Stabilising Resistor LV Side

Transformer Capacity (In MVA) Transformer % Impedance Voltage (In KV) Grounding Resistor CT Ratio Name Plate Full Load Current at LV Side E/F Setting Value CT Resistance Lead Resistance RL Vkp= CT Knee Pt Voltage in volts 600.00 Stabilizing resistor in ohms Stabilizing voltage Set Current (Set Current)x stabilizing Resistor (voltage) x Tr. % Imp MVA Grounding Resistor + Tr % Imp (voltage) Toltal Impedance 1.1(Fault MVA) 1.732 x Voltage 319.271 4.63 HV PRI

800.00 0.22 400.00 0.00 2500.00 2059.82 0.16

LV SEC

224.24 1.00

RCT

4.00

Stabilising Resistor Value Based on LV Voltage

Stabilizing Resistor Continous power Rating in watts Transformer Impedance in ohms

15.877

14.0165

Total Impedance in ohms

14.02

Max. Through Fault MVA (In MVA)

3587.44

Max. Through Fault Current in Amp

10160.5

Secondary Through Fault Current Stabilizing Voltage in Volts 1.5 x Through Fault current (Rct + RL) Vkp

4.06422 52.6113 300

Max. Stabilizing Voltage

2 Max. value of Stablizing Resistor Max St. Voltage Set Current 1820.55

Stabilising Resistor HV Side


Transformer Capacity (In MVA) 800.00 Transformer % Impedance Voltage (In KV) Grounding Resistor CT Ratio Name Plate Full load current at HV side E/F Setting Value 0.15 CT Resistance Lead Resistance CT knee Pt Voltage Vkp in volts Lead Resistance Stabilizing resistor in ohms RL Stabilizing voltage Set Current RCT RL 4.00 4.63 2800.00 4.63 Stablizing Resistor Value based on HV winding HV PRI 0.22 400.00 0.00 1500.00 1154.73 LV SEC 224.24 1.00

319.2713004

Stabilizing Resistor Continous power Rating in watts

(Set Current)x stabilizing Resistor

15.8770425

Transformer Impedance in ohms

(voltage) x Tr. % Imp MVA Grounding Resistor + Tr % Imp (voltage) Toltal Impedance 1.1*Fault MVA 1.732 x Voltage

44.6

Total Impedance in ohms

44.60

Max. Through Fault MVA (In MVA)

3587.443946

Max. Through Fault Current in Amp

5695.999337 3.797332891

Secondary Through Fault Current Stabilizing Voltage in Volts 1.5 x Through Fault current (Rct + RL)

49.15647428

Max. Stabilizing Voltage in volts

Vkp 2 Max St. Voltage Set Current

1400

Max. value of Stablizing Resistor in ohms

9093

Stabilising Resistor LV Side


Breaking Capacity of Breaker in KA Transformer Capacity (In MVA) Transformer % Impedance Voltage (In KV) Grounding Resistor CT Ratio Name Plate Full Load Current at LV Side E/F Setting Value CT Resistance Lead Resistance Vk= CT Knee Pt Voltage in volts Relay Resistance in ohms 60 800.00 0.22 400.00 0.00 2500.00 2059.82 0.07 4.00 4.63 600.00 0.2

HV PRI

LV SEC

RCT RL Rr

Stabilising Resistor Value on LV Voltage

Rs=Stabilizing resistor in ohms

Stabilizing voltage Set Current (Set Current)x stabilizing Resistor (voltage) x Tr. % Imp MVA Grounding Resistor + Tr % Imp (voltage) Toltal Impedance 1.1(Fault MVA) 1.732 x Voltage

Stabilizing Resistor Continous power Rating in watts Transformer Impedance in ohms

Total Impedance in ohms

Max. Through Fault MVA (In MVA)

Max. Through Fault Current in Amp

Secondary Through Fault Current Stabilizing Voltage in Volts 1.5 x Through Fault current (Rct + RL) Vkp 2 Max St. Voltage Set Current

Max. Stabilizing Voltage

Max. value of Stablizing Resistor Thermal Rating of Stabilising Resistor Continous Power Rating in watts Half-Second Power Rating in volts Vf

Pcon=(Icon)xR
((Vk)xRxIfs)x1.3

2nd half power rating (Phalf) in watts

(Vf) Stabilizing Resistor 2(2Vk(Vfs-Vk)) (4/)*Max. Through Fault Current*Vk

Voltage Limiting Resistor Vpk in V P=Metrosil Thermal Power Rating in Joule/sec There fore 6 inch metrosil is required

Fault Setting Ip=assume primary operating current of 0.02A at (nIe+Is+Inlr) setting voltage Ct Ratio n= no ct in parellel

Ie=excieting corrent of each ct Inlr=current in nonlinear resistor at the relay


circuit setting voltage Ish=Current through Shunt Resistor the setting range is 10% to30% of the minimum primary fault current ie 10% 30% Ish in Amp %fault current x (1/ct ratio)-nIe-Is-Inlr Therefore Rsh

224.24 1.00

ising Resistor Value Based on LV Voltage

501.0598265

24.91720411

14.01654726

14.02

3587.443946

10160.54109 4.064216438 35.07418786 300

4285.714286

2.45519315 1745.056528

6077.562248

11879.39392 22909.09091

275

1016.054109 3048.162328 0.296421644

118.3253268