QUALITROL 505ITM Series

QUALITROL 505ITM-100 Intelligent Transformer Monitor

Hardware and Software Instructions


Document ID: IST-104-1 ECN-28691

www.qualitrolcorp.com

Legal

Information in this document is subject to change without notice. This document is provided to purchasers of Qualitrol products for use in the installation, operation and servicing of such products. No other use, nor any reproduction, distribution or the making of any derivatives of this document is authorized, without the express prior written permission of Qualitrol. Qualitrol endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed or implied, is provided. Qualitrol disclaims any responsibility or liability for any direct or indirect damages resulting from the use of the information in this manual or products described in it. Mention of any product or brand does not constitute an endorsement by Qualitrol of that product or brand. This document was originally composed in English and was subsequently translated into other languages. The fidelity of subsequent translations cannot be guaranteed. In case of conflict between the English version and another language version, the English version takes precedence.
2010 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice. All trademarks are properties of their respective companies, as noted herein. IST-104-1.

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Contents
Hardware Instructions ..................................................................................... 1
Overview ................................................................................................................... 1
QUALITROL 505 Series Intelligent Transformer Monitor ............................................... 1

About Qualitrol ................................................................................................................ 2 About These Hardware Instructions ................................................................................ 2

Controls, Indicators, and Modules.......................................................................... 3


Front Panel ..................................................................................................................... 3 Modules .......................................................................................................................... 4 RTD Input Module ..................................................................................................... 4 CT Input Module ....................................................................................................... 4 AC Voltage Input Module .......................................................................................... 4 Potentiometer Input Module ...................................................................................... 4 DC Voltage Input Module .......................................................................................... 5 Current Input Module ................................................................................................ 5 Dry Contact Closure Module ..................................................................................... 5 Powered Contact Closure Module ............................................................................. 5

Installation ................................................................................................................ 6
Location and Mounting.................................................................................................... 6 Installing the Hardware ............................................................................................. 6 Mounting Styles ........................................................................................................ 8 Power Supply ................................................................................................................. 9 Heater Option ............................................................................................................... 10 RTD Input Modules ....................................................................................................... 10 CT Input Module ........................................................................................................... 11 AC Voltage Input Module .............................................................................................. 12 Potentiometer Input Module .......................................................................................... 12 DC Voltage Input Module .............................................................................................. 13 Current Input Module .................................................................................................... 13 Dry Contact Closure Input Module ................................................................................ 15 Powered Contact Closure Input Module ........................................................................ 15 Output Contacts ............................................................................................................ 16 Remote Output Signals ................................................................................................. 17

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Communications ........................................................................................................... 18

Operation ................................................................................................................ 19
Automatic Operation ..................................................................................................... 19 Viewing Channels or Viewing Mode Scrolling ......................................................... 19 MENU Mode ........................................................................................................... 19 Program Mode ........................................................................................................ 21 Testing the System ....................................................................................................... 21

Functional Specifications ...................................................................................... 22

Software Instructions .................................................................................... 24


General Information ............................................................................................... 24 Connecting to the 505ITM...................................................................................... 24 Installing/Running the Software............................................................................ 24 Desktop Communications Window ...................................................................... 25
File Menu ...................................................................................................................... 25

Establishing Communications with the 505ITM .................................................. 26 Troubleshooting the Communications Link ........................................................ 28 Overview of the 505ITM Tools on the Desktop Menu .......................................... 28 Opening a Tool ....................................................................................................... 30 Using the Monitor Tool .......................................................................................... 30 Using the Simulator Tool ....................................................................................... 32 Using the Factory Calibrator Tool (Advanced users only) ................................. 33 Using the Setup Tools ........................................................................................... 36
System Settings ............................................................................................................ 38 Password Setup ...................................................................................................... 39 Installed Features ................................................................................................... 40 Time and Date Setup .............................................................................................. 40 Display Setup.......................................................................................................... 42 Heater Setup........................................................................................................... 43 Communications ........................................................................................................... 44 Front USB - Service Port......................................................................................... 45 Main 485 - Main Port............................................................................................... 46 Aux 485 - Auxiliary Port........................................................................................... 48 Cancel and Load Buttons ........................................................................................ 48

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Input Modules ............................................................................................................... 49 Module .................................................................................................................... 50 Custom Scaling ....................................................................................................... 51 CT Current Parameters ........................................................................................... 52 Winding Temperature Setup (Calculated) ............................................................... 53 Simple Calculation Setup Method ..................................................................... 53 Advanced Calculation Setup Method................................................................. 57 Output Relays ............................................................................................................... 62 Relay Tabs.............................................................................................................. 63 Relay Control .......................................................................................................... 63 Seasonal Setpoint ................................................................................................... 66 Ambient Temperature Forecast............................................................................... 67 Cooling Equipment Exerciser .................................................................................. 70 Matrix Controlled ..................................................................................................... 71 Cancel and Load Buttons ........................................................................................ 72 Output Loops ................................................................................................................ 73 Loop Parameters .................................................................................................... 74 Custom Range ........................................................................................................ 74 Loop Controlled ...................................................................................................... 76 Bank Switching ............................................................................................................. 76 TransLife ................................................................................................................... 78 TransLifeTM Control ................................................................................................. 79 Consumed Life ........................................................................................................ 80 Critical Forecast ...................................................................................................... 81 Temperature Profiler ............................................................................................... 83

Importing and Exporting Configuration Files ...................................................... 85 Calibrating the 505ITM ........................................................................................... 86
Calibrating Remote Outputs for Alternate Values .......................................................... 86 Overview and Requirements ................................................................................... 86 Calibration Procedure ............................................................................................. 86 Calibrating a Level Gauge to the 505ITM ...................................................................... 90 Overview................................................................................................................. 90 Before You Begin .................................................................................................... 90 Calibration Procedure ............................................................................................. 91

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Frequently Asked Questions About the 505ITM .................................................. 97

Appendix ....................................................................................................... 101

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Hardware Instructions
Overview
QUALITROL 505 Series Intelligent Transformer Monitor

The QUALITROL 505 Series Intelligent Transformer Monitor (505ITM) for Liquid-Filled Transformers offers microprocessor technology and advanced digital signal processing to accurately assess the health and performance of oil-filled transformers.

The 505ITM can monitor up to four total parameters and can be adapted to suit the required application. Input 1: Liquid Temperatures (Main Tank Top or Bottom, Load Tap Changer) using a 100 ohm Resistance Temperature Detector (RTD) Input 2: Winding Temperature using a Clamp-on Current Transformer (0-5, 0-10, 020, 0-50, 0-100 amps) Inputs 3 & 4: Variable from the list below (factory configured) o o o o o o o Liquid Temperature Winding Temperature Winding Current Cooling Bank Current Liquid Level Switch Contact Inputs from other transducers such as Tank Pressure or Dissolved Gas in Oil

Required 505ITM inputs include:


Resistance Temperature Detectors (100 ohm RTDs) Clamp-on Current Transformers (0-5, 0-10, 0-20, 0-50, 0-100 amps) AC Voltage (0 - 140 VAC or 0 - 320 VAC) Potentiometer (5K - 15K) Current Loops (0 - 1 or 4 - 20 mA DC) DC Voltage (0 - 100 mV or 0 - 10 V) Switch Contact Closure (powered or dry)

www.qualitrolcorp.com

505ITM Hardware & Software Manual

The 505ITM offers:


Advanced thermal modeling of winding temperatures Superior temperature control for higher loads Standalone or networked substation monitoring Diagnostic tools for condition based maintenance Four, Form C adjustable relays to operate cooling equipment, signal alarms, and provide trip functions, depending on transformer conditions Two, 0 - 1 or 4 - 20 mA DC loops for use with SCADA systems Digital communication ports RS-232/USB and RS-485

The device is easy to install and use. It is designed to be mounted outdoors, with a heater available inside the enclosure, in a transformer control cabinet, and it is powered by a universal power supply of 90 - 264 VAC 47 - 63 Hz single-phase power or 40 - 290 VDC. It comes with a user-friendly, computer-aided setup software that can be supplied with nonintrusive, easy-to-retrofit sensors.

About Qualitrol
Qualitrol has been a leader in supplying pressure, liquid level, and temperature controls since 1945. As an ISO 9001 System-certified company, we are committed to providing quality and reliability, both in our products and in our service.

About These Hardware Instructions


These Hardware Instructions provide all the information you will need to configure, install, and operate your 505ITM. They are organized into the following sections: Controls, Indicators, and Modules - Diagrams and brief descriptions to help you locate and understand basic functions of each of the controls, indicators, and modules that make up the 505ITM. Installation - Illustrated instructions to guide you through mounting, supplying power to, and wiring your transformer monitor. Operation - A description of automatic operation, as well as easy instructions on viewing parameters and set points, resetting memories, programming the 505ITM using the Keypad, and testing the system. Functional Specifications - A detailed, functional specification of the monitor. Appendix - A functional wiring diagram for your reference, an example of the front panel menu diagram, and a rear cover view.

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Controls, Indicators, and Modules


Front Panel
The functions of the display and the keypad on the front panel are described below. For operating instructions, refer to the Operation section. DISPLAY - Every two seconds, the display automatically scrolls through the channels and displays the channel name and the value of the parameter. It also displays the selected indications of the keypad control. KEYPAD - The ENTER key is used to change menu modes or accept changes to values; the TEST key displays the set point source and value on the DISPLAY; the MENU key is used to access the programming menu; and the RESET key is used to reset the maximum and minimum values, while in the program menu, or unlatch any latched relays while in the normal scrolling mode. The ARROW keys are used to move through the various menus. For a full operation description, refer to the Operation section. SET POINT INDICATORS - A red LED illuminates to indicate that the set point for the relay, indicated on the overlay, has been exceeded. RS-232 PORT or USB PORT - When used with the Qualitrol software, this port allows for the setup of all of the parameters of the monitor. See the Software Instructions section for a full description of this setup procedure.
505 ITM
INTELLIGENT TRANSFORMER MONITOR

DISPLAY SET POINT INDICATORS


TEST MENU RELAY 1 RELAY 2 RELAY 3 RESET

KEYPAD

ENTER

RS-232 PORT USB PORT

RELAY 4

RS-232

505ITM Front Panel

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Modules
The modules comprising the 505ITM include:

RTD Input Module CT Input Module AC Voltage Input Module Potentiometer Input Module DC Voltage Input Module Current Input Module Dry Contact Closure Module Powered Contact Closure Module

RTD Input Module


RTD Input Modules are used for monitoring liquid, ambient, or if used in a heated well, winding temperatures. The input to the module is either a 100 ohm platinum RTD or 10 ohm copper RTD. For measuring liquid or ambient temperatures, the module is scaled over the range of -40 120 C. If it is used in a heated well, the scale is -40 - 200 C. When ordering the 505ITM from the factory, the temperature requirements need to be specified.

CT Input Module
The CT Input Module is used to monitor winding temperatures, winding currents, motor currents of LTCs, or fan currents. The input to the module is a clamp on the CT, provided by Qualitrol, which has an input range of 0 - 5 A, 0 - 10 A, or 0 - 20 A, other ranges are available, and an output of 0 - 0.333 VAC, can be used as the input to the CT Input Module. If this module is used for winding temperatures, the scaling is in the range of -40 - 200 C; for anything other than temperature, the range is scalable to a maximum of 99999.9 C.

AC Voltage Input Module


The AC Voltage Input Module is used to monitor any AC voltages under 320 VAC. The input module works in conjunction with the Qualitrol Voltage Sensor, TRA-600-1, and measures ranges of either 0 - 140 VAC or 0 - 320 VAC. The range is scalable to a maximum of 99999.9 VAC.

Potentiometer Input Module


The Potentiometer Input Module is used for monitoring liquid level, flow gauges, or gas accumulation. The input to the module is a potentiometer that is typically supplied by Qualitrol. The range of the potentiometer input is up to 15,000 ohm. Typically, the 25 mark on a liquid level dial is set to the center of the potentiometer range, and the high and low readings are simply ratios of the angular deflections from the normal setting. Qualitrol gauges use a 340 angular degree potentiometer on a 2:1 gear ratio from the dial travel to the potentiometer travel. The Potentiometer Input Module must be calibrated on site. For

www.qualitrolcorp.com

505ITM Hardware & Software Manual


more information, see the Using the Factory Calibrator Tool (Advanced users, only) section in the Software Instructions. The scaling of the 505ITM for this module is 0 - 100%.

DC Voltage Input Module


The DC Voltage Input Module is used for monitoring transducer outputs with an output signal in either the 0 - 100 mVDC or 0 - 10 VDC range. The range for this module is scalable to a maximum of 99999.9 VDC.

Current Input Module


The Current Input Module is used for monitoring transducer output with an output signal in either the 0 - 1 mA DC or 4 - 20 mA DC range. These can be devices such as pressure transducers for measuring main tank pressure, bushing pressure, or dissolved gas in oil transducers. The input module can be configured to operate with either two-wire loop transducers, which are powered by the module, or three-wire transducers that are powered by the module or from the transducer. The range for this module is scalable to a maximum of 9999.99 mA DC.

Dry Contact Closure Module


The Dry Contact Closure Module is used for monitoring a contact and indicating on a display if it is open or closed. An open contact means there is no connection between the contacts; a closed contact signifies a shorted connection across the contacts. This can be used, for example, to monitor pumps or fans. The system internally treats closed and opened contacts as either a 0 or 100 numeric value. Therefore, if the module is used to control a relay, the relay set point should be set at midrange, e.g., 50. This module can monitor a non-powered, dry contact.

