OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 1 of 14

Inspected by:

Juber Anwar Khan (Asst. Maint. Engineer)

Sl.No 1.

Picture

Remarks

Rusted tapchanger leaver in Tx 1 2&3

Breather not in good condition in Tx- 1


Page 1 of 14

Cooling fan is missing in Tx - 1

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 2 of 14

4&5

Transformer Oil leak in Tx 1

Rusted cooling fan in Tx - 1

6.

Oil on the top of tapchanger oil filter system in Tx 1

Page 2 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 3 of 14

7&8

Fire fighting system paint removed in Tx 1

Proper padlocks should be use in Tx - 1

9 &10

Transformer climbing lader is not locked in Tx - 1

Broken cable clids in Earthing TFR 1

Page 3 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 4 of 14

11&12

Temporary sealing of cable box in Earthing TFR 1

Rusted pad locks in Earthing TFR 1

13.

Oil leak in Earthing TFR 1

Page 4 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 5 of 14

14&15

Control Cable dressing is not proper in EAT 1

Rusted Handle of NER 1

16.

Rusted body of NER 1

Page 5 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 6 of 14

17.

Bird nest on Circuit Breaker

18&19

Damage Tx 1 Oil drainage pump switch

Damage Gland Shrouds

Page 6 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 7 of 14

20.

Damage Cable Gland Shrouds

21.

Damage Cable Gland Shrouds

Page 7 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 8 of 14

22&23

Bird nest in the centre of busbar

Damage earth pit

24.

Damage Cable Gland Shrouds

Damage Cable Gland Shrouds

Page 8 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 9 of 14

25.

Damage Cable Gland Scroud 26.

Oil leak in CT ( Phase B )

Page 9 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 10 of 14

27.

Rusted transformer cooling fans in Tx - 2

28&29

Damage gland scroud at MK box in Tx - 2

Old breathers in Tx - 2

Page 10 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 11 of 14

30&31

Cable cleats missing in Tx 2

Paint removed in EAT- 2

32&33

Temporary seald Cable box in EAT 2

Rusted body in NER 2

Page 11 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 12 of 14

34.

Missing foundation in fire

35&36

Broken Earth pit

Broken wall foundation

Page 12 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 13 of 14

37.

Faded Phase plates

Faded Phase plate

Page 13 of 14

Ref. OETC/2013 Visual Inspection Report (RAY) Region: Sharqyia Location: Mudhaibi Grid station March 2013 Page 14 of 14

Page 14 of 14