Integration in the different system types Air renewal and electronic filtration Active thermodynamic recovery Substantial system simplification
H10
Equivalent filtration efficiency
COP 7,6
at outdoor temperature of 5C
-50%
Primary energy
ZEPHIR2
The reversible heat pump that renews and purifies the air recovers energy from the exhaust air, simplifies the system and reduces its consumption, increasing overall efficiency.
Packaged heating pump for air renewal with active thermodynamic energy recovery. 100% outdoor air operation.
AUTOMATICALLY RENEWS THE AIR It extracts the used air from the rooms and introduces
C C
purified and conditioned renewal air. The optional electronic filters act as a highly efficient electrostatic purifier, without increasing ventilation consumption caused by the pressure drops of traditional filters.
RECOVERS ENERGY ALL YEAR ROUND The active thermodynamic circuit recovers the energy contained in the exhaust air all year round, multiplying it thanks to the heat pump technology and supplying it to the serviced environment, without the great drops in pressure as traditional recovery units, which offsets any gains from the recovered energy . This reduces the air renewal load and supplies additional capacity to the environment. SIMPLIFIES THE SYSTEM The energy generated by the thermodynamic recovery unit makes it possible to reduce the power and therefore the associated cost of the air conditioning system. INCREASES OVERALL EFFICIENCY The innovative thermodynamic cycle, the fans with
electronically controlled flow rate and the cooling circuit with high annual efficiency reduce the system's energy consumption, with benefits for the entire building.
ENERGY
RECOVERY
ENERGY
TWO VERSIONS MADE TO MEASURE FOR COMFORT AND BUSINESS The ENERGY
EXTRAPOWER
version has 30% more capacity than the RECOVERY version with an equal flow rate. The EXTRAPOWER option additionally increases the dehumidification capacity and extends the application range.
Technical data
Sizes Nominal air flow Dimensions (length x depth x height) CPAN-XHE ENERGY Total cooling capacity Sensible cooling capacity EER in reference to the compressors Heating capacity COP in reference to the compressors CPAN-XHE RECOVERY Total cooling capacity Sensible cooling capacity EER in reference to the compressors Heating capacity COP in reference to the compressors
Data in reference to the following conditions: (1) Exhaust air temperature 27C d.b. / 19C W.B.. - - Outdoor air temperature 35C d.b. / 24C W.B. (2) Exhaust air temperature 20C d.b. / 14C W.B... - Outdoor air temperature 7C d.b. / 6C W.B.. (1) (1) (1) (2) (2) kW kW kW (1) (1) (1) (2) (2) kW kW kW m3/h mm
45 4.500
52 5.200
60 6.000
70 7.000
90 9.000
110 11.000
130 13.000
160 16.000
2.917 x 1.891 x 884 32 21 3,57 35,4 5,28 20,8 15,1 4,86 22,1 5,94 36,4 24,4 3,46 40,6 5,19 24,4 17,3 4,49 26,4 6,02
2.917 x 1.844 x 1.234 44,1 29 3,49 50,4 5,50 32,9 22,6 3,89 37,0 5,47 51,5 34,4 3,68 58,2 5,36 37,8 25,6 3,86 42,6 5,36
2.917 x 2.244 x 1.234 61,5 41,8 3,64 70,5 5,78 48 32,9 4,24 52,3 5,61 73,9 44,7 3,97 82,5 5,78 55,5 38 4,24 61,5 5,57
2.917 x 2.244 x 1.634 89,7 60,8 4,02 98,8 6,00 65,7 44,5 4,41 72,4 5,65 106,1 72,3 4,46 112,7 6,20 77,1 52,3 4,38 84,6 5,57
CLIVET S.p.A. Via Camp Lonc 25 32032 Z.I. Villapaiera Feltre BL Tel. + 39 0439 3131 Fax. + 39 0439 313382 info@clivet.it
The data in this document is not binding and can be modified by the manufacturer without prior notice. Reproduction, even partial, is prohibited .
DF10A001GB00
CPAN-XHE 45 - 160