CURRENT CARRYING CAPACITY
Minimum
Nominal
In In Duct at In Air at *Normal
Thickness Nominal Approx. Approx Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
Thickness
40 C. Delivery
of PVC Thickness Overall Weight Dimension Thickness Overall Weight of Dimension Thickness Overall Weight of Ground at 30 C.
of XLPE
of
PVC
Diameter
of
Cable
of
GI
Flat
of
PVC
Diameter
Cable
of
GI
of
PVC
Diameter
Cable
30
C.
Inner
Length
Insulation
Strip
Outer of Cable
Round Outer of Cable
Sheath Outer of Cable
Sheath
Sheath
Wire
Sheath
mm
mm
mm
Kg/Km
mm
mm
mm
mm
Kg/Km
mm
mm
mm
Kg/Km
Amps.
Amps.
Amps.
Mtrs.
95
6.0
0.7
3.2
66.0
4450
0.8
2.36
66.0
5300
3.15
2.52
71.0
7750
190
170
230
500
120
6.0
0.7
3.4
70.0
5050
0.8
2.52
70.0
5900
3.15
2.68
75.0
8500
215
190
265
500
150
6.0
0.7
3.4
72.5
5550
0.8
2.68
72.5
6500
3.15
2.68
77.5
9200
240
215
300
250
185
6.0
0.7
3.6
77.5
6300
0.8
2.68
77.5
7250
3.15
2.84
82.0
10150
270
240
340
250
240
6.0
0.7
3.8
82.5
7300
0.8
2.84
82.5
8300
4.0
3.0
89.0
12600
310
275
400
250
300
6.0
0.7
4.0
87.5
8300
0.8
3.0
87.5
9350
4.0
3.0
93.5
13850
350
310
455
250
400
6.0
0.7
4.0
94.5
9850
0.8
3.0
94.5
10950
4.0
3.0
100.0
15800
395
355
530
250
Nominal
Size
of
Conductor
Nominal
Thickness
of XLPE
Insulation
Sq.mm.
mm
mm
mm
Kg/Km
mm
mm
mm
mm
Kg/Km
mm
mm
mm
Kg/Km
Amps.
Amps.
Amps.
Mtrs.
95
6.0
0.7
3.2
66.0
6200
0.8
2.36
66.0
7050
3.15
2.52
71.0
9500
245
215
300
500
120
6.0
0.7
3.4
70.0
7300
0.8
2.52
70.0
8150
3.15
2.68
75.0
10750
275
245
340
500
150
6.0
0.7
3.4
72.5
8300
0.8
2.68
72.5
9300
3.15
2.68
77.5
11950
305
275
385
250
185
6.0
0.7
3.6
77.5
9750
0.8
2.68
77.5
10700
3.15
2.84
82.0
13600
345
305
435
250
240
6.0
0.7
3.8
82.5
11750
0.8
2.84
82.5
12750
4.0
3.0
89.5
17050
395
350
510
250
300
6.0
0.7
4.0
87.5
13900
0.8
3.0
87.5
14950
4.0
3.0
93.5
19400
440
390
580
250
400
6.0
0.7
4.0
94.5
17250
0.8
3.0
94.5
18400
4.0
3.0
100.0
23250
495
440
660
200
26