Anda di halaman 1dari 10

Technical Data sheets 11kV MV Switch Board Item Details / Description 1 11kV Switchboard Cubicle Make Type Metal

clad switchgear and control gear Compartmented switchgear and control gear - rated voltage - operating voltage Air insulated Draw-out type With automatic shutter ( for safety ) Separate compartment for : - circuit breaker - busbars - low voltage equipment - cable termination Pressure relief covers / Flaps Rear access necessary Cable connection from bottom Ample cabling space shall be provided for ease of cable connection / Termination Lockable service position for circuit breaker Lockable test position for circuit breaker Lockable isolated position for circuit breaker Circuit breaker floor mounted Cable earthing by earthing switch Mechanical & Electrical safety interlocks for : - earthing switch - test position - buscoupler & incomer * Type of enclosure & degree of protection Thickness of sheet metal a) load bearing members b) Non load bearing members Door arrangement ( enclose details ) Location of instruments & protection relays Max.height of instruments & protection relays from the ground level Overall dimension ( L x D x H ) & approx. weight a) Double/Single bus board B/C b) Double/Single bus board I/C c) Single bus board O/G ( Trafo Feeder ) d) Single bus board O/G ( Motor Feeder ) GA drawings enclosed Space heaters with thermostat in all panels with suitable interlocks DC source for each switchboard Busbars Busbar and T-off connections : Page 1

Unit

Supplier data ABB/AREVA/SIEMENS VCB yes yes 11 11 yes yes yes yes yes yes yes yes yes yes yes yes yes yes yes no no yes yes IP42 2 2 During detailed Engg Metering chamber above CB chamber During detailed Engg During detailed Engg

yes/no yes/no kV kV yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no yes/no IP mm mm

mm mm / kg

yes/no yes/no AH

no yes As per BOQ

Technical Data sheets 11kV MV Switch Board Item Details / Description - Copper - Aluminium - insulated - Min clearance between a) Phase to Phase b) Phase to Ground - Busbar size 4000 A 2000A 1250A 500A -Current density - for copper busbars Maximum temperature rise at rated full load current above site ambient temperature ( 48 deg C ) Ground bus -material -one sec rating of ground bus 3 Current Transformers - Make -Type ( cast resin , bar primary ) -Service -Secondary current -Transformation ratio as per SLD -Rated burden -Accuracy class a)Metering b)Protection suitable CTs to be provided to take care of additional burden due to KW transducers - Class of insulation -Power frequency & Impulse withstand - short time thermal rating for 1 sec 4 Voltage Transformers - Make -Type -Service -Transformation ratio as per SLD -Rated burden (for line PT's) -Accuracy class -Power frequency & Impulse withstand -Whether withdrawable type -HT & LT fuses provided 5 Relays Solid state relays equivalent to mentioned in SLD with profibus communication facility 6 Meters Ammeter -Make -Type -Size -Range Page 2

Unit yes/no yes/no yes/no mm mm sq.mm sq.mm sq.mm sq.mm A/sq.mm

Supplier data Yes No No As per IEC As per IEC During detailed Engg

1.2A/sq.mm

deg C

42 deg C

KA

40

yes/no A yes/no VA

yes Indoor 1 yes 15 0.5 5P20 yes

yes/no

KV KA

28/75 min. 31.5

yes/no VA KV yes/no yes/no Yes/no

yes 100 1.0/3P 28/75 yes yes Yes

mmxmm

90 x 90

Technical Data sheets 11kV MV Switch Board Item Details / Description -Reference standard Voltmeter -Make -Type -Size -Range -Reference standard MW meter -Make -Type -Size -Range -Reference standard KWH meter -Make -Type -Size -Range -Reference standard Power factor meter -Make -Type -Size -Range -Reference standard KW Transducer -Make -Type -Size -Range -Reference standard

