
25%
25%
50%
50%
50%
50%
50%
50%
25%
kg
kg
kg
kg
56
59
62
30
68
72
75
30
105
110
116
30
44
46
48
15
47
49
52
22
50
52
55
22
49
51
53
22
75
79
83
28
73
77
81
28
94
99
103
30
kg
kg
kg
2330
2430
2560
2390
2500
2630
2790
2910
3170
1590
1640
1670
2010
2100
2120
2030
2140
2170
2050
2160
2200
2712
2860
3110
2720
2880
3140
3140
3310
3420
n
n
Charge
CSRH-Y
R134a
CSRH-D-Y R134a
CSRH-R-Y R134a
Oil
Operating weight
CSRH-Y
CSRH-D-Y
CSRH-R-Y
Sound power level(4)
dB(A)
97
97
97
94
97
97
97
97
97
97
dB(A)
80
80
80
77
80
80
80
80
80
80
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 C
(6) Recovery water (in/out) 40/45 C
CSRH-Y
2402
2602
2702
3202
3602
4202
4502
4802
5003
5203
Performance
Cooling capacity
Power input
Evaporator water flow
Evaporater water pressure drop
Condenser water flow
Condenser water pressure drop
Microprocessor
kW
kW
m3/h
kPa
m3/h
kPa
637.6
123.6
109.8
55.4
130.6
55.1
733.3
141.5
126.2
39.8
150.0
59.3
835.5
155.8
143.8
55.9
170.2
67.4
941.9
182.7
162.1
71.0
192.9
59.6
1086.4 1241.4
211.6 241.0
187.0 213.7
69.3 61.7
222.7 254.3
66.0 59.8
1314.5
250.7
226.3
69.1
268.6
59.9
1386.4
260.5
238.7
76.9
282.7
59.9
1462.8
286.7
251.8
85.6
300.2
60.3
1542.0
300.7
265.5
67.0
316.1
62.9
Cooling capacity
Power input
Desuperheater heating capacit
CSRH-D-Y Evaporator water flow
(1)(2)(5) Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
Microprocessor
kW
kW
kW
m3/h
kPa
m3/h
kPa
661.5
119.2
110.3
113.9
59.7
19.2
17.1
760.8
136.5
126.3
131.0
42.9
22.0
14.9
866.9
150.3
139.1
149.2
60.1
24.2
18.1
977.2
176.3
163.1
168.2
76.4
28.3
17.3
W3000
1127.1 1287.9 1363.8
204.2 232.5 241.9
188.9 215.1 223.7
194.0 221.7 234.8
74.5 66.4 74.4
32.9 37.4 38.9
23.3 23.8 25.8
1438.4
251.4
232.5
247.6
82.8
40.4
27.8
1517.7
276.6
255.8
261.3
89.0
44.5
19.0
1599.9
290.2
268.4
275.4
72.1
46.7
20.9
kW
kW
kW
m3/h
kPa
m3/h
kPa
572.3
151.6
714.9
98.5
44.7
124.2
69.5
653.3
168.0
811.3
112.5
31.6
141.0
73.5
746.7
188.3
923.7
128.6
44.6
160.5
77.3
1174.4
300.9
1457.2
202.2
55.2
253.2
83.3
1241.0
315.1
1537.2
213.6
61.6
267.1
87.1
1307.6
346.7
1633.5
225.1
68.4
283.9
77.4
1381.6
366.5
1726.1
237.9
53.7
300.0
82.7
2
2
3
3
3
3
CSRH-Y
(1)(2)
Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
CSRH-R-Y
Evaporator water pressure drop
(1)(6)
Heat recovery water flow
Heat recovery water pressure drop
Microprocessor
W3000
W3000
Compressors
Number of compressors
Number of circuits
Minimum resource step
n
n
2
2
2
2
2
2
2
2
2
2
2
2
2
2
25%
25%
25%
25%
25%
25%
25%
kg
kg
kg
kg
94
99
103
44
103
108
113
44
100
105
111
44
100
105
111
44
144
151
158
56
213
224
235
56
210
221
231
56
210
221
231
56
197
207
217
84
203
213
223
84
kg
kg
kg
3440
3590
3950
3720
3880
4220
3750
3900
4300
4550
4700
5230
5230
5380
5920
5540
5700
6240
6020
