Anda di halaman 1dari 4

HSA

Multicontact Auxiliary

Multi-contact hand reset relay to perform auxiliary functions on AC and

Features and Benefits


I I I I

Protection and Control


I

Electrically separate contact outputs Universal target dropping Mechanical target High seismic capability

Trip and/or block close circuit breaker control

Applications
I

Contact multiplication

GE Multilin

HSA Multicontact Auxiliary

Application
The HSA high-speed multicontact, auxiliary relays are applicable where it is desired that a number of operations be performed simultaneously from the operation of a single relay. Typical functions that can be performed by these relays are:
1. Trip and lock out the main circuit breaker of a system. 2. Trip station auxiliary breakers. 3. Trip main or auxiliary field breakers. 4. Trip and lock out all breakers on a bus.

Perhaps the most important use of the HSA relay is as an auxiliary used in conjunction with differential relays for bus, transformer, line or rotating machine protection.

latch which is especially constructed to resist shock and vibration. The latch is released through the action of a plunger device actuated by the relay operating coil. All HSA relays are made so that they should not normally be tripped manually; however, manual tripping can be accomplished through use of an escutcheon knockout (and predrilled hole in panel) which provides access to a screwdriveroperated tripping device. The time required to trip the relay, from the instant of energization of the coil to the closing of the contacts, is per HSA Relay Operating Characteristics (Figures 3 & 4), slightly less for opening of contacts.

Seismic Capability
The seismic capability of HSA N.O. (Normally Open) and N.C. (Normally Closed) contacts are given in Table 2.
Table 2. HSA seismic capability

Seismic Capability (gs ZPA) HSA Reset HSA Tripped


N.O. 6.0 N.C. 4.0 N.O. 6.0 N.C. 6.0

Service Temperature The HSA will operate over an ambient temperature range of 20C to +55C and will not be damaged by storage ambients of -40C to +65C.
Fig. 2. HSA11 Relay Contacts

Target Dropping
Universal targets in series with HSA trip coils increase HSA trip time. A typical increase in trip time for a single 0.2 A target and an HSA with a 125 VDC trip coil is 1.3 ms. Table 1 shows the maximum number and type of universal targets that can be dropped by the current pulse of HSA trip coils.
Table 1. Target dropping

Construction
The HSA multi-contact, auxiliary relays are built with many parts common to the SBM control switches. The mechanical target on the escutcheon plate assembly indicates the position of the relay. The black target indicates the reset position and the orange target, the tripped position. To reset the relay after it has been tripped, the handle is turned clockwise as indicated by the arrow on the escutcheon plate. Since the HSA relay is similar to the SBM switch, it is available with a shaft long enough to allow it to be mounted on panels with thickness up to 1/4 inch.

Number of Parallel HSA Coil Targets Dropped Coil Voltage Group 0.2 A 0.6 A 2.0 A
1 2 2 3 3 48 VDC 110 VDC 125 VDC 220 VDC 250 VDC 6 6 6 6 6 6 6 6 3 4 3 2 2 1 1

Dielectric Capability
HSA relays are rated 60 0 V in accordance with the Dielectric Test Section of Relay Standard ANSI/IEEE C37.90-1978.

Operation
The HSA relay is available with 9, 13 or 19 main electrically separate contacts. In addition, there are 2 normally closed contacts that are wired for opening the operating coil circuit. See Figure 2. The operating shaft is held in reset position by a positive roller

NOTE: A minimum of two parallel 0.2 A targets is recommended to assure tripping of 48 VDC HSA relays.

Trip Coil Ratings


The three trip coils available for HSA relays have multiple voltage ratings as shown in Table 3. To obtain maximum tripping speed, the coils are rated for intermittent duty only.

www.GEindustrial.com/Multilin

HSA Multicontact Auxiliary

Table 3. Trip coil voltage ratings

Contact Ratings
Operating Range (V)
32-55 70-145 70-145 140-290 140-290 45-80 70-140 70-140 140-280 140-280

Intermittent Rating (V)


