Tesisat Kablolar

Building Wires

H05V-K
H07V-K

300/500 V
450/750 V

Protodur Yaltkanl Harmonize letkenler


Protodur Insulated Harmonized Wires

TS 9758 HD 21.3 S3/VDE 0281-3


TS 9758 HD 21.3 S3/VDE 0281-3

PROTODUR
Yap / Construction

1
1- nce ok telli bakr iletken
Fine stranded copper conductor

nce ok telli, bakr iletkenli PROTODUR yaltkanl bklgen


kablolar.
PROTODUR insulated flexible wires with fine stranded copper conductors.

2- PROTODUR yaltkan
PROTODUR insulation

Teknik Bilgiler / Technical Data


Bu kablolar yukarda belirtilen standartlara gre tek damarl
olarak retilirler.
- zin verilen iletme scakl: 70 C
These cables are produced according to above standards as single core.
- Permissible operating temperature: 70 C

2
Kullanld Yerler / Applications
Pano ve elektrikli cihazlarn i tesisatlarnda, sva altnda veya
sva stnde boru iinde kullanlrlar.
Used in control panels and electrical equipments, on and under plaster
as laid in conduit.

Maksimum
letme Scakl
Maximum
Operating
Temperature

Ksa Devre
Scakl
Maximum
Short Circuit
Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Bklgen
Flexible

Kullanld Yerler / Applications

24

Serim Scakl
Installation
Temperature
Min 5 oC

Tesisat
Internal Wiring

Dahili Sva
Alt/st Boru
inde
Indoor Under
Plaster in Conduit

Datm Panolar
Distribution Panels

Kurunsuz
Lead Free

Test Gerilimi
(AC)
Test Voltage (AC)
(2 kV- 2,5 kV)

RoHS
Compliance

Teknik zellikler / Technical Features


H05V-K / H07V-K
Nominal Kesit

Bakr Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

mm

mm

kg/km

/km

Akm Tama Kapasitesi


Boru inde
Havada
Current Carrying Capacity in
Conduit

Air

4,8
7,2
9,6

2,0
2,2
2,4

8,5
12
13

39,0
23,0
19,5

14,4
24,0
38,0
58,0
96,0
154,0
240,0
336,0
480,0
672,0
912,0
1152,0
1440,0
1776,0
2304,0

2,8
3,4
3,9
4,4
6,1
7,4
9,0
10,9
12,7
14,7
16,9
18,8
21,0
23,3
26,6

19
30
44
63
112
169
251
369
528
730
969
1212
1521
1857
2443

13,3
7,98
4,95
3,3
1,91
1,21
0,78
0,544
0,386
0,272
0,206
0,161
0,129
0,106
0,080

12
15
19

100
100
100

450/750 V

H07V-K
1,5
2,5
4
6
10
16
25
35
50
70
95
120
150
185
240

Delivery Length
(Approx.)

300/500 V

H05V-K
0,5
0,75
1

Sevk Uzunluu
(Yaklak)

14,5*
19,5
26
34
46
61
80
99
119
151
182
210
240
273
320

24
32
42
54
73
98
129
158
198
245
292
344
391
448
528

100
100
100
100
100
100
100
1000
1000
1000
1000
1000
1000
1000
1000

* DIN VDE 0298-4 Tablo 3/2de 15,5 A olarak verilmitir.


Given as 15,5 A in DIN VDE 0298-4 Table 3/2.

NOT :

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

25

Alak Gerilim Kablolar


Low Voltage Cables

Y Tipi Protodur Yaltkanl Enerji Kablolar


Y Type Protodur Insulated Power Cables

YVV
NYY
YY

PROTODUR

0,6/1 kV
0,6/1 kV
0,6/1 kV

TS IEC 60502-1
VDE 0276-603
IEC 60502-1

Yap / Construction

1
2

1- Bakr iletken
Copper conductor

Bir veya ok telli, bakr iletkenli bir veya ok damarl, PROTODUR

yaltkanl, PROTODUR d klfl enerji kablolar.

Single or multi core energy cables with solid or stranded copper conductor,

PROTODUR insulation and PROTODUR outer sheath.

2- PROTODUR yaltkan

PROTODUR insulation
3- Dolgu
Filler

Teknik Bilgiler / Technical Data

4- PROTODUR d klf

PROTODUR outer sheath

Bu kablolar TS IEC 60502-1, IEC 60502-1 ve VDE 0276-603e


gre retilirler.
- zin verilen iletme scakl: 70 C
- zin verilen ksa devre scakl: 160 C
(Ksa devre zaman t< 5 sn. iin)
These cables are produced according to TS IEC 60502-1, IEC 60502-1 and
VDE 0276-603
- Permissible operating temperature: 70 C
- Permissible short-circuit temperature: 160 C
(for short circuit duration up to 5 sec.)

Kullanld Yerler / Applications


Enerji, ebeke ve aydnlatma kablosu olarak akta, kablo
kanallarnda, toprak altnda, zel olarak imal edildii takdirde
tatl ve tuzlu suda kullanlrlar.
Used outside as energy, utility and lighting cables, in cable ducts, under
ground, under normal and salty water if specially produced.

