Type
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: All Units Project: SAFIRE 8221-001
DO
DO
Effect
HMI Display
KY-1107A-1
KY-1107A-2
Cause
No. Equipment Description PLC Signal Type Interlock # Field Device Tag Scale / Setpoint
085-12-004B
085-12-004B
085-12-004B
085-12-004B
A1
F-1107A Desander
PLC-301
HC-1107A
085-12-004B
B1 B2 B3 B4
Level Switch High - Desander Timer Controller - Desander Crude Oil Inlet Valve Position Indicator - Desander Jet Water Inlet Valve Position Indicator - Desander Sand Outlet
DI
LSH-1107A
LAH-1107A KC-1107A
10 sec
085-12-004B 085-12-004B
X X X X
X O/C O/C
DI DI DI DI
ZI-1107A-1 ZI-1107A-2
5 sec 5 sec
085-12-004B 085-12-004B
X X
C1 C2 C3
Differential Pressure Alarm High - Desander Basket Strainer Differential Pressure Alarm High-High - Desander Valve Control Station - Desander Bypass
X X X
X X X
O/C
Notes: 1: 2: 3: 4: 4: 5:
Specific Symbology:
Page 1 of 57
085-12-004B O O
Dead Band
PID
PDY-1107A
HY-1107A
KC-1107A
DISPLAY
ALARM
Tag
Legend
Description
DO
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI AI
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 0-300 F
Dead Band
~2% ~1%
PID
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Inlet Header
Pressure Indicating Transmitter - Plant Oil Inlet Header Temperature Indicating Transmitter - Plant Oil Inlet Header
PLC-301 PLC-301
I-100, I-101
PIT-1110 TIT-1110
PI-1110 TI-1110
085-12-004A 085-12-004A
X X
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105A
~2%
X X X X X O X
10 PSIG
085-12-004B
F-1107A Desander
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-130 I-130
FIT-1107A
~5%
X X X X X X X X X X X X X X O O X X X O O X X O
PIT-1107A-1
PI-1107A-1 PAH-1107A-1
~2%
085-12-004B 085-12-004B
PIT-1107A-2
~2%
LSH-1107A
LAH-1107A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105B
~2%
X X X X X O X
10 PSIG
085-12-004C
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-131 I-131
FIT-1107B
~5%
X X X X X X X X X X X X X X O O X X X O O X X O
PIT-1107B-1
PI-1107B-1 PAH-1107B-1
~2%
085-12-004C 085-12-004C
PIT-1107B-2
~2%
LSH-1107B
LAH-1107B
Page 2 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI AI
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 0-300 F
Dead Band
~2% ~1%
PID
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Inlet Header
Pressure Indicating Transmitter - Plant Oil Inlet Header Temperature Indicating Transmitter - Plant Oil Inlet Header
PLC-301 PLC-301
I-100, I-101
PIT-1110 TIT-1110
PI-1110 TI-1110
085-12-004A 085-12-004A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105A
~2%
10 PSIG
085-12-004B
F-1107A Desander
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-130 I-130
FIT-1107A
~5%
PIT-1107A-1
PI-1107A-1 PAH-1107A-1
~2%
085-12-004B 085-12-004B
PIT-1107A-2
~2%
LSH-1107A
LAH-1107A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105B
~2%
10 PSIG
085-12-004C
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-131 I-131
FIT-1107B
~5%
PIT-1107B-1
PI-1107B-1 PAH-1107B-1
~2%
085-12-004C 085-12-004C
PIT-1107B-2
~2%
LSH-1107B
LAH-1107B
Page 3 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI AI
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 0-300 F
Dead Band
~2% ~1%
PID
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Inlet Header
Pressure Indicating Transmitter - Plant Oil Inlet Header Temperature Indicating Transmitter - Plant Oil Inlet Header
PLC-301 PLC-301
I-100, I-101
PIT-1110 TIT-1110
PI-1110 TI-1110
085-12-004A 085-12-004A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105A
~2%
10 PSIG
085-12-004B
F-1107A Desander
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-130 I-130
FIT-1107A
~5%
PIT-1107A-1
PI-1107A-1 PAH-1107A-1
~2%
085-12-004B 085-12-004B
PIT-1107A-2
~2%
LSH-1107A
LAH-1107A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105B
~2%
10 PSIG
085-12-004C
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-131 I-131
FIT-1107B
~5%
PIT-1107B-1
PI-1107B-1 PAH-1107B-1
~2%
085-12-004C 085-12-004C
PIT-1107B-2
~2%
LSH-1107B
LAH-1107B
Page 4 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI AI
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 0-300 F
Dead Band
~2% ~1%
PID
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
Inlet Header
Pressure Indicating Transmitter - Plant Oil Inlet Header Temperature Indicating Transmitter - Plant Oil Inlet Header
PLC-301 PLC-301
I-100, I-101
PIT-1110 TIT-1110
PI-1110 TI-1110
085-12-004A 085-12-004A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105A
~2%
10 PSIG
085-12-004B
F-1107A Desander
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-130 I-130
FIT-1107A
~5%
PIT-1107A-1
PI-1107A-1 PAH-1107A-1
~2%
085-12-004B 085-12-004B
PIT-1107A-2
~2%
LSH-1107A
LAH-1107A
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105B
~2%
10 PSIG
085-12-004C
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-131 I-131
FIT-1107B
~5%
PIT-1107B-1
PI-1107B-1 PAH-1107B-1
~2%
085-12-004C 085-12-004C
PIT-1107B-2
~2%
LSH-1107B
LAH-1107B
Page 5 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA I-132
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 75 PSIG
Dead Band
~2%
PID
42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Outlet
PIT-1105C
X X X X X O X
10 PSIG
085-12-004D
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-132 I-132
FIT-1107C
~5%
X X X X X X X X X X X X X X O O X X X O O X X O
PIT-1107C-1
PI-1107C-1 PAH-1107C-1
~2%
085-12-004D 085-12-004D
PIT-1107C-2
~2%
LSH-1107C
LAH-1107C
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105D
~2%
X X X X X O X
10 PSIG
085-12-004E
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-133 I-133
FIT-1107D
~5%
X X X X X X X X X X X X X X O O X X X O O X X O
PIT-1107D-1
PI-1107D-1 PAH-1107D-1
~2%
085-12-004E 085-12-004E
PIT-1107D-2
~2%
LSH-1107D
LAH-1107D
Page 6 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA I-132
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 75 PSIG
Dead Band
~2%
PID
42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Outlet
PIT-1105C
10 PSIG
085-12-004D
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-132 I-132
FIT-1107C
~5%
PIT-1107C-1
PI-1107C-1 PAH-1107C-1
~2%
085-12-004D 085-12-004D
PIT-1107C-2
~2%
LSH-1107C
LAH-1107C
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105D
~2%
10 PSIG
085-12-004E
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-133 I-133
FIT-1107D
~5%
PIT-1107D-1
PI-1107D-1 PAH-1107D-1
~2%
085-12-004E 085-12-004E
PIT-1107D-2
~2%
LSH-1107D
LAH-1107D
Page 7 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA I-132
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 75 PSIG
Dead Band
~2%
PID
42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Outlet
PIT-1105C
10 PSIG
085-12-004D
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-132 I-132
FIT-1107C
~5%
PIT-1107C-1
PI-1107C-1 PAH-1107C-1
~2%
085-12-004D 085-12-004D
PIT-1107C-2
~2%
LSH-1107C
LAH-1107C
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105D
~2%
10 PSIG
085-12-004E
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-133 I-133
FIT-1107D
~5%
PIT-1107D-1
PI-1107D-1 PAH-1107D-1
~2%
085-12-004E 085-12-004E
PIT-1107D-2
~2%
LSH-1107D
LAH-1107D
Page 8 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA I-132
Interlock #
Field Device
Tag
Scale / Setpoint
0-200 PSIG 75 PSIG
Dead Band
~2%
PID
42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Outlet
PIT-1105C
10 PSIG
085-12-004D
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-132 I-132
FIT-1107C
~5%
PIT-1107C-1
PI-1107C-1 PAH-1107C-1
~2%
085-12-004D 085-12-004D
PIT-1107C-2
~2%
LSH-1107C
LAH-1107C
Pressure Indicating Transmitter - Strainer Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Crude Oil Inlet
PIT-1105D
~2%
10 PSIG
085-12-004E
Flow Indicating Transmitter - Magmeter - Desander Jet Water Inlet Hand Controller - Desander Crude Oil Inlet Timer Controller - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Crude Oil Inlet Pressure Alarm High - Desander Crude Oil Inlet Pressure Indicating Transmitter - Desander Emulsion Outlet Pressure Alarm High - Desander Emulsion Outlet Differential Pressure Indicator - Desander Crude Oil Inlet Differential Pressure Alarm High - Desander Sand Outlet Differential Pressure Alarm High-High - Desander Bypass Differential Pressure Alarm Low - Low Differential Pressure Calculated Differential Pressure Signal - Desander Bypass Level Switch High - Desander
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AI SCADA SCADA AI SCADA AI SCADA SCADA SCADA SCADA SCADA SCADA DI I-133 I-133