Powered Contact Closure Module


The Powered Contact Closure Module is used to monitor a powered contact, and it indicates on the display whether it is opened or closed. An open means there is no connection between the contacts, and closed indicates a shorted connection across the contacts. This can be used to monitor alarms or active fans, for example. The system internally treats closed and open contacts as either a 0 or 100 numeric value. Therefore, if the module is used to control a relay, the relay set point should be set at midrange, e.g., 50. This module can monitor a powered contact of >80 VAC/DC or >130 VAC/DC jumper selectable.

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Installation
Location and Mounting
Installing the Hardware
1. Unpack the 505ITM. 2. Check that all of the materials on the packing slip are included. 3. Make four holes on the transformer panel for installation of the monitor.

Important:

Note the mounting differences between the enclosure style and the panel-only style. Allow space below the monitor for the wiring harness.

4. Install the monitor.

Important:

Ensure that the sensor type matches the input designator labels on the 505ITM dust cover.

1 2 3 4 5 6 7 8 9

TB1

17 18 19 20 21 22 23 24 25

TB3
1 2 3
INPUT MODULE 1

TB4
1 2 3
INPUT MODULE 2

Input Modules

10 26 11 27 12 28 13 29 14 30 15 31 16 32 1 2 3

TB5
INPUT MODULE 3

1 2 3 4 5

TB6
1 2 3
INPUT MODULE 4

Optional Heater TB1-1,17

TB2

1 2 3 4 5

EARTH GROUND

VAC LINE INPUT (+)

TB1 TB1
VAC LINE HEATER

1 2 3 4 5

17 18 19 20 21 22 23 24 25 26 27 28 29 30 32

VACC NEUT HEATER

VACC NEUT INPUT (-)

INPUT POWER: (UNIVERSAL) 90-264 VAC, 47-63 Hz 40-290 VDC WATTAGE: < 30 WATTS AC IN < 15 WATTS DC IN LINE FUSE - 3.15 AMPS RELAY CONTACTS: 10 A @ 115/230 VAC 10 A @ 30 VDC
MODEL NO. SERIAL NO. MFG. DATE

RXD+(B) RXD-(A) SIGNAL GND

RELAY 2
10 A

6 7 8

RELAY 3
10 A

9 10 11

T/RXD+(B) T/RXD-(A) SIGNAL GND

RS-485

Input Power

RELAY 1
10 A

TXD+(B) TXD-(A)

RS-485 Interface

RELAY 4
10 A

12 13 14 15 16

(+)

SYSTEM STATE RELAY 10A

CURRENT (-) LOOP 1 CURRENT (-) LOOP 2

Current Output Loops

31 (+)

Alarm Relays

505ITM Back Panel

www.qualitrolcorp.com

505ITM Hardware & Software Manual

5. Wire input sensors to the correct inputs, TB3 through TB6. 6. Connect the correct alarm control circuitry, TB1-2 through TB1-16. See the wiring schematics or engineering drawings for your specific transformer.

Note:

The optional VAC heater input is TB1-1 and TB1-17. Relay contact ratings: 10 A @ 115/230 VAC, 10 A @ 30 VDC potential damage to the 505ITM.

CAUTION: The loops must be connected to the isolated analog input to avoid
7. If required, connect the current output loops, TB-29 through TB1-32. 8. Connect the RS-485 communications to TB1-19 through TB2-23.

4-wire: TB1-19 through TB1-22; signal ground on TB1-23, not an earth ground 2-wire: TB1-25, 26; signal ground on TB1-27, not an earth ground Universal power supply: 90 - 264 VAC, 47 - 63 Hz 40 - 290 VDC the unit.

9. Connect the input power, TB2-3, 5, and earth ground to TB2-1.

CAUTION: Installing power outside of the recommended input range will damage
10. Energize the 505ITM. The monitor briefly displays Qualitrol and the version of the board firmware.

Important:

The following operation can cause the alarm output state to change.

11. On the front panel, press TEST. Relays 1 through 4 actuate.

Note:

Relays that have been configured with the test lockout feature enabled will not operate, but the corresponding LED will light.

12. Upon commissioning the 505ITM, do the following steps to reset the maximum and minimum values: (a) Press MENU. (b) Scroll to the View Maximum Value column (see menu flowchart). (c) Press RESET. (d) Scroll to the View Minimum Value column. (e) Press RESET. (f) Press MENU. When the test is complete, the monitor defaults back to the scrolling mode, cycling consecutively through the display of each active input. You are now ready to use the ITM Manager software which is found on the documentation CD-ROM, to view, change, or modify the settings of the 505ITM to meet your requirements.

www.qualitrolcorp.com

505ITM Hardware & Software Manual Mounting Styles


Enclosure Style The 505ITM is a 3R enclosure style, designed to be back-mounted on any smooth surface. Four 0.31 0.50 in. oval slots are provided for use with fasteners. The monitor requires an approximate area that is 11.5 inches in width, 13.0 inches in height, and 6.5 inches in depth. An additional area below the monitor should be allowed for the wiring harness. See Mounting the 505ITM figure for mounting centers and dimensions. Panel Mount Style The 505ITM is designed to be flush-mounted inside a transformer control cabinet on any smooth surface. Four 0.28 in. square holes are provided for use with the 0.25 in. diameter carriage bolts. The monitor requires an approximate area of 8.50 inches in width, 10.50 inches in height, and 3.00 inches in depth. An additional area below the monitor should be allowed for the wiring harness.
Captive Thumb Screw (2) Places

3.00 [76.3]

Suggested Panel Cutout = 7.8 WD x 9.3 HI

Mounting the 505ITM

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Power Supply
Supply power is applied to Terminal Block TB2 terminals 3 and 5. For DC input, positive voltage is applied to terminal 3, and ground or negative voltage is applied to terminal 5. Chassis ground is applied to terminal 1, as shown in the Power Supply Connection figure. This non-metallic enclosure does not automatically provide a common grounding lug. Grounding must be provided as part of the installation, and it must be in accordance with the requirements of the National Electrical Code (NEC) or any international code that is in effect.

1 2 3 4 5

EARTH GROUND

TB2

1 2 3 4 5

EARTH GROUND

VAC LINE INPUT (+)

VACC NEUT INPUT (-)

90-264 VAC, 47-63 Hz 40-290 VDC

Power Supply Connection

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Heater Option
If the Enclosure or Panel Mount monitor is supplied with the Heater Option, the supply power, 120 or 240 VAC, as specified when ordering, is applied to Terminal Block TB1 terminals 1 and 17, as shown in the Heater Option Connection figure.

Heater Option Connection

Qualitrol recommends that the heater circuit be installed with a fuse for safety and protection purposes. The fuse is the responsibility of the installer. The rating of the heater is 75 watts at 120 VAC. A 240 VAC heater uses two of these heaters in a series, for a total of 150 watts. Qualitrol recommends installing a slow-blow fuse rated at 1.00 A, at 600 V.

RTD Input Modules


For each RTD Input Module, one standard 100 ohm RTD (or 10 ohm RTD), with a threeconductor, shielded cable is required to measure liquid and ambient temperature, or if in a heated well, winding temperature. The three conductors and the shield drain lead are connected to the monitor, as shown in the RTD Input Wiring Connections figure.

CAUTION: RTD wiring should be continuous, and the shield drain lead must be
grounded only at the instrument. The monitor uses a compensation scheme for the RTD cable connection. The three-wire connection compensates for the resistance of the connecting wires.

RTD Input Wiring Connections

If you are upgrading an existing Qualitrol device, or if the RTD you have installed is a fourwire RTD, DO NOT connect the fourth wire in parallel with the third wire, this will adversely affect the compensation scheme. If you have a fourth wire on the RTD connection, cut the fourth wire flush with the jacket. Qualitrol recommends a maximum length of 75 feet for RTD cabling.

10

www.qualitrolcorp.com

505ITM Hardware & Software Manual Note:


Due to dimensional and mounting variations, the RTD, well, and connector must be ordered separately and are available from Qualitrol.

CT Input Module
For each CT Input Module, one standard clamp on the CT, TRA-017-X, is required to calculate winding temperature or currents. Input the current range as specified. Pull the supplied Qualitrol clamp on CT Sensor apart and place the wire which carries the current to be sensed, into the CT opening. Push the CT sensor back together and check that it is fully engaged. As shown in the CT Input Connections figure, connect the output wires of the clamp on CT to the terminal board.

CT Input Connections

The Qualitrol clamp-on CT sensor comes with 20 feet of cable. While it is not recommended to run the wire longer than 20 feet, if the application requires a longer distance, splice the longer cable as close to the clamp on sensor as possible. This replacement cabling should consist of shielded twisted pair wire.

Note:

Because the CT sensor is isolated from the transformer, the burden is so small it can only be measured in a laboratory. For all practical purposes, the burden sensed by the transformer is zero. current directly to the 505ITM will damage the unit.

Caution: The 505ITM measures current using the clamp on CT sensors. Wiring

11

www.qualitrolcorp.com

505ITM Hardware & Software Manual

AC Voltage Input Module


For each AC Voltage Input Module, one AC Voltage Sensor, TRA-600-1, is required to measure the AC voltage. The module can measure either 0 - 140 VAC or 0 - 320 VAC, 50/60 Hz, as specified at the factory. Connect the voltage to be measured to the sensor input Terminal Block TB1 of the voltage sensor (TRA-600-1). Then connect the sensor output to the terminal block of the AC Voltage Input Module, as shown in the AC Voltage Input Connections figure.

AC Voltage Input Connections

Caution: The 505ITM measures voltage using the Voltage sensor. Wiring directly to
the Voltage Input Module will damage the unit.

Potentiometer Input Module


For each Potentiometer Input Module, one standard potentiometer in the range of 1500 15000 ohm, as supplied by various Qualitrol case assemblies, is required to measure liquid level, flow, or gas accumulation. The module must be calibrated on site. See the Using the Factory Calibrator Tool (Advanced users, only) section in the Software Instructions. The three conductors and the shield drain lead are connected to the monitor, as shown in the Potentiometer Input Connections figure.

CAUTION: Wiring should be continuous, and the shield drain lead must be
grounded only at the instrument.

Potentiometer Input Connections

12

www.qualitrolcorp.com

505ITM Hardware & Software Manual

DC Voltage Input Module


For each Voltage Input Module, one voltage transducer, 0 - 100 mVDC or 0 - 10 VDC, as specified, is required. Connect the output wires of the transducer to the terminal block as shown in the DC Voltage Input Wiring figure.

DC Voltage Input Wiring

Current Input Module


The Current Input Module is configurable to accept either a 0 - 1 mA DC or a 4 - 20 mA DC (SCADA type) signal. Either of these options can be a transducer that is:

2-wire, self-powered from the transducer 2-wire, powered from the input module 3-wire, powered from the input module

For each Current Input Module, one current transducer (0 - 1 mA DC or 4 - 20 mA DC) is required. Connect the output wires of the transducer to the terminal block as shown in the Current Input Wiring figure.

13

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Current Input Wiring

14

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Dry Contact Closure Input Module


The Dry Contact (Switch) Closure Input Module is designed to detect the actuation or deactuation of one dry, non-powered switch contact. The system internally treats closed and open contacts as either a 0 or 100 numeric value. Therefore, if the module is used to control a relay, the relay set point should be set at midrange, e.g., 50. See the Contact Closure Wiring figure for the correct circuit wiring.

Contact Closure Wiring

Powered Contact Closure Input Module


The Powered Contact (Switch) Closure Input Module is designed to detect the actuation or de-actuation of a powered switch contact. This is accomplished by measuring a potential across the switch contact of 0 volts when closed and a potential greater than 80 volts AC/DC contact is open. For applications where a higher potential is being measured, e.g., 240 V AC, 250 V DC) there is a jumper on the board that can be moved that will raise the sense voltage to 130 V, if required. The system internally treats closed and open contacts as either a 0 or 100 numeric value. Therefore, if the module is used to control a relay the relay set point should be set at midrange, e.g., 50. See the Powered Contact Wiring figure for correct circuit wiring.

Powered Contact Wiring

15

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Output Contacts
Five isolated sets of normally open/normally closed output contacts, for Output Relays 1 - 4 and the System State Output Relay, are provided for controlling cooling equipment, sounding an alarm, or operating remote breaker coils. Each set is capable of switching 115/230 VAC, 30 VDC @ 10 A, and the sets are accessed on Terminal Block TB1, see the Relay Wiring figure for the Enclosure and Panel Mount monitors. Refer to the Software Instructions for configuring the relays controlling signal, as failsafe/non-failsafe, time delay, and other features. Refer to the back cover of the 505ITM for configuration and identification of the output contacts for each relay. Note that each relay is shown in the non-powered state.

Caution: Applying high DC voltage to the output relays will damage the relays.
TB1
1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 28 29 30 31 32

11 27

TB1
1 2
RELAY 1
10 A

TB1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

3 4 5

RELAY 2
10 A

6 7 8

RELAY 3
10 A

9 10 11

RELAY 4
10 A

12 13 14 15 16

SYSTEM STATE RELAY 10A

Relay Wiring

16

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Remote Output Signals


The monitor is configured to supply two milliamp (mA) current outputs for remote indication or use with SCADA devices. This output is proportional to the full scale of the parameter selected in the configuration. Refer to Functional Specifications section, for maximum load. The output signals are accessed on Terminal Block TB1 terminals 29 through 32, See the Remote Output Signal Terminals figure for the Enclosure and Panel Mount monitors.