Maksimum
letme Scakl
Maximum
Operating
Temperature

Ksa Devre
Scakl
Maximum
Short Circuit
Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Rijit
Rigid

Kurunsuz
Lead Free

Test Gerilimi (AC)


Test Voltage (AC)
(3,5 kV)

Beton inde
In Concrete

Boru inde
In Conduit

Tatl/Tuzlu Suda (*)


Normal and Salty
Water (*)

Kullanld Yerler / Applications

36

Serim Scakl
Installation
Temperature
Min 5 oC

Akta
In Free Air

Toprak Altnda
Direct Buried

(*) zel olarak imal edildii takdirde tatl ve tuzlu suda kullanlr.
(*) Can be used in normal or salty water if specially produced.

RoHS
Compliance

Teknik zellikler / Technical Features


YVV / NYY / YY

0,6/1 kV

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20

mm

kg/km

mm

/km

Akm Tama Kapasitesi


Toprakta
Havada
Current carrying capacity in
Ground

Sevk Uzunluu
(Yaklak)
Delivery Length
(Approx.)

Air

59
73
97
125
161
192
227
278
332
377
423
478
555

50
62
83
107
138
164
195
238
286
325
365
413
479

45
59
81
110
146
181
219
281
341
396
456
521
615

33
43
60
82
110
137
167
216
264
308
356
409
485

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

1 Damarl / 1 Core
1x4
1x6
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240

38
58
96
154
240
336
480
672
912
1152
1440
1776
2304

6,8
7,3
8,1
9,0
10,9
12,2
13,8
15,4
17,7
19,2
21,1
23,3
26,4

84
106
150
209
322
422
555
756
1035
1273
1559
1936
2525

4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
1,124
0,0991
0,0754

29
48
77
115
192
307
480
672
960

10,1
10,8
12,6
13,0
15,1
16,9
21,2
22,9
25,9

153
186
263
322
441
601
964
1210
1585

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387

32
42
54
68
90
116
150
181
-

22
30
40
51
70
94
119
148
180

1000
1000
1000
1000
1000
1000
1000
1000
1000

43
72
115
173
288
461
720
1008
1440
2016
2736
3456
4320

10,5
11,3
13,2
14,3
16,0
18,0
22,1
24,4
27,7
31,4
36,3
39,5
43,6

172
215
306
386
539
750
1175
1530
2010
2770
3765
4625
5665

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124

27
36
47
59
79
102
133
159
188
232
280
318
359

18,5
25
34
43
60
80
101
126
153
196
238
276
319

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

557
874
1162
1680
2352
3216
4128
4992
6240
8064

20,0
22,9
25,1
29,5
33,1
38,3
42,1
45,5
51,1
57,6

906
1318
1669
2265
3060
4181
5233
6198
7865
10169

1,150
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754

102
133
159
188
232
280
318
359
406
473

80
101
126
153
196
238
276
319
364
430

1000
1000
1000
1000
1000
1000
500
500
500
500

58
96
154
230
384
614
960
1344
1920

11,2
12,2
14,3
15,4
18,7
20,5
24,1
27,1
31,2

199
254
364
461
716
965
1455
1904
2539

12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387

27
36
47
59
79
102
133
159
188

18,5
25
34
43
60
80
101
126
153

1000
1000
1000
1000
1000
1000
1000
1000
1000

2 Damarl / 2 Cores
2x1,5
2x2,5
2x4
2x6
2x10
2x16
2x25
2x35
2x50

3 Damarl / 3 Cores
3x1,5
3x2,5
3x4
3x6
3x10
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150

3 1/2 Damarl / 3

1/
2

3x16/10
3x25/16
3x35/16
3x50/25
3x70/35
3x95/50
3x120/70
3x150/70
3x185/95
3x240/120

Cores

4 Damarl / 4 Cores
4x1,5
4x2,5
4x4
4x6
4x10
4x16
4x25
4x35
4x50
NOT :

Akm tama kapasiteleri toprak scakl 20 C, hava scakl 30 C, 1 Km / W ve 0,7 ykleme derecesi artlarnda geerlidir.
Current carrying capacities are valid at 20 C earth temperature, 30 C free air temperature, 1 Km/W and 0,7 loading (cyclic).

37

Alak Gerilim Kablolar


Low Voltage Cables

Y Tipi Protodur Yaltkanl Kumanda Kablolar


Y Type Protodur Insulated Control Cables

YVV
NYY
YY

PROTODUR

0,6/1 kV
0,6/1 kV
0,6/1 kV

TS IEC 60502-1
VDE 0276-627
IEC 60502-1

Yap / Construction

Bir veya ok telli, bakr iletkenli, ok damarl, PROTODUR

yaltkanl ve PROTODUR d klfl kumanda kablolar.

1- Bakr iletken
Copper conductor

Multi core control cables with solid or stranded copper conductors,

PROTODUR insulation and PROTODUR sheath.

