RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No Protection Description Type ref. 33KV Transformer Control and Relay Panel I 1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Protection Relay Setting Range Differential Protection (87GT) Idiff>=0.1-2.5 Iref Idiff>=2.5-30 Iref Idiff>>>=2.5-30 Iref m1: 0.15-1.5 m2: 0.15-1.5 IR,m2 (1.5-10.0 Iref) Op.del, trip signal:0-100S Restricted earthfault protection(64R) Effective setting: 10% High Impedance relay Stabilising resistor (0-1000) Ohm 2 50/51 50N/51N 67/67N, 50LBB 78, 27Z, 59, 81 60, 81R, 99, 27 Numerical Interconnection Protection Relay MICOM P341 Overcurrent protection (51) In: 0.08-4In T: 0-100 sec Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec Earth fault protection (51N) Ie: 0.08-4In T: 0-100 sec Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec Recommended Setting Remarks
Idiff>:0.1
10%In NCTR: *** A Rst: 200 ohm IDMT characterictics 3 Sec Curve
0.75*In 0.1
sec
6*In 0
sec (Inst)
0.2*In 0.1
Sec
0.3*In 0.5
sec
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No Protection Description Type ref. 33KV Transformer Control and Relay Panel Setting Range Dir. Overcurrent protection (67) In: 0.08-32In T: 0-100 sec Dir. Earth fault protection (67N) Ie: 0.08-32In T: 0-100 sec Under volatge protection (27) U<: 10-120V T: 0-100 sec Over voltage protection (59) U>: 60-185V T: 0-100 sec Under frequency protection (81U) f<: 45-65Hz T: 0-100 sec Over frequency protection (81O) f>: 45-65Hz T: 0-100 sec Local Breaker back-up protection (50LBB) In: 0.4-4*In Time delay df/dt protection (81R) df/dt: 0.1-10Hz/sec T: 0-100 sec Recommended Setting 0.75*In 0.35 Remarks RCA: 30 deg sec
0.1*In 0.35
80 2
V sec
121 3
V sec
47.7 2
Hz sec
PTR: 33KV/110V
52 2
Hz sec
1*In 0.3
4 Inst
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No Protection Description Type ref. 33KV Transformer Control and Relay Panel Setting Range Dead band lower frequency 45-65Hz Dead band upper frequency 45-65Hz Voltage Balance Relay (60) *** *** Overfluxing Protection Relay (99) *** *** Vector surge protection (78) dv/dt: 2-30 deg Standby Earth fault protection (51G) Ie: 0.08-4In T: 0-100 sec 3 50/51 Numerical 50N/51N protection relay (LV side of GT) MICOM P111L IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1 Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec Recommended Setting 49 Hz Remarks
51
Hz
deg
0.3 * In 0.3
Sec
0.9 * In 0.1
Sec
6 * In 0
Sec
RELAY SETTING CHART- 33KV SWITCHYARD RELAY Sr.No Protection Description Type ref. 33KV Transformer Control and Relay Panel Setting Range IDMT Earth fault protection (51N) Ie: 0.08-4In TMS: 0.1-1 Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec 4 27, 59 59D Numerical protection relay MICOM P921 Under voltage protection (27) U<: 10-120V T: 0-100 sec Over voltage protection (59) U>: 60-185V T: 0-100 sec Neutral displacement protection (59DLV) V: 5.4 -20V TMS NOTE: a) All settings are referred with respect to secondary values. b) All the other functions which are not mentioned in this chart shall be disabled. Recommended Setting 0.2 * In 0.3 Remarks IDMT curve (3 sec) Sec
0.3 * In 0.3
Sec
0.8 0.5
sec
1.1 0.5
sec
5.4 0.1
V sec
CLIENT
CONSULTANT
PROJECT