CAUTION: All remote output signals are independent, variable current loops, driven
by the system power and designed to drive an isolated load, such as a current meter. They cannot be grounded or tied together.
TB1

1 2 3 4 5 6 7 8 9

17 18 19 20 21 22 23 24 25 26 28 29 30 31 32

10 12 13 14 15 16

11 27

TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

TB1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
(+) (-) (+) (-) C URRENT LOOP 1

C URRENT LOOP 2

Remote Output Signal Terminals

17

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Communications
The monitor comes equipped with digital communication capabilities. A four-wire, RS-485 connection is located on the back of the monitor. See the Four-Wire RS-485 Connection figure. If the operator is using a two-wire, RS-485 connection with the 505ITM, short TXD+(B) with RXD+(B), and TXD-(A) with RXD-(A), then connect the two-wire, RS-485 as an A/B system. The RS-485 connection may be used with the Qualitrol Remote Software Package and other available protocols. Refer to the Software Instructions and the 505ITM Communications Manual, IST-105-1, for a complete description of these features. For specific options and/or options for a special communications protocol, contact Qualitrol or our authorized representative.
TB1
1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 28 29 30 31 32

11 27

TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

TB1
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
TXD+(B) TXD-(A) RXD+(B) RXD-(A) SIGNAL GND

Four-Wire RS-485 Connection

18

www.qualitrolcorp.com

RS-485

505ITM Hardware & Software Manual

Operation
Automatic Operation
Viewing Channels or Viewing Mode Scrolling
Power Up When power is applied to the 505ITM, it automatically begins to monitor the input and controls the output, based on the factory configuration that was specified by the customer. At power up, the display will Auto Scroll through all of the parameters being monitored at a frequency of one every two seconds.

MENU Mode
Viewing Channels (See the Appendix for an example of the menu structure.) Auto Scroll, MENU, View Mode Scrolling Press MENU to move the display out of Auto Scroll and into Viewing Mode. The Up and Down Arrows (or ENTER) will move you individually through each parameter being monitored. If no key activity takes place for 60 seconds, the monitor automatically reverts to Auto Scroll, or press MENU again to revert back to Viewing Mode Scrolling. Viewing Max Readings MENU, View Mode Scrolling, Right Arrow From Viewing Mode, press the Right Arrow twice. The Up and Down Arrows (or ENTER) will move you through the maximum values, as well as the time and date of each parameter being monitored. Press RESET to reset all of the maximum readings. If no activity takes place for 60 seconds, the monitor automatically reverts to Auto Scroll, or press MENU again to revert the system back to Viewing Mode Scrolling.

Note:

To avoid any erroneous readings caused by the installation, Qualitrol recommends resetting the maximum values immediately after setting up the monitor.

19

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Viewing Min Readings MENU, View Mode Scrolling, Right Arrow, Right Arrow From Viewing Mode, press the Right Arrow twice. The Up and Down Arrows (or ENTER) will move you through the minimum values, as well as the time and date of each parameter being monitored. Press RESET to reset all of the minimum readings. If no key activity takes place for 60 seconds, the monitor automatically reverts to Auto Scroll, or press MENU again to revert the system back to Viewing Mode Scrolling.

Note:

To avoid any erroneous readings caused by the installation, Qualitrol recommends resetting the minimum values immediately after setting up the monitor.

Viewing TransLifeTM Values MENU, View Mode Scrolling, Right Arrow, Right Arrow, Right Arrow From Viewing Mode, press the Right Arrow three times. The Up and Down Arrows (or ENTER) will move you through the TransLifeTM values, time to critical point, consumed life and temperature profiler. If no key activity takes place for 60 seconds, the monitor automatically reverts to Auto Scroll, or press MENU again to revert the system back to Viewing Mode Scrolling.

20

www.qualitrolcorp.com

505ITM Hardware & Software Manual Program Mode


MENU, View Mode Scrolling, Right Arrows From Viewing Mode, keep pressing the Right Arrow until you reach the Change Settings column. Press ENTER to go to Change Settings Mode. This is the location where you can change some of the settings of the monitor. This mode is protected. Before you are allowed to change any parameters, you must first enter a program user ID #. This is the same password that is used to enter the Customer Setup in the remote software. If you are not authorized to change these settings, press MENU to go back to Viewing Mode Scrolling. The Up and Down Arrows allow you to change the value of the character highlighted by the display, while the Right and Left Arrows move the highlighted character. Press ENTER to move to the next setting. At the end of the Program Mode menu, press ENTER to reboot the system. If no activity takes place for 60 seconds, the monitor automatically reverts to Auto Scroll and discards any changes that were made, or press MENU again to revert back to Auto Scroll.
505 ITM
INTELLIGENT TRANSFORMER MONITOR

DISPLAY SET POINT INDICATORS


TEST MENU RELAY 1 RELAY 2 RELAY 3 RESET

KEYPAD

ENTER

RS-232 PORT USB PORT

RELAY 4

RS-232

Front Panel Control

Testing the System


To perform a system confidence test, press and hold TEST. Press TEST to actuate all nonTest Lockout relays (see the Output Relays section in the Software Instructions) in onesecond intervals.

21

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Functional Specifications
Power Supply Front Panel and Interface Display: Universal; 90 - 264 VAC, 47 - 63 Hz and 40 - 290 VDC; (< 30 watts, AC in; < 15 watts, DC in) One easy-to-read 2-line, 16-character alphanumeric Liquid Crystal Display (LCD). Character size: 0.38" (9.66 mm) high x 0.19" (4.84 mm) wide. Four Light Emitting Diodes (LED) Eight large keys for programmable settings and user interaction UV stabilized polyester 0.5% full scale input range 100 ohm platinum (Pt100), 10 ohm copper (Cu10) RTD; simulated winding or fiber optic probe; Liquid/ambient range: -40 - 120 C Winding range: -40 - 200 C Current: DC Current Loops: DC Voltage: AC Voltage: Potentiometer: Switch Contact (dry): Switch Contact (powered): Clamp-on CT, 0 - 5 A, 10 A, 20 A, 100 A and others available 0 - 1 and 4 - 20 mA DC 0 - 100 mVDC and 0 - 10 VDC 0 - 140 VAC and 0 - 320 VAC; 50/60 Hz 1500 - 15,000 ohm Open/Closed >80 V or >130 V open, jumper selectable; optically isolated

Status Indicators: Controls: Front Panel Membrane: Input Parameters Accuracy: Temperature:

22

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Outputs Control/Alarm Contacts: Diagnostics Alarm: Heater Control: Relay Contact Ratings: Remote (SCADA) Outputs: Data Communications: Four Form C relay contacts for cooling control, alarms, trip, etc. One Form C relay for power, sensors and internal circuitry diagnostics One relay 10A @ 115/230 VAC, 10A @ 30 VDC Two loops; 0 - 1 mA (max resistive load 10,000 ), 4 - 20 mA (max resistive load 450 ), other options available RS-232, RS-485 (monolithic transformer isolation) Protocols: DNP 3.0 (Level 3 slave), Modbus, ASCII Immunity Dielectric Isolation (High-Pot): Surge Withstand Capability: Conducted/Radiated Emissions: Conducted/Radiated Radio Frequency Immunity: Safety: Environment Temperature Range: Storage Temperature: Humidity: Vibration: Shock: Weatherproof Enclosure: Weight Approximately: 2500 V AC, 60 seconds to ground IEEE C37.90.1 IEC 61000-6-1 IEC 61000-6-2

IEC 61010-1 -40 - +72 C -50 - +85 C 90% non-condensing 60/120 Hz @ .004 inch displacement 10 Gs half-sine, in 3-orthogonal planes NEMA #3R (vented), UV stabilized, corrosion-proof fiberglass Weatherproof enclosure version: 8.7 lb (4.0 kg) Panel Mount version: 4.0 lb (1.82 kg)

Terminal Connectors:

Accepts wire sizes from 24 - 12 AWG

23

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Software Instructions
General Information
The software for the QUALITROL 505ITM Series Monitor runs on a personal computer (PC) that connects to the 505ITM with an RS232/USB or RS485 cable for monitoring, simulation, calibration, and setup. You must do the initial setup through the RS232/USB connection on the front panel of the monitor. After that, you can use either the RS232/USB or the RS485 connection. Qualitrol recommends that you use a RS232 male-to-female DB-9 extension straight-thru (not a null) shielded cable or a USB-to-USB cable suitable for substation environments.

Note:

Throughout these instructions, the software for the QUALITROL 505ITM Series Monitor is also referred to as the remote software, because it allows you to communicate remotely with the 505ITM.

Connecting to the 505ITM


1. Check that the 505ITM is connected to the main power and is energized. 2. Connect a USB cable between the USB port on your PC and the port on the 505ITM. - or Connect an RS232 cable between the RS232 port on your PC and the port on the 505ITM.

Installing/Running the Software


The software runs on Microsoft Windows NT, 98, 2000, XP, and Vista operating systems. You can run the software directly from the CD provided by Qualitrol or from files installed on your PC. To install the software from the CD: 1. Place the CD into the CD drive of your PC. 2. In the CD drive directory, double-click the file named Setup.exe. This will automatically step through the procedure for loading the 505ITM software in a Qualitrol folder in the program directory and install a shortcut on the desktop. 3. Clicking on the shortcut the Qualitrol ITM Manager window displays.

24

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Desktop Communications Window


The Desktop Communications window provides the communications interface with the 505ITM and your PC.

The software automatically loads a default communications data file named default505ITM.qco on your desktop when it opens the Desktop Communications window.

File Menu
The File pull-down menu provides several options for selecting a communications file.

Open Save Save As... Close

Opens an existing communications file (*.qco). Saves the communications data under the current communications file name. Saves the communications data with a new communications file name. Closes all applications and communications with the 505ITM, and closes the Desktop Communications window. The Save Communication Setup window displays if any communications parameters have been changed and not saved before the Close command.

25

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Establishing Communications with the 505ITM


From the Desktop Communications window, select, set, or observe the following items as required: Address Each 505ITM has an assigned address that allows multiple 505ITMs to be used with a common communication link. The factory default configuration has an address of 00. Select the correct address from the pull-down menu. The baud rate on your PC must be the same as that on the 505ITM monitor with which you are communicating. The range is 1,200 38,400. The default is 19,200. (If using the USB port the baud rate goes from 1200 to 230,400). Select the correct baud rate from the pull-down menu. If the baud rate is unknown, it is possible to view it on the LCD display of the 505ITM. Enter the MENU Mode and go to the Change Settings column (see the MENU Mode section). Allows you to select the serial communications port on the PC from COM1 COM255. The default is COM1. Select the communication port that the serial port is connected to on your PC. You can run the software offline without being connected to the 505ITM. 1. With no communications to the 505ITM established, click the Off line check box. 2. Click on the Connect button. 3. Select the 505ITM icon and hit the Connect button. 4. Type demo into the Password field of either the Setup - Customer or Setup - Factory application section. The Setup window opens and displays the available features. This feature is useful during training or to learn how the product functions when there is no 505ITM available.

Baud Rate

COM

Off line

Important:

Changes made in the Demo mode are not permanent. These modifications cannot be saved or downloaded into a device.

Connect Button TX and RX

Click to start communications with a 505ITM. Displays transmission activity.

Note:
Close All Button

Short transmissions will often occur too fast to be viewed by the operator.

Closes all open 505ITM applications, terminates communications, and closes the Desktop Communications window. The Save Communication Setup window displays if any communications parameters have been changed and not saved before clicking [Close All].

26

www.qualitrolcorp.com

505ITM Hardware & Software Manual


A successful communications link is indicated when:

No error message displays.

An unsuccessful communications link is indicated when:

A Communications link failure message displays.

If this error message displays, troubleshoot the communications link.

27

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Troubleshooting the Communications Link


If a problem occurs in establishing a communications link between the PC and the 509 ITM, check the following:

Is the cable a straight-through cable (not a null) and is it securely connected to the PC and the 505ITM? Is the 505ITM energized? Is the cable connected to the same COM port displayed in the Desktop Menu Communications? Does the 505ITM device address match the selection in the Desktop Menu Communications Address field? Does the 505ITM service port baud rate match the baud rate in the Desktop Menu Communications? The default baud rate is 19,200 baud. If the 505ITM service port was reconfigured to another baud rate, the Desktop Menu Communications baud rate must match the new configuration. Click this button to attempt to establish communications with the 505ITM again. Click this button to ignore the communications error. However, for correct operation of the system, it is essential that communication to the 505ITM is established and functioning correctly. Click this button to discontinue further attempts to establish communications with the 505ITM.

Important:

RETRY Button IGNORE Button

ABORT Button

Overview of the 505ITM Tools on the Desktop Menu

There are five 505ITM software tools available to run from the Desktop Menu window: Monitor Simulator Factory Calibrator Customer Allows remote operation of the 505ITM. Allows simulation of field input signals/sensors. Allows calibration of 505ITM inputs and outputs. This tool is conditionally blocked to the user. Allows you to configure the 505ITM, including setup of cooling control,

28

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Setup Factory Setup alarms, communications, and other features. Allows the factory to configure the 505ITM. This tool is not accessible to the user.

Password

Each tool requires a password. Passwords are set at the factory, but you can change them when you are in the tool. The factory set passwords are: Monitor Simulator Calibrator Customer Setup 111111 111111 If required, call Qualitrol Application Engineering at 585-586-1515 x 410. 111111

The Factory Setup tool can only be entered by Qualitrol factory personnel. This section is reserved for the factory except in the Demo mode (offline). Remember Me Check Box By checking in this check box, the password is stored in the communications file so that you do not have to re-enter it every time you start the tool.

Important:

Enabling this feature will disable security protection and allow anyone using this computer to gain access to the software.

Start Button

Activates the selected tool.

29

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Opening a Tool
To open any of the 505ITM software tools, do the following: 1. Establish communications with the 505ITM. 2. From the Desktop Menu window, enter the correct password for the tool you wish to start.

Note:

If the Remember Me feature is enabled, you do not have to enter a password.