2- PROTODUR yaltkan

PROTODUR insulation

Teknik Bilgiler / Technical Data

3- Dolgu
Filler

4- PROTODUR d klf

PROTODUR outer sheath

Bu kablolar, TS IEC 60502-1, IEC 60502-1 ve VDE 0276-627ye


gre retilirler.
- zin verilen iletme scakl: 70 C
- zin verilen ksa devre scakl: 160 C
(Ksa devre zaman t <5 sn. iin)
These cables are produced according to TS IEC 60502-1, IEC 60502-1 and
VDE 0276-627
- Permissible operating temperature: 70 C
- Permissible short-circuit temperature: 160 C
(for short circuit duration up to 5 sec.)

4
Kullanld Yerler / Applications
Kumanda kablosu olarak dorudan toprak altnda, zel olarak
retildiklerinde tatl su veya tuzlu suda, harite ve dahilde
kullanlrlar. Enerji santrallerinin, tren istasyonlarnn, fabrika,
otel ve hastanelerin kumanda sistemlerinde kullanlrlar.
Damarlarn numaral oluu montajda byk fayda salar.
Used as control cable under ground, under normal and salty water if
specially produced. Also used in the control circuits of power plants, train
stations, factories, hotels and hospitals. It gives an easy installation
because of the numbered cores.

Maksimum
letme Scakl
Maximum
Operating
Temperature

Ksa Devre
Scakl
Maximum
Short Circuit
Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Rijit
Rigid

Kurunsuz
Lead Free

Boru inde
In Conduit

Kumanda
Kablosu
Control Cable

Kullanld Yerler / Applications

38

Serim Scakl
Installation
Temperature
Min 5 oC

Akta
In Free Air

Beton inde
In Concrete

Test Gerilimi (AC)


Test Voltage (AC)
(3,5 kV)

RoHS
Compliance

Teknik zellikler / Technical Features


YVV / NYY / YY - Kumanda / Control

0,6/1 kV

Nominal Kesit

Bakr Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

mm

5x1,5
7x1,5
10x1,5
12x1,5
14x1,5
19x1,5
21x1,5
24x1,5
30x1,5
40x1,5
5x2,5
7x2,5
10x2,5
12x2,5
14x2,5
19x2,5
21x2,5
24x2,5
30x2,5
40x2,5

72
101
144
173
202
274
305
346
432
576
120
168
240
288
336
456
504
576
720
960

mm

kg/km

12,1
12,9
15,5
15,9
16,6
18,3
19,2
21,2
22,4
25,0
13,1
14,1
17,0
17,5
18,3
20,2
21,2
23,5
24,8
27,9

231
282
392
433
481
604
664
753
886
1121
295
368
514
574
642
815
897
1020
1210
1558

/km

12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

Akm Tama Kapasitesi


Toprakta
Havada

Sevk Uzunluu
(Yaklak)

Current Carrying Capacity in

Delivery Length
(Approx.)

Ground

Air

26,0
15,6
13,1
12,4
11,7
10,4
9,3
9,1
8,5
7,8
34,0
20,0
17,0
16,2
15,3
13,6
12,5
11,9
11,1
10,2

18,6
12,0
10,2
9,7
9,3
8,3
7,9
7,4
6,9
6,5
25,0
16,3
13,8
13,1
12,5
11,3
10,8
10,0
9,4
8,8

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

NOT : Akm tama kapasiteleri toprak scakl 20 C, hava scakl 30 C, 1 Km/W ve 0,70 ykleme derecesi artlarnda geerlidir.
Current carrying capacities are valid at 20 C earth temperature, 30 C free air temperature, 1 Km/W and 0,7 loading (cyclic)

39

AFUMEXTM Kablolar
AFUMEXTM Cables

H07Z1-U
H07Z1-R
H07Z1-K

450/750 V
450/750 V
450/750 V

Alevi letmeyen Halojenden Arndrlm Kablolar


Halogen Free, Flame Retardant, Non-Corrosive Cables

TS HD 21.15 S1
TS HD 21.15 S1
TS HD 21.15 S1

AFUMEXTM
Yap / Construction

1
1- Tek veya ok telli bakr iletken
Solid or stranded copper conductor
2- zel sentetik yaltkan
Special synthetic insulation

Tek telli, ok telli veya ince ok telli bakr iletkenli, zel sentetik
yaltkanl, alevi iletmeyen ve halojenden arndrlm enerji
kablolar.
Flame retardant, halogen free energy cables with solid, stranded or
fine-stranded copper conductor and special synthetic insulation.

Teknik Bilgiler / Technical Data


Bu kablolar TS HD 21.15 S1 esas alnarak retilirler.
-zin verilen iletme scakl: 70 C
Aadaki standartlara uygun olarak test edilirler:
LS (Dk Duman) Testi: IEC 61034-1/2
HF (Halojenden Arndrlmlk) Testi: IEC 60754-1/2
FR (Aleve Dayankllk) Testi: IEC 60332-3-24 Cat.C
These cables are produced based on TS HD 21.15 S1
-Permissible operating temperature: 70 C
Tested according to below standards:
LS (Low Smoke) Test: IEC 61034-1/2
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Retardant) Test: IEC 60332-3-24 Cat.C

Kullanld Yerler / Applications


Kuru mekanlarda, alt tesislerinde, datm sistemlerinde,
iletmelerde aydnlatma ve tesisat kablosu olarak kullanlrlar.
Used in dry places, switchgear rooms, distribution boards, industrial
plants as lighting and building wire.

