VOLUME CONTROL DAMPER

VOLUME CONTROL DAMPERS VCDS 800 SERIES

DESCRIPTION . ILLUSTRATIONS
With its opposed blade operation closing system, volume control damper (VCDS 800 series) is designed for controling air flow and pressure in HVAC systems. Designed to operate with opposed blade action (providing better aerodynamics), volume control damper provides better balancing control or airflow rates. Blades are formed from single skin construction with grooved blade tips to produce an interlocking blade closure, either via manual or automatic operation. Manually operated dampers are supplied as standard with a lockable quadrant assembly, thus allowing for conversion to motor operation without the need for additional components.

CONSTRUCTION
. Square and round VCDs available . Triple V-Groove Opposed Blade operation . Available in manual or motorised models . Actuation available in following configurations: i) Hand locking quadrant arm ii) Worm gear drive iii) Bare shaft iv) Factory installed actuator

MATERIALS
. Stainless steel construction available . Frame construction: 0.7-1.5 mm galvanized steel (Size dependant) . Blade construction: 0.7-1.0 mm galvanized steel (Size dependant)

150 mm HEIGHT + 60 mm HEIGHT

LENGTH LENGTH + 60 mm

WALL THICKNESS

VCDS 800 SERIES| Page 1 of 5

VOLUME CONTROL DAMPERS VCDS 800 SERIES

ACTUATOR INSTALLATION LOCATIONS

Configuration A: Shaft Outside

Configuration B: Inside Bottom

Configuration C: Inside Top

Configuration D: Inside Middle

Configuration E: Compartment

Configuration F: Infront Shaft

VCDS 800 SERIES| Page 2 of 5

VOLUME CONTROL DAMPERS VCDS 800 SERIES

AERODYNAMIC PERFORMANCE

STATIC PRESSURE DROP


PRESSURE DROP VS DUCT VELOCITY 100

5 4

200 3 300 V ( m / s )

400

500 600

10

20

30 P (Pa)

40

50

60 70 80 100 0 = Fully Open


0

200

300

400 500

. V = Duct Velocity (m/s) .


0

P = Static Pressure Drop (Pa)

. 0 , 100, 200, ... etc = Degree Opening . Max static pressure drop for fully open dampers is 10 Pa

VCDS 800 SERIES| Page 3 of 5

VOLUME CONTROL DAMPERS VCDS 800 SERIES

AERODYNAMIC PERFORMANCE
CLOSED DAMPER LEAKAGE
P: 100 P: 250 P: 500 P: 1000

L: 1200

P: 1500

L: 1000

L: 800 L: 600

1210

1010

810 H

610

410

210

20

30

40

60

80 100 V
L

150 200

300 400 500

. L = Length (mm) . H = Height (mm) . . VL = Volume Flowrate (cmh) P: = Pressure Difference (Pa)

OPERATION RANGE
1500 A B

900 800 700 PRESSURE (Pa) 600 500 400

. A = Recommended operation range . B = Critical operation range

300

200

VCDS 800 SERIES| Page 4 of 5

VOLUME CONTROL DAMPERS VCDS 800 SERIES

ACTUATOR TORQUE REQUIREMENTS


FOR PRESSURE LESS OR EQUAL TO 500 PA FOR PRESSURE LESS OR EQUAL TO 1000 PA

H (m) 1.4

H (m) 1.4 15 Nm

1.0

10 Nm

1.0 10 Nm

0.5

5 Nm

0.5

5 Nm

0.5
. H = Damper Height (m) . L = Damper Length (m)

1.0

1.4 L (m)

0.5

1.0 L (m)

VCDS 800 SERIES| Page 5 of 5