3. Click [Start].

Using the Monitor Tool


The Monitor tool provides remote monitoring and control of the 505ITM by simulating the contents on the 505ITM LCD, and relay LEDs appear on your PC screen. The monitor requests an update from the 505ITM three times every second.

30

www.qualitrolcorp.com

505ITM Hardware & Software Manual


There are eight control buttons on your PC screen: Test, Reset, Menu, Enter, Up, Down, Left, and Right. These buttons are activated by clicking on them with the left mouse button. Activating a button in this way has the same effect as pressing the same button on the 505ITM monitor itself. See the Operation section of the Hardware Instructions for specific information on the control and operation of the 505ITM. Click [Close] to exit the tool.

Note:

The actual 505ITM continues to operate when the Monitor tool is closed.

31

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Using the Simulator Tool


The Simulator tool allows you to simulate values regardless of the actual inputs that the sensors register. The 505ITM responds to the input signal changes from the Simulator window as if the signals originated in the field. This mode is useful for testing items such as relay connections and wiring.

When you click [Start Simulation]: The field inputs disconnect from the actual field signals and connect to the signals from the Simulator tool. You can now change the simulated signals remotely as you desire. The 505ITM responds to the simulated signals as if they were the actual field signals. With the exception of the CT, Temperature signals, the transfer from the field to the simulation is almost undetectable because the initial simulation value is set to the last value of the actual field signal. The winding temperature (CT, Temperature) is a calculated value using load currents, oil temperatures, and time constants. All of these are bypassed in the simulation mode where the calculated values are replaced with the simulated values.

Important:

While the simulation is active, the actual field signals are not being monitored. If you have Trip functions connected to the 505ITM, you can activate them in simulation mode.

When you click [End Simulation]: The field signals reconnect to the input of the 505ITM. The 505ITM responds immediately to the actual field signals.

Note:

If you make no changes to any of the input signals for more than 3 minutes, the simulation ends automatically. Whenever any button is pressed, the 3-minute timer resets.

32

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Using the Factory Calibrator Tool (Advanced users only)


The Factory Calibrator tool allows you to calibrate most inputs. When you first enter the Calibrator - Signal Selection window, the Input 1 channel is selected by default.

Important:

All channels, except for the Potentiometer Input module, are calibrated at the factory. Under normal operation, they will not need to be calibrated again. You must have a separate password for this application for the ITM manager to allow you to use this tool.

33

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Calibrating the Input Channels 1. Open the Factory Calibrator tool. 2. Select the input channel to calibrate. 3. Click [Calibrate]. The Input Channel Calibration window displays. 4. In the terminal block that corresponds to the input module being calibrated, enter the signal value displayed in the Set input signal to field.

Important:

The Set input signal to field displays the value of the external signal that must be applied to the module terminals. For the RTD Input Modules, the input signal is expressed in terms of degrees C. If you continue the calibration procedure without inputting the correct excitation (stimulus) signal, you will overwrite the calibration with invalid data. This will cause the monitor to malfunction.

5. After you have entered the input signal on the terminal block and it is stabilized, click [Next] to accept the value in the Set input signal to field.

Note:

All channels require at least a two-step calibration procedure. The [Next] button changes to [Finish] for the second step in the procedure. If you want to return to the previous step, click [Back].

6. Enter the value for the second input and click [Finish]. The calibration of this channel is complete.

34

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Calibrating the Output Channels The analog outputs can be adjusted in a four-point calibration; see the Output Calibration section of the manual for more details. However, this calibration should not be necessary because it is done at the factory. Saving Calibrations in Files You can save calibration values in files using the File pull-down menu. These files have the default file extension .qca3. Import Export Export As... Allows you to import a valid calibration file stored in the PC. Allows you to save the current calibration to a previously specified file for future use. Allows you to save the current calibration in a newly specified file for future use.

35

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Using the Setup Tools


The User Setup tool allows you to set all the adjustable parameters of the 505ITM. The Factory Setup tool is used to set the hardware configurations of the monitor. The Customer Setup limits access to some of the 505ITM parameters, such as serial number, manufacturing date, and configuration date.

Note:

You can save configurations as files, which you can use to restore settings or to preconfigure before connecting to the 505ITM. See Importing and Exporting Configuration Files.

When you open the Customer Setup tool, the Customer - Setup window displays. When you open the Factory Setup tool, the Factory - Setup window appears. The windows for both tools are the same and allow for a specific subsystem to be configured.

36

www.qualitrolcorp.com

505ITM Hardware & Software Manual

The Setup windows have three main sections: Model Information Model Type System Index Displays the fields for Serial number, Manufacturing date, and the last Configuration date of the 505ITM. The Configuration date field displays when the 505ITM was last updated. Displays that the monitor is a Transformer Monitor. Displays the system buttons required to set up and view the parameters of the 505ITM. Click the buttons to begin setting up the configurations. [System Settings] [Communications] [Input Modules] [Output Relays] [Output Loops] [Bank Switching] [TransLifeTM]

37

www.qualitrolcorp.com

505ITM Hardware & Software Manual

System Settings
The System Settings window opens when you click [System Settings] from the Setup window. This window allows you to set the configuration for the items displayed in the different sections of the window.

More Information

Password Setup Installed Features Time and Date Setup Display Setup Heater Setup

38

www.qualitrolcorp.com

505ITM Hardware & Software Manual Password Setup


This section of the System Settings window allows you to configure the passwords that provide access for the different software tools. The passwords are stored in the 505ITM and have the following characteristics and requirements:

Passwords consist of one to six alphanumeric characters, and they are case-sensitive. The password for the User Setup tool is also the password used to enter the modification section of the MENU Mode from the front panel of the 505ITM. The password for the Calibrator tool must be different from the other tool passwords. This is a precaution to prevent users from accidentally entering the calibration section of the monitor. There is a hierarchy to the password system. The password for the Customer Setup tool will also work in the Monitor and Simulator tools, even if they have different passwords. This is because all of the passwords can be changed in the Customer Setup tool, so it is treated as the master password. When passwords are changed in the Password Setup tool, the user must enter the new password values the next time the tools are opened.

There are five Password fields and five corresponding Verify fields. The Password fields accept the password values for the associated tools. The Verify fields are used to check the corresponding password.

Note:

The Factory Setup password is not available to the customer.

To enter a new password: 1. Type the new password value into the Password field. Use one to six alphanumeric characters. 2. Type the same password value into the Verify field. Use the same alphanumeric characters and the same case as you did in the Password field. 3. Click [Load]. The software compares the values in the Password and Verify fields when they are loaded into the 505ITM. If the values do not match, an error message displays.

39

www.qualitrolcorp.com

505ITM Hardware & Software Manual Installed Features


This section of the System Settings window displays the installed features available in the 505ITM. If a feature is installed, there will be a check mark in the check box next to the legend.

Time and Date Setup


This section of the System Settings window allows you to configure the time and date values stored in the 505ITM.

Note:

The time and date values can also be changed along with the front panel operations.

40

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Current PC Time Displays the current time of the PC that is connected to the 505ITM when the Time and Date Setup window is opened. This value is not automatically updated. The current time of this PC is loaded into the 505ITM when you click [Load]. If the Current PC Time value is not correct: 1. Adjust the PC clock to the correct time. 2. Click [Load] on the System Settings window. 3. Continue with the setup procedure.

41

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Time Zone Difference Allows you to adjust for a difference in time zones between the location of setup and the location of the installed 505ITM. If the two locations are the same, set the value to 0. Otherwise, select the appropriate number of hours, positively or negatively, to provide for a correct time at the installation location. For example, if the setup is done in New York and the installation is in California, set the Time Zone Difference to -3 hours. Displays the current date of the PC that is connected to the 505ITM when the Time and Date Setup window is opened. Displays the current values for the date, time, and time zone in the 505ITM.

Current PC date 505 Time and date

Display Setup
This section of the System Settings window allows you to adjust the contrast and intensity of the 505ITM Display.

Brightness Contrast

The slider adjusts the intensity of the back light of the display. You also have the option to disable the back light. The slider adjusts the display contrast to an appropriate viewing level.

42

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Heater Setup
This section of the System Settings window allows you to configure the 505ITM Heater option. The Heater is not a standard feature and has to be ordered. It is used in extremely cold or moist environments. The Heater is controlled by a 505ITM internal temperature measurement. If the Heater option is installed, the following fields are available for setup.

Heater Function Heater Setpoint Heater Hysteresis

Allows you to enable or disable this feature. Allows you to set the temperature at which the Heater is energized. The Heater energizes when the internal temperature of the 505ITM drops below the setpoint value. Allows you to set the temperature at which the Heater is de-energized. The Heater de-energizes when the internal temperature of the 505ITM rises above the sum of the setpoint and the hysteresis values.

43

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Communications
The Communications Setup window opens when you click [Communications] from the Setup window. This window allows you to configure the 505ITM communications ports displayed in the different tabs of the window.

More Information

Front USB - Service Port Front Serial Service Port Main 485 - Main Port Aux 485 - Auxiliary Port Cancel and Load Buttons

44

www.qualitrolcorp.com

505ITM Hardware & Software Manual Front USB - Service Port


This section of the Communications Setup window includes the fields described below.

Type Baud Rate

Indicates the type of signaling hardware used for the Service Port. This field is for informational purposes only. Configures the baud rate that is used to communicate over the USB Service Port at the front panel. The default value is 19,200 baud. The Desktop Menu software automatically configures the PC's COM port with the correct parameters for communicating with the Remote Software.

45

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Front Serial - Service Port


This section of the Communications Setup window includes the fields described below.

Type Baud Rate

Indicates the type of signaling hardware used for the Service Port. This field is for informational purposes only. Configures the baud rate that is used to communicate over the RS232 Service Port at the front panel. The default value is 19,200 baud. The Desktop Menu software automatically configures the PC's COM port with the correct parameters for communicating with the Remote Software.

46

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Main 485 - Main Port


This section of the Communications Setup window includes the fields described below.

Type Installed Protocol Optional Protocols

Indicates the type of signaling hardware used for the Main Port. This is an information-only field. The Qualitrol ITM Manager software comes standard with every 505ITM unit.

Note:

All of these options are upgradeable by the factory. DNP Indicates if the DNP V3.00 Level 3 communications protocol is installed. Modbus Indicates if the Modbus communications protocol is installed. QASCII Indicates if the Qualitrol ASCII communications protocol is

47

www.qualitrolcorp.com

505ITM Hardware & Software Manual


installed. Protocol Address Baud Rate Number of Data Bits Parity Number of Stop Bits Selects between the available communications protocols to be used by the Main Port communications. Indicates the communication address of the 505ITM used by the specified protocol. Selects the desired baud rate for the Main Port communications protocol. The default value is 9,600. Selects the desired number of data bits for the Main Port communications protocol. The default value is 8. Selects the desired type of parity for the Main Port communications protocol. The default is none. Selects the desired number of stop bits for the Main Port communications protocol. The default value is 1.

Aux 485 - Auxiliary Port


This port is unused at the present time.

Cancel and Load Buttons


This section of the Communications Setup window includes the command buttons described below.

Cancel Button Load Button

Cancels all changes made in this window and returns you to the Setup window. Loads all communications parameters from the PC into the 505ITM. All new communications parameters take effect only after the 505ITM hardware has been reset.

48

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Input Modules
The Input Module Setup window opens when you click [Input Modules] from the Setup window. The 505ITM has up to four input modules. The types of available modules are described in the Modules section of the Hardware Instructions. To begin, click the tab of the input module that you want to configure. The Input Module Setup window displays for the selected input module.

Low-End and High-End Scaling Values

More Information

Module Custom Scaling CT Current Parameters Winding Temperature Setup (Calculated)

49

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Module
This section of the Input Module Setup window includes the fields described below.

Input Module Number Input Module Type

Indicates the input module number that is being configured. This field is for informational purposes only. Indicates what module type was installed in this corresponding site of the 505ITM. This is designated at the factory according to the input module that was ordered and installed. If the module type indicates "undefined," there is no physical module installed in that location. Enables and disables the module function. If the input module is disabled: It cannot be viewed on the LCD display located on the front panel. It cannot control any relays. Identifies the input module name. The name can be changed and can consist of up to seven alphanumeric characters. This name will also appear on the 505ITM LCD display, along with its input signal value.

Input Module Function

Input Signal Name

50

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Custom Scaling
The configuration parameters in this section of the Input Module Setup window allow you to change the scaling of the process input signal. Custom Scaling is not available if the Input Module Type field is set to a "Logic Switch", "AC/DC Input" or Temperature input module, for example, RTDs, Ambient, and CT, Temperature. The fields in this section are described below.

Low-End and High-End Scaling Values

Use Custom Scaling

Indicates that custom scaling is defined for the input signal. If the check box is checked, you must specify three additional parameters for the input: Custom Units Label field allows the user up to three characters for a unit of measure, for example, ppm, RH, %. Low-End Value field is the scaled minimum value for the corresponding minimum input value. High-End Value field is the scaled maximum value for the corresponding maximum input value. If the Use Custom Scaling field is checked, the 505ITM uses this label instead of the default label defined by the Input Module Type field. This label can consist of up to three alphanumeric characters. Provide the custom values corresponding to the indicated low-end and high-end values for the selected module type. The 505ITM translates the input signal into the alternate monitors using the low- and high-end values provided. Example: You have a Dissolved Gas Monitor with 0 - 1 mA representing a 0 - 2000 PPM scale. Using a 0 - 1 mA input module, set: Low-End Scaling Value field to 0 mA = 0 High-End Scaling Value field to 1 ma = 2000 Custom Units Label field to PPM An input of 0.4 mA would appear as 800 PPM on the display.