6180
6710
6490
6590
7120
6880
7115
7885
6910
7145
7925
Charge
CSRH-Y
R134a
CSRH-D-Y R134a
CSRH-R-Y R134a
Oil
Operating weight
CSRH-Y
CSRH-D-Y
CSRH-R-Y
Sound power level(4)
dB(A)
99
99
99
99
99
99
99
99
101
101
dB(A)
81
81
81
81
81
81
81
81
82
82
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 C
(6) Recovery water (in/out) 40/45 C
CSRH-Y
SIZE
5414
5904
6404
6804
7204
7804
8404
9004
9604
Performance
CSRH-Y
(1)(2)
Cooling capacity
Power input
Evaporator water flow
Evaporater water pressure drop
Condenser water flow
Condenser water pressure drop
Microprocessor
Cooling capacity
Power input
Desuperheater heating capacit
Evaporator water flow
CSRH-D-Y
(1)(2)(5) Evaporator water pressure drop
Desuperheater water flow
Desuperheater water pressure
Microprocessor
Cooling capacity
Power input
Heat recovery capacity
Evaporator water flow
CSRH-R-Y
Evaporator water pressure drop
(1)(6)
Heat recovery water flow
Heat recovery water pressure drop
Microprocessor
2048.8 2172.7
394.7 423.1
352.7 374.0
61.6 69.3
419.3 445.4
63.3 65.4
2328.6 2482.7
452.1 482.1
400.9 427.4
80.4 61.7
477.0 508.6
61.4 59.5
2628.9
501.4
452.6
69.2
537.1
60.6
2772.7
521.0
477.3
77.0
565.2
60.7
kW
kW
kW
m3/h
kPa
m3/h
kPa
1659.9 1733.7
302.5 300.8
279.8 278.2
285.8 298.5
77.6 60.1
48.6 48.3
22.7 18.1
W3000
2125.6 2254.2
380.8 408.4
352.3 377.8
365.9 388.1
66.3 74.5
61.2 65.6
20.2 23.3
2415.9 2575.8
436.2 465.2
403.5 430.3
415.9 443.4
86.5 66.5
70.2 74.8
23.5 23.8
2727.5
483.8
447.5
469.6
74.5
77.7
25.8
2876.7
502.8
465.1
495.2
82.9
80.8
27.8
kW
kW
kW
m3/h
kPa
m3/h
kPa
1436.8
384.6
1798.4
247.4
58.1
312.5
85.9
4
4
4
4
1845.3
324.6
300.2
317.7
68.1
52.1
17.5
1994.8
354.1
327.6
343.4
58.4
56.9
17.5
W3000
W3000
Compressors
Number of compressors
Number of circuits
Minimum resource step
n
n
4
4
3
3
4
4
4
4
4
4
4
4
4
4
4
4
16.6% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5%
Charge
kg
kg
kg
kg
201
211
221
84
201
211
231
243
295
310
291
306
288
302
357
375
427
448
420
441
413
434
88
100
112
112
112
112
112
112
112
kg
kg
kg
6910
7175
7965
8070
8310
8820
9120
dB(A)
101
102
102
102
102
102
102
102
102
102
dB(A)
82
83
83
83
83
83
83
83
83
83
R134a
CSRH-Y
CSRH-D-Y R134a
CSRH-R-Y R134a
Oil
Operating weight
CSRH-Y
CSRH-D-Y
CSRH-R-Y
(4) According to ISO 3744 (see "Full load sound level" section)
(5) Desuperheater water (in/out) 40/45 C
(6) Recovery water (in/out) 40/45 C
CSRH-Y
OPERATING RANGE
CSRH-Y
CSRH-D-Y
CSRH-R-Y
Evaor.
Desuperh.
Heat. Rec.
Water side
Min
Max
Min
Max
Min
Max
Exch. Water(in)(
8 (1)
23 (1)
18(2)
10(2)
51(2)
Exch. Water(in)(
5 (1)(6)
15 (1)
26(2)
26(2)
55(4)(5)
Exch. Water(in)(
16
Limits to exchanger water temperature are valid within the minimum maximum water flow range indicated in the Hydraulic Data section.
