Anda di halaman 1dari 6

Solid-state Twin Timers

H3CR-F
DIN 48 48-mm Twin Timers
Wide power supply ranges of 100 to 240 VAC and 48 to 125 VDC respectively. ON- and OFF-times can be set independently and so combinations of long ON- or OFF-time and short OFF- or ON-time settings are possible. Fourteen time ranges from 0.05 s to 30 h or from 1.2 s to 300 h depending on the model to be used. Models with a flicker ON start or flicker OFF start are available. Easy sequence checks through instantaneous outputs for a zero set value at any time range. Length, when panel-mounted with a Socket, of 80 mm or less. 11-pin and 8-pin models are available.

Model Number Structure


Model Number Legend
H3CR - F @ @ - @ @
1 2 3 4 5

1. Classification F: Twin timers 2. Configuration None: 11-pin socket 8: 8-pin socket

3. Twin Timer Mode None: Flicker OFF start N: Flicker ON start 4. Time Range None: 0.05 s to 30 h models 300: 1.2 s to 300 h models

5. Supply Voltage 100-240AC: 100 to 240 VAC 24AC/DC: 24 VAC/VDC 12DC: 12 VDC 48-125DC: 48 to 125 VDC

Ordering Information
List of Models
Operating modes Flicker OFF start Supply voltage 100 to 240 VAC 24 VAC/DC 12 VDC 48 to 125 VDC Flicker ON start 100 to 240 VAC 24 VAC/DC 12 VDC 48 to 125 VDC 0.05 s to 30 h models 11-pin models H3CR-F 100-240AC H3CR-F 24AC/DC H3CR-F 12DC H3CR-F 48-125DC H3CR-FN 100-240AC H3CR-FN 24AC/DC H3CR-FN 12DC H3CR-FN 48-125DC 8-pin models H3CR-F8 100-240AC H3CR-F8 24AC/DC H3CR-F8 12DC H3CR-F8 48-125DC H3CR-F8N 100-240AC H3CR-F8N 24AC/DC H3CR-F8N 12DC H3CR-F8N 48-125DC 1.2 s to 300 h models 11-pin models H3CR-F-300 100-240AC H3CR-F-300 24AC/DC H3CR-F-300 12DC H3CR-F-300 48-125DC H3CR-FN-300 100-240AC H3CR-FN-300 24AC/DC H3CR-FN-300 12DC H3CR-FN-300 48-125DC 8-pin models H3CR-F8-300 100-240AC H3CR-F8-300 24AC/DC H3CR-F8-300 12DC H3CR-F8-300 48-125DC H3CR-F8N-300 100-240AC H3CR-F8N-300 24AC/DC H3CR-F8N-300 12DC H3CR-F8N-300 48-125DC

Note: Specify both the model number and supply voltage when ordering. Example: H3CR-F 100-240AC Supply voltage

24

Solid-state Twin Timers H3CR-F

Accessories (Order Separately)


Name/specifications Flush Mounting Adapter Y92F-30 Y92F-73 Y92F-74 Mounting Track 50 cm (l) 7.3 mm (t) 1 m (l) 7.3 mm (t) 1 m (l) 16 mm (t) End Plate Spacer Protective Cover Track Mounting/ Front Connecting Socket 8-pin 8-pin, finger safe type 11-pin 11-pin, finger safe type Back Connecting Socket 8-pin 8-pin, finger safe type 11-pin 11-pin, finger safe type Hold-down Clip (See note 2) For PL08 and PL11 Sockets For PF085A Socket PFP-50N PFP-100N PFP-100N2 PFP-M PFP-S Y92A-48B P2CF-08 P2CF-08-E P2CF-11 P2CF-11-E P3G-08 P3G-08 with Y92A-48G (See note 1) P3GA-11 P3GA-11 with Y92A-48G (See note 1) Y92H-7 Y92H-8 Models

Note: 1. Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket. 2. Hold-down Clips are sold in sets of two.

