Anda di halaman 1dari 1

WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

TABLE 27 - 12.7/22 KV (E) HT XLPE THREE CORE ALUMINIUM CONDUCTOR CABLES


POLYCAB THREE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
Nominal
Size
of
Conductor
Sq.mm.

UNARMOURED CABLE
FORMED WIRE / STRIP ARMOURED CABLE
ROUND WIRE ARMOURED CABLE
CURRENT CARRYING CAPACITY
Minimum
Nominal
In In Duct at In Air at *Normal
Thickness Nominal Approx. Approx Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
Thickness
40 C. Delivery
of PVC Thickness Overall Weight Dimension Thickness Overall Weight of Dimension Thickness Overall Weight of Ground at 30 C.
of XLPE
of
PVC
Diameter
of
Cable
of
GI
Flat
of
PVC
Diameter
Cable
of
GI
of
PVC
Diameter
Cable
30
C.
Inner
Length
Insulation
Strip
Outer of Cable
Round Outer of Cable
Sheath Outer of Cable
Sheath
Sheath
Wire
Sheath
mm

mm

mm

Kg/Km

mm

mm

mm

mm

Kg/Km

mm

mm

mm

Kg/Km

Amps.

Amps.

Amps.

Mtrs.

95

6.0

0.7

3.2

66.0

4450

0.8

2.36

66.0

5300

3.15

2.52

71.0

7750

190

170

230

500

120

6.0

0.7

3.4

70.0

5050

0.8

2.52

70.0

5900

3.15

2.68

75.0

8500

215

190

265

500

150

6.0

0.7

3.4

72.5

5550

0.8

2.68

72.5

6500

3.15

2.68

77.5

9200

240

215

300

250

185

6.0

0.7

3.6

77.5

6300

0.8

2.68

77.5

7250

3.15

2.84

82.0

10150

270

240

340

250

240

6.0

0.7

3.8

82.5

7300

0.8

2.84

82.5

8300

4.0

3.0

89.0

12600

310

275

400

250

300

6.0

0.7

4.0

87.5

8300

0.8

3.0

87.5

9350

4.0

3.0

93.5

13850

350

310

455

250

400

6.0

0.7

4.0

94.5

9850

0.8

3.0

94.5

10950

4.0

3.0

100.0

15800

395

355

530

250

TABLE 28 - 12.7 / 22 KV (E) HT XLPE THREE CORE COPPER CONDUCTOR CABLES


POLYCAB THREE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
UNARMOURED CABLE
FORMED WIRE / STRIP ARMOURED CABLE
ROUND WIRE ARMOURED CABLE
CURRENT CARRYING CAPACITY
Minimum
In In Duct at In Air at *Normal
Thickness Nominal Approx. Approx Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
Thickness
Overall
Weight
Dimension
Thickness
Overall
Weight
of
Dimension
Thickness
Overall
Weight
of
Ground
at 30 C.
40 C. Delivery
of PVC
of PVC Diameter of Cable of GI Flat of PVC Diameter Cable
of GI
of PVC Diameter Cable
30 C.
Inner
Length
Strip
Outer of Cable
Round Outer of Cable
Sheath Outer of Cable
Sheath
Sheath
Wire
Sheath

Nominal
Size
of
Conductor

Nominal
Thickness
of XLPE
Insulation

Sq.mm.

mm

mm

mm

Kg/Km

mm

mm

mm

mm

Kg/Km

mm

mm

mm

Kg/Km

Amps.

Amps.

Amps.

Mtrs.

95

6.0

0.7

3.2

66.0

6200

0.8

2.36

66.0

7050

3.15

2.52

71.0

9500

245

215

300

500

120

6.0

0.7

3.4

70.0

7300

0.8

2.52

70.0

8150

3.15

2.68

75.0

10750

275

245

340

500

150

6.0

0.7

3.4

72.5

8300

0.8

2.68

72.5

9300

3.15

2.68

77.5

11950

305

275

385

250

185

6.0

0.7

3.6

77.5

9750

0.8

2.68

77.5

10700

3.15

2.84

82.0

13600

345

305

435

250

240

6.0

0.7

3.8

82.5

11750

0.8

2.84

82.5

12750

4.0

3.0

89.5

17050

395

350

510

250

300

6.0

0.7

4.0

87.5

13900

0.8

3.0

87.5

14950

4.0

3.0

93.5

19400

440

390

580

250

400

6.0

0.7

4.0

94.5

17250

0.8

3.0

94.5

18400

4.0

3.0

100.0

23250

495

440

660

200

The above data is approximate and subject to manufacturing tolerance.





* Delivery Length tolerance is 5 %. Length more than normal as per customer request.

26

Anda mungkin juga menyukai