Maksimum
letme Scakl
Maximum
Operating
Temperature

Ksa Devre
Scakl
Maximum
Short Circuit
Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-3-24
Cat.C

Halojenden
Arndrlm
Halogen Free
IEC 60754-1/2

Dk Duman
Younluu
Low Smoke
Emission
IEC 61034-1/2

Dahili Sva
Alt/st Boru
inde
Indoor Under
Plaster in Conduit

Datm Panolar
Distribution Panels

Kullanld Yerler / Applications

90

Serim Scakl
Installation
Temperature
Min 5 oC

Tesisat
Internal Wiring

Boru inde
In Conduit

Kurunsuz
Lead Free

RoHS
Compliance

Teknik zellikler / Technical Features


H07Z1-U / H07Z1-R / H07Z1-K

450/750 V

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Sath zerinde Akm


Tama Kapasitesi

Sevk Uzunluu
(Yaklak)

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

Operating Carrying
Capacity on Surface

Delivery Length
(Approx.)

mm

kg/km

14,4
24,0
38,0
58,0
96,0

2,7
3,3
3,7
4,2
5,4

21
34
50
71
116

12,10
7,41
4,61
3,08
1,83

24
32
42
54
73

100
100
100
100
100

154,0
240,0
336,0
480,0
672,0

7,0
8,4
9,4
11,0
12,6

181
280
382
542
745

1,150
0,727
0,524
0,387
0,268

98
129
158
198
245

100
100
100
1000
1000

14,4
24,0
38,0
58,0
96,0

2,8
3,4
3,9
4,4
5,8

19
30
44
63
112

13,30
7,98
4,95
3,30
1,91

24
32
42
54
73

100
100
100
100
100

mm

/km

H07Z1-U
1,5
2,5
4
6
10

H07Z1-R
16
25
35
50
70

H07Z1-K
1,5
2,5
4
6
10

NOT :

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

91

AFUMEXTM Kablolar
AFUMEXTM Cables

Alevi letmeyen Halojenden Arndrlm Kablolar


Halogen Free, Flame Retardant, Non-Corrosive Cables

052XZ1-U

300/500 V

TS 9759 HD 21.4 S2 e.

NHXMH

300/500 V

VDE 0250-214 e.

AFUMEXTM
Yap / Construction
Bir veya ok telli bakr iletkenli, zel sentetik yaltkanl, zel
dolgu tabakal, zel sentetik d klfl, alevi iletmeyen, halojenden
arndrlm enerji kablolar.

1
2

1- Bir veya ok telli bakr iletken


Solid or stranded copper conductor

2- zel sentetik yaltkan


Special synthetic insulation
3- zel dolgu
Special filler
4- zel sentetik d klf
Special synthetic outer sheath

Solid or stranded copper conductored, special synthetic insulated, special


synthetic outer sheathed flame retardant, halogen free cables.

Teknik Bilgiler / Technical Data


Bu kablolar TS 9759 HD 21.4 S2 esas alnarak veya VDE 0250-214e
uygun olarak retilirler.
-zin verilen iletme scakl: 90 C
Aadaki standartlara uygun olarak test edilirler:
LS (Dk Duman) Testi: IEC 61034-1/2
HF (Halojenden Arndrlmlk) Testi: IEC 60754-1/2
FR (Aleve Dayankllk ) Testi: IEC 60332-1-2 ve IEC 60332-3-24 Cat.C
These cables are produced based on TS 9759 HD 21.4 S2 or according to
VDE 0250-214
-Permissible operating temperature: 90 C
Tested according to below standards:
LS (Low Smoke) Test: IEC 61034-1/2
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Retardant) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C

Kullanld Yerler / Applications


Oteller, hastaneler, alveri merkezleri, enerji santralleri ve
bilgi ilem merkezleri ile rayl sistemlerle toplu tamacln
yapld ok sayda insann ve deerli cihazn bulunduu yangn
tehlikesi olan tesislerde kullanlrlar. Bu kablolar, yangn srasnda
alevi iletmezler, youn duman tabakas oluturmazlar ve
korozyona elverili ortam yaratmazlar, bylece can ve mal
gvenlii salarlar.
Used in hotels, hospitals, shopping centers, power plants, information
technology centers and in places where human groups are carried by
railway systems, valuable equipments are located, subject to fire danger.
These cables do not conduct flame during fire, do not create high smoke
density, do not create corrosive ambients and therefore provide health
and goods protection.

