Important: Retain these instructions
If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

LINC

These instructions shall be used by trained service personnel only

Contents
1 Unpacking......................................................................1 2 Storing............................................................................1 3 InstalLation. ...................................................................1

3.1 Installation - Mounting....................................................1 3.2 Installation - Configuring................................................5 4 Disposal. ........................................................................8 5 Cleaning and Maintainance...........................................8

Unpacking

LINC Installation Instructions, TG103062

Storing
-10 C (14 F) +50 C (122 F) 0 95 %RH

H2 O

InstalLation

3.1 Installation - Mounting


Caution: The LINC contains static sensitive devices. Suitable anti-static precautions shoud be taken throughout this operation to prevent damage to the unit. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices.

It is recommended that the installation should comply with the local electrical safety installation practices (e.g.HSE Memorandum of Guidance on Electricity at Work Regulations 1989, National Electric Code) Note that this product may involve LONWORKS system integration as referred to in section 3.2 step 14: this procedure should only be performed by an installer with LONWORKS engineering expertise.

Dimensions
35 mm (1.38) 160 mm (6.3)
POWER 0V

Mounting Requirements

POWER 0V

POWER 0V

175 mm (6.89)

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

BAUD

ADDRESS

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 1

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

LINC 3.1 Installation - Mounting(continued)

Installation Instructions

Requirements (continued)

Protection: Altitude Pollution degree 0 C (32 F) +45 C (113 F)

IP30 <2000m (6562) 2 (only non-conduction pollution occurs)


BAUD ADDRESS 1 2 4 8 16 32 64 19K2 9K6 1K2 S3

POWER 0V

POWER 0V

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

0 %RH

90 %RH

SERVICE RESET

H2 O

This unit is UL rated as UL916 accessory to open energy management equipment.

Mounting the Node


151 mm (5.94)
POWER 0V

The LINC can be fitted into enclosures and controllers as shown in the table below: NETB/NETBB 4 off 4 mm (0.157) IQ101+/102+ IQ111+ IQ131+ IQ25x 141 mm (5.55) IQ241/242 IQ23x *

BAUD

ADDRESS

Connect Power

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

* LINC board fits with 3 screws in normal node position or fits in NDP position (if no NDP). Must use NDP position if RDS fitted. See appropriate enclosure/controller installation instructions for more details about node installation.

LINC consumption < =6 VA

The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit. Do not position the equipment so that the disconnecting device is difficault to opperate.

POWER 0V

0V +24V

24 Vdc
O

DO NOT SWITCH ON POWER

0 18

18 18-0-18 Vac

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

SERVICE RESET

18 Vac 18 Vac (isolated)

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012

Installation Instructions 3.1 Installation - Mounting(continued)

LINC

Connect Earth (Ground)

POWER 0V

BAUD

ADDRESS

Connect Current Loop Network

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

SERVICE RESET

Warning: This apparatus must be earthed (grounded) using earth (ground) tag.
Note that the earth (ground) tag is internally connected to 0V

Normally Local Lan address <100 Note that 3xtend/EINC Ls, EINCs, INCs, LINCs cannot be on same local Lan Internetwork segment A if address >=100 Network Engineering Manual, 92-1735 Cable Belden 9182 Belden 9207 1k2 baud 4k8 baud 9k6 baud 19k2 baud No. of Wires 2 2 2

POWER 0V

1000 m 1000 m 1000 m 700 m (1090 yds) (1090 yds) (1090 yds) (765 yds) 1000 m 1000 m 1000 m 500 m (1090 yds) (1090 yds) (1090 yds) (545 yds) 350 m 700 m (765 yds) (380 yds) 250 m 500 m (545 yds) (270 yds)

BAUD

ADDRESS

Trend 1000 m 1000 m TP/1/1/22/HF/200 (1090 yds) (1090 yds) (Belden 8761) Trend 1000 m 1000 m TP/2/2/22/HF/200 (1090 yds) (1090 yds) (Belden 8723) Terminal size 0.5 to 2.55 m2 (20 to 14 AWG)

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

2 wire
R R

SERVICE RESET

Polarity independent

4 wire
T T RR

T R T R T R T R T R T R
X

TT+ RR+ TT+ RR+ SCN SCN T T

T R T R
internal links

TT+ R- internal links R+ TT+ RR+ SCN SCN RRTT


X

T R T R T R T R T R T R

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 3

LINC 3.1 Installation - Mounting (Continued)

Installation Instructions

Connect LONWORKS network

Cable Belden 85102 Trend TP/1/0/16/HF/200 (Beldon 8471) UL Level IV, 22 AWG JY(St) Y2 x 2 x 0.8 TIA568A Cat. 5, 24 AWG