(1) Condenser water temp. 30/35 C
(2) Evaporator water (in/out) 12/7 C
(3) With temperatures down to -8C use anti-freeze mixtures. In case of lower temperatures, please contact our Sales Department.
(4) Values related only to total heat-recovery version.
(5) Valid for temperature of fluid the evaporator >= -3C. In case of lower temperatures, please contact our Sales Department.
-5
-10
12%
20%
30%
35%
cPf
0,985
0,98
0,974
cQ
1,02
1,04
cdp
1,07
1,11
-15
-20
-25
-30
-35
40%
45%
50%
0,97
0,965
0,964
0,96
1,075
1,11
1,14
1,17
1,2
1,18
1,22
1,24
1,27
1,3
FOULING FACTORS
Performances are based on clean condition of tubes (fouling factor =1). For different fouling values, performance should be
adjusted using the correction factors shown in the following table.
Fouling factors
Evaporator
f1
(m /W)
-5
4,4 x 10
-4
(m /W) 1,72 x 10
fk1
Heat recovery
Desuperheater
fx1
f2
fk2
fx2
f3
fk3
fx3
0,99
1,03
1,03
0,99
1,03
1,03
0,96
0,99
0,99
0,98
1,04
1,04
0,98
1,04
1,04
0,93
0,98
0,98
0,95
1,06
1,06
0,95
1,06
1,06
10
CSRH-Y
Dp=K x Q 2 /1000
Evaporator
SIZE
Q
K
min
C.a./W.c.
m3/h
m3/h
min m3
min
Desuperheater
max
m3/h
m3/h
Q
K
min
max
m3/h
m3/h
0401
79
10
45.1
0.8
98
5.6
26.3
2813
3.8
0501
52
11.1
50.9
104
6.9
28.2
203
4.8
0551
28.1
15.9
73.7
1.2
58.6
8.4
35
116
5.6
0651
28.1
15.9
73.7
1.3
46.2
9.5
39.4
116
6.4
0751
28.1
15.9
73.7
1.5
37.5
10.7
43.8
74.4
7.2
0802
18.8
17.6
81.7
1.3
37.5
11.5
46.5
703
7.7
0851
18.8
17.6
81.7
1.8
30.9
12.8
51.6
74.4
8.3
0951
28.5
17.6
81.7
18
14.4
61.3
40.1
9.7
1002
28.5
17.6
81.7
1.6
26
14.2
57.1
50.8
9.6
1102
28.5
17.6
81.7
1.8
14.7
16.3
69.9
28.9
11
1302
17.5
28
108
2.1
11.6
19.4
78.7
28.9
12.9
1502
12.1
28
114
2.4
9.4
22.1
88.9
18.6
14.5
1702
12.1
28
114
2.8
7.7
25.5
103.1
18.6
16.6
1902
42
162
3.2
4.5
29.2
122.1
10
19.4
1001
26.3
21.4
74.5
2.1
12.9
14.7
73.8
186
9.9
1201
17.5
28
108
2.5
12.9
14.7
73.8
186
11.7
1301
12.1
28
114
2.9
10.5
16.3
83.7
124
13.4
1351
12.1
28
114
3.2
9.3
17.3
93.6
124
14.5
1601
42
162
3.8
6.4
20.8
110.1
86.4
17.2
1801
42
162
4.3
5.3
22.8
125.1
86.4
19.9
2002
4.6
42
171
3.3
3.2
29.4
147.1
46.5
19.2
2402
4.6
42
171
3.2
29.4
147.1
46.5
23.2
2602
2.5
55.8
201
4.6
2.6
32.5
167.1
31
26.6
2702
2.7
55.8
210
5.3
2.3
34.5
189.1
31
28.9
3202
2.7
55.8
221
5.9
1.6
41.5
215.1
21.6
34.2
3602
102
300
6.8
1.3
45.5
248.1
21.6
39.7
4202
1.4
117
313
7.8
0.9
54
283.1
17
45.2
4502
1.4
124
330
8.3
0.8
57
299.1
17
47
4802
1.4
131
330
8.7
0.8
60
315.1
17
48.9
5003
1.4
138
330
9.2
0.7
64.3
334.1
9.6
54
5203
145
330
9.7
0.6
66.3
352.1
9.6
56.6
5403
151
330
10.1
0.6
68.3
366.1
9.6
59.4
5414
0.7
112
421
10.5
0.6
69
378.1
7.7
57.6
5904
0.7
112
448
11.2
0.5
76
404.1
6.4
63
6404
0.5
181
600
12.1
0.4
83
437.1
5.4
68.7
6804
0.5
193
600
12.9
0.4
87
467.1
5.4
74
7204
0.5
205
600
13.7
0.3
91
496.1
5.4
79.2
7804
0.5
220
600
14.7
0.3
99.5
531.1
4.7
84.7
8404
0.3
234
625
15.6
0.2
108
566.1
4.2
90.4
9004
0.3
248
660
16.5
0.2
114
598.1
4.2
93.9
9604
0.3
262
660
17.4
0.2
120
629.1
4.2
97.6
(1) Rec. = Heat Recovery. For units with total heat recovery.