Maksimum
letme Scakl
Maximum Operating
Temperature

Maksimum ksa
devre Scakl
Maximum short
circuit Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Aleve
Dayankllk
Flame Retardant
IEC 60332-3-24
Cat.C

Kullanld Yerler / Applications

92

Serim Scakl
Installation
Temperature
Min 5 oC

Tesisat
Internal Wiring

Boru inde
In Conduit

Dahili Sva
Alt/st Boru
inde
Indoor Under
Plaster in Conduit

Halojenden
Arndrlm
Halogen Free
IEC 60754-1/2

Dk Duman
Younluu
Low Smoke
Emission
IEC 61034-1/2

Rijit
Rigid

RoHS
Compliance

Teknik zellikler / Technical Features


052XZ1-U/NHXMH

300/500 V

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Sath zerinde Akm


Tama Kapasitesi

Sevk Uzunluu
(Yaklak)

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

Operating Carrying
Capacity on Surface

Delivery Length
(Approx.)

mm

kg/km

29
48
77
115
192

8,0
8,8
10,0
11,0
13,5

95
125
171
224
351

12,1
7,41
4,61
3,08
1,83

22
30
40
51
70

1000
1000
1000
1000
1000

43
72
115
173
288

8,4
9,3
10,5
12,0
14,5

112
150
207
286
448

12,1
7,41
4,61
3,08
1,83

22
30
40
51
70

1000
1000
1000
1000
1000

58
96
154
230
384
614

9,2
10,1
12,1
13,3
15,7
19,4

139
186
277
367
559
868

12,1
7,41
4,61
3,08
1,83
1,15

18,5
25
34
43
60
80

1000
1000
1000
1000
1000
1000

72
120
193
288

9,8
10,8
13,0
14,4

160
216
325
435

12,1
12,1
12,1
12,1

18,5
25
34
43

1000
1000
1000
1000

mm

/km

2 Damarl / 2 Cores
2x1,5
2x2,5
2x4
2x6
2x10

3 Damarl / 3 Cores
3x1,5
3x2,5
3x4
3x6
3x10

4 Damarl / 4 Cores
4x1,5
4x2,5
4x4
4x6
4x10
4x16 rm

5 Damarl / 5 Cores
5x1,5
5x2,5
5x4
5x6

NOT :

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

93

AFUMEXTM Kablolar
AFUMEXTM Cables

Alevi letmeyen Halojenden Arndrlm Kablolar


Halogen Free, Flame Retardant, Non-Corrosive Cables

052XZ1-F

300/500 V

TS 9760 HD 21.5 S3 e.

NHXMH

300/500 V

VDE 0250-214 e.

AFUMEXTM
Yap / Construction
nce ok telli bakr iletkenli, zel sentetik yaltkanl, zel dolgu
tabakal, zel sentetik d klfl, alevi iletmeyen, halojenden
arndrlm enerji kablolar.

1
2

1- nce ok telli bakr iletken


Multi stranded Cu-conductor

Multi stranded copper conductor, special synthetic insulated, special


synthetic outer sheathed flame retardant, halogen free cables.

2- zel sentetik yaltkan


Special synthetic insulation

Teknik Bilgiler / Technical Data

3- zel dolgu
Special filler
4- zel sentetik d klf
Special synthetic outer sheath

Bu kablolar TS 9760 HD 21.5 S3 veya VDE 0250-214 esas alnarak


retilirler.
-zin verilen iletme scakl: 90 C
Aadaki standartlara uygun olarak test edilirler:
LS (Dk Duman) Testi: IEC 61034-1/2
HF (Halojenden Arndrlmlk) Testi: IEC 60754-1/2
FR (Aleve Dayankllk ) Testi: IEC 60332-1-2 ve IEC 60332-3-24 Cat.C
These cables are produced based on TS 9760 HD 21.5 S3 or
VDE 0250-214
-Permissible operating temperature: 90 C
Tested according to below standards:
LS (Low Smoke) Test: IEC 61034-1/2
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Retardant) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C

Kullanld Yerler / Applications


Oteller, hastaneler, alveri merkezleri, enerji santralleri ve
bilgi ilem merkezleri ile rayl sistemlerle toplu tamacln
yapld ok sayda insann ve deerli cihazn bulunduu yangn
tehlikesi olan tesislerde kullanlrlar. Bu kablolar, yangn srasnda
alevi iletmezler, youn duman tabakas oluturmazlar ve
korozyona elverili ortam yaratmazlar, bylece can ve mal
gvenlii salarlar.
Used in hotels, hospitals, shopping centers, power plants, information
technology centers and in places where human groups are carried by
railway systems, valuable equipments are located, subject to fire danger.
These cables do not conduct flame during fire, do not create high smoke
density, do not create corrosive ambients and therefore provide health
and goods protection.

