PRIMARY SUBSTATIONS

Use: company

Main content

HV network scheme Standardised primary substation HV section: AIS and Hybrid module MV section: Standard and Container section

Neutral earthing system

Use: company

Enel Distribuzione Endesa LATAM Workshop


The HV network
TRANSMISSION NETWORK Transmission Substation Transmission Substation

Primary Substation

Use: company

Primary Substations
Enel Distribuzione standard (H) scheme
HV Line HV SECTION SCHEME Simple busbar system with disconnector Two line poles (other lines can be added) Two transformer poles 16 - 25 - 40 or 63 MVA (other transformers can be added) MV SECTION SCHEME Neutral Earthing System
HV/MV Transformers

Disconnector HV Busbar

MV Busbar

Bus-tie CB

Simple busbar system with bus-tie CB Two transformer poles Emergency supply from the other transformer Up to 20 line poles (including auxiliary services)

MV Lines
4

Use: company

Primary Substations
Remote Control System
HV line HV line

2000 Primary Substations: all remotely controlled

HV section

HV/M V transformers

System connected online to the Network Operating Centers

M V section Neutral earthing system


By means of the remote control system: switches position can be known; main electrical parameters can be measured; closing and opening commands can be sent.

Use: company

Primary Substations
HV line bay and transformer bay
HV line
CVT Disconnector HV busbar

CT Disconnector Earthing Sw itch Circuit Breaker Surge Arrester

CT Circuit Breaker

Transformer Disconnector HV busbar


6

Use: company

Primary Substations
HV section Two main solutions
Traditional AIS Substation (Air Insulated Switchgear) MTS Substation with Hybrid Modules (Mixed Technology Switchgear)

Enel standard since 2000

Hybrid Modules LTB DTB


Circuit Breaker Current Transformer Circuit Breaker Current Transformer Voltage Transformer Disconnector Earthing Switch

GIS

Circuit Breaker

Circuit Breaker Current Transformer Voltage Transformer Disconnector Earthing Switch Busbar / Busducts

Use: company

Primary Substations
Traditional Standardised Primary Substation
HV section - layout
CVT DISC. CB DISC. CT

BUSBAR SYSTEM

TRANSFORMER BAY

21 m

CT

HV LINE BAY

700 m2

32,5 m
8

ARRESTER

DISC.

CB

Use: company

Primary Substations
Traditional Standardised Primary Substation
HV switchboard HV busbar system

Use: company

Primary Substations
MTS Substation Hybrid Modules
HV compact switchgear, integrated and pre-assembled, SF6 insulated, equipped with bushings for the connection to the HV lines (bare conductors or cables), the HV busbars and the transformers.

Three bays with 2 (or 1) circuit breakers (Y2 o Y1), motor driven disconnectors and earthing disconnectors.

One bay with 1 circuit breaker and motor driven disconnector and earthing disconnector.

10

Use: company

Primary Substations
Standard Schemes with Hybrid Modules
CB
Y2 Y2+Y2

CB

CB CB CB

CB

Simplified configuration

Traditional HV/MV (H) Scheme

11

Use: company

Primary Substations
Standard Schemes with Hybrid Modules

21 m

12 m

250 m2
12

Use: company

Primary Substations
Hybrid Main Characteristics

Rated Characteristics, Enel Specs DY105 (Y1). DY106B (Y2) and DY107B (single bay)
Rated voltage Rated impulse withstand voltage Rated power frequency withstand voltage Rated current Rated short circuit current 170 kV 650 kV 275 kV 1250 A 31,5 kA

13

Use: company

Primary Substations
Y2 type

14

Use: company

Primary Substations
Hybrid Module Basic Components

DISCONNECTOR + EARTHING SWITCH CIRCUIT BREAKER

Plug-in/plug-out
BUSHING

Traditional

CURRENT TRANSFORMER

DRY-TYPE CABLE TERMINALS


15

Use: company

Primary Substations
Hybrid Module Basic Architecture

16

Use: company

Primary Substations
Hybrid Module in operation

DISCONNECTORS AND EARTHING SWITCHES

BUSHINGS CURRENT TRANSFORMERS

CIRCUIT BREAKERS

SPRING M ECHANISM

17

Use: company

Primary Substations
Hybrid Modules solutions

Y1 Hybrid Module

Y2 Hybrid Module with SF6 cable bushings Y2 Hybrid Module with SF6 air and cable bushings Single Bay cable connected Hybrid Module
18

Use: company

Primary Substations
Standardized Primary Substations with Hybrid Modules

ADVANTAGES
reduction of environmental impact and permission easier to obtain (construction under the HV line) reduction of necessary space for installation (compact HV switchboard) limited civil works easily transportable (three pieces per road width) fast installation reduction of mountings and on-site tests (extended prefabrication with tests on manufacturing site) fewer maintenance needs (reduction in component numbers) easy maintenance (reduced times for substitution of integrated components) higher reliability (active HV parts hermetically protected from the environment) total cost reduction

19

Use: company

Primary Substations
Comparison between AIS and MTS HV section

Traditional HV section of a Primary Substation

Compact H Primary Substation with Two Y2 Modules


20

Use: company

Primary Substations
MV section Three main solutions
Single floor air insulated switchgear Double floor air insulated switchgear Compact air insulated switchgear

Enel standard since 2000

21

Use: company

Primary Substations
MV section Traditional solutions (single and double floor)

10 m

30 m

22

Use: company

Primary Substations
MV section Compact switchgear

Rated values: - Rated voltage: 24 kV - Rated Current: 1600 A - Short circuit current: 16 kA - Rated duty cycle: O-0,3s-CO-30s-CO

Main characteristics: - Air insulated busbars - Vacuum circuit breakers - Withdrawable circuit breakers - Protections installed on the panels - Compact size: Height 1820 mm; Width 750 or 850 mm; Depth 1200 mm
23

Use: company

Primary Substations
MV Container Section

Extreme modularity and flexibility MV Busbar system with bus-tie circuit breakers Up to 12 MV lines Auxiliary services included Protection and control systems integrated all in one No civil works need, just plug and play
24

Use: company

Primary Substations
MV Container Section

25

Use: company

Primary Substations
MV Container Section

9m

14 m
26

Use: company

Primary Substations
MV Container Section in operation

27

Use: company

Primary Substations
MV Container Section Main advantages

Permission easier to be obtained No buildings needed Easily transportable Fast installation MV switchgear preassembled (no mountings on site) Simplified maintenance operations Enhanced reliability (vacuum CB) Reduction of environmental impact (no SF6) Cost reduction

28

Use: company

Primary Substations
The Neutral Earthing System

Direct connection

Connection by means of Earthing Transformer


29