48 110 125 220 250 69 110 120 220 240

Frequency (Hz)
DC DC DC DC DC 50/60 50/60 50/60 50/60 50/60

Coil Group
1 2 2 3 3 1 2 2 3 3

The current-closing ratings of the contacts is 30 A for voltages not exceeding 60 0 V. The contacts have a current carrying capacity of 20 A continuously. The interrupting ability of the contacts varies with the inductance of the circuit. The values (in amperes) given in Table 4 for DC inductive circuits are based on the average trip coil.
Table 4. Contact interrupting ratings

CAUTION: Do not hold the reset handle in the reset position if the HSA will not reset. Failure to reset indicates that the trip coil is energized. Holding the reset handle in the reset position with the trip coil energized at rated voltage will cause rapid coil heating and possible insulation damage.
Fig. 3. Operating characteristics, 8- and 11-stage HSA relays

Amps Amps Inductive (L/R- .04) Circuit Non-inductive Volts Single Two in Single Two in Contact Series Contact Series
48 DC 125 DC 250 DC 120 AC 240 AC 10 5 1.5 50 50 50 22 4 50 50 6 4 1.4 50 25 30 13 3.5 50 50

Burdens
The burdens for the HSA relays are given in Table 5 and Table 6.
Table 5. DC burden data for HSA relays

DC Inrush Coil Volts Coil Resistance ( at Current Group 25C 10%) (A)
1 2 2 3 3 48 110 125 220 250 2.85 11.8 11.8 47.5 47.5 17 12 13 5 5.5

Fig. 4. Operating characteristics, 6-stage HSA relays

Table 6. AC Burdens

Coil Group Volts Frequency


1 2 2 3 3 1 2 2 3 3 69 110 120 220 240 69 110 120 220 240 60 60 60 60 60 50 50 50 50 50

Z ()
10 11 11 45 45 10 11 11 45 45

Voltage Lead Angle


30 29 29 28 28 27 24 24 23 23

www.GEindustrial.com/Multilin

HSA Multicontact Auxiliary

Selection Guide
Approx. Wt. in Contact lbs (kg) Contact Contact Option 48VDC 110/125VDC 220/250DC Numbers Numbers 69VAC 110/120VAC 220/240AC Norm. Norm. 50/60HzAC 50/60HzAC 50/60HzAC Closed Open Net Ship 9 CONTACT (Plus 2 Contacts in Coil Circuit) Group
A A A A A A A A A A B B B B B B B B B B B B B B C C C C C C C C C C C C C C C C C C C C 100 101 102 103 104 105 106 107 108 109 200 201 202 203 204 205 206 207 208 209 210 211 212 213 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 110 111 112 113 114 115 116 117 118 119 220 221 222 223 224 225 226 227 228 229 230 231 232 233 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 120 121 122 123 124 125 126 127 128 129 240 241 242 243 244 245 246 247 248 249 250 251 252 253 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 None 4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 None 4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 4-13 4-14 4-15 4-16 None 4 4-5 4-6 4-7 4-8 4-9 4-10 4-11 4-12 4-13 4-14 4-15 4-16 4-17 4-18 4-19 4-20 4-21 4-22 4-12 5-12 6-12 7-12 8-12 9-12 10-12 11-12 12 None 4-16 5-16 6-16 7-16 8-16 9-16 10-16 11-16 12-16 13-16 14-16 15-16 16 None 4-22 5-22 6-22 7-22 8-22 9-22 10-22 11-22 12-22 13-22 14-22 15-22 16-22 17-22 18-22 19-22 20-22 21-22 22 None

Order Code Breakdown


Contact Arrangement
1) Choose the required number of contacts and their action (N.O. and N.C.) 2) Choose the operating voltage of the HSA.

HSA11 * *** *
A B C XXX X
9 contacts (plus 2 contacts in coil circuit) 13 contacts (plus 2 contacts in coil circuit) 19 contacts (plus 2 contacts in coil circuit) Electrical data (see Group column under Selection guide) Enter the panel thickness in inches

3.1 5 (1.4) (2.3)

13 CONTACT (Plus 2 Contacts in Coil Circuit)

3.5 5.4 (1.6) (2.4)

19 CONTACT (Plus 2 Contacts in Coil Circuit)

6 4 (1.8) (2.7)

Order online save time


www.GEindustrial.com/pm

www.GEindustrial.com/Multilin

Anda mungkin juga menyukai