Maksimum
letme Scakl
Maximum Operating
Temperature

Maksimum ksa
devre Scakl
Maximum short
circuit Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Kullanld Yerler / Applications

94

Serim Scakl
Installation
Temperature
Min 5 oC

Tesisat
Internal Wiring

Hareketli Ev
Aletleri
Mobile Household
Appliances

Aleve
Dayankllk
Flame Retardant
IEC 60332-3-24
Cat.C

Halojenden
Arndrlm
Halogen Free
IEC 60754-1/2

Dk Duman
Younluu
Low Smoke Emission
IEC 61034-1/2

Bklgen
Flexible

RoHS
Compliance

Teknik zellikler / Technical Features


052XZ1-F/NHXMH

300/500 V

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Sath zerinde Akm


Tama Kapasitesi

Sevk Uzunluu
(Yaklak)

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

Operating Carrying
Capacity on Surface

Delivery Length
(Approx.)

mm

kg/km

/km

29
48
77
115
192

8,9
9,8
10,0
10,9
13,2

117
150
171
215
340

13,30
7,98
4,95
3,30
1,91

22
30
40
51
70

1000
1000
1000
1000
1000

43
72
115
173
288

9,3
10,3
11,7
13,1
14,4

131
173
239
319
425

13,30
7,98
4,95
3,30
1,91

22
30
40
51
70

1000
1000
1000
1000
1000

58
96
154
230
384
614

10,0
11,1
12,0
13,2
16,0
20,0

152
203
255
340
530
860

13,30
7,98
4,95
3,30
1,91
1,21

18,5
25
34
43
60
80

1000
1000
1000
1000
1000
1000

72
120
193
288

10,0
10,8
13,2
14,5

145
200
300
405

13,30
7,98
4,95
3,30

18,5
25
34
43

1000
1000
1000
1000

mm

2 Damarl / 2 Cores
2x1,5
2x2,5
2x4
2x6
2x10

3 Damarl / 3 Cores
3x1,5
3x2,5
3x4
3x6
3x10

4 Damarl / 4 Cores
4x1,5
4x2,5
4x4
4x6
4x10
4x16

5 Damarl / 5 Cores
5x1,5
5x2,5
5x4
5x6

NOT :

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

95

AFUMEXTM Kablolar
AFUMEXTM Cables

N2XH

0,6/1 kV

Alevi letmeyen Halojenden Arndrlm Kablolar


Halogen Free, Flame Retardant, Non-Corrosive Cables

TS HD 604 S1

AFUMEXTM
Yap / Construction
Tek veya ok telli bakr iletkenli, zel sentetik yaltkanl zel
sentetik d klfl, alevi iletmeyen, halojenden arndrlm yangn
srasnda youn duman tabakas oluturmayan kablolar.

1
2

1- Tek veya ok telli bakr iletken


Solid or stranded copper

2- zel sentetik yaltkan


Special synthetic insulation

Teknik Bilgiler / Technical Data


Bu kablolar TS HD 604 S1 e uygun olarak retilirler.
-zin verilen iletme scakl: 90 C
-D klf rengi: Siyah

3- zel dolgu
Special filler
4- zel sentetik d klf
Special synthetic outer sheath

Low smoke, halogen free and flame retardant cables with solid or stranded
copper conductor, special synthetic insulation and special synthetic outer
sheath.

Aadaki standartlara uygun olarak test edilirler:


LS (Dk Duman) Testi: IEC 61034-1/2
HF (Halojenden Arndrlmlk) Testi: IEC 60754-1/2
FR (Aleve Dayankllk ) Testi: IEC 60332-1-2 ve IEC 60332-3-24 Cat.C
These cables are produced according to TS HD 604 S1.
-Permissible operating temperature: 90 C
-Colour of outer sheath: Black
Tested according to below standards:
LS (Low Smoke) Test: IEC 61034-1/2
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Retardant) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C

Kullanld Yerler / Applications


Bu kablolar, yangna kar alnmas zorunlu gvenlik tedbirlerinin
olduu okullar, hastaneler, toplant ve alveri merkezleri gibi
yerlerde dahili ve harici mekanlarda kullanlrlar.
These cables are used in internal and external places in where safety
regulations must be taken against fire such as schools, hospitals, meeting
rooms and shopping centers.

Maksimum
letme Scakl
Maximum Operating
Temperature

Maksimum ksa
devre Scakl
Maximum short
circuit Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Aleve
Dayankllk
Flame Retardant
IEC 60332-3-24
Cat.C

Kullanld Yerler / Applications

98

Serim Scakl
Installation
Temperature
Min 5 oC

Akta
In Free Air

Beton inde
In Concrete

Boru inde
In Conduit

Halojenden
Arndrlm
Halogen Free
IEC 60754-1/2

Dk Duman
Younluu
Low Smoke
Emission
IEC 61034-1/2

Rijit
Rigid

RoHS
Compliance

Teknik zellikler / Technical Features


N2XH

0,6/1 kV

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Sath zerinde Akm


Tama Kapasitesi

Sevk Uzunluu
(Yaklak)

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

Operating Carrying
Capacity on Surface

Delivery Length
(Approx.)