Custom Units Label Low-End and High-End Scaling Values

51

www.qualitrolcorp.com

505ITM Hardware & Software Manual

CT Current Parameters
If the Input Module Type field is set to "CT, Current" or CT, Temperature, this section of the Input Module Setup window provides linear scaling between the 505ITM output and the actual current sensed by the Power Transformer CT. The fields in this section are described below.

CT clamp-on sensor Rating

Indicates the maximum rating of the CT clamp-on sensor used with this module, for example, 10 Amp, 30 Amp). You can read this rating from the clamp-on sensor. When selecting the sensor value, make sure that: the maximum rating of the sensor value is greater than the current it will be sensing. This will prevent saturation. the sensor value is as close to the maximum current reading as possible. This will optimize the resolution. Provides the parameters needed for CT Current Scaling. The left field identifies the true current, such as winding or bushing, being sensed by the instrumentation or metering CT. The right field identifies the secondary or output of the instrumentation or metering CT that will be used with the 505ITM Clamp-On CT Sensor. Example: If the Instrument CT on the transformer has a ratio of 1200 : 5 Amps, the two CR ratio fields are set to CT Ratio = 1200 : 5. The clampon sensor is on the 5 Amp circuit and now acknowledges that the 5 Amp are passing through the CT to scale the current to the 1200 Amp range.

CT ratio (2 fields)

52

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Winding Temperature Setup (Calculated)


This section of the Input Module Setup window allows you to configure the "CT, Temperature" input module type.

The checked box indicates which winding calculation method is active. Click either method to open the corresponding setup window.

Simple Calculation Setup Method Advanced Calculation Setup Method

Simple Calculation Setup Method


This method allows you to configure the simple scaling parameters for input module types that are set to CT, Temperature. The winding calculation method presented here corresponds to the process used by the IEEE Guide for Loading Mineral-Oil-Immersed Transformers (IEEE Std C57.91). The Simple CT Temperature Scaling Setup window opens when you click [Simple Calculation Setup] from the Winding Temperature Setup section of the Input Module Setup window.

53

www.qualitrolcorp.com

505ITM Hardware & Software Manual

More Information

Input Module Number and Input Signal Name Fields Winding Rise Parameters Oil Rise Parameters

54

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Input Module Number and Input Signal Name Fields This section of the Simple CT Temperature Scaling Setup window includes the fields described below.

Input module number Input signal name

Displays the input module number for which the simple CT, Temperature scaling parameters are being configured. Displays the user-assigned name of the signal for which the simple CT, Temperature scaling parameters are being configured.

Winding Rise Parameters This section of the Simple CT Temperature Scaling Setup window includes the fields described below.

Oil Temperature Adder Winding Rise Temperature

Allows you to select one of the available RTD Input Modules. The selected RTD Input Module will be the liquid temperature measurement that is added to the winding curve simulation, for example, top oil temperature. Allows you to set the number of degrees that the winding temperature will be over the oil temperature (delta T) at nominal load for the transformer. You can calculate this parameter from the transformer heat run test reports by subtracting the oil temperature at nominal loading from the winding temperature at nominal loading. If you cannot obtain the heat run report, contact the transformer manufacturer for these values. Displays the value measured at the clamp-on CT sensor of the 505ITM at nominal loading of the transformer.

Current Factor

55

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Winding Time Constant Allows you to set the time constant for the temperature rise of this winding. The time constant is defined as the time it takes the winding temperature to reach 63.2% of its final value for a given current input.

Note:

It takes approximately five time constants to elapse for the temperature to reach full value for a given load. If the time constant is unknown, the IEEE Std C57.91-1995 Annex G recommends a value between 3 and 7 minutes. Qualitrol uses a default value of 6 minutes.

Oil Rise Parameters This section of the Simple CT Temperature Scaling Setup window includes the parameters that are required if you want to use the Critical Forecast feature of the TransLifeTM Setup. If you are not using the Critical Forecast feature, leave these parameters at the default values. The fields in this section are described below.

Oil rise temperature

Allows you to set the temperature rise value of the transformer oil at nominal load. This is derived from the Transformer Heat Run Report by taking the value of the Oil Rise Temperature field over ambient at nominal load, and subtracting the ambient test temperature. Oil Rise Temp = (Oil Rise Temp over Ambient - Ambient Temp) Allows you to set the time constant for the temperature rise of this winding. The time constant is defined as the time it takes the winding temperature to reach 63.2% of its final value for a given current input. It takes approximately five time constants to elapse for the temperature to reach full value for a given load. If the Oil Time Constant is not provided, the IEC 354 Loading Guide for OilImmersed Power Transformers recommends: For distribution transformers: All cooling types: 180 minutes For medium and large transformers: ON (natural convection): 150 minutes OF (oil forced): 90 minutes OD (oil directed): 90 minutes

Oil time constant

Note:

56

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Advanced Calculation Setup Method
This method allows you to configure the advanced scaling parameters for input module types that are set to CT, Temperature. The advanced calculation method is capable of adapting the winding temperature model for all the different stages of cooling, thereby giving a more accurate response than the Simple Calculation Method. But to use this method, the winding rise parameters are required for each cooling stage. The formulas for calculating winding temperatures for this window were derived from the IEEE Std C57.91-1995. The Advanced CT Temperature Scaling Setup window opens when you click [Advanced Calculation Setup] from the Winding Temperature Setup section of the Input Module Setup window.

More Information

The Importance of Winding Temperature and Cooling Upper Fields Advanced Winding Rise Parameters TransLifeTM

57

www.qualitrolcorp.com

505ITM Hardware & Software Manual


The Importance of Winding Temperature and Cooling Paper insulation used in transformers contains organic materials that deteriorate over time at elevated temperatures. Cooling that is activated too slowly allows elevated temperatures to degrade this insulation. Cooling systems that are activated too early or too often will lead to reduced fan and/or oil pump life. The 505ITM implements advances in thermal modeling technology to increase both insulation and cooling system life. You can set different parameters for each of the possible cooling modes, or stages: ONAN, ONAF, OFAF, and ODAF are the designations for natural convection, forced air, directed air, and oil cooling, respectively. During operation, the 505ITM can dynamically alter the parameters to match the present cooling stage being used. You can individually program each winding for accurate representation of the winding "rise" (gradient). You can also program the winding time constant and the load current "exponent" for each cooling stage. More Information

Advanced Calculation Setup Method Upper Fields Advanced Winding Rise Parameters TransLifeTM

Upper Fields This section of the Advanced CT Temperature Scaling Setup window includes the fields described below.

Input module number Input signal name Oil temperature adder

Displays the input module number that is being configured with the advanced CT, Temperature scaling parameters. Displays the user-assigned name of the signal that is being configured with the advanced CT, Temperature scaling parameters. Allows you to select the RTD Input Module that is the selected liquid temperature measurement being added to the winding rise, for example, top oil.

58

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Advanced Winding Rise Parameters This section of the Advanced CT Temperature Scaling Setup window includes the fields described below.

Cooling Relay (3 fields)

Allows you to input the relay number that controls the cooling system for each cooling stage. Example: Relay 2 controls fan bank 1, Relay 3 controls fan bank 2, and Relay 4 energizes the oil pump. Allows you to enter the measured current that the clamp-on CT will sense on the secondary side of the instrumentation or metering CT for each current stage at nominal loading. Example: A 30/40/50 MVA Single-Phase Transformer with a 32 kV secondary and an instrumentation CT 2000/5 A on its secondary side, which is the winding to be configured. In ONAN mode: 30 MVA / 32 kV * 5/2000 = X In first cooling mode: 40 MVA / 32 kV * 5/2000 = X In second cooling mode: 50 MVA / 32 kV * 5/2000 = X

Current Factor (4 fields)

Note:

For a three- phase transformer application, divide the current by the square root of three.

Winding Rise Temperature (4 fields)

Allows you to set the temperature gradients (delta T) for each winding at each cooling stage. This value is the winding temperature rise over the specified liquid temperature for that given current factor. The liquid temperature will typically be the top oil temperature measurement. The 505ITM accepts a maximum of 70 C for the temperature gradient. You can calculate the winding rise value from data in the transformer heat run report. The winding rise gradient is the winding rise temperature over ambient minus the oil rise temperature over ambient.

59

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Exponent (4 fields) Allows you to enter the exponent parameter used in the temperature calculation for each of the four Cooling Modes. The exponent describes the rise curve of the winding temperature above the oil temperature. When installing a 505ITM on older transformers, this information might be difficult to obtain. In those cases, Qualitrol recommends: Winding Time Constant (4 fields) For ONAN (natural convection): 1.6 For ONAF (natural convection; forced air fans only): 1.6 For OFAF (forced oil; forced air fans and pumps): 1.8 For ODAF (directed forced oil and forced air): 2.0

Allows you to enter a time constant for each of the four cooling modes. The time constant is defined as the time required to reach 63.2% of the final winding temperature rise for a specific load increase. The winding temperature reaches its final value for a given load in approximately five time constants.

Note:

You can program the 505ITM for up to four cooling modes, including natural convection. If there are less than four cooling modes, the unused rows should match the last configured row. Do not enter zeroes as a value.

TransLifeTM This section of the Advanced CT Temperature Scaling Setup window includes the parameters that are required if you want to use the Critical Forecast section of the TransLifeTM Setup. If you are not using the Critical Forecast feature, leave these parameters at the default values. The fields in this section are described below.

Oil Rise (4 fields)

Allows you to set the temperature rise value of the oil of the transformer at nominal load. This is derived from the Transformer Heat Run Report by taking the Oil Rise Temperature over ambient at nominal load and subtracting the Ambient Test Temperature.

60

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Oil Time Constant (4 fields) Allows you to set the time constant for the temperature rise of this winding. The time constant is defined as the time it takes the winding temperature to reach 63.2% of its final value for a given current input.

Note:

It takes approximately five time constants to elapse for the temperature to reach full value for a given load. If the oil time constant is not provided, the IEC 354 Loading Guide for OilImmersed Power Transformers recommends: For Distribution Transformers: All cooling types: 180 minutes For Medium and Large Transformers: ON (natural convection): 150 minutes OF (forced oil): 90 minutes OD (directed forced oil): 90 minutes

61

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Output Relays
The Output Relay Setup window opens when you click [Output Relays] from the Setup window. This window displays the tab array of the four relays with the Relay 1 tab being selected. By selecting the different tabs, you can index through the relay array. To begin, click the tab of the output relay that you want to configure. The Output Relay Setup window displays for the selected input module.

More Information

Relay Tabs Relay Control Seasonal Setpoint Ambient Temperature Forecast Cooling Equipment Exerciser Matrix Controlled Cancel and Load Buttons

62

www.qualitrolcorp.com

505ITM Hardware & Software Manual Relay Tabs


This section of the Output Relay Setup window includes the fields described below.

Relay 1 Relay 4 System Status Relay

The tabs at the top of the window allow you to select which relay to display for setup. The system relay is actuated by: Any abnormal condition in the internal circuitry. A microprocessor malfunction. A power supply malfunction if in the failsafe mode.

Note: Relay Control

Relays that are not in Test Lock Out mode are also actuated when the system relay is actuated.

This section of the Output Relay Setup window includes the fields described below.

Relay Number Enabled / Disabled

Indicates the number of the relay being configured. Allows you to enable or disable the relay function. If the relay is disabled, it remains in the non-energized state (the normally closed and common contacts are shorted together, while the normally open and common contacts are open).

63

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Failsafe / Nonfailsafe Allows you to select the actuation function of the relay. When you select the Non-failsafe condition: The normally closed and common contacts are shorted together if the monitor is de-energized and the setpoints are not exceeded. The relay changes states when the setpoints are exceeded. When you select the Failsafe condition: The normally closed and common contacts are shorted together when the monitor is de-energized. If the monitor is energized and the setpoints are not exceeded, the relay changes states. This causes the normally open and common contacts to be shorted. If the setpoints are exceeded or if the monitor loses power, the normally closed and common contacts are shorted together.

Important:

Qualitrol recommends setting any trip contacts for a transformer to Non-failsafe. See the following table for further clarification of Failsafe/Non-failsafe operation. Monitor Energized < Set Point NC - C NO - C Monitor Energized >= Set Point NO - C NC - C Loss of Power to Monitor NC - C NC - C

Relay Condition Non-failsafe Failsafe Test lock out On / Off

No Power to Monitor NC - C NC - C

When you press the TEST switch on the display panel of the 505ITM, the monitor executes a test cycle of all the relays in the system. The test actuates each relay for one second starting with relay one and finishing with relay four. The test continues until all the relays in all the relay modules are cycled. There might be situations when you do not want the relays to actuate. In these situations, use the Test Lock Out switch function. By setting Test Lock Out to ON when you press the TEST switch, the LED corresponding to the relay illuminates, but the relay does not change states.

Important:
Latching

Any relay wired to a trip function should have the Test Lockout function set to ON.

On: The relay remains in the actuated state even after the controlling signal no longer exceeds the setpoint value. The relay can only be released if you press the RESET switch while the controlling signals do not meet the setpoint conditions. Off: The relay actuates and de-actuates according to the output of the Control Signal Matrix table and other function settings.

64

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Manual / Automatic Manual: The relay actuates regardless of the setpoint values. Automatic: The relay actuates according to the Control Signal Matrix table and other function settings. This feature can be toggled through the communication channels, which allows you to actuate a relay remotely. On: If any of the control signals in the Control Signal Matrix table have sensor errors, the relay actuates. Off: If a control signal has an error, it is not used in controlling the relay. The status of the other control signals controls the relay.

Actuate On Errors

Actuation Delay

Allows you to enter the amount of time the actuation of the relay will be delayed after the control signals have continually exceeded the setpoint values. (Range: from 1 second - 10 hours).

65

www.qualitrolcorp.com

505ITM Hardware & Software Manual Seasonal Setpoint


This section of the Output Relay Setup window includes the fields described below.