IKE ELECTRIC PVT. LTD. 601 - 602, MARIEGOLD NECO GARDENS, VIMAN NAGAR, PUNE - 411 014 MAHARASHTRA INDIA PHONE - 020 - 66290300 / 301 TELEFAX - 020 - 66290302
IKE-ISGEC-KWL61-DOC-133 00 11.10.2013
PREPARED BY ARD
CHECKED BY KBD
APPROVED BY ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Sr.No Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel I 1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT) Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 Idiff>=2.5-30 Iref Idiff>>>=2.5-30 Iref m1: 0.15-1.5 m1: 0.2 m2: 0.15-1.5 m2: 0.7 IR, m2 (1.5-10.0 Iref) 4 Op.del, trip signal:0-100S Restricted earthfault protection(64R) Effective setting: 10% High Impedance relay Stabilising resistor (0-1000) Ohm 2 50/51 50N/51N 67/67N, 50LBB 78, 27Z, 59, 81 60, 81R, 99, 27 Numerical Interconnection Protection Relay MICOM P341 Overcurrent protection (51) In: 0.08-4In T: 0-100 sec Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec Earth fault protection (51N) Ie: 0.08-4In T: 0-100 sec Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
Remarks
0.75*In 0.1
6*In 0
sec (Inst)
0.2*In 0.1
Sec
0.3*In 0.5
sec
Sr.No
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel Dir. Overcurrent protection (67) In: 0.08-32In 0.75*In T: 0-100 sec 0.35 sec Dir. Earth fault protection (67N) Ie: 0.08-32In T: 0-100 sec Under volatge protection (27) U<: 10-120V T: 0-100 sec Over voltage protection (59) U>: 60-185V T: 0-100 sec Under frequency protection (81U) f<: 45-65Hz T: 0-100 sec Over frequency protection (81O) f>: 45-65Hz T: 0-100 sec Local Breaker back-up protection (50LBB) In: 0.4-4*In Time delay df/dt protection (81R) df/dt: 0.1-10Hz/sec T: 0-100 sec
0.1*In 0.35
80 2
V sec
121 3
V sec
47.7 2
Hz sec
PTR: 132KV/110V
52 2
Hz sec
1*In 0.3
4 Inst
Hz/ sec
Sr.No
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel Dead band lower frequency 45-65Hz 49 Hz Dead band upper frequency 45-65Hz Voltage Balance Relay (60) *** *** Overfluxing Protection Relay (99) *** *** Vector surge protection (78) dv/dt: 2-30 deg Standby Earth fault protection (51G) Ie: 0.08-4In T: 0-100 sec
Remarks
51
Hz
deg
0.3 * In 0.3
Sec
MICOM P111L IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1 Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec
0.7 * In 0.1
Sec
6 * In 0
Sec
Sr.No
RELAY SETTING CHART- 132KV SWITCHYARD RELAY Recommended Setting Protection Description Type ref. Setting Range 132KV Transformer Control and Relay Panel IDMT Earth fault protection (51N) Ie: 0.08-4In 0.2 * In TMS: 0.1-1 0.3 Sec Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.3 * In 0.3
Sec
MICOM P127
IDMT overcurrent protection (51) In: 0.08-4In TMS: 0.025-1 Inst. Overcurrent protection (50) In: 0.08-32In T: 0-100 sec IDMT Earth fault protection (51N) Ie: 0.08-4In TMS: 0.1-1 Inst.Earth fault protection (50N) Ie: 0.08-4In T: 0-100 sec
0.7 * In 0.1
Sec
6 * In 0
Sec
0.2 * In 0.3
0.3 * In 0.3
Sec
27, 59 59D
MICOM P921
Under voltage protection (27) U<: 10-120V T: 0-100 sec Over voltage protection (59) U>: 60-185V T: 0-100 sec Neutral displacement protection (59DLV) V: 5.4 -20V TMS
0.8 0.5
sec
1.1 0.5
sec
5.4 0.1
V sec
NOTE: a) All settings are referred with respect to secondary values. b) All the other functions which are not mentioned in this chart shall be disabled.