(2) Cond. = Condenser. For water to water type units. In units with heatrecovery ,
this data is valid for both the condensing and the heatrecovery exchangers.
11
CSRH-Y
Electrical Data
Maximum values
Compressor
Size
n
Total unit
F.L.I.
F.L.A.
L.R.A.
F.L.I.
F.L.A.
S.A.
(kW)
(A)
(A)
(kW)
(A)
(kW)
0401
32.6
55.4
153
32.6
55.4
153
0501
40.5
67.1
169
40.5
67.1
169
0551
48.7
80.4
206
48.7
80.4
206
0651
51.7
91.7
267
51.7
91.7
267
0751
64.3
105
290
64.3
105
290
0802
32.6
55.4
153
65.2
111
208
0851
70.2
115
350
70.2
115
350
0951
82.1
132
423
82.1
132
423
1002
40.5
67.1
169
81
134
236
1102
48.7
80.4
206
97.4
161
286
1302
51.7
91.7
267
103
183
359
1502
64.3
105
290
129
210
395
1702
70.2
115
350
140
230
465
1902
82.1
132
423
164
264
555
1001
82.1
132
423
82
132
423
1201
101
165
300
101
165
300
1301
112
184
360
112
184
360
1351
127
208
404
127
208
404
1601
145
235
436
145
235
436
1801
171
272
465
171
272
465
2002
82.1
132
423
164
263
555
2402
101
165
300
201
329
465
2602
112
184
360
223
367
544
2702
127
208
404
255
416
612
3202
145
235
436
291
470
671
3602
171
272
465
341
544
737
4202
191
310
586
382
620
896
4502
191/217
310/351
586/650
408
661
960
4802
217
351
650
434
702
1001
5003
145/171
235/272
436/465
461
742
935
5203
145/171
235/272
436/465
487
779
972
5403
171
272
465
512
816
1009
5414
127
208
404
509
832
1028
5904
127/145
208/235
404/436
545
886
1087
6404
145
235
436
581
940
1141
6804
145/171
235/272
436/465
632
1014
1207
7204
171
272
465
683
1088
1281
7804
171/191
272/310
465/586
724
1164
1440
8404
191
310
586
764
1240
1516
9004
191/217
310/351
586/650
816
1322
1621
9604
217
351
650
868
1404
1703
F.L.I.
Power input
F.L.A.
Current absorption
L.R.A.
S.A.
