Type T & TA
Class 10, 30
Description
• Available for starter construction with A, B • UL File No: E48139
& EH contactors and separate panel • CSA File No: LR98336
mounting • Trip indication
• Designed for close couple mounting for 10 • Remote trip and reset option available (T25
contactors, B9 - EH210; all larger are base & all CT type overloads)
mounted • Single phase and phase unbalance
• Separate base mounting available for all protection
overload relays • Isolated alarm circuit (N.O.) contact
• Class 10 adjustable overload relays are • Ambient compensation:
standard with all ABB Line starters -25°C to +55 °C (-13 oF to +131 oF)
• Reset can also be adjusted to function as a • Manual test
stop button • Manual or automatic reset
• Screwdriver guide holes • Factory calibrated and tested
• All terminal screws are available from the • Wide adjustment range
front • Class 30 available, 40-850A (CT Type)
Index
Overload relays
• Features ............................................ 2.1
• OLRs for B9 - B75 contactors ........... 2.2
• OLRs for A95 - EH800 contactors .... 2.3
• Technical data ................................... 2.4
• Approximate dimensions ....... 2.5 - 2.10
AC 1000 – 2/97
OVERLOAD RELAYS: Selection: 2.2 - 2.3 Technical data: 2.4 Approximate dimensions: 2.5 - 2.10
2.1
Overload relays
For contactors B9 - B75
Type T, Class 10
Overload relay selection chart Accessories for the T25 overload relay
For Current Starter Description Catalog List
Catalog List
contactor range suffix number price
number price
sizes (motor fla) code Remote trip AS25-★ $ 40
0.1 - 0.16 T25DU0.16 A Remote reset AR25-★
0.16 - 0.25 T25DU0.25 B
0.25 - 0.4 T25DU0.4 C ★ Select the desired coil voltage from the Coil Voltage Selection chart
0.4 - 0.63 T25DU0.63 D and place the suffix code as the last digit in the catalog number.
2 0.63 - 1.0 T25DU1.0 E
Remote tripping coil
1.0 - 1.4 T25DU1.4 F
The remote tripping unit is operated by a magnetic coil. Some motors
B9
2.2 - 3.1 T25DU3.1 J $ 42 case of excessive heating. This contact would close the coil circuit of
2.8 - 4.0 T25DU4.0 K the tripping unit and mechanically release the thermal overload relay.
3.5 - 5.0 T25DU5.0 L Suitable for use with AC or DC applications.
B40
The overload relay dial should be set on the actual nameplate FLA for
motors with a service factor of 1.0 and may be set at 1.15 times the
FLA rating for motors with a 1.15 service factor.
When installing the relay, set the adjustable dial to the FLA of the
motor using a phillips head screwdriver.
OVERLOAD RELAYS: Selection: 2.2 - 2.3 Technical data: 2.4 Approximate dimensions: 2.5 - 2.10
Overload relay selection chart — Class 10 Overload relay selection chart — Class 30
Starter suffix For Current Catalog Starter List
contactor range number suffix price
For Current Catalog NEMA All List sizes (motor fla)
contactor range number size 4 other price
sizes (motor fla) only sizes 40 … 60 T450SU60 K
55 … 80 T450SU80 L
29 - 42 TA80DU42 A $ 350
70 … 105 T450SU105 M
36 - 52 TA80DU52 B 95 … 140 T450SU140 N
A95 $ 90 EH175, EH210
45
60
-
-
63
80
TA80DU63
TA80DU80 R
C
D
EH260, EH300
130 … 185 T450SU185 P 2
EH450
65 - 90 TA110DU90 S A 165 … 235 T450SU235 R
110 475
A110 220 … 310 T450SU310 S
80 - 110 TA110DU110 T B
285 … 400 T450SU400 T
100 - 135 T200DU135 A
EH145 110 - 150 T200DU150 B 265 … 375 T900SU375 P
