HV network scheme Standardised primary substation HV section: AIS and Hybrid module MV section: Standard and Container section
Use: company
Primary Substation
Use: company
Primary Substations
Enel Distribuzione standard (H) scheme
HV Line HV SECTION SCHEME Simple busbar system with disconnector Two line poles (other lines can be added) Two transformer poles 16 - 25 - 40 or 63 MVA (other transformers can be added) MV SECTION SCHEME Neutral Earthing System
HV/MV Transformers
Disconnector HV Busbar
MV Busbar
Bus-tie CB
Simple busbar system with bus-tie CB Two transformer poles Emergency supply from the other transformer Up to 20 line poles (including auxiliary services)
MV Lines
4
Use: company
Primary Substations
Remote Control System
HV line HV line
HV section
HV/M V transformers
Use: company
Primary Substations
HV line bay and transformer bay
HV line
CVT Disconnector HV busbar
CT Circuit Breaker
Use: company
Primary Substations
HV section Two main solutions
Traditional AIS Substation (Air Insulated Switchgear) MTS Substation with Hybrid Modules (Mixed Technology Switchgear)
GIS
Circuit Breaker
Circuit Breaker Current Transformer Voltage Transformer Disconnector Earthing Switch Busbar / Busducts
Use: company
Primary Substations
Traditional Standardised Primary Substation
HV section - layout
CVT DISC. CB DISC. CT
BUSBAR SYSTEM
TRANSFORMER BAY
21 m
CT
HV LINE BAY
700 m2
32,5 m
8
ARRESTER
DISC.
CB
Use: company
Primary Substations
Traditional Standardised Primary Substation
HV switchboard HV busbar system
Use: company
Primary Substations
MTS Substation Hybrid Modules
HV compact switchgear, integrated and pre-assembled, SF6 insulated, equipped with bushings for the connection to the HV lines (bare conductors or cables), the HV busbars and the transformers.
Three bays with 2 (or 1) circuit breakers (Y2 o Y1), motor driven disconnectors and earthing disconnectors.
One bay with 1 circuit breaker and motor driven disconnector and earthing disconnector.
10
Use: company
Primary Substations
Standard Schemes with Hybrid Modules
CB
Y2 Y2+Y2
CB
CB CB CB
CB
Simplified configuration
11
Use: company
Primary Substations
Standard Schemes with Hybrid Modules
21 m
12 m
250 m2
12
Use: company
Primary Substations
Hybrid Main Characteristics
Rated Characteristics, Enel Specs DY105 (Y1). DY106B (Y2) and DY107B (single bay)
Rated voltage Rated impulse withstand voltage Rated power frequency withstand voltage Rated current Rated short circuit current 170 kV 650 kV 275 kV 1250 A 31,5 kA
13
Use: company
Primary Substations
Y2 type
14
Use: company
Primary Substations
Hybrid Module Basic Components
Plug-in/plug-out
BUSHING
Traditional
CURRENT TRANSFORMER
Use: company
Primary Substations
Hybrid Module Basic Architecture
16
Use: company
Primary Substations
Hybrid Module in operation
CIRCUIT BREAKERS
SPRING M ECHANISM
17
Use: company
Primary Substations
Hybrid Modules solutions
Y1 Hybrid Module
Y2 Hybrid Module with SF6 cable bushings Y2 Hybrid Module with SF6 air and cable bushings Single Bay cable connected Hybrid Module
18
Use: company
Primary Substations
Standardized Primary Substations with Hybrid Modules
ADVANTAGES
reduction of environmental impact and permission easier to obtain (construction under the HV line) reduction of necessary space for installation (compact HV switchboard) limited civil works easily transportable (three pieces per road width) fast installation reduction of mountings and on-site tests (extended prefabrication with tests on manufacturing site) fewer maintenance needs (reduction in component numbers) easy maintenance (reduced times for substitution of integrated components) higher reliability (active HV parts hermetically protected from the environment) total cost reduction
19
Use: company
Primary Substations
Comparison between AIS and MTS HV section
Use: company
Primary Substations
MV section Three main solutions
Single floor air insulated switchgear Double floor air insulated switchgear Compact air insulated switchgear
21
Use: company
Primary Substations
MV section Traditional solutions (single and double floor)
10 m
30 m
22
Use: company
Primary Substations
MV section Compact switchgear
Rated values: - Rated voltage: 24 kV - Rated Current: 1600 A - Short circuit current: 16 kA - Rated duty cycle: O-0,3s-CO-30s-CO
Main characteristics: - Air insulated busbars - Vacuum circuit breakers - Withdrawable circuit breakers - Protections installed on the panels - Compact size: Height 1820 mm; Width 750 or 850 mm; Depth 1200 mm
23
Use: company
Primary Substations
MV Container Section
Extreme modularity and flexibility MV Busbar system with bus-tie circuit breakers Up to 12 MV lines Auxiliary services included Protection and control systems integrated all in one No civil works need, just plug and play
24
Use: company
Primary Substations
MV Container Section
25
Use: company
Primary Substations
MV Container Section
9m
14 m
26
Use: company
Primary Substations
MV Container Section in operation
27
Use: company
Primary Substations
MV Container Section Main advantages
Permission easier to be obtained No buildings needed Easily transportable Fast installation MV switchgear preassembled (no mountings on site) Simplified maintenance operations Enhanced reliability (vacuum CB) Reduction of environmental impact (no SF6) Cost reduction
28
Use: company
Primary Substations
The Neutral Earthing System
Direct connection