FIT-1107D
~5%
PIT-1107D-1
PI-1107D-1 PAH-1107D-1
~2%
085-12-004E 085-12-004E
PIT-1107D-2
~2%
LSH-1107D
LAH-1107D
Page 9 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110A I-113 I-113 LXSLL-1110A PIT-1110A I-111 I-112 I-113 LSHH-1110A LSLL-1110A LXIT-1110A I-113 LIT-1110A-2 LIT-1110A-1 FIT-1110A-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
V-1110A FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110A FIT-1110A-1
AI-1110A FI-1110A-1 FQI-1110A-1 FI-1110A-2 FQI-1110A-2 LI-1110A-1 LAH-1110A-1 LAL-1110A-1 LALL-1110A-1 LIC-1110A-2 LAH-1110A-2 LAHH-1110A-2 LAL-1110A-2 LAHH-1110A LALL-1110A LXIC-1110A LXAH-1110A LXAL-1110A LXALL-1110A PIC-1110A-1/2/3 PAH-1110A PAHH-1110A PAL-1110A TI-1110A
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-10000 BPD
~5%
085-12-004F 085-12-004F
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F
~2%
~1%
085-12-004F
Page 10 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110A I-113 I-113 LXSLL-1110A PIT-1110A I-111 I-112 I-113 LSHH-1110A LSLL-1110A LXIT-1110A I-113 LIT-1110A-2 LIT-1110A-1 FIT-1110A-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
V-1110A FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110A FIT-1110A-1
AI-1110A FI-1110A-1 FQI-1110A-1 FI-1110A-2 FQI-1110A-2 LI-1110A-1 LAH-1110A-1 LAL-1110A-1 LALL-1110A-1 LIC-1110A-2 LAH-1110A-2 LAHH-1110A-2 LAL-1110A-2 LAHH-1110A LALL-1110A LXIC-1110A LXAH-1110A LXAL-1110A LXALL-1110A PIC-1110A-1/2/3 PAH-1110A PAHH-1110A PAL-1110A TI-1110A
0-10000 BPD
~5%
085-12-004F 085-12-004F
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F C M M O
C C
~2%
~1%
085-12-004F
Page 11 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110A I-113 I-113 LXSLL-1110A PIT-1110A I-111 I-112 I-113 LSHH-1110A LSLL-1110A LXIT-1110A I-113 LIT-1110A-2 LIT-1110A-1 FIT-1110A-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
V-1110A FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110A FIT-1110A-1
AI-1110A FI-1110A-1 FQI-1110A-1 FI-1110A-2 FQI-1110A-2 LI-1110A-1 LAH-1110A-1 LAL-1110A-1 LALL-1110A-1 LIC-1110A-2 LAH-1110A-2 LAHH-1110A-2 LAL-1110A-2 LAHH-1110A LALL-1110A LXIC-1110A LXAH-1110A LXAL-1110A LXALL-1110A PIC-1110A-1/2/3 PAH-1110A PAHH-1110A PAL-1110A TI-1110A
0-10000 BPD
~5%
085-12-004F 085-12-004F
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F
~2%
~1%
085-12-004F
Page 12 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110A I-113 I-113 LXSLL-1110A PIT-1110A I-111 I-112 I-113 LSHH-1110A LSLL-1110A LXIT-1110A I-113 LIT-1110A-2 LIT-1110A-1 FIT-1110A-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
V-1110A FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110A FIT-1110A-1
AI-1110A FI-1110A-1 FQI-1110A-1 FI-1110A-2 FQI-1110A-2 LI-1110A-1 LAH-1110A-1 LAL-1110A-1 LALL-1110A-1 LIC-1110A-2 LAH-1110A-2 LAHH-1110A-2 LAL-1110A-2 LAHH-1110A LALL-1110A LXIC-1110A LXAH-1110A LXAL-1110A LXALL-1110A PIC-1110A-1/2/3 PAH-1110A PAHH-1110A PAL-1110A TI-1110A
0-10000 BPD
~5%
085-12-004F 085-12-004F
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F 085-12-004F
~2%
~1%
085-12-004F
Page 13 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110B I-110 I-110 LXSLL-1110B PIT-1110B I-108 I-109 I-110 LSHH-1110B LSLL-1110B LXIT-1110B I-110 LIT-1110B-2 LIT-1110B-1 FIT-1110B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129
V-1110B FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110B FIT-1110B-1
AI-1110B FI-1110B-1 FQI-1110B-1 FI-1110B-2 FQI-1110B-2 LI-1110B-1 LAH-1110B-1 LAL-1110B-1 LALL-1110B-1 LIC-1110B-2 LAH-1110B-2 LAHH-1110B-2 LAL-1110B-2 LAHH-1110B LALL-1110B LXIC-1110B LXAH-1110B LXAL-1110B LXALL-1110B PIC-1110B-1/2/3 PAH-1110B PAHH-1110B PAL-1110B TI-1110B
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-10000 BPD
~5%
085-12-004G 085-12-004G
0-126 " WC 6'-0" 4'-0" 9'-6" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G
~2%
~1%
085-12-004G
Page 14 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110B I-110 I-110 LXSLL-1110B PIT-1110B I-108 I-109 I-110 LSHH-1110B LSLL-1110B LXIT-1110B I-110 LIT-1110B-2 LIT-1110B-1 FIT-1110B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129
V-1110B FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110B FIT-1110B-1
AI-1110B FI-1110B-1 FQI-1110B-1 FI-1110B-2 FQI-1110B-2 LI-1110B-1 LAH-1110B-1 LAL-1110B-1 LALL-1110B-1 LIC-1110B-2 LAH-1110B-2 LAHH-1110B-2 LAL-1110B-2 LAHH-1110B LALL-1110B LXIC-1110B LXAH-1110B LXAL-1110B LXALL-1110B PIC-1110B-1/2/3 PAH-1110B PAHH-1110B PAL-1110B TI-1110B
0-10000 BPD
~5%
085-12-004G 085-12-004G
0-126 " WC 6'-0" 4'-0" 9'-6" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G C M M O
C C
~2%
~1%
085-12-004G
Page 15 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110B I-110 I-110 LXSLL-1110B PIT-1110B I-108 I-109 I-110 LSHH-1110B LSLL-1110B LXIT-1110B I-110 LIT-1110B-2 LIT-1110B-1 FIT-1110B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129
V-1110B FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110B FIT-1110B-1
AI-1110B FI-1110B-1 FQI-1110B-1 FI-1110B-2 FQI-1110B-2 LI-1110B-1 LAH-1110B-1 LAL-1110B-1 LALL-1110B-1 LIC-1110B-2 LAH-1110B-2 LAHH-1110B-2 LAL-1110B-2 LAHH-1110B LALL-1110B LXIC-1110B LXAH-1110B LXAL-1110B LXALL-1110B PIC-1110B-1/2/3 PAH-1110B PAHH-1110B PAL-1110B TI-1110B
0-10000 BPD
~5%
085-12-004G 085-12-004G
0-126 " WC 6'-0" 4'-0" 9'-6" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G
~2%
~1%
085-12-004G
Page 16 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110B I-110 I-110 LXSLL-1110B PIT-1110B I-108 I-109 I-110 LSHH-1110B LSLL-1110B LXIT-1110B I-110 LIT-1110B-2 LIT-1110B-1 FIT-1110B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129
V-1110B FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110B FIT-1110B-1
AI-1110B FI-1110B-1 FQI-1110B-1 FI-1110B-2 FQI-1110B-2 LI-1110B-1 LAH-1110B-1 LAL-1110B-1 LALL-1110B-1 LIC-1110B-2 LAH-1110B-2 LAHH-1110B-2 LAL-1110B-2 LAHH-1110B LALL-1110B LXIC-1110B LXAH-1110B LXAL-1110B LXALL-1110B PIC-1110B-1/2/3 PAH-1110B PAHH-1110B PAL-1110B TI-1110B
0-10000 BPD
~5%
085-12-004G 085-12-004G
0-126 " WC 6'-0" 4'-0" 9'-6" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G 085-12-004G
~2%
~1%
085-12-004G
Page 17 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110C I-116 I-116 LXSLL-1110C PIT-1110C I-114 I-115 I-116 LSHH-1110C LSLL-1110C LXIT-1110C I-116 LIT-1110C-2 LIT-1110C-1 FIT-1110C-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154
V-1110C FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110C FIT-1110C-1
AI-1110C FI-1110C-1 FQI-1110C-1 FI-1110C-2 FQI-1110C-2 LI-1110C-1 LAH-1110C-1 LAL-1110C-1 LALL-1110C-1 LIC-1110C-2 LAH-1110C-2 LAHH-1110C-2 LAL-1110C-2 LAHH-1110C LALL-1110C LXIC-1110C LXAH-1110C LXAL-1110C LXALL-1110C PIC-1110C-1/2/3 PAH-1110C PAHH-1110C PAL-1110C TI-1110C
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-10000 BPD
~5%
085-12-004H 085-12-004H
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H
~2%
~1%
085-12-004H
Page 18 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110C I-116 I-116 LXSLL-1110C PIT-1110C I-114 I-115 I-116 LSHH-1110C LSLL-1110C LXIT-1110C I-116 LIT-1110C-2 LIT-1110C-1 FIT-1110C-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154
V-1110C FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110C FIT-1110C-1
AI-1110C FI-1110C-1 FQI-1110C-1 FI-1110C-2 FQI-1110C-2 LI-1110C-1 LAH-1110C-1 LAL-1110C-1 LALL-1110C-1 LIC-1110C-2 LAH-1110C-2 LAHH-1110C-2 LAL-1110C-2 LAHH-1110C LALL-1110C LXIC-1110C LXAH-1110C LXAL-1110C LXALL-1110C PIC-1110C-1/2/3 PAH-1110C PAHH-1110C PAL-1110C TI-1110C
0-10000 BPD
~5%
085-12-004H 085-12-004H
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H C M M O
C C
~2%
~1%
085-12-004H
Page 19 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110C I-116 I-116 LXSLL-1110C PIT-1110C I-114 I-115 I-116 LSHH-1110C LSLL-1110C LXIT-1110C I-116 LIT-1110C-2 LIT-1110C-1 FIT-1110C-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154
V-1110C FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110C FIT-1110C-1
AI-1110C FI-1110C-1 FQI-1110C-1 FI-1110C-2 FQI-1110C-2 LI-1110C-1 LAH-1110C-1 LAL-1110C-1 LALL-1110C-1 LIC-1110C-2 LAH-1110C-2 LAHH-1110C-2 LAL-1110C-2 LAHH-1110C LALL-1110C LXIC-1110C LXAH-1110C LXAL-1110C LXALL-1110C PIC-1110C-1/2/3 PAH-1110C PAHH-1110C PAL-1110C TI-1110C
0-10000 BPD
~5%
085-12-004H 085-12-004H
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H
~2%
~1%
085-12-004H
Page 20 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110C I-116 I-116 LXSLL-1110C PIT-1110C I-114 I-115 I-116 LSHH-1110C LSLL-1110C LXIT-1110C I-116 LIT-1110C-2 LIT-1110C-1 FIT-1110C-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154
