Incoming A 0.4kV
Incoming B 0.4kV
Bus Coupler
Incoming A
Incoming B
Involving Brief Parallel Operation Fault level rising Not used in the normal course In case of an emergency
Incoming A
Incoming B
Fast Changeover
Slow Changeover
Not fault level rising Decay of residual voltage of motors connected to the bus to sufficiently (about 20 per cent of the rated voltage) Starting current inrush, heavy voltage drop Pre-selected number of non-essential auxiliary motors (less than 15% drop voltage )
Fast Changeover
Before residual motor voltage vector has fallen Motor speed dropped down only marginally Only a small rise of current Phase Comparison Relay
Under Fault Condition (Voltage Drop) Automatic Changeover with Voltage Interruption
ATS
The reduction of the voltage below a preselected value and after a pre selected time period the affected incoming breaker will trip. After the breaker has disconnected the main the bus-tie breaker will close. This operation will not take place if the incomer was tripped by any future protection device.
Transfer Scheme
Local
Transfer Scheme
1
Open
Transfer Scheme
ATS Remote
Close
Local
Bus Coupler
I
3 0.4kV 0.4kV
3 S.S 27R
3 S.S 27R
Normal Operation
Incoming A 0.4kV
Incoming B 0.4kV
Initial Conditions
2 1
Open or No Service
4 3 6
In Service TCS Close Service No 27i
0.4kV
0.4kV
27R
B
Panel Ready Common Fault 50,51
Initial Conditions
4 3
Close Service No 27i
2 1 6
In Service TCS Open or No Service
0.4kV
0.4kV
A
27R
Panel Ready Common Fault 50,51
B
5
Start
Stop
Closing Coil
Initial Conditions
Incoming A Open or No Service Relay not operated Incoming B Close & Service & Relay not operated 27i not operated Service Position TCS Relay
Local
&
Close PB
ATS
&
&
Selector Switch
Closing Coil
Remote
Busbar A (27R)
Close Command
&
Opening
Opening-Local
+
OFF
Shunt Trip
Opening-Trip
2
Both Incomings are Open or Closed Or no in Service. Incoming A 0.4kV Incoming B 0.4kV
Opening-Remote
+
Remote
Shunt Trip
Signal Lamp
+
TCS