DESCRIPTION . ILLUSTRATIONS
With its opposed blade operation closing system, volume control damper (VCDS 800 series) is designed for controling air flow and pressure in HVAC systems. Designed to operate with opposed blade action (providing better aerodynamics), volume control damper provides better balancing control or airflow rates. Blades are formed from single skin construction with grooved blade tips to produce an interlocking blade closure, either via manual or automatic operation. Manually operated dampers are supplied as standard with a lockable quadrant assembly, thus allowing for conversion to motor operation without the need for additional components.
CONSTRUCTION
. Square and round VCDs available . Triple V-Groove Opposed Blade operation . Available in manual or motorised models . Actuation available in following configurations: i) Hand locking quadrant arm ii) Worm gear drive iii) Bare shaft iv) Factory installed actuator
MATERIALS
. Stainless steel construction available . Frame construction: 0.7-1.5 mm galvanized steel (Size dependant) . Blade construction: 0.7-1.0 mm galvanized steel (Size dependant)
LENGTH LENGTH + 60 mm
WALL THICKNESS
Configuration E: Compartment
AERODYNAMIC PERFORMANCE
5 4
200 3 300 V ( m / s )
400
500 600
10
20
30 P (Pa)
40
50
200
300
400 500
. 0 , 100, 200, ... etc = Degree Opening . Max static pressure drop for fully open dampers is 10 Pa
AERODYNAMIC PERFORMANCE
CLOSED DAMPER LEAKAGE
P: 100 P: 250 P: 500 P: 1000
L: 1200
P: 1500
L: 1000
L: 800 L: 600
1210
1010
810 H
610
410
210
20
30
40
60
80 100 V
L
150 200
. L = Length (mm) . H = Height (mm) . . VL = Volume Flowrate (cmh) P: = Pressure Difference (Pa)
OPERATION RANGE
1500 A B
300
200
H (m) 1.4
H (m) 1.4 15 Nm
1.0
10 Nm
1.0 10 Nm
0.5
5 Nm
0.5
5 Nm
0.5
. H = Damper Height (m) . L = Damper Length (m)
1.0
1.4 L (m)
0.5
1.0 L (m)