V-1110C FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110C FIT-1110C-1
AI-1110C FI-1110C-1 FQI-1110C-1 FI-1110C-2 FQI-1110C-2 LI-1110C-1 LAH-1110C-1 LAL-1110C-1 LALL-1110C-1 LIC-1110C-2 LAH-1110C-2 LAHH-1110C-2 LAL-1110C-2 LAHH-1110C LALL-1110C LXIC-1110C LXAH-1110C LXAL-1110C LXALL-1110C PIC-1110C-1/2/3 PAH-1110C PAHH-1110C PAL-1110C TI-1110C
0-10000 BPD
~5%
085-12-004H 085-12-004H
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H 085-12-004H
~2%
~1%
085-12-004H
Page 21 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110D I-119 I-119 LXSLL-1110D PIT-1110D I-117 I-118 I-119 LSHH-1110D LSLL-1110D LXIT-1110D I-119 LIT-1110D-2 LIT-1110D-1 FIT-1110D-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179
V-1110D FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110D FIT-1110D-1
AI-1110D FI-1110D-1 FQI-1110D-1 FI-1110D-2 FQI-1110D-2 LI-1110D-1 LAH-1110D-1 LAL-1110D-1 LALL-1110D-1 LIC-1110D-2 LAH-1110D-2 LAHH-1110D-2 LAL-1110D-2 LAHH-1110D LALL-1110D LXIC-1110D LXAH-1110D LXAL-1110D LXALL-1110D PIC-1110D-1/2/3 PAH-1110D PAHH-1110D PAL-1110D TI-1110D
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-10000 BPD
~5%
085-12-004J 085-12-004J
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J
~2%
~1%
085-12-004J
Page 22 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110D I-119 I-119 LXSLL-1110D PIT-1110D I-117 I-118 I-119 LSHH-1110D LSLL-1110D LXIT-1110D I-119 LIT-1110D-2 LIT-1110D-1 FIT-1110D-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179
V-1110D FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110D FIT-1110D-1
AI-1110D FI-1110D-1 FQI-1110D-1 FI-1110D-2 FQI-1110D-2 LI-1110D-1 LAH-1110D-1 LAL-1110D-1 LALL-1110D-1 LIC-1110D-2 LAH-1110D-2 LAHH-1110D-2 LAL-1110D-2 LAHH-1110D LALL-1110D LXIC-1110D LXAH-1110D LXAL-1110D LXALL-1110D PIC-1110D-1/2/3 PAH-1110D PAHH-1110D PAL-1110D TI-1110D
0-10000 BPD
~5%
085-12-004J 085-12-004J
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J C M M O
C C
~2%
~1%
085-12-004J
Page 23 of 57
PY-1110D-2 M
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110D I-119 I-119 LXSLL-1110D PIT-1110D I-117 I-118 I-119 LSHH-1110D LSLL-1110D LXIT-1110D I-119 LIT-1110D-2 LIT-1110D-1 FIT-1110D-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179
V-1110D FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110D FIT-1110D-1
AI-1110D FI-1110D-1 FQI-1110D-1 FI-1110D-2 FQI-1110D-2 LI-1110D-1 LAH-1110D-1 LAL-1110D-1 LALL-1110D-1 LIC-1110D-2 LAH-1110D-2 LAHH-1110D-2 LAL-1110D-2 LAHH-1110D LALL-1110D LXIC-1110D LXAH-1110D LXAL-1110D LXALL-1110D PIC-1110D-1/2/3 PAH-1110D PAHH-1110D PAL-1110D TI-1110D
0-10000 BPD
~5%
085-12-004J 085-12-004J
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J
~2%
~1%
085-12-004J
Page 24 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA DI AI SCADA SCADA SCADA AI TIT-1110D I-119 I-119 LXSLL-1110D PIT-1110D I-117 I-118 I-119 LSHH-1110D LSLL-1110D LXIT-1110D I-119 LIT-1110D-2 LIT-1110D-1 FIT-1110D-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-50 % BS&W 0-75000 BPD
Dead Band
PID
155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179
V-1110D FWKO
Analyzer Indicating Transmitter - FWKO Oil Outlet Flow Indicating Transmitter - Magmeter - FWKO Produced Water Outlet Totalized Flow Indicator - FWKO Produced Water Outlet Flow Indicating Transmitter - Turbine - FWKO Oil Outlet Flow Indicator - FWKO Oil Outlet Level Indicating Transmitter - DP - FWKO Water Level Alarm High - FWKO Water Level Alarm Low - FWKO Water Level Alarm Low-Low - FWKO Water Level Indicating Transmitter - DP - FWKO Oil Level Alarm High - FWKO Oil Level Alarm High-High - FWKO Oil Level Alarm Low - FWKO Oil Level Switch High-High - FWKO Oil Level Switch Low-Low - FWKO Oil Interface Level Indicating Transmitter - FWKO Oil/Water Interface Level Interface Alarm High - FWKO Produced Water Outlet Level Interface Alarm Low - FWKO Produced Water Outlet Level Interface Switch Low-Low - FWKO Pressure Indicating Transmitter - FWKO Pressure Alarm High - FWKO Pressure Alarm High-High - FWKO Pressure Alarm Low - FWKO Temperature Indicating Transmitter - FWKO Oil Outlet
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1110D FIT-1110D-1
AI-1110D FI-1110D-1 FQI-1110D-1 FI-1110D-2 FQI-1110D-2 LI-1110D-1 LAH-1110D-1 LAL-1110D-1 LALL-1110D-1 LIC-1110D-2 LAH-1110D-2 LAHH-1110D-2 LAL-1110D-2 LAHH-1110D LALL-1110D LXIC-1110D LXAH-1110D LXAL-1110D LXALL-1110D PIC-1110D-1/2/3 PAH-1110D PAHH-1110D PAL-1110D TI-1110D
0-10000 BPD
~5%
085-12-004J 085-12-004J
0-126 " WC 9'-6" 6'-0" 4'-0" -125 to -17.8 " WC 10'-0" 8'-0" 5'-0" 12'-0" 4'-0" 0-114 " WC 9'-6" 8'-6" 4'-0" 0-150 PSIG 80 PSIG 95 PSIG 40 PSIG 0-300 F
~5%
~5%
085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J 085-12-004J
~2%
~1%
085-12-004J
Page 25 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120A-4 I-102 TIT-1120A-3 I-102 TIT-1120A-1 TIT-1120A-2 PIT-1120A-2 I-102 I-120 PIT-1120A-1 LIT-1120A-2 I-120 FIT-1120A-2 LIT-1120A-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120A-1
FIC-1120A-1 FAH-1120A-1 FI-1120A-2 LIC-1120A-1 LAH-1120A-1 LAL-1120A-1 LI-1120A-2 LAHH-1120A-2 LALL-1120A-2 PIC-1120A-1 PAH-1120A-1 PAL-1120A-1 PI-1120A-2 PAHH-1120A-2 TI-1120A-1 TIC-1120A-2 TAH-1120A-2 TAL-1120A-2 TI-1120A-3 TAHH-1120A-3 TAL-1120A-3 TI-1120A-4 TAH-1120A-4
085-12-004K 085-12-004K
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004K 085-12-004K
~1% ~1%
~1%
~1%
085-12-004K 085-12-004K
Page 26 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120A-4 I-102 TIT-1120A-3 I-102 TIT-1120A-1 TIT-1120A-2 PIT-1120A-2 I-102 I-120 PIT-1120A-1 LIT-1120A-2 I-120 FIT-1120A-2 LIT-1120A-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120A-1
FIC-1120A-1 FAH-1120A-1 FI-1120A-2 LIC-1120A-1 LAH-1120A-1 LAL-1120A-1 LI-1120A-2 LAHH-1120A-2 LALL-1120A-2 PIC-1120A-1 PAH-1120A-1 PAL-1120A-1 PI-1120A-2 PAHH-1120A-2 TI-1120A-1 TIC-1120A-2 TAH-1120A-2 TAL-1120A-2 TI-1120A-3 TAHH-1120A-3 TAL-1120A-3 TI-1120A-4 TAH-1120A-4
085-12-004K 085-12-004K
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004K 085-12-004K
~1% ~1%
~1%
~1%
085-12-004K 085-12-004K
Page 27 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120A-4 I-102 TIT-1120A-3 I-102 TIT-1120A-1 TIT-1120A-2 PIT-1120A-2 I-102 I-120 PIT-1120A-1 LIT-1120A-2 I-120 FIT-1120A-2 LIT-1120A-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120A-1
FIC-1120A-1 FAH-1120A-1 FI-1120A-2 LIC-1120A-1 LAH-1120A-1 LAL-1120A-1 LI-1120A-2 LAHH-1120A-2 LALL-1120A-2 PIC-1120A-1 PAH-1120A-1 PAL-1120A-1 PI-1120A-2 PAHH-1120A-2 TI-1120A-1 TIC-1120A-2 TAH-1120A-2 TAL-1120A-2 TI-1120A-3 TAHH-1120A-3 TAL-1120A-3 TI-1120A-4 TAH-1120A-4
085-12-004K 085-12-004K
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004K 085-12-004K C
~1% ~1%
~1%
~1%
085-12-004K 085-12-004K
Page 28 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120A-4 I-102 TIT-1120A-3 I-102 TIT-1120A-1 TIT-1120A-2 PIT-1120A-2 I-102 I-120 PIT-1120A-1 LIT-1120A-2 I-120 FIT-1120A-2 LIT-1120A-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120A-1
FIC-1120A-1 FAH-1120A-1 FI-1120A-2 LIC-1120A-1 LAH-1120A-1 LAL-1120A-1 LI-1120A-2 LAHH-1120A-2 LALL-1120A-2 PIC-1120A-1 PAH-1120A-1 PAL-1120A-1 PI-1120A-2 PAHH-1120A-2 TI-1120A-1 TIC-1120A-2 TAH-1120A-2 TAL-1120A-2 TI-1120A-3 TAHH-1120A-3 TAL-1120A-3 TI-1120A-4 TAH-1120A-4
085-12-004K 085-12-004K
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004K 085-12-004K
~1% ~1%
~1%
~1%
085-12-004K 085-12-004K
Page 29 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120B-4 I-103 TIT-1120B-3 I-103 TIT-1120B-1 TIT-1120B-2 PIT-1120B-2 I-103 I-121 PIT-1120B-1 LIT-1120B-2 I-121 FIT-1120B-2 LIT-1120B-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120B-1
FIC-1120B-1 FAH-1120B-1 FI-1120B-2 LIC-1120B-1 LAH-1120B-1 LAL-1120B-1 LI-1120B-2 LAHH-1120B-2 LALL-1120B-2 PIC-1120B-1 PAH-1120B-1 PAL-1120B-1 PI-1120B-2 PAHH-1120B-2 TI-1120B-1 TIC-1120B-2 TAH-1120B-2 TAL-1120B-2 TI-1120B-3 TAHH-1120B-3 TAL-1120B-3 TI-1120B-4 TAH-1120B-4
085-12-004L 085-12-004L
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004L 085-12-004L
~1% ~1%
~1%
~1%
085-12-004L 085-12-004L
Page 30 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120B-4 I-103 TIT-1120B-3 I-103 TIT-1120B-1 TIT-1120B-2 PIT-1120B-2 I-103 I-121 PIT-1120B-1 LIT-1120B-2 I-121 FIT-1120B-2 LIT-1120B-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120B-1