Seasonal setpoint installed

A check mark indicates that the Seasonal Setpoint feature is installed. This feature only affects the setpoint for the Control Signal 1 column in the Controlled by Matrix section. If the Seasonal Setpoint is active and the conditions are met, the Seasonal Setpoint has priority over the setpoint in the Control Signal 1 column. Allows you to enable or disable this feature. Opens the Seasonal Setpoint Setup window that allows you to configure the Seasonal Setpoint feature. You can adjust the setpoint to compensate for changing seasonal weather conditions. For example, for the warmer summer months when the cooling system is not efficient, you might want to enter a Seasonal Setpoint value of 70 C for a cooling bank that is normally set to actuate at 80 C at other times of the year.

Seasonal function Configure Button

66

www.qualitrolcorp.com

505ITM Hardware & Software Manual


To set the Seasonal Setpoint: 1. Enter the appropriate information in the following fields: Start Date: Select the Month and Day when the Seasonal Setpoint becomes active. End Date: Select the Month and Day when the Seasonal Setpoint is discontinued. Normal setpoint operation resumes the day after this date. Seasonal Setpoint: Select the temperature setpoint that will control the relay when the Seasonal Setpoint is active.

2. Click [Load].

Ambient Temperature Forecast


This section of the Output Relay Setup window includes the fields described below.

Ambient temperature forecast installed

A check mark indicates that the Ambient Temperature Forecast feature is installed. This feature only affects the setpoint in the Control Signal 1 column of the Controlled by Matrix section. If the Ambient Temperature Forecast is active and the conditions are met, the Ambient Temperature Forecast Setpoint has priority over the Seasonal Setpoint and the setpoint in the Control Signal 1 column. Allows you to enable or disable this feature.

Forecast function

67

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Configure Button Opens the window that allows you to configure the Ambient Temperature Forecast feature. This window provides a common path for setting the values of the Ambient Temperature Forecast feature for all eight relays. This function measures the ambient temperature for a specified amount of time and allows you to adjust the setpoint for relay operation during forecasted periods of high temperatures. This feature is similar to the seasonal setback option except that the seasonal setback is used for a specific period of time, such as summer, while the ambient temperature forecast is used for a specific condition, for example, a heat wave. If the ambient temperature exceeds the number of the Threshold Value for more than the number of Exceeded Hours during the Measurement Period, the system substitutes the forecast override setpoint for the setpoint in the Control Signal 1 column. Example: In the Ambient Temperature Forecast Setup window, the following parameters are entered: Controlled By: Ambient probe in Input Module 4 Measurement Period: 120 hours (5 days) Exceeded Hours: 12 hours Threshold Value: 30 C Forecast Override Setpoint: 50 C If at any time during a rolling 120 hour time period the ambient temperature exceeds 30 C for a total of 12 hours, the setpoint for Column 1 of the relay matrix is 50 C.

68

www.qualitrolcorp.com

505ITM Hardware & Software Manual

To set the Ambient Temperature Forecast: 1. Enter the appropriate information in the following fields: Controlled By: Select a temperature signal source to use in forecasting the temperature. This should be an ambient temperature probe.

Note:

If the 505ITM does not have an ambient temperature probe installed as one of its input modules, this feature cannot be used.

Measurement Period: Select the number of hours to measure the ambient temperature. Exceeded Hours: Select the number of hours that the controlling signal must exceed the Threshold Value during the Measurement Period for the setpoint temperature shift to occur. Threshold Value: Select a value to override the standard value. All other settings for the relay, such as hysteresis and time delay, remain the same. Forecast Override Setpoint: Enter a setpoint for the first column of the relay matrix when the Threshold Value is exceeded for the

69

www.qualitrolcorp.com

505ITM Hardware & Software Manual


specified number of hours. 2. Click [Load]. Example: If the ambient temperature exceeds 30C for at least 12 hours over the previous 120 hours, the effective setpoint for the first column is 50C.

Cooling Equipment Exerciser


The Cooling Equipment Exerciser actuates the relay for a set period of time at a specified interval of days. This feature allows you to exercise a seldom-used fan circuit to prevent rust, lubricate bearings, and to keep wildlife from nesting in fan cages. This section of the Output Relay Setup window includes the fields described below.

Important:
Enabled / Disabled

Do not enable the exerciser for any relay that controls a trip function. Allows you to enable or disable this feature. Allows you to set the number of minutes that the relay remains actuated when the cycle time is reached. The range is 0 - 59 minutes. Allows you to set the amount of time between each exerciser actuation. The range is 0 - 30 days. Allows you to set the time of day that the exerciser starts to run once the cycle time is completed. The range is 0 - 23, in military time format.

Exercise time Cycle time Start time

70

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Matrix Controlled
This section of the Output Relay Setup window provides a variety of input signal configurations and logic to control the relay actuation. For example, using the math function or, you can actuate the relay with a maximum of four different input signals. Conversely, by using the or function and setting the Actuation Direction to down, you can actuate on the minimum signal of the four control signals inputs. The fields in this section of the Output Relay Setup window are described below.

Control signal X (4 fields) Setpoint (4 fields) Hysteresis (4 fields)

Allows you to select up to four input modules and/or relay states, the measured values of which, when compared to the setpoints, actuate or de-actuate the relay according to the logic of the matrix. Allows you to select a value corresponding to the control signal, which, when it equals or exceeds the setpoint value, meets the conditions to actuate the relay in that column. Allows you to select a switching differential required to de-actuate the relay. Without hysteresis, a relay could toggle on and off rapidly when the control signal reaches the setpoint value, causing stress on relay circuits. The hysteresis prevents this by providing a dead band between on and off. Example: If there is only one signal controlling the relay and the Actuation direction field (see below) is set to up, when the control signal reaches the setpoint value, the relay actuates. The relay deactuates only when the control signal falls below the setpoint value minus the hysteresis. Select up to actuate the relay when the input signal becomes greater than the setpoint value. Select down to actuate the relay when the input signal becomes less than the setpoint value. Example: You could use the up actuation direction for rising temperature values and the down actuation for alarming on low oil level values.

Actuation direction (4 fields)

71

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Math Expression (3 fields) Allows you to enter a math function in each of the three available fields. The first and third fields allow the math functions or, and, and minus. The second field allows only or and and. The minus function(s) are first evaluated in the matrix math expression. Otherwise, the overall equation is evaluated from left to right. Example: If the Matrix table is set up as: Control Signal 1 Control Signal 2 Control Signal 3 Control Signal 4

or

or

minus

The system will evaluate this as: ((Control Signal 1 OR Control Signal 2) OR (Control Signal 3 MINUS Control Signal 4)). Auxiliary Setpoint and Low Temperature Lockout Feature The original IED509 had a feature for an auxiliary current setpoint and a low temperature lockout feature. This has now been incorporated into the relay matrix and can be accomplished using the following example: 1. Set Control Signal 1 to WINDING, Setpoint to 80.00 ( C), and Actuation Direction to up. 2. Set the first (far left) Math Expression to or. 3. Set Control Signal 2 set to WINDING - current, Setpoint to 500.00 (Amps), and Actuation Direction to up. 4. Set the middle Math Expression to and. 5. Set Control Signal 3 to AMBIENT, Setpoint to 10.00 ( C), and Actuation Direction to up. The system will evaluate the relay if the winding temperature or winding current exceed the setpoints and will actuate the relay only if the ambient temperature is above 10 C.

Cancel and Load Buttons


This section of the Output Relay Setup window includes the buttons described below. Cancel Button Load Button Cancels any changes made and returns you to the Setup window. Saves all the settings from this window to the 505ITM and returns you to the Setup window.

72

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Output Loops
The Output Loops Setup window opens when you click [Output Loops] from the Setup window. This window allows you to configure the two current loop output channels. The 505ITM is equipped with two software selectable 0 - 1 mA or 4 - 20 mA (0 - 10 mA on request) outputs to provide information to Supervisory Control & Data Acquisition (SCADA) systems or remote indications. You can configure each output to send data from any of the inputs or send a derived calculation, such as:

the maximum value of up to three inputs, or a difference calculation between two input modules

To begin, click the tab of the output loop that you want to configure. The Output Loops Setup window displays for the selected output loop.

More Information

Loop Parameters Custom Range Loop Controlled

73

www.qualitrolcorp.com

505ITM Hardware & Software Manual Loop Parameters


This section of the Output Loops Setup window includes the fields described below.

Output Loop Loop function Loop type

Displays the number of the analog current loop that is to be configured. Allows you to enable or disable the output loop operation. Allows you to select between current loop ranges of 0 - 1 mA and 4 - 20 mA.

Note:

If requested at the time the monitor is ordered, this field can be made to select between current loop ranges of 0 - 1 mA and 0 10 mA.

Custom Range
This section of the Output Loops Setup window allows you to select the value range for the current loop output. Example: An RTD measures temperatures from -40 - 120 C. You select an output of 4 - 20 mA and a custom range of 0 - 100. For temperature measurements of:

40 - 0 C, the current loop output will read 4 mA 0 - 100 C, the output will correspond directly to 4 - 20 mA

Any temperature measurement over 100 C will continue to read 20 mA. The fields in this section of the Output Loops Setup window are described below.

Use Custom Range Minimum Maximum

Allows you to activate the custom scaling of the analog outputs by clicking to put a check mark in the check box. Allows you to enter a value that corresponds to 0 mA for a 0 - 1 mA output, or 4 mA for a 4 - 20 mA output loop. Allows you to enter a value that corresponds to 1 mA for a 0 - 1 mA

74

www.qualitrolcorp.com

505ITM Hardware & Software Manual


output, or 20 mA for a 4 - 20 mA output loop.

75

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Loop Controlled
This section of the Output Loops Setup window allows up to three different input measurements and two math functions to correspond to the analog output loop. You can set up the current output loops to be controlled by one of these three options:

a single input measurement the maximum value of up to three input parameters the difference between two inputs

The fields in this section of the Output Loops Setup window are described below.

Control Signal 1, 2, 3 (3 fields) Math Expression

Allows you to select the input module(s) that will control the current loop output. Allows you to select the math expression(s) used for selecting maximum values or difference measurements corresponding to the output current loop value.

Bank Switching
The Bank Switching Setup window opens when you click [Bank Switching] from the Setup window. This window configures the cooling circuit management feature. This feature provides a method for evenly spreading the wear of cooling equipment between two or more different cooling groups. Example: If Relay 1 activates a cooling group at 60 C, and Relay 2 activates another cooling group at 75 C, the first group will be used more extensively than the second group. By periodically switching the relay functions, the wear is spread evenly between the two groups. To set up the Cooling Circuit Management section of the Bank Switching Setup window: 1. Determine two relays to be exchanged. 2. In the entry field for the first relay, select the second relay from the drop-down field. 3. In the entry field for the second relay, select the first relay from the drop-down field. Example: If you want to bank switch Relays 2 and 4, select Relay 4 in the Relay 2 field, and select Relay 2 in the Relay 4 field.

76

www.qualitrolcorp.com

505ITM Hardware & Software Manual

You can bank switch more than two relays in a loop, but this can only be accomplished if the bank switching loop is closed or completed after the setup. This means that the last relay of the bank switching loop must select the first relay of the loop. Example: If Relay 2 selects Relay 3, and Relay 3 selects Relay 4, you must set up Relay 4 to select Relay 2 since Relay 2 was the start of the bank switching loop. The bank switching is accomplished by exchanging all the matrix controls of the selected relay with the one selecting it. This occurs at midnight each night so if you were to view the relay settings on any two consecutive days, you would notice the changes.

77

www.qualitrolcorp.com

505ITM Hardware & Software Manual

TransLife
The TransLifeTM Setup window opens when you click [TransLifeTM] from the Setup window. The TransLifeTM feature provides detailed information for a winding temperature of the transformer.

More Information

TransLifeTM Control Consumed Life Critical Forecast Temperature Profiler

78

www.qualitrolcorp.com

505ITM Hardware & Software Manual TransLifeTM Control


This section of the TransLifeTM Setup window allows you to configure the TransLifeTM settings for the individual winding temperatures. It includes the fields described below.

Enable / Disable Winding Temperature Input Module # Ambient Temperature Input Module # Oil Temperature Input Module # Load Current Input Module #

Allows you to enable or disable the TransLifeTM feature. Allows you to select the number of the input module, or if suitably equipped, the fiber optic probe that will measure the winding temperature. This winding temperature measurement is used to calculate the consumed life, the time to reach critical winding temperature, and the values for the temperature profiler. Allows you to select the number of the RTD Input Module that will measure the ambient temperature.

Note:

This field is only required if you are using the Critical Forecast feature. It is not required for the Consumed Life or Temperature Profiling features.

Allows you to select number of the RTD Input Module sensors that will measure the oil temperature.

Note:

This field is only required if you are using the Critical Forecast feature. It is not required for the Consumed Life or Temperature Profiling features.

Allows you to select the number of the current input module sensors that will measure the current load of the selected winding.

Note:

This field is only required if the winding temperature input module is a direct-winding, fiber optic probe and you are using the Critical Forecast feature. It is not required if the winding temperature input module is not a fiber optic probe, or for the Consumed Life and Temperature Profiling features. This field is not required for a 505ITM.

79

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Consumed Life
The 505ITM calculates relative life consumption according to IEEE standards. These standards are based on the Arrhenius formulas for deterioration of organic insulation material with time and temperature. Each 6 - 8 degree increase in temperature approximately doubles the rate of life decay. Based on the cumulative exponential affects of temperature over time, life consumption metering helps to prioritize maintenance activities between transformers. It also helps to equalize the load between transformers to maximize system life and minimize maintenance. This section of the TranslifeTM Setup window includes the fields described below.