mm

kg/km

/km

6,0
6,5
7,3
8,2
10,2
11,2
12,6
14,4
16,2
17,9
19,7
21,9
24,5
9,0
9,7
10,4
11,6
13,2
9,1
10,0
11,0
12,0
13,8
16,8
21,6
23,4
27,4
31,1
35,2
39,6
43,0
47,7
53,8
9,8
10,8
11,9
13,1
15,2
17,4
10,6
11,9
14,7
15,1
16,0
17,6
18,5
20,6
21,0
23,4
11,6
13,1
16,4
16,9
17,7
19,5
20,7
22,9
23,4
26,3

66
86
128
183
287
376
495
693
944
1176
1442
1786
2337
117
146
187
243
348
128
167
224
293
437
741
1202
1508
2063
2844
3827
4882
5825
7286
9475
149
198
268
357
543
788
173
225
318
348
395
495
543
627
721
907
231
302
432
483
541
688
766
872
1020
1309

4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
12,1
7,41
4,61
3,08
1,83
12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
12,1
7,41
4,61
3,08
1,83
1,15
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

mm

1x4 re
1x6 re
1x10 re
1x16 re
1x25 rm
1x35 rm
1x50 rm
1x70 rm
1x95 rm
1x120 rm
1x150 rm
1x185 rm
1x240 rm
2x1,5 re
2x2,5 re
2x4 re
2x6 re
2x10 re
3x1,5 re
3x2,5 re
3x4 re
3x6 re
3x10 re
3x16 re/10 re
3x25 rm/16 re
3x35 rm/16 re
3x50 rm/25 rm
3x70 rm/35 rm
3x95 rm/50 rm
3x120 rm/70 rm
3x150 rm/70 rm
3x185 rm/95 rm
3x240 rm/120 rm
4x1,5 re
4x2,5 re
4x4 re
4x6 re
4x10 re
4x16 re
5x1,5 re
7x1,5 re
10x1,5 re
12x1,5 re
14x1,5 re
19x1,5 re
21x1,5 re
24x1,5 re
30x1,5 re
40x1,5 re
5x2,5 re
7x2,5 re
10x2,5 re
12x2,5 re
14x2,5 re
19x2,5 re
21x2,5 re
24x2,5 re
30x2,5 re
40x2,5 re

NOT :

38
58
96
154
240
336
480
672
912
1152
1440
1776
2304
29
48
77
115
192
43
72
115
173
288
557
874
1162
1680
2352
3216
4128
4992
6240
8064
58
96
154
230
384
614
72
101
144
173
202
274
305
346
432
576
120
168
240
288
336
456
504
576
720
960

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

56
73
101
137
182
226
275
353
430
500
577
661
781

40
53
74
101
135
169
207
268
328
383
444
510
607

26
36
49
63
86
23
32
42
54
75
100
127
158
192
246
298
346
399
456
538
23
32
42
54
75
100
23
15
13
13
12
11
10
10
9
8
32
21
18
17
16
15
15
13
12
11

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

99

AFUMEXTM FE 180 Kablolar


AFUMEXTM FE 180 Cables

N2XH FE 180

0,6/1 kV

TS HD 604 S1

Alevi letmeyen Halojenden Arndrlm Kablolar


Halogen Free, Flame Retardant, Non-Corrosive Cables

AFUMEXTM
Yap / Construction

1
2
1- Tek veya ok telli bakr iletken
Solid or stranded copper

3
4

2- zel ayrc tabaka


Special seperator
3- zel sentetik yaltkan
Special synthetic insulation

Tek veya ok telli bakr iletkenli, zel aleve dayankl ayrc


tabakal, zel sentetik yaltkanl, zel sentetik d klfl, alevi
iletmeyen, halojenden arndrlm, yangn esnasnda youn duman
tabakas oluturmayan ve IEC 60331-21e gre alev altnda 180
dakika ilevini devam ettiren enerji ve kumanda kablolar.
Energy and control cables with solid or stranded copper conductor, special
synthetic insulation and special synthetic outer sheath. These cables are
flame retardant, halogen free, do not generate high smoke density during
fire and they can function under flame for 180 minutes.

Teknik Bilgiler / Technical Data


Bu kablolar, TS HD 604 S1 e uygun olarak retilirler.

4- zel dolgu
Special filler
5- zel sentetik d klf
Special synthetic outer sheath

- zin verilen iletme scakl: 90 C


- D Klf Rengi : Portakal
Aadaki standartlara uygun olarak test edilirler:
LS (Dk Duman) Testi: IEC 61034 -1/2
HF (Halojenden Arndrlmlk) Testi: IEC 60754 - 1/2
FR (Aleve Dayankllk) Testi: IEC 60332-1-2 ve IEC 60332-3-24 Cat.C
FE (Akm letme) Testi: IEC 60331-21
These cables are produced according to TS HD 604 S1.
-Permissible operating temperature: 90 C
-Colour of outer sheath: Orange
Tested according to below standards:
LS (Low Smoke) Test: IEC 61034-1/2
HF (Halogen Free) Test: IEC 60754-1/2
FR (Flame Retardant) Test: IEC 60332-1-2 and IEC 60332-3-24 Cat.C
FE (Function Endurance) Test: IEC 60331-21

Kullanld Yerler / Applications


Bu kablolar, yangna kar alnmas zorunlu gvenlik tedbirlerinin
olduu okullar, hastaneler, toplant ve alveri merkezleri gibi
yerlerde dahili ve harici mekanlarda kullanlrlar.
These cables are used in internal and external places in where safety
regulations must be taken against fire such as schools, hospitals, meeting
rooms and shopping centers.

