Anda di halaman 1dari 1

WEIGHT, DIMENSION DATA & CURRENT CARRYING CAPACITY OF CABLES

TABLE 13 - 12.7/22 KV (E) HT XLPE SINGLE CORE ALUMINIUM CONDUCTOR CABLES


POLYCAB SINGLE CORE ALUMINIUM CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
Nominal
Size
of
Conductor
Sq.mm.
95
120
150
185
240
300
400
500
630
800
1000

UNARMOURED CABLE
Nominal Nominal Approx. Approx.
Thickness Thickness Overall Weight of
of XLPE of PVC Diaeter Cable
Insulation Outer
of
Sheath Cable
mm
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

mm
2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.6
2.6
2.8
3.0

mm
32.0
34.0
35.0
37.0
39.0
41.0
45.0
48.0
51.5
56.0
61.0

Kg/Km
1100
1200
1350
1500
1750
2000
2400
2850
3300
4000
4800

ALUMINIUM STRIP ARMOURED CABLE


Minimum Nominal Minimum Approx. Approx.
Thickness Dimesion Thickness Overall Weight of
of Inner
of
of PVC Diameter Cable.
Sheath
Strip
Outer of Cable
Sheath
mm
0.40
0.40
0.40
0.40
0.40
0.40
0.50
0.50
0.50
0.60
0.60

mm
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

mm
1.56
1.56
1.56
1.56
1.56
1.72
1.88
1.88
2.04
2.04
2.2

mm
33.0
35.0
36.0
38.0
40.5
43.0
47.0
50.0
54.0
58.0
62.5

Kg/Km
1250
1400
1530
1700
1950
2250
2700
3100
3700
4350
5150

ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY


Nominal
Dimesion
of
Round
Wire

Minimum
Thickness
of PVC
Outer
Sheath

mm
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5

mm
1.56
1.56
1.56
1.72
1.72
1.72
1.88
2.04
2.04
2.2
2.36

Approx. Approx.
In In Duct at In Air at *Normal
Overall Weight of Ground at 30 C.
40 C. Delivery
Diameter Cable
30 C.
Length
of Cable
mm
36.0
37.5
39.0
41.0
43.0
45.0
49.0
53.5
57.0
61.0
66.0

Kg/Km
1450
1600
1750
2000
2250
2500
3000
3650
4150
5000
5800

Amps.
205
230
260
290
335
380
430
485
550
610
660

Amps.
180
200
225
255
290
325
370
420
470
520
560

Amps.
270
310
350
400
470
540
630
730
840
950
1060

Mtrs.
500
500
500
500
500
500
500
500
500
500
500

TABLE 14 - 12.7 / 22 KV (E) HT XLPE SINGLE CORE COPPER CONDUCTOR CABLES


POLYCAB SINGLE CORE COPPER CONDUCTOR, XLPE INSULATED, UNARMOURED & ARMOURED CABLES CONFORMING
TO IS: 7098 PART-2/1985:
Nominal
Size
of
Conductor
Sq.mm.
95
120
150
185
240
300
400
500
630
800
1000

UNARMOURED CABLE
Nominal Nominal Approx. Approx.
Thickness Thickness Overall Weight of
of XLPE of PVC Diaeter Cable
Insulation Outer
of
Sheath Cable
mm
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

mm
2.2
2.2
2.2
2.2
2.2
2.2
2.4
2.6
2.6
2.8
3.0

mm
32.0
34.0
35.0
37.0
39.0
41.0
45.0
48.0
51.5
56.0
61.0

Kg/Km
1650
1950
2250
2650
3200
3850
4900
5950
7200
8950
11000

ALUMINIUM STRIP ARMOURED CABLE


Minimum Nominal Minimum Approx. Approx.
Thickness Dimesion Thickness Overall Weight of
of Inner
of
of PVC Diameter Cable
Sheath
Strip
Outer of Cable
Sheath
mm
0.40
0.40
0.40
0.40
0.40
0.40
0.50
0.50
0.50
0.60
0.60

mm
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8

mm
1.56
1.56
1.56
1.56
1.56
1.72
1.88
1.88
2.04
2.04
2.2

mm
33.0
35.0
36.0
38.0
40.5
43.0
47.0
50.0
54.0
58.0
62.5

Kg/Km
1850
2150
2450
2850
3450
4100
5200
6200
7600
9300
11350

ALUMINIUM ROUND WIRE ARMOURED CABLE CURRENT CARRYING CAPACITY


Nominal
Dimesion
of
Round
Wire

Minimum
Thickness
of PVC
Outer
Sheath

mm
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5

mm
1.56
1.56
1.56
1.72
1.72
1.72
1.88
2.04
2.04
2.2
2.36

Approx. Approx.
In In Duct at In Air at *Normal
Overall Weight of Ground at 30 C.
40 C. Delivery
Diameter Cable
30 C.
Length
of Cable
mm
36.0
37.5
39.0
41.0
43.0
45.0
49.0
53.5
57.0
61.0
66.0

Kg/Km
2050
2350
2700
3150
3750
4350
5500
6750
8050
9900
12000

The above data is approximate and subject to manufacturing tolerance.





* Delivery Length tolerance is 5 %. Length more than normal as per customer request.

Amps.
265
300
330
375
430
480
540
600
660
720
760

Amps.
230
260
290
325
370
415
465
520
570
620
660

Amps.
345
400
450
510
600
690
790
910
1020
1140
1240

Mtrs.
500
500
500
500
500
500
500
500
500
500
500

19