Max bus length Max node to node 500 m 500 m 500 m 500 m 450 m 500 m 400 m 400 m 320 m 250 m

POWER 0V

BAUD

ADDRESS

Normal current loop Lan cable is not recommended. Do not use screened cable. Terminal size 0.5 to 2.55 m2 (20 to 14 AWG) If used with LPT-10 (powered bus), cable lengths differ - see Link Power Transceiver Users Guide (078-0105-01C). LONWORKS - FTT (free topology) internal links

LONWORKS network

polarity independent LONWORKS network


LINC
SCN LonA LonB SCN LonA LonB

Recommend terminate at LINC or Router. e.g. use IQLRouter integral terminators Maximum 64 nodes per LONWORKS segment Maximum 40 IQLs (and LONCs) per Lan
100 m F, 50 V min

Close Panel
POWER 0V

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

SCN LonA LonB SCN LonA LonB

SERVICE RESET

T e r m in a to r

T e r m in a to r

Loop topology

Star topology

T e r m in a to r

Bus topology
IQLROUTER
T A 4 5 6 7 B 8 9 10 11 w x y z

IQL

Do not allow wires to cross on a loop

*Terminate LONWORKS bus at one end only using IQLROUTER integrated LONWORKS terminator or LONTERMINATOR
IQLROUTER
T A 4 5 6 7 B 8 9 10 11 w x y z T

IQL

LONTERMINATOR

100 m F, 50 V min

BAUD

ADDRESS

This unit is UL rated as UL916 accessory to open energy management equipment.

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012

Installation Instructions 3.2 Installation - Configuration

LINC

Switch off
O I

Open Panel
POWER 0V

WARNING:

Opening the panel may expose dangerous voltages. 417-IEC-5036

BAUD

ADDRESS

Set LINC Internetwork Address (Lan number)


Address = D
POWER 0V

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

Caution:

This LINC contains static sensitive devices. Suitable anti-static precautions should be taken throughout this operation to prevent damage to the unit. BS EN100015/1 Basic Specification: protection of electrostatic sensitive devices

Lan =D

LINC
Lan = /D

Lan = /D

address

1, 4 to 9, 11 to 119 0, 2, 3, 10 or >119

Lan = /D

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

if address < 100, address defines Lan number on Internetwork (LONWORKS internetwork)

SERVICE RESET

Lan

LINC

Internetwork on LONWORKS

if address = > 100, address is for configuration only (Internetwork LONWORKS Extension)
Internetwork Segment A

LINC

Internetwork Segment B on LONWORKS

ON

e.g.
ON

BAUD

ADDRESS

19K2

SET
8

Address = 2 + 16 = 18

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 5

9K6 1K2

16

32

64

NOT SET

LINC 3.2 Installation - Configuration


(continued)

Installation Instructions

Set Network Baud Rate


ON
POWER 0V

Baud = C =C LINC =C

=C
BAUD ADDRESS 1 2 4 8 16 32 64 19K2 9K6 1K2 S3

=C

If address < 100, baud rate of current loop Lan Internetwork on LONWORKS network

SERVICE RESET

= 19k2 baud

Lan

LINC

SET NOT SET

= 9k6 baud

If address = > 100, baud rate of current loop Internetwork (Segment A)


Internetwork Segment A

LINC

Internetwork segment B on LONWORKS network

= 1k2 baud

Switch On

O I

Set Network Baud Rate


POWER 0V

if address < 100, current loop Lan If address = > 100, current loop Internetwork (Segment A)

Lan OK (green)

Lan OK

NETB/LINC

Lan OK Check baud rate. Power up other nodes until faulty node is found (OK ). Correct fault.

LINC Faulty
BAUD ADDRESS 1 2 4 8 16 32 64 19K2 9K6 1K2 S3

Check LINC on LONWORKS network


Lon OK (green)
POWER 0V

SERVICE RESET

O I

Check network cabling for short circuits with a multimeter (NOT Megger)

Flashes every 24 s, ON after 1 mins (Check LONWORKS network, LINC, LINC,and IQL)

Close Panel
POWER 0V

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2

Lan
LINC

S3

SERVICE RESET

and

LINC

IQL

or

IQL

LONWORKS network

This unit is UL rated as UL916 accessory to open energy management equipment.

