Anda di halaman 1dari 4

NUFLO

Scanner 2000 Expansion Board

QuickStart
Installation
Before installing the expansion board, remove all power from the Scanner 2000 (battery and external power). The expansion board attaches to two headers positioned between the two large terminal blocks on the main board. Remove wiring from the main board if necessary to guide the expansion board into position. 1. Remove the standoff from packaging and press it into the hole near the center of the main board until it snaps into place. 2. Guide the expansion board over the standoff and align the pins on the under side with the headers on the main board.

The Scanner 2000 Expansion Board expands the Scanner 2000s input/output to include: an additional turbine input a pulse input (3-30 VDC or contact closure) two analog inputs (1-5 V, 0-5 V, or 4-20 mA) an analog output (4-20 mA)

Align hole in expansion board with stando .

Align pins on back of expansion board with black headers.

CAUTION: FAILURE TO ALIGN PINS AND HEADERS CAN DAMAGE THE BOARDS. When the board is positioned correctly, text on both boards should face the same direction. 3. Gently press the expansion board and the main board together until the expansion board snaps into place over the standoff. 4. Restore wiring connections to the main board, reconnect the MVT if disconnected, and make field wiring connections to the expansion board. 5. Restore power to the Scanner 2000 and reboot the Scanner to allow detection of the expansion board.
Part No. 9A-30165026, Rev. 03

TB8

Pulse Input
The pulse input provides an optically isolated input for high-amplitude pulse (frequency) signals, which includes signals from a turbine meter equipped with a preamplifier or signals from a PD meter (via contact closure). The Scanner 2000 can calculate flow from no more than two pulse (frequency) inputs at a time. Therefore, a pulse input can be used simultaneously with only one turbine input (main board or expansion board).
Expansion Board PN: 9A-30160014

TB7

Another turbine input (Turbine Input 1) is provided on the main circuit board. When the expansion board is installed, a differential pressure flow run and two turbine runs can be monitored and logged simultaneously.

TB9

The Turbine Input 2 accepts a turbine flowmeter input signal generated by a magnetic pickup. The Scanner 2000 can be configured to use this signal to calculate and display instantaneous flow rates and accumulated totals.

TB4

TB7

TB6

TB5

Turbine Input 2

TURBINE INPUT (TB9)

B
28

27
Expansion Board PN: 9A-30160014

TURBINE MAGNETIC PICKUP

PULSE INPUT (TB8)

TB4

TB6

25
TB8

26 PULSE INPUT 3 TO 30 VDC


TB9

TB5 TB5 TB7 TB6

PULSE INPUT/ SWITCH (TB7 &TB8)


TB7 AND TB8 ARE CONNECTED BY JUMPER; TB7 IS THEN WIRED TO THE SWITCH.

TB4

23
Expansion Board PN: 9A-30160014

24 26
TB9

25
TB8

SWITCH CLOSURE

TB4

TB5

Analog Inputs
POWER RETURN SIGNAL

IN+ IN- PWR

17 18 19

1-5 VDC TRANSMITTER

TB7

TB6

TB8

TB9

Expansion Board PN: 9A-30160014

ANALOG INPUT 1 (TB5) WITH 1-5V TRANSMITTER

The analog inputs, which can be configured for a 1-5 V, 0-5 V or 4-20 mA signal, can receive readings from a pressure or temperature sensor for use in AGA-7 gas calculations. Alternatively, they can be used to log measurements from any device with a 1-5 V, 0-5 V or 4-20 mA output. Transmitter power is provided by the Scanner only when the Scanner is externally powered. The output voltage equals the input voltage less 0.25 VDC, and is limited to 20 mA. If a 4-20 mA transmitter is used, a resistor must be added to the circuit. The expansion board circuit will support a resistor range of 200 to 300 ohms; 250 ohms is recommended.

TB4

1-5 VDC TRANSMITTER

SIGNAL RETURN POWER


TB7

20 21 22

TB6

ANALOG INPUT 2 (TB6) WITH 1-5V TRANSMITTER

Expansion Board PN: 9A-30160014

TB8

4-20 mA TRANSMITTER WIRING (CAN BE USED WITH ANALOG INPUT 1 OR 2)


TB5

TB9

TB5
IN+ IN- PWR

Configuring Inputs/Outputs
4-20 mA TRANSMITTER

17

18

19

Resistor Required (250-ohm recommended)

All inputs and outputs are configured with ModWorX Pro software provided with each Scanner 2000 microEFM.

ANALOG OUTPUT (TB4) WITH POWER SUPPLIED VIA MAIN BOARD (TB2)
POWER SUPPLY 8-30 VDC
GND
TB4
TB5

ANALOG READOUT
*Resistor may be included in readout device.

15

16

7 8 9 10 11 12

POWER

GROUND SCREW INSIDE ENCLOSURE

Expansion Board PN: 9A-30160014

TB8

TB7

TB6

TB9

TB2

Analog Output (4-20 mA)


The 4-20 mA linear current output can be configured with ModWorX Pro software to represent any parameter in the holding registers. This output requires a twoconductor cable to be connected to an 8 to 30 VDC power supply (voltage required is dependent on loop resistance) and an analog readout device to be located in the remote location. The graph above shows the minimum voltage
LOAD RESISTANCE (OHMS)

SCANNER 2000 Main Circuit Board PN: 9A-30160010

800

200

OPERATING REGION

0 8 12 24 30

LOOP SUPPLY VOLTAGE (VDC)

required to power the instrument for a given loop resistance. In addition, the mathematical relationship between loop voltage and load resistance is given.

For example, if a power supply voltage of 24 volts is available to power the current loop, the maximum load resistance would be 800 ohms.

Anda mungkin juga menyukai