Specifications
General
Item Operating mode Pin type Operating/Reset method Output type Mounting method Approved standards 11-pin Relay output (DPDT) DIN track mounting, surface mounting, and flush mounting UL508, CSA C22.2 No.14, NK, Lloyds Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2. Output category according to EN60947-5-1. H3CR-F Flicker OFF start 8-pin Time-limit operation/Time-limit reset or self-reset H3CR-F8 11-pin H3CR-FN Flicker ON start 8-pin H3CR-F8N

Time Ranges
0.05 s to 30 h Models
Time unit Setting 1.2 3 12 30 0.05 to 1.2 0.3 to 3 1.2 to 12 3 to 30 s (sec) 3 to 30 12 to 120 30 to 300

10 s (10 s)
1.2 to 12 0.3 to 3 1.2 to 12 3 to 30

min (min) 0.12 to 1.2

h (hrs)

Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.

1.2 s to 300 h Models


Time unit Setting 1.2 3 12 30 3 to 30 12 to 120 30 to 300

10 s (10 s)
1.2 to 12

10 min (10 min)


1.2 to 12 3 to 30 12 to 120 30 to 300 0.3 to 3 1.2 to 12 3 to 30

h (hrs) 0.12 to 1.2 3 to 30

10 h (10 h)
1.2 to 12 12 to 120 30 to 300

Note: Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.

Solid-state Twin Timers

H3CR-F

25

Ratings
Rated supply voltage (See notes 1, 2, and 3.) 100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC Operating voltage range Power reset Power consumption 85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models Minimum power-opening time: 0.1 s 100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC 24 VAC/VDC: approx. 2 VA (1.7 W) at 24 VAC approx. 1 W at 24 VDC 48 to 125 VDC: approx. 1.5 W at 125 VDC 12 VDC: approx. 1 W at 12 VDC Contact output: 5 A at 250 VAC/30 VDC, resistive load (cos = 1)

Control outputs

Note: 1. A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model. 2. Do not use an inverter output as the power supply. Refer to Power Supplies in Safety Precautions for All Timers on page 51 for details. 3. Refer to Power Supplies in Safety Precautions for All Timers on page 51 when using the Timer together with a 2-wire AC proximity sensor.

Characteristics
Accuracy of operating time Setting error Reset time Reset voltage Influence of voltage Insulation resistance Dielectric strength

0.2% FS max. (0.2% FS 10 ms max. in ranges of 1.2 and 3 s) 5% FS 50 ms max.


0.1 s max. 10% max. of rated voltage

0.2% FS max. (0.2% FS 10 ms max. in ranges of 1.2 and 3 s)


100 M min. (at 500 VDC) 2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts) 2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit) 2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities) 1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other) 3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC 1 kV for 12 VDC, 24 VAC/DC 4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC, 48 to 125 VDC 1.5 kV for 12 VDC, 24 VAC/DC

Influence of temperature 1% FS max. (1% FS 10 ms max. in ranges of 1.2 and 3s)

Impulse withstand voltage

Noise immunity Static immunity Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy EMC

1.5 kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 s, 1-ns rise) 400 V for 12 VDC
Malfunction: 8 kV Destruction: 15 kV Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions Destruction: 980 m/s2 three times each in six directions Malfunction: 98 m/s2 three times each in six directions Operating: Storage: Operating:

10C to 55C (with no icing) 25C to 65C (with no icing)


35% to 85%

Mechanical: 20 million operations min. (under no load at 1,800 operations/h) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note) (EMI) Emission Enclosure: Emission AC Mains: (EMS) Immunity ESD: EN61812-1 EN55011 Group 1 class A EN55011 Group 1 class A EN61812-1 IEC61000-4-2:

6 kV contact discharge (level 3) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (9005 MHz) (level 3) Immunity Conducted Disturbance: IEC61000-4-6: 10 V (0.15 to 80 MHz) (level 3) Immunity Burst: IEC61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Immunity Surge: IEC61000-4-5: 1 kV line to line (level 3) 2 kV line to ground (level 3) Case color Degree of protection Weight Light Gray (Munsell 5Y7/1) IP40 (panel surface) Approx. 100 g

Note: Refer to the Life-test Curve.