Life Consumption Formula Variables

Depending on the application, allows you to select different Unity Hot Spot Temperatures by entering the corresponding constants. Unity Hot Spot Temperature is defined as the value of the winding temperature at which exactly one hour of consumed life has occurred. The 505ITM uses the IEEE Std C57.91-1995 and CEI/IEC 354:1991 for calculating the transformer loss of life in its life-consumption equations. Both standards use Montsingers rule of thermal degradation, which is a simplified version of Arrhenius Law of General Chemical/Thermal Degradation. See the following table for recommended values. A B Unity Hot Spot Temperature ( C) -11.269 6328.8 -11.968 6328.8 -11.804 6328.8 -13.391 6972.15 110 95 98 101 Recommended for 65 C insulation Recommended for 55 C insulation IEC 354:1991 specification Notes

80

www.qualitrolcorp.com

505ITM Hardware & Software Manual


-14.133 6972.15 Present Loss of Life Rate Loss of Life in the Last Hour Loss of Life in the Last Day Total Loss of Life Assumed Transformer Life Remaining Life Left Operating Hours 87

Displays the consumed life rate of the winding at this instant in time. Example: If the Unity Hot Spot Temperature is 110 C and the winding is reading exactly 110 C, the present loss of life rate is 1.00. Displays the consumed life lost in the past hour. In hours, displays the consumed life lost in the past 24 hours. Displays the total loss of consumed life for the transformer. If the consumed life is known, this value can be preset for transformers that are already commissioned. Transformer life entered by the user. Default value is 20 years.

Displays the remaining life left of the transformer by subtracting the total loss of life calculated so far from the assumed transformer life. Displays the operating hours of the 505ITM. You can preset this number.

Critical Forecast
This section of the TranslifeTM Setup window allows you to set up the Critical Forecast feature. For the present loading conditions, the Critical Forecast can predict how long it will take the winding temperature to reach a given critical temperature. Before you use the Critical Forecast feature:

Check that values are entered in the Oil Rise Temperature and Oil Time Constant fields for the winding temperature input module. See Winding Temperature Setup for more information about these parameters. Check that input modules are selected in the Ambient Temperature Input Module # and Oil Temperature Input Module # fields in the TransLifeTM Control section of the TransLifeTM Setup window.

81

www.qualitrolcorp.com

505ITM Hardware & Software Manual


The Critical Forecast section includes the fields described below.

Critical Temperature (3 Range fields) Time to Critical Temperature (3 Range fields)

Allows you to enter three temperature values for monitoring the time it takes for the winding temperature to reach the present load conditions.

Displays the time calculated for the winding temperature to reach the critical setpoint values, given the present loading, oil/winding temperatures, and ambient conditions. If the number displayed is 0.00 hours, the winding temperature has already reached the critical point. If 99.9 hours are displayed, the winding temperature will never reach the critical point, given these loading conditions.

82

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Temperature Profiler
This section of the TransLifeTM Setup window allows you to configure the Temperature Profiler. The Temperature Profiler has 12 ranges of temperature values - six ranges each above and below the value in the Unity Temperature field. The Temperature Profiler monitors how many hours the measured winding temperature remains in each temperature range. This provides you with a visual indication of how and when the transformer has been used in conjunction with the consumed life value, and it provides a more accurate indication of the total loss of life of the transformer. The ranges are divided into six-degree increments, because the consumed life of a transformer doubles for approximately every six degree rise in temperature. The Temperature Profiler section includes the fields described below.

Unity Temperature

Allows you to enter a temperature value where one hour of operating time equals one hour of consumed life. If the Unity Temperature parameter is unknown, use the recommended values from the table provided in the Consumed Life section. The 12 temperature legends are displayed after you: 1. Enter a temperature value in the Unity Temperature field. 2. Press [Load]. 3. Re-enter the TransLifeTM Setup window. The legends will be in 12 ranges, 6 below the Unity Temperature and 6 above.

Temperature Legends

12 Temperature Range Fields Graph Button

Display the amount of hours the selected winding temperature remained in each range. Displays a bar graph of the 12 temperature ranges. The 6 blue ranges indicate the operating times that exceeded the consumed life rate. Conversely, 6 red ranges indicate the consumed life that exceeded the operating time.

83

www.qualitrolcorp.com

505ITM Hardware & Software Manual

84

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Importing and Exporting Configuration Files


Configurations can be saved as files. This is convenient if:

you want to restore the 505ITM to its original settings you want to configure a 505ITM offline and import this configuration at the site

You can save configuration settings in files using the File pull-down menu. These files have the default file extension .qcf3. The pull-down menu commands are described below:

Import Export Export as... Print Print preview

Allows you to import a configuration from a file stored on your PC. Allows you to store the current configuration in a previously specified file for future use. Allows you to store the configuration in a newly specified file for future use. Allows you to print the current configuration file for recordkeeping and reference. Displays the current configuration file on the PC monitor.

85

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Calibrating the 505ITM


Calibrating Remote Outputs for Alternate Values
Overview and Requirements
Unless otherwise specified, the 505ITM remote output current loops are calibrated for 0 - 1 mA and 4 - 20 mA. If necessary, you can recalibrate the current loop outputs for the following alternate values:

0 - 5 mA 0 - 10 mA 0 - 20 mA

This procedure provides steps for recalibrating the current loop outputs. You will need the following items to perform this procedure:

505ITM ammeter (or multi-meter set to measure DC milliamps) Qualitrol Remote Software

Calibration Procedure
1. Connect the computer to the 505ITM and start the ITM Manager Software. The Desktop Menu window displays.

2. Click [Connect] and enter the password for the Calibrator tool.

Note:

If you do not know this password, call Qualitrol at 585-586-1515, Ext. 410.

3. Click [Start]. The Calibrator - Signal Selection window displays with the radio button for Input 1 selected.

86

www.qualitrolcorp.com

505ITM Hardware & Software Manual

CAUTION: Be extremely careful in the Calibrator tool. Changing calibration values


incorrectly might cause the 505ITM to malfunction. 4. Connect the ammeter (or multi-meter set to measure DC milliamps) to TB1 pins 29 and 30 with the positive probe on 29. 5. In the Calibrator - Signal Selection window, select the radio button for Output 1 and click [Calibrate]. The next two windows that appear are for calibrating the 0 - 1 mA section, which will remain the same.

87

www.qualitrolcorp.com

505ITM Hardware & Software Manual


6. Click [Next] until you reach the Output Channel Calibration window. The Adjust output signal to field displays 4.80 mA, which is the value used to calibrate for a 4 - 20 mA current loop output.
Output Channel Calibration

7. Adjust the slide bar control until the ammeter displays the correct lower calibration value for the new current loop output range. Current Loop Output Range 4 - 20 mA 0 - 5 mA 0 - 10 mA 0 - 20 mA Lower Calibration Value 4.80 mA 0.25 mA 0.50 mA 1.00 mA

88

www.qualitrolcorp.com

505ITM Hardware & Software Manual


8. Click [Next]. The Output Channel Calibration window displays again.
Output Channel Calibration

9. Adjust the slide bar control until the ammeter displays the correct upper calibration value for the new current loop output range. Current Loop Output Range 4 - 20 mA 0 - 5 mA 0 - 10 mA 0 - 20 mA 10. Click [Finish]. 11. Repeat the process for the remaining current output loops. When you are finished, immediately exit from the Calibrator tool. The current loops are now be calibrated for the new values. Upper Calibration Value 20.00 mA 5.00 mA 10.00 mA 20.00 mA

89

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Calibrating a Level Gauge to the 505ITM


Overview
All of the input modules on the 505ITM are calibrated at Qualitrol, except for the Potentiometer (Level Gauge) input modules. These modules and sensor inputs are specific to the transformer with which they are associated and must be calibrated on the transformer. This procedure provides the steps for calibrating a Level Gauge to a 509 ITM.

CAUTION: Except for the Potentiometer (Level Gauge) Input Modules, the input
modules of the 505ITM are calibrated using highly precise measurement equipment. If you inadvertently try to calibrate the wrong input module, you might cause the 505ITM to malfunction. Calibrate only the Potentiometer input module. When you are finished, immediately exit the Calibration tool.

Before You Begin


1. Connect the potentiometer output wires of the Level Gauge to the 505ITM. See the Hardware Instructions for details. 2. Check that the wiring is correct by adjusting the case face to raise and lower the dial pointer. Observe the front LCD display of the 505ITM.

As you raise the pointer, the displayed value should increase. As you lower the pointer, the displayed value should decrease.

If the 505ITM is not operating correctly, check the wiring before you begin the calibration procedure.

90

www.qualitrolcorp.com

505ITM Hardware & Software Manual Calibration Procedure


1. Connect the computer to the 505ITM and start the Remote Software. The Desktop Menu window displays.

2. Click [Connect] and enter the password (505) for the Calibrator tool. 3. Click [Start]. The Calibrator - Signal Selection window displays with the radio button for Input 1 selected.

91

www.qualitrolcorp.com

505ITM Hardware & Software Manual

4. Click the radio button for the input module that displays Potentiometer. In the example above, this is Input 3.

CAUTION: Check again that you have selected the correct input module before
proceeding. Calibrating any other input module could erase the systems calibration values and cause the 505ITM to malfunction. 5. Click [Calibrate].

92

www.qualitrolcorp.com

505ITM Hardware & Software Manual

93

www.qualitrolcorp.com

505ITM Hardware & Software Manual


The Input Channel Calibration window displays. The Set input signal to field prompts you to set the pointer to minimum (MIN). 6. Adjust the case face until the pointer is set at the minimum position.

Case face adjusted with the pointer (and potentiometer) moved to minimum

7. Click [Next].

94

www.qualitrolcorp.com

505ITM Hardware & Software Manual

The Input Channel Calibration window now prompts you to set the pointer to maximum (MAX). 8. Adjust the case face until the pointer is set at the maximum position.

Case face adjusted with the pointer (and potentiometer) moved to maximum

95

www.qualitrolcorp.com

505ITM Hardware & Software Manual


9. Click [Finish]. The Level Gauge is now calibrated to the 505ITM. The Minimum value will read 0% on the LCD display and the Maximum value will read 100%. 10. Immediately exit the Calibrator tool. 11. To use the Level Gauge for alarm setpoints: (a) Adjust the case face until the pointer is set to an alarm value, either low or high. (b) Read the LCD display on the front of the 505ITM. Record the value. (c) In the Output Relays section of the Configurator - Customer tool, use this number for the setpoint value.

96

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Frequently Asked Questions About the 505ITM


Q: A: In the Simple CT Temperature Scaling Setup window, what is the Oil Temperature Adder? And where do I get the values for the other three variables? The Simple Calculation Setup Method, which uses the Simple CT Temperature Scaling Setup window, calculates the winding temperature of the transformer by using the oil temperature of the transformer and the load or current running through the windings. The RTD input module that measures this oil temperature is the Oil Temperature Adder. The other three variables in this section of the window are: Winding Rise Temperature Current Factor Winding Time Constant

You can determine the values for these variables from the Transformer Test Report that is included with the transformer. The temperature rise (or delta T) is the hot spot temperature of the winding over the oil temperature at a given load. You can calculate the current by using these steps: 1. Divide the secondary kVA by the secondary voltage. 2. Divide by the instrumentation CT ratio that is being used to give you the load current for that delta T rise. Example: The transformer is a 14000 kVA with a winding of 34400 V. The instrumentation CT is 1200 : 5. 14000 kVA divided by 34400 V equals 407 Amp 407 Amp divided by 1200/5 (or 240) equals 1.69 Amp

The same report indicates that the hot spot rise over fluid is 12.7 C. Therefore, in the Simple CT Temperature Scaling Setup window, enter: 12.7 C in the Winding Rise Temperature field 1.69 Amp in the Current Factor field

If no value for the Winding Time Constant field is provided on the Transformer Heat Run Test Report and the manufacturer cannot supply it, then the IEEE Std C57.91 recommends using a number between 5 and 8 minutes. Q: A: What is a time constant? The time constant is the time that it takes for the winding temperature to reach 63.2% of its full value for a given current load. That means for a given load on a transformer, it will take approximately 5 time constants for the winding temperature to reach its final value. So if the time constant is 6 minutes, it will take the winding temperature 30 minutes (5 time constants 6 minutes) to reach full temperature for a given load.

97

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Q: A: What do I do if there isnt a Transformer Heat Run Test Report? First, call the transformer manufacturers to see if they have a copy of the test report. If they do not, ask if they have a test report for a similar transformer type or if there are any specifications mounted directly onto the transformer. If none of this information is available and this is a retrofit project, do the following: 1. Read the mechanical winding gauge and subtract the oil measurement. 2. Measure the current coming directly off the instrumentation CT. 3. Enter these two values into the remote software. If you select method 3, the closer to full load that the transformer is running, the more accurate the values for entering into the system. Q: A: What is the difference between failsafe and non-failsafe for a relay? In the 505ITM, Qualitrol uses Form C relays. These relays have three contacts: normally open, normally closed, and common. When the monitor has no power applied, the common and normally closed contacts are shorted together, while the common and normally open contacts are open. For a non-failsafe relay, when power is applied to the 505ITM, the relay contacts are shorted on the common/normally closed side and open on the common/normally open side. (This is the same situation as if no power was supplied to the monitor.) When the controlling input signal reaches the setpoint, the relay changes states so that the common/normally open side is shorted (closed) and the common/normally closed side is open. A non-failsafe relay only changes states when the setpoint is exceeded. This is the reason the trip function is normally assigned to a nonfailsafe relay. When power is applied to the monitor with a failsafe relay, it immediately changes states so that the common/normally open side is shorted together and the common/normally closed side is open. If the controlling signal reaches the setpoint, or if power is removed from the monitor, the relay changes back to the common/normally closed state being shorted and the common/normally open state being open. It is for this reason that most alarms and cooling systems are connected to failsafe relays, because they will actuate if the setpoint is exceeded or if the monitor loses power. Q: A: How does the Latching Relay function work? A latched relay will actuate in the same manner as a non-latching relay when the setpoint conditions have been exceeded. The difference between a non-latching relay and a latching relay is that a non-latching relay will return to its pre-existing state when the setpoint conditions are no longer being exceeded. A latching relay will remain latched. A latched relay may only return to its pre-existing state if the setpoint conditions are no longer exceeded and the operator presses the RESET button on the front panel of the unit during the normal scrolling operation.