FIC-1120B-1 FAH-1120B-1 FI-1120B-2 LIC-1120B-1 LAH-1120B-1 LAL-1120B-1 LI-1120B-2 LAHH-1120B-2 LALL-1120B-2 PIC-1120B-1 PAH-1120B-1 PAL-1120B-1 PI-1120B-2 PAHH-1120B-2 TI-1120B-1 TIC-1120B-2 TAH-1120B-2 TAL-1120B-2 TI-1120B-3 TAHH-1120B-3 TAL-1120B-3 TI-1120B-4 TAH-1120B-4
085-12-004L 085-12-004L
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004L 085-12-004L
~1% ~1%
~1%
~1%
085-12-004L 085-12-004L
Page 31 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120B-4 I-103 TIT-1120B-3 I-103 TIT-1120B-1 TIT-1120B-2 PIT-1120B-2 I-103 I-121 PIT-1120B-1 LIT-1120B-2 I-121 FIT-1120B-2 LIT-1120B-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120B-1
FIC-1120B-1 FAH-1120B-1 FI-1120B-2 LIC-1120B-1 LAH-1120B-1 LAL-1120B-1 LI-1120B-2 LAHH-1120B-2 LALL-1120B-2 PIC-1120B-1 PAH-1120B-1 PAL-1120B-1 PI-1120B-2 PAHH-1120B-2 TI-1120B-1 TIC-1120B-2 TAH-1120B-2 TAL-1120B-2 TI-1120B-3 TAHH-1120B-3 TAL-1120B-3 TI-1120B-4 TAH-1120B-4
085-12-004L 085-12-004L
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004L 085-12-004L C
~1% ~1%
~1%
~1%
085-12-004L 085-12-004L
Page 32 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA SCADA AI SCADA TIT-1120B-4 I-103 TIT-1120B-3 I-103 TIT-1120B-1 TIT-1120B-2 PIT-1120B-2 I-103 I-121 PIT-1120B-1 LIT-1120B-2 I-121 FIT-1120B-2 LIT-1120B-1
Interlock #
Field Device
Tag
Scale / Setpoint
NOTE 2 15,000 BPD 0-15000 LB/HR
Dead Band
~5%
PID
204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227
Flow Indicating Transmitter - Turbine - Emulsion Heater Oil Inlet Flow Alarm High - Emulsion Heater Oil Inlet Flow Indicating Transmitter - Ultrasonic - Emulsion Heater Condensate Outlet Level Indicating Transmitter - DP - Emulsion Heater Condensate Level Alarm High - Emulsion Heater Condensate Level Alarm Low - Emulsion Heater Condensate Level Indicating Transmitter - DP - Emulsion Heater Steam Condensate Level Alarm High-High - Emulsion Heater Level Alarm Low-Low - Emulsion Heater Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High - Emulsion Heater Steam Inlet Pressure Alarm Low - Emulsion Heater Steam Inlet Pressure Indicating Transmitter - Emulsion Heater Steam Inlet Pressure Alarm High-High - Emulsion Heater Steam Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Inlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Local Alarm - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Oil Outlet Temperature Alarm High-High - Emulsion Heater Oil Outlet Temperature Alarm Low - Emulsion Heater Oil Outlet Temperature Indicating Transmitter - Emulsion Heater Condensate Temperature Alarm High - Emulsion Heater Condensate
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
FIT-1120B-1
FIC-1120B-1 FAH-1120B-1 FI-1120B-2 LIC-1120B-1 LAH-1120B-1 LAL-1120B-1 LI-1120B-2 LAHH-1120B-2 LALL-1120B-2 PIC-1120B-1 PAH-1120B-1 PAL-1120B-1 PI-1120B-2 PAHH-1120B-2 TI-1120B-1 TIC-1120B-2 TAH-1120B-2 TAL-1120B-2 TI-1120B-3 TAHH-1120B-3 TAL-1120B-3 TI-1120B-4 TAH-1120B-4
085-12-004L 085-12-004L
~5% ~5%
~5%
0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 240 F 190 F 0-300 F 250 F 190 F 0-300 F 320 F
~2%
~2%
085-12-004L 085-12-004L
~1% ~1%
~1%
~1%
085-12-004L 085-12-004L
Page 33 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130A I-104 PIT-1130A I-122 I-123 LSHH-1130A LSLL-1130A LXIT-1130A I-124 LIT-1130A-2 LIT-1130A-1 FIT-1130A-2 FIT-1130A-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130A
AIC-1130A AAH-1130A FI-1130A-1 FQI-1130A-1 FI-1130A-2 FQI-1130A-2 LI-1130A-1 LAH-1130A-1 LAL-1130A-1 LALL-1130A-1 LIC-1130A-2 LAHH-1130A-2 LAH-1130A-2 LAL-1130A-2 LAHH-1130A LALL-1130A LXIC-1130A LXAH-1130A LXAL-1130A PIC-1130A-1/2 PAHH-1130A PAH-1130A PAL-1130A PALL-1130A TI-1130A TAL-1130A HC-1130A
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-20000 BPD
~5%
085-12-004N 085-12-004N
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Page 34 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130A I-104 PIT-1130A I-122 I-123 LSHH-1130A LSLL-1130A LXIT-1130A I-124 LIT-1130A-2 LIT-1130A-1 FIT-1130A-2 FIT-1130A-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130A
AIC-1130A AAH-1130A FI-1130A-1 FQI-1130A-1 FI-1130A-2 FQI-1130A-2 LI-1130A-1 LAH-1130A-1 LAL-1130A-1 LALL-1130A-1 LIC-1130A-2 LAHH-1130A-2 LAH-1130A-2 LAL-1130A-2 LAHH-1130A LALL-1130A LXIC-1130A LXAH-1130A LXAL-1130A PIC-1130A-1/2 PAHH-1130A PAH-1130A PAL-1130A PALL-1130A TI-1130A TAL-1130A HC-1130A
0-20000 BPD
~5%
085-12-004N 085-12-004N
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Page 35 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130A I-104 PIT-1130A I-122 I-123 LSHH-1130A LSLL-1130A LXIT-1130A I-124 LIT-1130A-2 LIT-1130A-1 FIT-1130A-2 FIT-1130A-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130A
AIC-1130A AAH-1130A FI-1130A-1 FQI-1130A-1 FI-1130A-2 FQI-1130A-2 LI-1130A-1 LAH-1130A-1 LAL-1130A-1 LALL-1130A-1 LIC-1130A-2 LAHH-1130A-2 LAH-1130A-2 LAL-1130A-2 LAHH-1130A LALL-1130A LXIC-1130A LXAH-1130A LXAL-1130A PIC-1130A-1/2 PAHH-1130A PAH-1130A PAL-1130A PALL-1130A TI-1130A TAL-1130A HC-1130A
0-20000 BPD
~5%
085-12-004N 085-12-004N
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
C C
~2%
~1%
Page 36 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130A I-104 PIT-1130A I-122 I-123 LSHH-1130A LSLL-1130A LXIT-1130A I-124 LIT-1130A-2 LIT-1130A-1 FIT-1130A-2 FIT-1130A-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130A
AIC-1130A AAH-1130A FI-1130A-1 FQI-1130A-1 FI-1130A-2 FQI-1130A-2 LI-1130A-1 LAH-1130A-1 LAL-1130A-1 LALL-1130A-1 LIC-1130A-2 LAHH-1130A-2 LAH-1130A-2 LAL-1130A-2 LAHH-1130A LALL-1130A LXIC-1130A LXAH-1130A LXAL-1130A PIC-1130A-1/2 PAHH-1130A PAH-1130A PAL-1130A PALL-1130A TI-1130A TAL-1130A HC-1130A
0-20000 BPD
~5%
085-12-004N 085-12-004N
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Page 37 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130B I-104 PIT-1130B I-125 I-126 LSHH-1130B LSLL-1130B LXIT-1130B I-127 LIT-1130B-2 LIT-1130B-1 FIT-1130B-2 FIT-1130B-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130B
AIC-1130B AAH-1130B FI-1130B-1 FQI-1130B-1 FI-1130B-2 FQI-1130B-2 LI-1130B-1 LAH-1130B-1 LAL-1130B-1 LALL-1130B-1 LIC-1130B-2 LAHH-1130B-2 LAH-1130B-2 LAL-1130B-2 LAHH-1130B LALL-1130B LXIC-1130B LXAH-1130B LXAL-1130B PIC-1130B-1/2 PAHH-1130B PAH-1130B PAL-1130B PALL-1130B TI-1130B TAL-1130B HC-1130B
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
0-20000 BPD
~5%
085-12-004P 085-12-004P
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210A-1
~5%
X X X X X X X X X X X X X X X X X X X X X X X
LIT-1210A-2
~5%
LSH-1210A PIT-1210A
LAH-1210A PI-1210A PAH-1210A PAL-1210A -5 to 15 " WC 6" WC 0" WC 0-300 F 215 F 180 F ~1% ~2%
TIT-1210A-2
Page 38 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130B I-104 PIT-1130B I-125 I-126 LSHH-1130B LSLL-1130B LXIT-1130B I-127 LIT-1130B-2 LIT-1130B-1 FIT-1130B-2 FIT-1130B-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130B
AIC-1130B AAH-1130B FI-1130B-1 FQI-1130B-1 FI-1130B-2 FQI-1130B-2 LI-1130B-1 LAH-1130B-1 LAL-1130B-1 LALL-1130B-1 LIC-1130B-2 LAHH-1130B-2 LAH-1130B-2 LAL-1130B-2 LAHH-1130B LALL-1130B LXIC-1130B LXAH-1130B LXAL-1130B PIC-1130B-1/2 PAHH-1130B PAH-1130B PAL-1130B PALL-1130B TI-1130B TAL-1130B HC-1130B
0-20000 BPD
~5%
085-12-004P 085-12-004P
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210A-1
~5%
LIT-1210A-2
~5%
LSH-1210A PIT-1210A
LAH-1210A PI-1210A PAH-1210A PAL-1210A -5 to 15 " WC 6" WC 0" WC 0-300 F 215 F 180 F ~1% ~2%
TIT-1210A-2
Page 39 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130B I-104 PIT-1130B I-125 I-126 LSHH-1130B LSLL-1130B LXIT-1130B I-127 LIT-1130B-2 LIT-1130B-1 FIT-1130B-2 FIT-1130B-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130B
AIC-1130B AAH-1130B FI-1130B-1 FQI-1130B-1 FI-1130B-2 FQI-1130B-2 LI-1130B-1 LAH-1130B-1 LAL-1130B-1 LALL-1130B-1 LIC-1130B-2 LAHH-1130B-2 LAH-1130B-2 LAL-1130B-2 LAHH-1130B LALL-1130B LXIC-1130B LXAH-1130B LXAL-1130B PIC-1130B-1/2 PAHH-1130B PAH-1130B PAL-1130B PALL-1130B TI-1130B TAL-1130B HC-1130B
0-20000 BPD
~5%
085-12-004P 085-12-004P
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
C C
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210A-1
~5%
LIT-1210A-2
~5%
LSH-1210A PIT-1210A
LAH-1210A PI-1210A PAH-1210A PAL-1210A -5 to 15 " WC 6" WC 0" WC 0-300 F 215 F 180 F ~1% ~2%
TIT-1210A-2
Page 40 of 57
PY-1130B-2 M
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA AI SCADA AI SCADA SCADA SCADA AI SCADA SCADA SCADA DI DI AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA TIT-1130B I-104 PIT-1130B I-125 I-126 LSHH-1130B LSLL-1130B LXIT-1130B I-127 LIT-1130B-2 LIT-1130B-1 FIT-1130B-2 FIT-1130B-1