Unit

Supplier data

mmxmm

90 x 90

mmxmm

90 x 90

mmxmm

90 x 90

mmxmm

During detailed Engg

mmxmm

During detailed Engg

Page 3

Technical Data sheets 11kV MV Switch Board Circuit Breaker Item Details/Description Unit General Make Type Rated voltage kV Operating voltage kV Frequency Hz Rated short circuit breaking current KA Rated short time current (1 sec) KA Total interrupting time ( measured in cycles from trip coil energisation ) cycles Closing time cycles Service Rated duty cycle Reference standard One minute power frequency test voltage KVrms Lightning Impulse withstand test voltage KVp Routine tests to be performed yes/no Type test certificates to be furnished yes/no Max. temperature rise on contacts at rated full load current at site ambient (50 deg C)deg C Arc extinctionMinimum volume oil SF6 Vacuum Others : Operating mechanism yes/no yes/no yes/no

Supplier As per Make list Vacuum 11 11 50 40kA 40kA <80 msec <80 msec

28 60 yes yes 42 deg C no no yes

Loaded-spring mechanism yes/no Loading . electrically yes/no . manually yes/no Circuit breaker closing : -motor operated , spring charged yes/no -voltage for spring charging motor V -contol voltage for closing coil V - allowable range of control voltage for closing %V - Latch-in mechanism for closing coil yes/no - DC power pack in each panel yes/no

yes yes yes yes 220 V AC 110 V DC 85-110% yes No. Separate battery bank provided. yes yes 110 V DC 70-110% Approx 2A yes

Circuit breaker control & tripping : - electrically (remote and local) yes/no - mechanically (emerg.-off at local) yes/no -contol voltage for trip coil V - Allowable range of control voltage for tripping %V - current required for tripping A Mounting Draw-out in metal clad cubicle (Separate technical data sheet) Lockable in racked-out position yes/no

Safety

yes/no

yes 4

Technical Data sheets 11kV MV Switch Board Circuit Breaker Item Details/Description No-voltage release (control voltage) measures

Unit yes/no

Interlocks to : - prevent moving of C.B. in closed position yes/no - allow closing of C.B. in defined position only yes/no Maintanence C.B. operation in racked-out/test/isolated position yes/no Additional accessories Switching status indicator Operation counter No. of auxiliary contacts a) Normally closed b) Normally open c) Whether convertible type yes/no yes/no nos. nos. yes/no

Supplier No Volt Coil shall be considered for only HT motor feeders. yes yes

yes yes yes 6 6 No

Technical Data sheets 11kV MV Switch Board Incoming Feeder Item General Feeder cubicle Details/Description Location : Main Sub-station & Load Sub-station Totally enclosed metal clad cubicle (separate technical data sheet) rated current of busbars considering deration due to site conditions - for Double bus I/C - for Single bus I/C - rated voltage - operating voltage Switchgear - short circuit capacity at operating voltage for 3 sec Circuit breaker (separate technical data sheet) for single bus I/C - for Double - for Single bus I/C bus I/C A A yes/no yes/no yes/no qty. qty. Not applicable As per SLD yes No No As per SLD As per SLD As per the spec yes/no qty. qty. yes/no yes/no yes/no No yes 1 1 On MFM yes/no yes Unit Supplier

A A KV KV KA yes/no

Not applicable As per SLD 11 11 40kA yes

Surge diverter Earthing Protection , metering, & Indications

Whether suitable for voltage and frequency variations as given in specifications Surge diverter with counter Earthing switch Current transformers Voltage transformers Protections: Indications: ( Enclose detailed list of indications provided )

Energy / Power Metering

Ammeters with selector switch Voltmeter with selector switch Power factor meter kWh meter kW - tranducer with isolated 4-20 mA