98

www.qualitrolcorp.com

505ITM Hardware & Software Manual


Q: A: What does it mean when the unit reads SENSOR ERROR or INVALID READING? If the 505ITM detects incorrect wiring, a broken wire, pinched insulation in the connector, or missing sensor on the RTD input module, it will display SENSOR ERROR. This alerts the user to investigate the RTD sensor and correct the situation. The INVALID READING will display for any CT, Temperature input modules that use an RTD probe that has a sensor error. The winding temperature is calculated from the current load and an oil temperature measurement. If the oil temperature measurement has a sensor error, any calculation will be invalid. Fixing the RTD issue will correct both the RTD sensor error and the invalid reading for the winding temperature. Are there any particular wiring methods for wiring a 505ITM? Wire the 505ITM according to your OEM/utility companys practices and industry standards. For those areas not covered, Qualitrol recommends the following: Separate all power wiring (supply power, relay outputs, etc.) from analog wiring (sensor inputs, current loop outputs, etc.) and digital wiring (RS-232, RS-485) in different conduits, if possible. Use shielded wire for all and twisted pairs for analog and digital wires. Shielding and twisted pair will minimize noise radiating to and from the wire. For all wiring, keep lengths as short as possible and use the heaviest gauge wire thats practical for the application. Wire has resistance and shorter lengths and thicker wire minimizes that resistance. Dress the wires so that none of the leads are pinched or strained, which might shorten the life of the cabling. What exactly is an RTD? RTD stands for Resistance Temperature Detector, and it is a device whose resistance changes directly proportional to changes in temperature. For a 100 ohm RTD, this is approximately 0.385 ohm per degree Celsius, and for a 10 ohm RTD, this is approximately 0.0385 ohm per degree Celsius. See the following chart for resistance values of the two types of RTDs at points of interest. RTD Type 10 ohm RTD 100 ohm RTD -40C 7.490 ohm 84.27 ohm 0C 9.035 ohm 100.0 ohm 25C 10.00 ohm 109.73 ohm 120C 13.669 ohm 146.06 ohm

Q: A:

Q: A:

Because of the small resistance values in an RTD sensor, Qualitrol recommends a maximum of 75 feet of cable length. A typical application to measure the resistance (temperature) changes in an RTD is for a monitor to send an excitation current through the RTD and then measure the voltage across the device. This voltage is then translated to the appropriate temperature value by the monitor. Because an RTD is a resistive device, you must take the wire resistance into account when doing any accurate measurement calculations. This can be accomplished in different ways. One way is to send the excitation current through its own pair of wires and measure the voltage across another pair of wires using only sensing current. The excitation current will be great enough to make a large

99

www.qualitrolcorp.com

505ITM Hardware & Software Manual


voltage value, while the sensing current will be small to negate any wire resistance from being detected. This is the basis for a four-wire RTD measurement and is considered one of the most accurate. The 505ITM can accomplish the same accuracy of a four-wire measurement using only three wires by measuring the wire resistance in one leg of the RTD and subtracting the resistance temperature twice. For that reason, if you are trying to connect a four-wire RTD sensor to the 505ITM, tie off one of the legs so that it is not connected to the terminal block. Q: A: Why does the RTD sensor read either -50 C or 130 C, instead of the correct value? The measurement range of the RTD sensor is from -40 - 120 C, but the 509 ITM will over-range to -50 C or 130 C when one of the following occurs: 1. The wrong sensor is installed: a 10 ohm RTD sensor is connected to a 100 ohm input module, or a 100 ohm RTD sensor is connected to a 10 ohm input module.

Verify that the RTD sensor type matches the label on the back of the 509 ITM dust cover. If the two of these do not match, do one of the following: obtain the correct sensor type, or contact Qualitrol about updating the 505ITM unit in the field (purchasing a new module and getting an update software disk).

2. The calibration for the RTD Input Module has been altered or overwritten. If the 505ITM was incorrectly recalibrated in the field, reinstall the factory calibration settings. See Using the Factory Calibrator Application Tool (Advanced users only) in the Software Instructions. Q: A: How do I specify and use the clamp-on CT? Clamp-on CTs are used with the current input modules and CT, temperature input modules for calculating simulated winding temperature. Since they are a clamp-on device, they offer a physical isolation from the transformer and the sensing device The question sometimes arises of how much burden this CT sensor places on the transformer. The burden is so small that it can only be measured in a laboratory, so for all practical purposes the answer is zero as sensed by the transformer. The output of the clamp-on sensor is from 0 - 0.333 V AC for the entire sensing range. (0 - 10 Amp AC in corresponds linearly to 0 - 0.333 V AC out.) The clamp-on CTs have an accuracy of 1% over the full measurement range specified for that CT. Therefore, when selecting a clamp-on CT for the application, the CT rating should be as close as possible without being less than the maximum value it will be measuring. The label value on the clamp-on CT should match the CT clamp-on sensor rating value. See Input Modules in the Software Instructions.

100

www.qualitrolcorp.com

505ITM Hardware & Software Manual

Appendix
TB1
1 2 3 4 5 6 7 8 9 17 18 19 20 21 22 23 24 25 1 2 3

TB3
1 2 3
INPUT MODULE 1

TB4
INPUT MODULE 2

Input Modules

10 26 11 27 12 28 13 29 14 30 15 31 16 32 1 2 3

TB5
INPUT MODULE 3

1 2 3 4 5

TB6
1 2 3
INPUT MODULE 4

Optional Heater TB1-1,17

TB2

1 2 3 4 5

EARTH GROUND

VAC LINE INPUT (+)

TB1 TB1
VAC LINE HEATER

1 2 3 4 5

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

VACC NEUT HEATER

VACC NEUT INPUT (-)

INPUT POWER: (UNIVERSAL) 90-264 VAC, 47-63 Hz 40-290 VDC WATTAGE: < 30 WATTS AC IN < 15 WATTS DC IN LINE FUSE - 3.15 AMPS RELAY CONTACTS: 10 A @ 115/230 VAC 10 A @ 30 VDC
MODEL NO. SERIAL NO. MFG. DATE

RXD+(B) RXD-(A) SIGNAL GND

RELAY 2
10 A

6 7 8

RELAY 3
10 A

9 10 11

T/RXD+(B) T/RXD-(A) SIGNAL GND

RS-485

Input Power

RELAY 1
10 A

TXD+(B) TXD-(A)

RS-485 Interface

RELAY 4
10 A

12 13 14 15 16

(+)

SYSTEM STATE RELAY 10A

CURRENT (-) LOOP 1 (+) CURRENT (-) LOOP 2

Current Output Loops

Alarm Relays

505 Wiring diagram

101

www.qualitrolcorp.com

505ITM Hardware & Software Manual

505ITM Hardware & Software Manual

MENU SWITCH

right left

05/24/2001 08:28:15 up down/enter TOP OIL CHAN 1 77.5 C up down/enter WINDING CHAN 2 92.5 C up down/enter WINDING CHAN 2 CURRNT 1224.5 A up down/enter AMBIENT CHAN 3 18.4 C up down/enter DGA CHAN 4 675.1 PPM up down/enter OPERATING HOURS TOTAL 013992 HRS up down/enter top of column

right left

VIEW/RESET MAXIMUM MEMORY up down/enter TOP OIL 84.5 C MAX1 1524 051701 up down/enter WINDING 96.3 C MAX2 1524 051701 up down/enter WINDING 1300.3 A MAX2 1524 051701 up down/enter AMBIENT 22.1 C MAX3 1524 051701 up down/enter DGA 702.8 PPM MAX4 1524 051701 up

right left

VIEW/RESET MINIMUM MEMORY up down/enter TOP OIL 73.2 C MIN1 1524 051701 up down/enter WIND 1 87.1 C MIN2 1524 051701 up down/enter AMBIENT 16.5 C MIN3 1524 051701 up down/enter DGA 204.3 PPM MIN4 1524 051701 up

right left

VIEW TRANSLIFE up down/enter TL1 CRITCAL TIME 0.4 HR TO 100 up

right left

CHANGE SETTINGS ID # REQUIRED enter PROGRAM USER ID: 111111 enter

right left

INVALID NUMBER ID: 111111 (valid) (invalid) enter SET TIME/DATE 15:24 05/24/01 down/enter TL1 CRITCAL TIME 5.4 HR TO 105 up down/enter TL1 CRITCAL TIME 99.9 HR TO 110 up down/enter TL1 LOSS OF LIFE PRES RATE 0.96 up down/enter enter DGA CHAN 4 ON enter RS232 BAUD RATE 19200 enter RS485 BAUD DATA 9600 8 enter RS485 PARITY STP NONE 1 enter AMBIENT CHAN 3 ON enter WINDING CHAN 2 ON enter TOP OIL CHAN 1 ON

down/enter top of column

down/enter top of column

TL1 LOSS OF LIFE HOUR 0.82 HRS up down/enter TL1 LOSS OF LIFE DAY 22.94 HRS up down/enter TL1 LOSS OF LIFE TOTAL 012751 HRS up down/enter TL1 REMAIN LIFE 18.58 YEARS up

down/enter B

enter UNIT WILL AUTOMATICALLY REBOOT NOW!

505ITM Hardware & Software Manual


B up down/enter OPERATING HOURS TOTAL 013992 HRS up down/enter TEMP TL1 up down/enter TEMP TL1 up down/enter TEMP TL1 up down/enter TEMP TL1 up down/enter TEMP TL1 up down/enter TEMP TL1 104 - 110 C 001221 H up down/enter TEMP TL1 110 - 116 C 000095 H up down/enter TEMP TL1 116 - 122 C 000081 H up down/enter TEMP TL1 up down/enter TEMP TL1 up 128 - 134 C 000000 H 122 - 128 C 000032 H TEMP TL1 down/enter 134 - 140 C 000000 H up down/enter TEMP TL1 > 140 C 000000 H down/enter top of column 98 - 104 C 000326 H 92 - 98 C 000256 H 86 - 92 C 000207 H 80 - 86 C 000200 H < 80 C 000171 HR

505ITM Hardware & Software Manual


Index

A
about Qualitrol, 6 about the hardware instructions, 6 AC voltage input connections, 16 input module, 8 advanced calculation setup, 59 ambient temperature forecast, 69 application, open an, 34 automatic operation, 23

exporting configuration files, 86

F
file menu, 29 four wire RS-485 connection, 22 framework window, 29 frequently asked questions, 98 front panel, 7 functional specifications, 26

H B
bank switching, 77 hardware installation, 10 heater configuration, 46 option, 14

C
calibrate input channels, 38 output channels, 39 calibrations, saving, 39 calibrator application, 37 command buttons, 50, 74 communicate with monitor, 30 communications configuration, 47 configurator applications, 40 connecting monitor, 28 consumed life, 81 controlled by matrix, 73 cooling equipment exerciser, 72 critical forecast, 82 CT current parameters, 54 input connections, 15 input module, 8 current input module, 9 input wiring, 17 custom range, output loops, 76 custom scaling, 53

I
importing configuration files, 86 input module configuration, 51, 52 install hardware, 10 monitor, 10 software, 28

L
life consumption, 81 loop parameters, 76

M
main port, 49 menu mode, 23 monitor application, 34 monitor installation, 10 mounting monitors, 12

O
oil rise parameters, 58 open an application, 34 output loops, 75 relays, 64 output contacts relay wiring, 20 overview applications, 32 hardware, 5 software, 28

D
date configuration, 44 DC voltage input module, 9 input wiring, 17 digital communications, 22 display configuration, 45 dry contact closure input wiring, 19 module, 9

P
panel mount style monitor, 12 password configuration, 43 new, 43

E
enclosure style monitor, 12 expansion port, 50

www.qualitrolcorp.com

505ITM Hardware & Software Manual


potentiometer input connections, 16 input module, 8 power supply, 13 power up, 23 powered contact closure module, 9 wiring, 19 program mode, 25 software instructions, 28 system setup, 42

T
temperature profiler, 84 testing the system, 25 time configuration, 44 translife, 62, 79 translife control, 80 troubleshooting the communications link, 32

R
relay control, 65 output, 64 tabs, 65 remote output signal terminals, 21 RS-485 connection, 22 RTD input module, 8 input wiring, 14 running software, 28

U
upper fields, 60

V
view channels, 23 max readings, 23 min readings, 24

S
save calibrations, 39 seasonal setpoint, 68 service port, 48 setup system, 42 simple calculation setup, 55 simulator application, 36

W
winding rise parameters, 61 temperature and cooling, 60 temperature configuration, 55

www.qualitrolcorp.com

505ITM Hardware & Software Manual

About Qualitrol: Qualitrol manufactures substation and transformer monitoring and protection devices used by electric utilities and manufacturing companies. It is the global leader in sales and installations of transformer asset protection equipment, fault recorders and fault locators. Established in 1945, Qualitrol produces thousands of different types of products on demand, each customized to customers' unique requirements.
2008 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice. All trademarks are properties of their respective companies, as noted herein. IST-099-1.

www.qualitrolcorp.com