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >33 % BS&W 0-5000 BPD
Dead Band
PID
256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297
Analyzer Indicating Transmitter - Oil Treater Oil Outlet Analyzer Indicating Controller - Oil Treater Oil Outlet Flow Indicating Transmitter - Magmeter - Oil Treater Water Outlet Flow Indicator - Oil Treater Water Outlet Flow Indicating Transmitter - Turbine - Oil Treater Dry Oil Outlet Flow Indicator - Oil Treater Dry Oil Outlet Level Indicating Transmitter - DP - Oil Treater Water Level Indicator - Oil Treater Water Level Alarm High - Oil Treater Water Level Alarm Low - Oil Treater Water Level Indicating Transmitter - DP - Oil Treater Oil Level Indicating Controller - Oil Treater Oil Level Alarm High-High - Oil Treater Oil Level Alarm High - Oil Treater Oil Level Switch High-High - Oil Treater Level Switch Low-Low - Oil Treater Interface Level Indicating Transmitter - Oil Treater Interface Level Indicating Controller - Oil Treater Level Interface Alarm High - Oil Treater Water Outlet Pressure Indicating Transmitter - Oil Treater Pressure Indicating Controller - Oil Treater Pressure Alarm High-High - Oil Treater Pressure Alarm High - Oil Treater Pressure Alarm Low - Oil Treater Temperature Indicating Transmitter - Oil Treater Oil Outlet Temperature Indicator - Oil Treater Oil Outlet Hand Controller - Oil Treater
PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301 PLC-301
AIT-1130B
AIC-1130B AAH-1130B FI-1130B-1 FQI-1130B-1 FI-1130B-2 FQI-1130B-2 LI-1130B-1 LAH-1130B-1 LAL-1130B-1 LALL-1130B-1 LIC-1130B-2 LAHH-1130B-2 LAH-1130B-2 LAL-1130B-2 LAHH-1130B LALL-1130B LXIC-1130B LXAH-1130B LXAL-1130B PIC-1130B-1/2 PAHH-1130B PAH-1130B PAL-1130B PALL-1130B TI-1130B TAL-1130B HC-1130B
0-20000 BPD
~5%
085-12-004P 085-12-004P
-125 to -17.8 " WC 11'-6" 6'-0" 4'-0" -127.4 to -21.2 " WC 10'-0" 8'-0" 5'-0" 2'-6" 4'-0" 0-114 " WC 9'-6" 8'-6" 0-150 PSIG 40 PSIG 50 PSIG 20 PSIG 15 PSIG 0-300 F 200 F
~5%
~5%
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210A-1
~5%
LIT-1210A-2
~5%
LSH-1210A PIT-1210A
LAH-1210A PI-1210A PAH-1210A PAL-1210A -5 to 15 " WC 6" WC 0" WC 0-300 F 215 F 180 F ~1% ~2%
TIT-1210A-2
Page 41 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA AI SCADA SCADA DI AI SCADA SCADA AI SCADA SCADA TIT-1210B-2 I-105 LSH-1210B PIT-1210B LIT-1210B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-338" WC 28'-0" WC 3'-0" WC 0-338 " WC
Dead Band
~5%
PID
298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210B-1
LIC-1210B-1 LAH-1210B-1 LAL-1210B-1 LI-1210B-2 LAHH-1210B-2 LALL-1210B-2 LAH-1210B PI-1210B PAH-1210B PAL-1210B TI-1210B-2 TAH-1210B-2 TAL-1210B-2
X X X X X X X X X X X X X X X X X X X X X X X
~5%
-5 to 15 " WC
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210C-1
~5%
X X X X X X X X X X X X X X X X X X X X X X X
LIT-1210C-2
~5%
LSH-1210C PIT-1210C
TIT-1210C-2
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
XI-1220A XA-1220A YI-1220A YA-1220A ZI-1220A PI-1220A PAHH-1220A PAH-1220A 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
X X X X X X
Page 42 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA AI SCADA SCADA DI AI SCADA SCADA AI SCADA SCADA TIT-1210B-2 I-105 LSH-1210B PIT-1210B LIT-1210B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-338" WC 28'-0" WC 3'-0" WC 0-338 " WC
Dead Band
~5%
PID
298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210B-1
LIC-1210B-1 LAH-1210B-1 LAL-1210B-1 LI-1210B-2 LAHH-1210B-2 LALL-1210B-2 LAH-1210B PI-1210B PAH-1210B PAL-1210B TI-1210B-2 TAH-1210B-2 TAL-1210B-2
~5%
-5 to 15 " WC
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210C-1
~5%
LIT-1210C-2
~5%
LSH-1210C PIT-1210C
TIT-1210C-2
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
XI-1220A XA-1220A YI-1220A YA-1220A ZI-1220A PI-1220A PAHH-1220A PAH-1220A 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Page 43 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA AI SCADA SCADA DI AI SCADA SCADA AI SCADA SCADA TIT-1210B-2 I-105 LSH-1210B PIT-1210B LIT-1210B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-338" WC 28'-0" WC 3'-0" WC 0-338 " WC
Dead Band
~5%
PID
298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210B-1
LIC-1210B-1 LAH-1210B-1 LAL-1210B-1 LI-1210B-2 LAHH-1210B-2 LALL-1210B-2 LAH-1210B PI-1210B PAH-1210B PAL-1210B TI-1210B-2 TAH-1210B-2 TAL-1210B-2
~5%
-5 to 15 " WC
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210C-1
~5%
LIT-1210C-2
~5%
LSH-1210C PIT-1210C
TIT-1210C-2
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
XI-1220A XA-1220A YI-1220A YA-1220A ZI-1220A PI-1220A PAHH-1220A PAH-1220A 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Page 44 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA AI SCADA SCADA DI AI SCADA SCADA AI SCADA SCADA TIT-1210B-2 I-105 LSH-1210B PIT-1210B LIT-1210B-2
Interlock #
Field Device
Tag
Scale / Setpoint
0-338" WC 28'-0" WC 3'-0" WC 0-338 " WC
Dead Band
~5%
PID
298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210B-1
LIC-1210B-1 LAH-1210B-1 LAL-1210B-1 LI-1210B-2 LAHH-1210B-2 LALL-1210B-2 LAH-1210B PI-1210B PAH-1210B PAL-1210B TI-1210B-2 TAH-1210B-2 TAL-1210B-2
~5%
-5 to 15 " WC
~2%
~1%
Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicating Controller - LACT/Reject Tank Level Alarm High - LACT/Reject Tank Level Indicating Transmitter- DP - LACT/Reject Tank Level Indicator - LACT/Reject Tank Level Alarm High-High - LACT/Reject Tank Level Switch High - LACT/Reject Tank Overflow Pressure Indicating Transmitter - LACT/Reject Tank Pressure Indicator - LACT/Reject Tank Pressure Alarm High - LACT/Reject Tank Temperature Transmitter - LACT/Reject Tank Temperature Indicator - LACT/Reject Tank Temperature Alarm High - LACT/Reject Tank
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
LIT-1210C-1
~5%
LIT-1210C-2
~5%
LSH-1210C PIT-1210C
TIT-1210C-2
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
XI-1220A XA-1220A YI-1220A YA-1220A ZI-1220A PI-1220A PAHH-1220A PAH-1220A 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Page 45 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA AI SCADA SCADA SCADA TIT-1220
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >3% BS&W CLOSED
Dead Band
PID
335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371
Analyzer Indicating Transmitter - LACT Charge Pumps Discharge Analyzer Indicating Controller - LACT Charge Pumps Discharge Valve Open Indicator - LACT Charge Pumps Dry Oil Discharge Level Indicating Controller - LACT Charge Pumps Discharge Temperature Indicating Transmitter - LACT Charge Pumps Suction Temperature Indicator - LACT Charge Pumps Suction Temperature Alarm High-High - LACT Charge Pumps Suction Temperature Alarm High - LACT Charge Pumps Suction
AIT-1220
X X X
X X X X X X X X
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Indicator - LACT Charge Pumps Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
NAI SCADA NDI SCADA NDI AI SCADA SCADA SCADA I-107 PIT-1220B
XI-1220B XA-1220B YI-1220B YA-1220B ZI-1220B PI-1220B PAHH-1220B PAH-1220B 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
X X X X X X X
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-135 I-135 PIT-1250A-2 PIT-1250A-1
XI-1250A XA-1250A YI-1250A YA-1250A ZI-1250A PI-1250A-1 PAL-1250A-1 PALL-1250A-1 PI-1250A-2 PAHH-1250A-2 PAH-1250A-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
X X X X X X X X X X X X
Flow Indicating Transmitter - Turbine - Reject Pumps Discharge Temperature Indicating Transmitter - Reject Pumps Suction Temperature Indicator - Reject Pumps Suction Temperature Alarm High-High - Reject Pumps Suction Temperature Alarm High - Reject Pumps Suction
FIT-1250 TIT-1250
~5% ~1%
X X X X X X X X
Page 46 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA AI SCADA SCADA SCADA TIT-1220
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >3% BS&W CLOSED
Dead Band
PID
335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371
Analyzer Indicating Transmitter - LACT Charge Pumps Discharge Analyzer Indicating Controller - LACT Charge Pumps Discharge Valve Open Indicator - LACT Charge Pumps Dry Oil Discharge Level Indicating Controller - LACT Charge Pumps Discharge Temperature Indicating Transmitter - LACT Charge Pumps Suction Temperature Indicator - LACT Charge Pumps Suction Temperature Alarm High-High - LACT Charge Pumps Suction Temperature Alarm High - LACT Charge Pumps Suction
AIT-1220