(1)Safety values to be considered when cabling the unit for power supply and
line-protections
Voltage tolerance: 10%
Maximum voltage unbalance: 3%
12
CSRH-Y
63
125
250
500
1000
2000
4000
8000
Total
55
44
60
74
70
64
55
49
74
0501
52
44
61
75
71
65
56
47
75
0551
48
54
71
75
74
67
59
49
77
0651
56
59
77
73
74
67
60
48
77
0751
55
58
73
72
74
69
63
53
77
0802
58
47
63
77
73
67
58
52
77
0851
55
58
73
72
74
69
63
53
77
0951
55
58
73
72
74
69
63
53
77
1002
55
47
64
78
74
68
59
50
78
1102
51
57
74
78
77
70
62
52
80
1302
59
62
80
76
77
70
63
51
80
1502
58
61
76
75
77
72
66
56
80
1702
58
61
76
75
77
72
66
56
80
1902
58
61
76
75
77
72
66
56
80
1001
55
58
73
72
74
69
63
53
77
1201
53
51
70
79
77
68
55
44
80
1301
63
55
71
74
79
70
57
45
80
1351
67
57
80
76
78
68
52
40
80
1601
55
74
77
75
78
69
63
51
80
1801
50
70
82
77
76
70
62
52
80
2002
58
61
76
75
77
72
66
56
80
2402
54
52
71
80
78
69
56
45
81
2602
64
56
72
75
80
71
58
46
81
2702
68
58
81
77
79
69
53
41
81
3202
55
74
78
75
78
69
63
51
81
3602
51
71
83
78
77
71
63
53
81
4202
51
71
83
78
77
71
63
53
81
4502
51
71
83
78
77
71
63
53
81
4802
51
71
83
78
77
71
63
53
81
5003
52
72
84
79
78
72
64
54
82
5203
52
72
84
79
78
72
64
54
82
5403
52
72
84
79
78
72
64
54
82
5414
70
60
83
79
81
71
55
43
83
5904
69
74
83
79
81
72
64
51
83
6404
58
77
80
78
81
72
66
54
83
6804
57
76
83
79
80
73
66
55
83
7204
53
73
85
80
79
73
65
55
83
7804
57
76
83
79
80
73
66
55
83
8404
53
73
85
80
79
73
65
55
83
9004
57
76
83
79
80
73
66
55
83
9604
53
73
85
80
79
73
65
55
83
Working conditions:
evaporator water (in/out) 12/7 [C]
condenser water (in/out) 30/35 [C]
Sound pressure
Sound pressure level values in free-field conditions, at 1 m distance.
13
14
8
Main isolator
Power inlet
For installation purposes, please refer to the documentation sent after the purchase-contract. This technical
data should be considered as indicative. CLIMAVENETA may modify them at any moment.
REMARKS:
`poeMTRNNVMOJv
Dimension Drawing
Well water
Condenser interface
Cooling tower
15
8
Main isolator
Power inlet
For installation purposes, please refer to the documentation sent after the purchase-contract. This technical
data should be considered as indicative. CLIMAVENETA may modify them at any moment.
REMARKS:
`poeNMMNQUMOJv
Dimension Drawing
6
7 3
`poeRQNQVSMQJv
`poeRMMPRQMPJv
5
4
0401
0501
0551
0651
0751
0802
0851
0951
1002
1102
1302
1502
1702
1902
1001
1201
1301
1351
1601
1801
2002
2402
2602
2702
3202
3602
4202
4502
4802
5003
5203
5403
5414
5904
6404
6804
7204
7804
8404
9004
9604
Size
A(mm)
2260
2510
2595
2595
2595
2800
2985
2985
2800
3000
3200
3150
3150
3200
2650
3530
3530
3530
3530
3530
3715
3715
4500
4500
4500
4500
4500
4500
4585
4420
4420
4420
4500
4500
4500
4500
4500
4500
4500
4500
4500
H(mm)
1300
1300
1350
1350
1490
1500
1490
1500
1500
1500
1600
1600
1600
1860
1795
1795
1795
1795
1920
1900
1950
1950
1950
1950
1950
2050
2240
2240
2240
2100
2100
2100
2050
2180
2300
2300
2300
2330
2330
2330
2330
CSRH-Y
B(mm)
840
840
840
840
840
1020
840
840
1020
1020
1020
1020
1020
1045
915
915
915
915
980
980