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012

Installation Instructions 3.2 Installation - Configuration(continued)

LINC

Config LINC
LONWORKS network
LINC

SET Manual TE200147 LONWORKS network


LINC

or

top menu :

address 126, local Lan

Lan

I/N

address 126, Lan number set by address switch

e.g. R

select addRess module

Lan

to eXit module having changed parameter SET Note that the LINC can be configured across the LONWORKS network (using another LINC) if TARP is set to Yes (default) in both LINCs (see step 14) to Quit module and discard changes Q

10

Set up following parameters

Note that a PIN may be required to make changes in configuration mode. If the PIN has been forgotton the users should contact their supplier (installers contact Technical Support) quoting the generator number (User module) and neuron id (Address module) whereupon a default PIN will be supplied. This will only work during the same configuration mode session i.e. the utility must not be exited between reading the generator and entering the default PIN. After the PIN is entered a new PIN should be set up and remembered.
Settings that must be made Parameter Setting Function Condition *Change to No unless connected to second LINC by LONWORKS network to send current loop network alarms to send current loop network alarms to send alarms from LONWORKS internetwork to send alarms from LONWORKS internetwork

Address

tarP

address resolution Switches on or off global protocol, address resolution messages default=Yes node address of LINC alarm target Lan number of LINC alarm target node address of LINC alarm target Lan number of LINC alarm target

local Addr node address alarms Remote lan Lan number int/net nodE alarms remoTe lan node address Lan number

*Note that to speed up communications,TARP should be changed to No unless there is more than one LINC physically connected by the LONWORKS network. Installation on a LONWORKS Management Tool sets TARP to Yes and it can no longer be changed in configuration mode (see step 14).

11

Set up the following parameters if required. The table shows setting that may be required for special circumstances Note 1: If PIN is forgotton see note in step 10 2: Message code can only be changed in configuration mode if LONWORKS managed is set to No (i.e. managed by LINC). If the LINC is installed on LONWORKS Management Tool (see step 14), lonworks managed is set to YES, and Message code cannot be changed in configuration mode.
Setting number 15 alphanumeric characters - not ^({;?* characters code number. Default = 64. buffer size (bytes) Default = 146 number defines transceiver type Default=0 (FTT-10) Function Protects changes in configuration mode identifier for this LINC All LINCs/IQLs must use same code specifies smallest router buffer on system Condition Default is blank (unprotected). Set up if security required. Set up for supervisors, display panels If message code being used by other users - must be exclusive to IQ system If routers separate LINCs and have buffer size smaller than 146 bytes - set to smallest buffer size. (minimum = 66) DO NOT CHANGE FROM 0 See IQ system LONWORKS Products Engineering Guide for details See Note 1

Optional Settings

Settings that may be made Parameter User Pin

Address IDentifier lonworks Message code router Buffer size transceiVer r-retry time i-interpacket delay s-service class

LINC Installation Instructions TG103062 Issue 3 , 26-Nov-2012 7

LINC 3.2 Installation - Configuration(continued)

Installation Instructions

12

Note Neuron ID

13

Exit Configuration

If user wishes to install LINC using Neuron ID - see step 14 a addRess/ neuron chip id 00:00:00:00:00:00

"Exit from Utility

14
If a or b or c or d

Install on LONWORKS Network Management Tool (LMT)


binding IQLs to LON MARK Devices LINCs version <3.23 straddle router other devices have address conflicts with IQ system devices IQLROUTERs used on system already installed on LMT

15

Check LINC Operation

If LONWORKS Internetwork (LINC address <100)

terse text comms

If one IQ system LONWORKS device is installed on LMT, all must be installed Note that if a 3xtend/EINC L is installed in the LONWORKS segment, IQ system devices cannot be installed on a LMT because 3xtend/EINC L does not support installation on a LMT. a). When installing LINC on LONWORKS tool enter Neuron ID from step 12 - or press service button.
POWER 0V

Lan
or LINC LINC
IQL

or
IQL

LONWORKS network

If Internetwork LONWORKS Extension (LINC address =>100)

terse text comms

BAUD

ADDRESS

1 2 4 8 16 32 64 19K2 9K6 1K2 S3

sevice button

Lan

I/N
or LINC LINC
IQL

SERVICE RESET

or
IQL

b).

The LINC network image can be retrieved by uploading the XIF file from LINC to tool

LONWORKS network

See LONWORKS network management tool manual. See IQ system LONWORKS Products Engineering Guide (TE200292). L O N W O R KS System Integrator must have L O N W O R KS engineering expertise.

Disposal
WEEE Directive: At the end of their useful life the packaging, and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

Cleaning and maintainance

There are no serviceable parts inside the unit. Cleaning of the unit should be carried out in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning. Clean surfaces with a cloth moistened with water.

Please send any comments about this or any other Trend technical publication to techpubs@trendcontrols.com 2012 Honeywell Technologies Srl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Srl, Z.A. La Pice, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited. Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.