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Indicator - LACT Charge Pumps Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
NAI SCADA NDI SCADA NDI AI SCADA SCADA SCADA I-107 PIT-1220B
XI-1220B XA-1220B YI-1220B YA-1220B ZI-1220B PI-1220B PAHH-1220B PAH-1220B 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-135 I-135 PIT-1250A-2 PIT-1250A-1
XI-1250A XA-1250A YI-1250A YA-1250A ZI-1250A PI-1250A-1 PAL-1250A-1 PALL-1250A-1 PI-1250A-2 PAHH-1250A-2 PAH-1250A-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Flow Indicating Transmitter - Turbine - Reject Pumps Discharge Temperature Indicating Transmitter - Reject Pumps Suction Temperature Indicator - Reject Pumps Suction Temperature Alarm High-High - Reject Pumps Suction Temperature Alarm High - Reject Pumps Suction
FIT-1250 TIT-1250
~5% ~1%
Page 47 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA AI SCADA SCADA SCADA TIT-1220
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >3% BS&W CLOSED
Dead Band
PID
335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371
Analyzer Indicating Transmitter - LACT Charge Pumps Discharge Analyzer Indicating Controller - LACT Charge Pumps Discharge Valve Open Indicator - LACT Charge Pumps Dry Oil Discharge Level Indicating Controller - LACT Charge Pumps Discharge Temperature Indicating Transmitter - LACT Charge Pumps Suction Temperature Indicator - LACT Charge Pumps Suction Temperature Alarm High-High - LACT Charge Pumps Suction Temperature Alarm High - LACT Charge Pumps Suction
AIT-1220
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Indicator - LACT Charge Pumps Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
NAI SCADA NDI SCADA NDI AI SCADA SCADA SCADA I-107 PIT-1220B
XI-1220B XA-1220B YI-1220B YA-1220B ZI-1220B PI-1220B PAHH-1220B PAH-1220B 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-135 I-135 PIT-1250A-2 PIT-1250A-1
XI-1250A XA-1250A YI-1250A YA-1250A ZI-1250A PI-1250A-1 PAL-1250A-1 PALL-1250A-1 PI-1250A-2 PAHH-1250A-2 PAH-1250A-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Flow Indicating Transmitter - Turbine - Reject Pumps Discharge Temperature Indicating Transmitter - Reject Pumps Suction Temperature Indicator - Reject Pumps Suction Temperature Alarm High-High - Reject Pumps Suction Temperature Alarm High - Reject Pumps Suction
FIT-1250 TIT-1250
~5% ~1%
Page 48 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA SCADA SCADA AI SCADA SCADA SCADA TIT-1220
Interlock #
Field Device
Tag
Scale / Setpoint
0-10 % BS&W >3% BS&W CLOSED
Dead Band
PID
335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371
Analyzer Indicating Transmitter - LACT Charge Pumps Discharge Analyzer Indicating Controller - LACT Charge Pumps Discharge Valve Open Indicator - LACT Charge Pumps Dry Oil Discharge Level Indicating Controller - LACT Charge Pumps Discharge Temperature Indicating Transmitter - LACT Charge Pumps Suction Temperature Indicator - LACT Charge Pumps Suction Temperature Alarm High-High - LACT Charge Pumps Suction Temperature Alarm High - LACT Charge Pumps Suction
AIT-1220
~1%
Torque Indicator - LACT Charge Pump Motor Torque Alarm - LACT Charge Pump Motor Run Status - LACT Charge Pump Motor Fault Alarm - LACT Charge Pump Motor JOA in Auto - LACT Charge Pump Motor Pressure Indicating Transmitter - LACT Charge Pump Discharge Pressure Indicator - LACT Charge Pumps Discharge Pressure Alarm High-High - LACT Charge Pumps Discharge Pressure Alarm High - LACT Charge Pumps Discharge
NAI SCADA NDI SCADA NDI AI SCADA SCADA SCADA I-107 PIT-1220B
XI-1220B XA-1220B YI-1220B YA-1220B ZI-1220B PI-1220B PAHH-1220B PAH-1220B 110% RUNNING FAULT AUTO 0-200 PSIG 130 PSIG 120 PSIG ~2%
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-135 I-135 PIT-1250A-2 PIT-1250A-1
XI-1250A XA-1250A YI-1250A YA-1250A ZI-1250A PI-1250A-1 PAL-1250A-1 PALL-1250A-1 PI-1250A-2 PAHH-1250A-2 PAH-1250A-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V C C C X C
Flow Indicating Transmitter - Turbine - Reject Pumps Discharge Temperature Indicating Transmitter - Reject Pumps Suction Temperature Indicator - Reject Pumps Suction Temperature Alarm High-High - Reject Pumps Suction Temperature Alarm High - Reject Pumps Suction
FIT-1250 TIT-1250
~5% ~1%
Page 49 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-136 I-136 PIT-1250B-2 PIT-1250B-1
Interlock #
Field Device
Tag
Scale / Setpoint
Dead Band
PID
372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
XI-1250B XA-1250B YI-1250B YA-1250B ZI-1250B PI-1250B-1 PAL-1250B-1 PALL-1250B-1 PI-1250B-2 PAHH-1250B-2 PAH-1250B-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
X X X X X X X X X X X
Torque Indicator - Oil Recycle Pump Motor Torque Alarm - Oil Recycle Pump Motor Run Status - Oil Recycle Pump Motor Fault Status - Oil Recycle Pump Motor JOA in Auto - Oil Recycle Pump Motor Pressure Indicating Transmitter - Oil Recycle Pump Suction Pressure Indicator - Oil Recycle Pump Suction Pressure Alarm Low - Oil Recycle Pump Suction Pressure Indicating Transmitter - Oil Recycle Pump Discharge Pressure Indicator - Oil Recycle Pump Discharge Pressure Alarm High-High - Oil Recycle Pump Discharge Temperature Indicating Transmitter - Oil Recycle Pump Suction Temperature Indicator - Oil Recycle Pump Suction Temperature Alarm High-High - Oil Recycle Pump Suction Temperature Alarm High - Oil Recycle Pump Suction
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA SCADA I-137 TIT-1255 I-138 I-138 PIT-1255-2 PIT-1255-1
XI-1255 XA-1255 YI-1255 YA-1255 ZI-1255 PI-1255-1 PAL-1255-1 PALL-1255-1 PI-1255-2 PAHH-1255-2 PAH-1255-2 TI-1255 TAHH-1255 TAH-1255 TAL-1255 250 F 240 F 190 F 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~1% ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
X X X X X X X X X X X X X X X X X X
Analyzer Indicating Transmitter - LACT Unit Oil Outlet Analyzer Indicator - LACT Unit Oil Outlet Analytical Alarm High-High - LACT Unit Oil Outlet Flow Indicating Transmitter - LACT Unit Oil Outlet Flow Indicator - LACT Unit Oil Outlet Flow Switch Low - LACT Unit Sample Line Timer Indicating Controller - LACT Unit Oil Sampler Pressure Indicating Transmitter - LACT Unit Oil Outlet Pressure Indicating Controller - LACT Unit Oil Outlet Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicator - LACT Unit Oil Inlet Basket Strainer Temperature Indicating Transmitter - LACT Unit Oil Outlet Open/Close Command - LACT Unit Oil Inlet
LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC
AIT-1230
X X X X X X X X X X X X X X X X X X
FIT-1230
FI-1230 FQI-1230
FSL-1230
FAL-1230 KIC-1230
PIT-1230
PIC-1230 PI-1230
0-100 PSIG
~2%
085-12-004W 085-12-004W
PIT-1230-1 PDIT-1230
0-150 PSIG
~2%
TIT-1230
TI-1230 XC-1230
0-300 F OPEN
~1%
085-12-004W 085-12-004W
Page 50 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-136 I-136 PIT-1250B-2 PIT-1250B-1
Interlock #
Field Device
Tag
Scale / Setpoint
Dead Band
PID
372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
XI-1250B XA-1250B YI-1250B YA-1250B ZI-1250B PI-1250B-1 PAL-1250B-1 PALL-1250B-1 PI-1250B-2 PAHH-1250B-2 PAH-1250B-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Torque Indicator - Oil Recycle Pump Motor Torque Alarm - Oil Recycle Pump Motor Run Status - Oil Recycle Pump Motor Fault Status - Oil Recycle Pump Motor JOA in Auto - Oil Recycle Pump Motor Pressure Indicating Transmitter - Oil Recycle Pump Suction Pressure Indicator - Oil Recycle Pump Suction Pressure Alarm Low - Oil Recycle Pump Suction Pressure Indicating Transmitter - Oil Recycle Pump Discharge Pressure Indicator - Oil Recycle Pump Discharge Pressure Alarm High-High - Oil Recycle Pump Discharge Temperature Indicating Transmitter - Oil Recycle Pump Suction Temperature Indicator - Oil Recycle Pump Suction Temperature Alarm High-High - Oil Recycle Pump Suction Temperature Alarm High - Oil Recycle Pump Suction
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA SCADA I-137 TIT-1255 I-138 I-138 PIT-1255-2 PIT-1255-1
XI-1255 XA-1255 YI-1255 YA-1255 ZI-1255 PI-1255-1 PAL-1255-1 PALL-1255-1 PI-1255-2 PAHH-1255-2 PAH-1255-2 TI-1255 TAHH-1255 TAH-1255 TAL-1255 250 F 240 F 190 F 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~1% ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Analyzer Indicating Transmitter - LACT Unit Oil Outlet Analyzer Indicator - LACT Unit Oil Outlet Analytical Alarm High-High - LACT Unit Oil Outlet Flow Indicating Transmitter - LACT Unit Oil Outlet Flow Indicator - LACT Unit Oil Outlet Flow Switch Low - LACT Unit Sample Line Timer Indicating Controller - LACT Unit Oil Sampler Pressure Indicating Transmitter - LACT Unit Oil Outlet Pressure Indicating Controller - LACT Unit Oil Outlet Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicator - LACT Unit Oil Inlet Basket Strainer Temperature Indicating Transmitter - LACT Unit Oil Outlet Open/Close Command - LACT Unit Oil Inlet
LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC
AIT-1230
FIT-1230
FI-1230 FQI-1230
FSL-1230
FAL-1230 KIC-1230
PIT-1230
PIC-1230 PI-1230
0-100 PSIG
~2%
085-12-004W 085-12-004W
PIT-1230-1 PDIT-1230
0-150 PSIG
~2%
TIT-1230
TI-1230 XC-1230
0-300 F OPEN
~1%
085-12-004W 085-12-004W
Page 51 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-136 I-136 PIT-1250B-2 PIT-1250B-1
Interlock #
Field Device
Tag
Scale / Setpoint
Dead Band
PID
372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
XI-1250B XA-1250B YI-1250B YA-1250B ZI-1250B PI-1250B-1 PAL-1250B-1 PALL-1250B-1 PI-1250B-2 PAHH-1250B-2 PAH-1250B-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Torque Indicator - Oil Recycle Pump Motor Torque Alarm - Oil Recycle Pump Motor Run Status - Oil Recycle Pump Motor Fault Status - Oil Recycle Pump Motor JOA in Auto - Oil Recycle Pump Motor Pressure Indicating Transmitter - Oil Recycle Pump Suction Pressure Indicator - Oil Recycle Pump Suction Pressure Alarm Low - Oil Recycle Pump Suction Pressure Indicating Transmitter - Oil Recycle Pump Discharge Pressure Indicator - Oil Recycle Pump Discharge Pressure Alarm High-High - Oil Recycle Pump Discharge Temperature Indicating Transmitter - Oil Recycle Pump Suction Temperature Indicator - Oil Recycle Pump Suction Temperature Alarm High-High - Oil Recycle Pump Suction Temperature Alarm High - Oil Recycle Pump Suction
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA SCADA I-137 TIT-1255 I-138 I-138 PIT-1255-2 PIT-1255-1
XI-1255 XA-1255 YI-1255 YA-1255 ZI-1255 PI-1255-1 PAL-1255-1 PALL-1255-1 PI-1255-2 PAHH-1255-2 PAH-1255-2 TI-1255 TAHH-1255 TAH-1255 TAL-1255 250 F 240 F 190 F 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~1% ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V
Analyzer Indicating Transmitter - LACT Unit Oil Outlet Analyzer Indicator - LACT Unit Oil Outlet Analytical Alarm High-High - LACT Unit Oil Outlet Flow Indicating Transmitter - LACT Unit Oil Outlet Flow Indicator - LACT Unit Oil Outlet Flow Switch Low - LACT Unit Sample Line Timer Indicating Controller - LACT Unit Oil Sampler Pressure Indicating Transmitter - LACT Unit Oil Outlet Pressure Indicating Controller - LACT Unit Oil Outlet Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicator - LACT Unit Oil Inlet Basket Strainer Temperature Indicating Transmitter - LACT Unit Oil Outlet Open/Close Command - LACT Unit Oil Inlet
LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC
AIT-1230
FIT-1230
FI-1230 FQI-1230
FSL-1230
FAL-1230 KIC-1230
PIT-1230
PIC-1230 PI-1230
0-100 PSIG
~2%
085-12-004W 085-12-004W
PIT-1230-1 PDIT-1230
0-150 PSIG
~2%
TIT-1230
TI-1230 XC-1230
0-300 F OPEN
~1%
085-12-004W 085-12-004W
Page 52 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA I-136 I-136 PIT-1250B-2 PIT-1250B-1
Interlock #
Field Device
Tag
Scale / Setpoint
Dead Band
PID
372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414
Torque Indicator - Reject Pump Motor Torque Alarm - Reject Pump Motor Run Status - Reject Pump Motor Fault Status - Reject Pump Motor JOA in Auto - Reject Pump Motor Pressure Indicating Transmitter - Reject Pump Suction Pressure Indicator - Reject Pump Suction Pressure Alarm Low - Reject Pump Suction Pressure Indicating Transmitter - Reject Pump Discharge Pressure Indicator - Reject Pump Discharge Pressure Alarm High-High - Reject Pump Discharge
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
XI-1250B XA-1250B YI-1250B YA-1250B ZI-1250B PI-1250B-1 PAL-1250B-1 PALL-1250B-1 PI-1250B-2 PAHH-1250B-2 PAH-1250B-2 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V C C C X C
Torque Indicator - Oil Recycle Pump Motor Torque Alarm - Oil Recycle Pump Motor Run Status - Oil Recycle Pump Motor Fault Status - Oil Recycle Pump Motor JOA in Auto - Oil Recycle Pump Motor Pressure Indicating Transmitter - Oil Recycle Pump Suction Pressure Indicator - Oil Recycle Pump Suction Pressure Alarm Low - Oil Recycle Pump Suction Pressure Indicating Transmitter - Oil Recycle Pump Discharge Pressure Indicator - Oil Recycle Pump Discharge Pressure Alarm High-High - Oil Recycle Pump Discharge Temperature Indicating Transmitter - Oil Recycle Pump Suction Temperature Indicator - Oil Recycle Pump Suction Temperature Alarm High-High - Oil Recycle Pump Suction Temperature Alarm High - Oil Recycle Pump Suction
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
NAI SCADA NDI SCADA NDI AI SCADA SCADA AI SCADA SCADA AI SCADA SCADA SCADA I-137 TIT-1255 I-138 I-138 PIT-1255-2 PIT-1255-1
XI-1255 XA-1255 YI-1255 YA-1255 ZI-1255 PI-1255-1 PAL-1255-1 PALL-1255-1 PI-1255-2 PAHH-1255-2 PAH-1255-2 TI-1255 TAHH-1255 TAH-1255 TAL-1255 250 F 240 F 190 F 110% RUNNING FAULT AUTO 0-50 PSIG 3 PSIG 2 PSIG 0-200 PSIG 180 PSIG 160 PSIG ~1% ~2% ~2%
085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V 085-12-004V C C C C X C
Analyzer Indicating Transmitter - LACT Unit Oil Outlet Analyzer Indicator - LACT Unit Oil Outlet Analytical Alarm High-High - LACT Unit Oil Outlet Flow Indicating Transmitter - LACT Unit Oil Outlet Flow Indicator - LACT Unit Oil Outlet Flow Switch Low - LACT Unit Sample Line Timer Indicating Controller - LACT Unit Oil Sampler Pressure Indicating Transmitter - LACT Unit Oil Outlet Pressure Indicating Controller - LACT Unit Oil Outlet Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicating Transmitter - LACT Unit Oil Inlet Differential Pressure Indicator - LACT Unit Oil Inlet Basket Strainer Temperature Indicating Transmitter - LACT Unit Oil Outlet Open/Close Command - LACT Unit Oil Inlet
LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC LACT PLC
AIT-1230
FIT-1230
FI-1230 FQI-1230
FSL-1230
FAL-1230 KIC-1230
PIT-1230
PIC-1230 PI-1230
0-100 PSIG
~2%
085-12-004W 085-12-004W
PIT-1230-1 PDIT-1230
0-150 PSIG
~2%
TIT-1230
TI-1230 XC-1230
0-300 F OPEN
~1%
085-12-004W 085-12-004W O
Page 53 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO
10
11
12
13
14
15
16
HMI Display
Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
KY-1107D-1
KY-1107D-2
KY-1107A-1
KY-1107A-2
KY-1107B-1
KY-1107B-2
KY-1107C-1
KY-1107C-2
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA AI SCADA I-128 TIT-1215-4 TIT-1215-3 I-128 TIT-1215-1 TIT-1215-2 PIT-1215-2 I-129 PIT-1215-1 I-128 LIT-1215-2 LIT-1215-1 LIC-1215-1 LAH-1215-1 LAL-1215-1 LIC-1215-2 LAHH-1215-2 LAH-1215-2 LAL-1215-2 LALL-1215-2 PIC-1215-1 PAH-1215-1 PAL-1215-1 PI-1215-2 PAHH-1215-2 TI-1215-1 TIC-1215-2 TAH-1215-2 TAL-1215-2 TI-1215-3 TAHH-1215-3 TI-1215-4 TAH-1215-4 0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 210 F 190 F 0-300 F 220 F 0-300 F 320 F
Interlock #
Field Device
Tag
Scale / Setpoint
0-1800 LB/HR
Dead Band
~5%
PID
415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438
Flow Indicating Transmitter - Dry/Reject Oil Heater Condensate Outlet Flow Indicator - Dry/Reject Oil Heater Condensate Outlet Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High - Dry/Reject Oil Heater Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High-High - Dry/Reject Oil Heater Level Alarm High - Dry/Reject Oil Heater Level Alarm Low - Dry/Reject Oil Heater Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Controller - Dry/Reject Oil Heater Steam Inlet Pressure Alarm High - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicator - Dry/Reject Oil Heater Steam Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicating Controller - Dry/Reject Oil Heater Oil Outlet Temperature Alarm High - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicator - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Condensate Temperature Indicator - Dry/Reject Oil Heater Condensate
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
FIT-1215
FI-1215
085-12-004X 085-12-004X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
~5%
~5%
~2%
~2%
085-12-004X 085-12-004X
~1% ~1%
~1%
085-12-004X 085-12-004X
~1%
085-12-004X 085-12-004X
Notes: 1: Strainer F-1105B/C/D & Desander F-1107B/C/D are future. 2: Setpoint by operator. Flow between Emulsion Heaters E-1120A/B to be split manually by operator using valves FV-1120A-1/B-1. Refer to Control Philosophy for further Interlock details. if Treater V-1130A or V-1130B is out of service, FV-1120A-1 is forced full open. 3: 4: 4: 5:
Specific Symbology:
Page 54 of 57
PDY-1107D
PDY-1107A
PDY-1107B
PDY-1107C
HY-1107D
HY-1107A
HY-1107B
HY-1107C
DISPLAY
ALARM
Tag
I-100
Description
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA AI SCADA I-128 TIT-1215-4 TIT-1215-3 I-128 TIT-1215-1 TIT-1215-2 PIT-1215-2 I-129 PIT-1215-1 I-128 LIT-1215-2 LIT-1215-1 LIC-1215-1 LAH-1215-1 LAL-1215-1 LIC-1215-2 LAHH-1215-2 LAH-1215-2 LAL-1215-2 LALL-1215-2 PIC-1215-1 PAH-1215-1 PAL-1215-1 PI-1215-2 PAHH-1215-2 TI-1215-1 TIC-1215-2 TAH-1215-2 TAL-1215-2 TI-1215-3 TAHH-1215-3 TI-1215-4 TAH-1215-4 0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 210 F 190 F 0-300 F 220 F 0-300 F 320 F
Interlock #
Field Device
Tag
Scale / Setpoint
0-1800 LB/HR
Dead Band
~5%
PID
415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438
Flow Indicating Transmitter - Dry/Reject Oil Heater Condensate Outlet Flow Indicator - Dry/Reject Oil Heater Condensate Outlet Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High - Dry/Reject Oil Heater Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High-High - Dry/Reject Oil Heater Level Alarm High - Dry/Reject Oil Heater Level Alarm Low - Dry/Reject Oil Heater Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Controller - Dry/Reject Oil Heater Steam Inlet Pressure Alarm High - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicator - Dry/Reject Oil Heater Steam Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicating Controller - Dry/Reject Oil Heater Oil Outlet Temperature Alarm High - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicator - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Condensate Temperature Indicator - Dry/Reject Oil Heater Condensate
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
FIT-1215
FI-1215
085-12-004X 085-12-004X
~5%
~5%
~2%
~2%
085-12-004X 085-12-004X
~1% ~1%
~1%
085-12-004X 085-12-004X
~1%
085-12-004X 085-12-004X
Notes: 1: Strainer F-1105B/C/D & Desander F-1107B/C/D are future. 2: Setpoint by operator. Flow between Emulsion Heaters E-1120A/B to be split manually by operator using valves FV-1120A-1/B-1. Refer to Control Philosophy for further Interlock details. if Treater V-1130A or V-1130B is out of service, FV-1120A-1 is forced full open. 3: 4: 4: 5:
Specific Symbology:
Page 55 of 57
PY-1110D-2
PY-1110A-2
PY-1110B-2
PY-1110C-2
LY-1110D-2
LY-1110D-3
LY-1110A-2
LY-1110A-3
LY-1110B-2
LY-1110B-3
LY-1110C-2
LY-1110C-3
LXY-1110D
LXY-1110A
LXY-1110B
LXY-1110C
PY-1110D
PY-1110A
PY-1110B
PY-1110C
Tag
Description
AO
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
57
58
56
59
60
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
DO
DO
DO
DO
DO
DO
DO
DO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
AO
PY-1120A-1
PY-1130A-2
PY-1120B-1
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA AI SCADA I-128 TIT-1215-4 TIT-1215-3 I-128 TIT-1215-1 TIT-1215-2 PIT-1215-2 I-129 PIT-1215-1 I-128 LIT-1215-2 LIT-1215-1 LIC-1215-1 LAH-1215-1 LAL-1215-1 LIC-1215-2 LAHH-1215-2 LAH-1215-2 LAL-1215-2 LALL-1215-2 PIC-1215-1 PAH-1215-1 PAL-1215-1 PI-1215-2 PAHH-1215-2 TI-1215-1 TIC-1215-2 TAH-1215-2 TAL-1215-2 TI-1215-3 TAHH-1215-3 TI-1215-4 TAH-1215-4 0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 210 F 190 F 0-300 F 220 F 0-300 F 320 F
Interlock #
Field Device
Tag
Scale / Setpoint
0-1800 LB/HR
Dead Band
~5%
PID
415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438
Flow Indicating Transmitter - Dry/Reject Oil Heater Condensate Outlet Flow Indicator - Dry/Reject Oil Heater Condensate Outlet Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High - Dry/Reject Oil Heater Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High-High - Dry/Reject Oil Heater Level Alarm High - Dry/Reject Oil Heater Level Alarm Low - Dry/Reject Oil Heater Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Controller - Dry/Reject Oil Heater Steam Inlet Pressure Alarm High - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicator - Dry/Reject Oil Heater Steam Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicating Controller - Dry/Reject Oil Heater Oil Outlet Temperature Alarm High - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicator - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Condensate Temperature Indicator - Dry/Reject Oil Heater Condensate
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
FIT-1215
FI-1215
085-12-004X 085-12-004X
~5%
~5%
~2%
~2%
085-12-004X 085-12-004X
~1% ~1%
~1%
085-12-004X 085-12-004X
~1%
085-12-004X 085-12-004X
Notes: 1: Strainer F-1105B/C/D & Desander F-1107B/C/D are future. 2: Setpoint by operator. Flow between Emulsion Heaters E-1120A/B to be split manually by operator using valves FV-1120A-1/B-1. Refer to Control Philosophy for further Interlock details. if Treater V-1130A or V-1130B is out of service, FV-1120A-1 is forced full open. 3: 4: 4: 5:
Specific Symbology:
Page 56 of 57
PY-1130B-2
FY-1120A-1
FY-1120B-1
LY-1130A-2
LY-1130A-3
LY-1130B-2
LY-1130B-3
LXY-1130A
LXY-1130B
PY-1120-4
XY-1120-4
HY-1130A
HY-1130B
AY-1130A
AY-1130B
XY-1120A
PY-1130A
XY-1120B
LY-1120A
LY-1120B
Tag
Description
AO
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
77
76
Effect
CAUSE & EFFECT DIAGRAM Client: AERA ENERGY LLC Unit: Oil Dehydration Project: SAFIRE 8221-001 Legend Date - 07/23/2013 Revision C In Progress Doc. # Legend C - Close / Stop O - Open / Start X - Energize D - De-Energize M - Modulate SP - Setpoint I - Initiate Callout System T - Timed Shutdown PP - Pulse/Pause Pump Action TC- Timer Controlled
Percentage listed is for reference starting point based on signal type. Reference ISA 18.2 Section 10.4.2.2 Alarm Deadband Recommendations
NDO
NDO
NDO
NDO
NDO
NDO
NDO
NAO
NAO
NAO
NAO
DO
DO
AO
AO
AO
SIC-1220A
SIC-1250A
Cause
No. Equipment Description PLC Signal Type
AI SCADA AI SCADA SCADA AI SCADA SCADA SCADA SCADA AI SCADA SCADA AI SCADA AI AI SCADA SCADA AI SCADA AI SCADA I-128 TIT-1215-4 TIT-1215-3 I-128 TIT-1215-1 TIT-1215-2 PIT-1215-2 I-129 PIT-1215-1 I-128 LIT-1215-2 LIT-1215-1 LIC-1215-1 LAH-1215-1 LAL-1215-1 LIC-1215-2 LAHH-1215-2 LAH-1215-2 LAL-1215-2 LALL-1215-2 PIC-1215-1 PAH-1215-1 PAL-1215-1 PI-1215-2 PAHH-1215-2 TI-1215-1 TIC-1215-2 TAH-1215-2 TAL-1215-2 TI-1215-3 TAHH-1215-3 TI-1215-4 TAH-1215-4 0-150 PSIG 60 PSIG 40 PSIG 0-150 PSIG 70 PSIG 0-300 F 0-300 F 210 F 190 F 0-300 F 220 F 0-300 F 320 F
Interlock #
Field Device
Tag
Scale / Setpoint
0-1800 LB/HR
Dead Band
~5%
PID
415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438
Flow Indicating Transmitter - Dry/Reject Oil Heater Condensate Outlet Flow Indicator - Dry/Reject Oil Heater Condensate Outlet Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High - Dry/Reject Oil Heater Level Indicating Transmitter - DP - Dry/Reject Oil Heater Condensate Level Indicating Controller - Dry/Reject Oil Heater Condensate Level Alarm High-High - Dry/Reject Oil Heater Level Alarm High - Dry/Reject Oil Heater Level Alarm Low - Dry/Reject Oil Heater Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Controller - Dry/Reject Oil Heater Steam Inlet Pressure Alarm High - Dry/Reject Oil Heater Steam Inlet Pressure Indicating Transmitter - Dry/Reject Oil Heater Steam Inlet Pressure Indicator - Dry/Reject Oil Heater Steam Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Inlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicating Controller - Dry/Reject Oil Heater Oil Outlet Temperature Alarm High - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Oil Outlet Temperature Indicator - Dry/Reject Oil Heater Oil Outlet Temperature Transmitter - Dry/Reject Oil Heater Condensate Temperature Indicator - Dry/Reject Oil Heater Condensate
PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201 PLC-201
FIT-1215
FI-1215
085-12-004X 085-12-004X
~5%
~5%
~2%
~2%
085-12-004X 085-12-004X
~1% ~1%
~1%
085-12-004X 085-12-004X
~1%
085-12-004X 085-12-004X
Notes: 1: Strainer F-1105B/C/D & Desander F-1107B/C/D are future. 2: Setpoint by operator. Flow between Emulsion Heaters E-1120A/B to be split manually by operator using valves FV-1120A-1/B-1. Refer to Control Philosophy for further Interlock details. if Treater V-1130A or V-1130B is out of service, FV-1120A-1 is forced full open. 3: 4: 4: 5:
Specific Symbology:
Page 57 of 57
PY-1215-1
SIC-1220B
SIC-1250B
LY-1215-1
YS-1220A
YS-1250A
YS-1220B
YS-1250B
SIC-1255
PV-1230
XV-1230
AY-1220
KY-1230
YS-1255
Tag
Description
AO