Maksimum
letme Scakl
Maximum Operating
Temperature

Maksimum ksa
devre Scakl
Maximum short
circuit Temperature

Aleve
Dayankllk
Flame Retardant
IEC 60332-1-2

Aleve
Dayankllk
Flame Retardant
IEC 60332-3-24
Cat.C

Kullanld Yerler / Applications

106

Serim Scakl
Installation
Temperature
Min 5 oC

Akta
In Free Air

Beton inde
In Concrete

Boru inde
In Conduit

Yangna
Dayankl
Fire Resistance
IEC 60331-21

Halojenden
Arndrlm
Halogen Free
IEC 60754-1/2

Dk Duman
Younluu
Low Smoke
Emission
IEC 61034-1/2

RoHS
Compliance

Teknik zellikler / Technical Features


N2XH FE 180

0,6/1 kV

Nominal Kesit

Bakr
Faktr

Kablo D ap
(Yaklak)

Net Arlk
(Yaklak)

20 Cde letken
DA Direnci

Sath zerinde Akm


Tama Kapasitesi

Sevk Uzunluu
(Yaklak)

Rated
Cross-section

Cu Factor
1000 m

Overall Diameter
of Cable (Approx.)

Net Weight
(Approx.)

Conductor DC
Resistance at 20 C

Operating Carrying
Capacity on Surface

Delivery Length
(Approx.)

mm

kg/km

6,4
6,9
7,7
8,6
10,6
11,6
13,0
14,8
16,6
18,3
20,1
22,3
24,9
9,6
10,4
11,3
12,3
14,0
9,9
10,8
11,8
12,9
14,6
17,8
22,6
24,3
28,4
32,1
36,2
40,5
44,0
48,7
54,8
10,7
11,6
12,9
14,0
16,2
18,4
11,6
12,9
15,6
16,5
17,5
19,3
20,3
22,6
23,6
26,7
12,6
14,1
17,8
18,3
19,2
21,2
22,5
24,9
26,3
29,6

71
91
133
190
293
383
502
700
951
1184
1451
1795
2345
131
164
208
264
374
145
186
245
318
463
778
1245
1552
2113
2900
3886
4946
5900
7362
9561
169
218
294
384
576
825
195
254
346
379
446
559
614
709
832
1050
255
335
481
536
600
762
848
966
1144
1473

mm

1x4 re
1x6 re
1x10 re
1x16 re
1x25 rm
1x35 rm
1x50 rm
1x70 rm
1x95 rm
1x120 rm
1x150 rm
1x185 rm
1x240 rm
2x1,5 re
2x2,5 re
2x4 re
2x6 re
2x10 re
3x1,5 re
3x2,5 re
3x4 re
3x6 re
3x10 re
3x16 re/10 re
3x25 rm/16 re
3x35 rm/16 re
3x50 rm/25 rm
3x70 rm/35 rm
3x50 rm/50 rm
3x120 rm/70 rm
3x150 rm/70 rm
3 x185 rm/95 rm
3x240 rm/120 rm
4x1,5 re
4x2,5 re
4x4 re
4x6 re
4x10 re
4x16 re
5x1,5 re
7x1,5 re
10x1,5 re
12x1,5 re
14x1,5 re
19x1,5 re
21x1,5 re
24x1,5 re
30x1,5 re
40x1,5 re
5x2,5 re
7x2,5 re
10x2,5 re
12x2,5 re
14x2,5 re
19x2,5 re
21x2,5 re
24x2,5 re
30x2,5 re
40x2,5 re

NOT :

38
58
96
154
240
336
480
672
912
1152
1440
1776
2304
29
48
77
115
192
43
72
115
173
288
557
874
1162
1680
2352
3216
4128
4992
6240
8064
58
96
154
230
384
614
72
101
144
173
202
274
305
346
432
576
120
168
240
288
336
456
504
576
720
960

Akm tama kapasiteleri 30 C ortam scaklnda geerlidir.


Current carrying capacities are valid at 30 C ambient temperature.

/km

4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
12,1
7,41
4,61
3,08
1,83
12,1
7,41
4,61
3,08
1,83
1,15
0,727
0,524
0,387
0,268
0,193
0,153
0,124
0,0991
0,0754
12,1
7,41
4,61
3,08
1,83
1,15
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
12,1
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41
7,41

56
73
101
137
182
226
275
353
430
500
577
661
781

40
53
74
101
135
169
207
268
328
383
444
510
607

1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000

26
36
49
63
86
23
32
42
54
75
100
127
158
192
246
298
346
399
456
538
23
32
42
54
75
100
23
15
13
13
12
11
10
10
9
8
32
21
18
17
16
15
15
13
12
11

107

Anda mungkin juga menyukai