thru 150 EH450, EH550 355 … 500 T900SU500 R
EH210 130 - 175 T200DU175 C EH700 550
150 - 200 T200DU200 D 465 … 650 T900SU650 S
EH800 610 … 850 T900SU850 T
130 - 185 T450DU185 A
EH260 165 - 235 T450DU235 B
220 - 310 T450DU310 C Terminal kits
130 - 185 T450DU185 A
165 - 235 T450DU235 B Contactor Overload Wire Catalog List
EH300 type type size number price
220 - 310 T450DU310 C
285 - 400 T450DU400 D 325 EH175, EH210 6 – 250 MCM EHTK210 $ 30
EH260 T450 4 – 500 MCM EHTK260 45
130 - 185 T450DU185 A EH300, EH450 (2) 4 – 500 MCM EHTK550/OL ➀ 75
165 - 235 T450DU235 B
EH450
220 - 310 T450DU310 C EH450, EH550 (2) 4 – 500 MCM EHTK550N 75
285 - 400 T450DU400 D EH700 T900 (2) 4 – 500 MCM EHTK700 100
265 - 375 T900DU375 A EH800 (3) 2 – 600 MCM EHTK800 225
EH550 355 - 500 T900DU500 B
465 - 650 T900DU650 C
265 - 375 T900DU375 A 450 Terminal covers for overload relays
EH700
& 355 - 500 T900DU500 B Contactor Overload Catalog List
EH800 465 - 650 T900DU650 C type type number price
610 - 850 T900DU850 D EH145 - EH210 T200 LT200/160 $ 60
EH175 - EH300 T450 LT450/250 80
EH450 T450 LT450/450 100
Busbar Kits EH450 - EH700 T900 LT900/700 120
Contactor Overload Catalog List EH800 T900 LT900/800 140
type type number price
EH175, EH210 AT450/EH175
EH260, EH300 T450 AT450/EH300 $ 150 Base mounted overload relays for T450 – T900
EH450 AT450/EH450
Catalog number List price
Overload relay type
EH450,EH550 AT900/EH550 suffix adder
EH700 T900 AT900/EH700 200 T450 -B $ 300
EH800 AT900/EH800 T900 -B 425
➀ The standard EHTK300 terminal kit will not mount properly on the busbar; therefore, the EHTK550/OL is required.
OVERLOAD RELAYS: Selection: 2.2 - 2.3 Technical data: 2.4 Approximate dimensions: 2.5 - 2.10
Thermal overload relays T ... DU are 3 pole with manual or automatic reset. The reset button can also be used for disconnection.
The integrated auxiliary contacts are physically separated and are therefore suitable for two different circuits (control circuit, signalling circuit).
All relays are equipped with a component for temperature compensation and phase failure protection.
All overload relays up to size T75 DU are finger protected. Terminal shrouds are available for relays size T80 DU up to T900 DU/SU.
Connecting terminals are delivered in open position, with pozidrive (±) screwhead and screw-driver guide.
T25DU (tripping class 10A) T75DU / TA80DU (tripping class 10A) TA110, T135, T200DU (tripping class 10A)
120 120
2 100
80
120
100
80
100
80
60 60 60
40 40 40
20 20 20
10 10 10
8 8 8
6 6 from cold state 6
4 4 4
from cold state
minutes
minutes
minutes
Tripping time
Tripping time
2 Phase 2 Phase
1 1 1
2 Phase 3 Phase
40 40 3 Phase 40
20 20 2 Phase 20
3 Phase
seconds
seconds
seconds
2 Phase
10 2 Phase 10 3 Phase 10
8 8 8
6 6 6
3 Phase 3 Phase
4 4 4
from warm state
2 from warm state 2 2 from warm state
1 1 1
0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10
T450DU / T900DU (tripping class 10A) T450SU / T900SU (tripping class 30)
120 120
100 100
80 80
60 60
40 40
20 20
10 10
8 8
6 6
4 4
from cold state from cold state
minutes
minutes
2 2
Tripping time
Tripping time
2 Phase 2 Phase
1 1
3 Phase
40 40
3 Phase
20 20
seconds
seconds
2 Phase
10 2 Phase 10
8 8
6 6
3 Phase
4 3 Phase 4
1 1
0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10 0.8 1 1.2 1.5 2 3 4 5 6 7 8 9 10
2.4