Anda di halaman 1dari 2

PROJECT : PROJ. NO.

: CLIENT : UNIT :

DATE : BY : REV : DOC NO.:

S.Rahimi 0

Steam Trap Load Calculation (Process Tracing)


Input Data Process Fluid temperature Process line size Ambient Temperature Insulation Efficiency Safety Factor Tracer Length No of Tracer Steam Pressure Calculation Results Steam latent heat Pipe surface area /1 m Overall heat transfer Coe. Heat loss Total Heat Loss Total Condensate Rate Steam Trap Rate

C in C % --m ---barg

85 20 4 85 3 50 2 4.5

kj/kg m2 w/m2 C W/m kW kg/hr kg/hr

2096.8 1.595 32 620.2 31.0 159.7 79.9

8 tracers

Note

www.chemwork.org

PROJECT : PROJ. NO.: CLIENT : UNIT :

DATE : BY : REV : DOC NO.:

S.Rahimi 0

Steam Trap Load Calculation (Steam Main Header)


Input Data Steam Temperature Steam Pressure Process line size Ambient Temperature Insulation Efficiency Safety Factor Length between legs Calculation Results Steam latent heat Pipe surface area /1 m Overall heat transfer Coe. Heat loss Total Heat Loss Steam Trap Rate

C barg in C % --m

371 10 36 4.4 93.76 2 50

kj/kg m2 w/m2 C W/m kW kg/hr

1999.0 2.871 32 2101.8 105.1 378.5

Note

www.chemwork.org

Anda mungkin juga menyukai