Technical Data sheets 11kV MV Switch Board Transformer Feeder Item General Details/Description Location : Crusher, RM, Kiln & Cement Mill Substation Feeders : Single bus board Feeder cubicle Totally enclosed metal clad cubicle (separate technical data sheet) rated current (Contactor feeder) - rated voltage - operating voltage A KV KV Not Applicable VCB Offered As per the requirement 11 11 40kA yes no As per SLD As per the spec yes/no yes yes/no yes Unit Supplier

Switchgear

short circuit capacity at operating voltage for 1 KA sec Contactor feeder with fuses yes/no (separate technical data sheet) - rated current - rated voltage - operating voltage short circuit capacity at operating voltage for 1 sec Whether suitable for voltage and frequency variations as given in specifications Earthing switch Current transformers, output side A KV KV KA yes/no yes/no qty.

Earthing Protection,

Protections: metering, & Indications Indications: ( Enclose detailed list of indications including transformer faults provided, Annunciator window shall be for transformer faults ) Ammeters with selector switch Energy / Power Metering kWh-meter Metering: - unbalanced load - accuracy class kW-transmitter with 4-20 mA output

qty. yes/no yes/no % yes/no

1 MFM no applicable for motor feeder

Technical Data sheets 11kV MV Switch Board Motor feeder Item Make General Location : Feeders : Single bus board Feeder cubicle Totally enclosed metal clad cubicle (separate technical data sheet) rated current (Contactor feeder) Derated current (Contactor feeder) rated current (Breaker feeder) Derated current (Breaker feeder) - rated voltage - operating voltage Switchgear Contactor and VCB/SF6 Breakers (separate technical data sheet) - rated current - derated current at site conditions - rated current - derated current at site conditions as given in Specifications Surge diverter Surge diverter with counter Earthing switch Earthing Protection , Current transformers, output side Current transformers for capacitor line current metering, & Indications Protections: Motor protection (microprocessor based) Trip circuit supervision High speed lock out Relay Antipumping protection Others : Indications: ( Enclose detailed list of indications provided ) Ammeters Energy / Power Ammeters with selector switch Metering ( for capacitor line currents) MFM yes/no As per Requirement yes/no yes/no yes/no yes/no As per Requirement As per Requirement As per Requirement As per Requirement yes/no A A A A yes/no yes/no yes/no qty. qty. A A A A KV KV Not Applicable Not Applicable As per Tender As per Tender 11 11 40kA VCB yes As per Tender As per Tender yes without counter no As per Requirement As per Requirement yes/no yes Main Sub-station Feed to : 11kV/MV motors Details/Description Unit Supplier ABB/AREVA/SIEME NS

- short circuit capacity at operating voltage for 3 KA sec

Whether suitable for voltage and frequency variations

qty. qty. Yes/no

1 Confirmed 1 Yes

Technical Data sheets 11kV MV Switch Board Motor feeder Item Details/Description Unit Supplier

Technical Data sheets 11kV MV Switch Board Buscoupler Item General Feeder Cubicle Location : Details/Description Main Sub-station yes/no A A KV KV yes/no A A yes/no yes/no qty. yes As pe the requirement As pe the requirement 11 11 40 yes As pe the requirement 2500 yes no 3 Totally enclosed metal clad cubicle (separate technical data sheet) rated current Derated current - rated voltage - operating voltage Switchgear Circuit breaker (separate technical data sheet) - rated current -derated current at site conditions as given in Specifications Earthing Earthing switch Protection , Voltage transformers ( one for each bus section) metering, & Indications Protections: As per SLD O/C (Low set & high set) E/F (Low set & high set) Under voltage Protection Trip circuit supervision DC fail protection High speed lock out Relay Others : Indications: yes/no ( Enclose detailed list of indications provided ) Voltmeters with selector switch Energy/power metering qty. yes 1 yes/no yes/no yes/no yes/no yes/no yes/no yes yes yes yes yes yes Unit Supplier

- short circuit capacity at operating voltage for 3 KA sec

Whether suitable for voltage and frequency variations

10

Anda mungkin juga menyukai