26

Solid-state Twin Timers H3CR-F

Life-test Curve
10,000

Switching operations (x 103)

5,000

1,000 500 30 VDC L/R = 7 ms 250 VAC/30 VDC (cos = 1)

Reference: A maximum current of 0.15 A can be switched at 125 VDC (cos = 1) and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5 VDC (failure level: P).

100 250 VAC (cos = 0.4)

Load current (A)

Connections
Block Diagrams
ON indicator OFF indicator Zero setting detection circuit

Indicator circuit ROM RAM Clock Output circuit

AC (DC) input

Power supply circuit

One-chip microcomputer

Time range/unit selectors

I/O Functions
Inputs Outputs Control output --Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.

Terminal Arrangement
H3CR-F8 H3CR-F8 NH3CR-F8-300 H3CR-F8N-300 H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300

(+)(~)

Power supply

Power supply Note: Leave terminals 5, 6, and 7 open. Do not use them as relay terminals.

Solid-state Twin Timers

H3CR-F

27

Operation
Timing Chart
tON: ON set time tOFF: OFF set time Operating mode Flicker OFF start
Power ON OFF

Timing chart
0.1 s min.

tOFF

tON

tOFF

tON

tOFF

tOFF

Lit ON indicator Not lit OFF Lit indicator Not lit Output NO

ON OFF ON OFF
0.1 s min.

Output NC

Flicker ON start
Power ON OFF

tON

tOFF

tON

tOFF

tON

tOFF

Lit ON indicator Not lit Lit OFF indicator Not lit Output NO ON OFF ON OFF

Output NC

Note: 1. The reset time requires a minimum of 0.1 s. 2. When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance of the Timer.

Nomenclature
OFF indicator (green) Lit when the output is OFF. ON indicator (orange) Lit when the output is ON. OFF-time unit display window OFF-time unit selector (select one from sec. 10 s, min., and hrs, or from 10 s, 10 min, hrs, and 10 h)

Scale range display windows

ON-time setting knob (with orange pointer) For ON-time setting OFF-time setting knob (with green pointer) For OFF-time setting

Time range selector (select one from 1.2, 3, 12, and 30 at full scale) For both ON-time and OFF-time.

ON-time unit display window ON-time unit selector (select one from sec, 10 s, min, and hrs, or from 10 s, 10 min, hrs, and 10 h)

28

Solid-state Twin Timers H3CR-F

Dimensions
Note: All units are in millimeters unless otherwise indicated.

H3CR-F H3CR-FN H3CR-F-300 H3CR-FN-300


48

48

17.4 5.7 6

66.6 52.3

0.7

37 dia. 14 dia.

44.8 44.8

R1.3 11 pins

H3CR-F8 H3CR-F8N H3CR-F8-300 H3CR-F8N-300


48

48

17.4 5.7 6

66.6 52.3

0.7

37 dia. 14 dia.

44.8 44.8

R1.3 8 pins

Dimensions with Front Connecting Socket P2CF-08-@/P2CF-11-@

Dimensions with Back Connecting Socket P3G-08/P3GA-11


17.4 81.5 80 81.5 75

17.4

H3CR-F H3CR-FN 103.2* 100.9 92.3*

H3CR-F8 H3CR-F8N 90.0

H3CR-F H3CR-FN

H3CR-F8 H3CR-F8N

Y92F-30 P2CF-11 P2CF-11-E


2.3*

P2CF-08 P2CF-08-E

2.3*

P3GA-11 (When Y92A-48G mounted)

Y92F-30

P3G-08 (When Y92A-48G mounted)

*These dimensions vary with the kind of DIN track (reference value).

Solid-state Twin Timers

H3CR-F

29

Anda mungkin juga menyukai