1240
1240
1240
1240
1240
1240
1240
1240
1240
1860
1860
1860
2275
2275
2275
2275
2275
2275
2275
2275
2275
P./W.(Kg) A(mm)
800
2260
840
2510
1160
2595
1180
2595
1190
2595
1538
2800
1270
2985
1350
2985
1560
2800
2000
3000
2290
3200
2330
3150
2390
3150
2790
3200
1590
2650
2010
3530
2030
3530
2050
3530
2710
3530
2720
3530
3140
3715
3450
3715
3720
4500
3750
4500
4550
4500
5230
4500
5540
4500
6020
4500
6490
4585
6880
4420
6910
4420
6910
4420
8070
4500
8820
4500
10340
4500
10400
4500
10470
4500
10690
4500
11060
4500
11920
4500
12740
4500
B(mm)
840
840
840
840
840
1020
840
840
1020
1020
1020
1020
1020
1045
915
915
915
915
980
980
1240
1240
1240
1240
1240
1240
1240
1240
1240
1860
1860
1860
2275
2275
2275
2275
2275
2275
2275
2275
2275
H(mm)
1405
1405
1460
1460
1460
1600
1590
1700
1600
1600
1700
1830
1840
1950
1795
1795
1795
1795
1920
1920
1950
1950
1950
1950
1950
2050
2400
2240
2240
2100
2100
2100
2050
2180
2300
2300
2300
2330
2330
2330
2330
CSRH-D-Y
P./W.(Kg) A(mm)
830
2375
890
2530
1210
2610
1230
2610
1240
2610
1598
2800
1330
2985
1410
2985
1660
2800
2100
3000
2390
3200
2430
3150
2500
3150
2910
3200
1640
2650
2100
3530
2140
3530
2160
3530
2860
3530
2880
3530
3310
3715
3590
3715
3880
4500
3900
4500
4700
4500
5380
4500
5700
4500
6180
4500
6590
4585
7115
4420
7145
4420
7175
4420
8310
9120
10650
10710
10780
11100
11420
12320
13070
H(mm)
1300
1390
1440
1440
1580
1500
1580
1590
1610
1610
1660
1790
1800
1900
1795
1935
1935
1935
2120
2120
1990
2110
2110
2110
2110
2240
2240
2240
2240
2340
2340
2340
CSRH-R-Y
B(mm)
840
840
840
840
840
1020
840
830
1060
1060
1060
1060
1060
1090
915
915
915
915
980
980
1240
1240
1240
1240
1240
1240
1240
1240
1240
1860
1860
1860
R3(mm) R4(mm)
750
500
750
500
750
500
750
500
750
500
850
500
750
500
750
500
850
500
850
500
850
500
850
500
850
500
850
500
1000
1800
1000
1800
1000
1800
1000
1800
1000
1800
1000
1800
1200
1800
1200
1500
1200
1500
1200
1500
1200
1500
1200
1500
1200
1500
1200
1500
1200
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
1800
1500
FREE SPACES
R2(mm)
500
500
500
500
500
500
500
500
500
500
500
500
500
500
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
900
16
17
INSTRUCTIONS
- Make sure that all the panels are firmly fixed in place before moving the unit.
Climaveneta Italy:
36061 BASSANO DEL GRAPPA (VICENZA) ITALIA - VIA SARSON 57/c
TEL. +39 / 0424 509 500 (r.a.) - TELEFAX +39 / 0424 509 509
E-mail:info@climaveneta.com http://www.climaveneta.com
Climaveneta China:
No,88 Baiyun Road Xinghuo Developing Zone ,Shanghai,China Post Code:201419
TEL: +86-21-57505566 FAX: +86-21-57505797
E-mail:info@climaveneta.com.cn http://www.climaveneta.com.cn
Climaveneta Hongkong:
Room 2003,CCT Telecom Building, 11 Wo Shing Street,Fotan,Shatin,N.T.,Hongkong
TEL: +85-2-26871755 FAX: +85-2-26873078
E-mail:info@climaveneta.com.cn http://www.climaveneta.asia
Climaveneta Vietnam:
381A1 Cong Hoa Street Ward 13 Tan Binh District, HCM City, Vietnam
TEL: +84-8-38497529 FAX: +84-8-38124190
E-mail:info@climaveneta.com.cn http://www.climaveneta.asia
B212 CCU/01-12-2009EN-SH