Outline
Faults in power systems Power system protection Zones of protection Time-delay overcurrent relay Coordination Directional relays Reclosers and sectionalizers
Electric Power Systems - Olof Samuelsson 2
Open-circuit faults
One phase of circuit breaker stuck open Conductor falling down Short-circuit faults more common
Short-circuit faults
Lightning Dirt/salt on insulators Flashover line-line (wind) Flashover to tree Tower/pole or conductor falls Objects fall on conductors Cable insulation failure
Electric Power Systems - Olof Samuelsson 4
10 kV
www.dmi.dk
Electric Power Systems - Olof Samuelsson 5
Galopping spectacular
Heating
Fire and explosion
Heating
Resistive losses RI2 Temperature rise with stored heat energy I2t (no cooling assumed) Same I2t gives equal heating (see graph)
Time Overload
Aims
Continued supply for rest of system Protect faulted part from damage
11
High selectivity
Only react to targeted faults High sensitivity bad
Compromise
Coordination
Which protection unit should react? Isolate as small area as possible Must work also if component fails
Electric Power Systems - Olof Samuelsson 14
Fast
Good for (transient) stability Safety
Electric Power Systems - Olof Samuelsson 13
Zones of protection
Defined for protected objects
Dedicated protection for each zone
Protection types
Overcurrent protection
Lines (distribution)
Differential protection
Lines Transformers Busbars Generators
Ex
Electric Power Systems - Olof Samuelsson 16
15
PT Relay
Trip
Large number of relays needed: One for each phase and fault type
Electric Power Systems - Olof Samuelsson 17
Relative overcurrent
18
Radial system
ISC increases when approaching source R1 has higher current setting than R2 Time
Load1 CB2 R1 R2
Trip
R2
Relative overcurrent
19
Load2
Relative overcurrent
Electric Power Systems - Olof Samuelsson 20
If fuse F2 fails
R1 R2
If R2 or CB2 fails
Load2
R1 not reset Current Extra delay of R1 R1 operates CB1 Isolates fault + Load 2 but also Load 1
F1 F2 Current
Me Neighbor
21
Coordination
Relays 1 and 2 coordinated in example: For the line, Relay 2 provides Primary protection Relay 1 provides Backup protection Always true since t(I) curves do not cross Rule: Longer delay close to source
Electric Power Systems - Olof Samuelsson 23
24
Impedance relay
Let relay measure V/I=Z=R+jX Normally load makes Z > Zline Fault on line makes Z < Zline - TRIP!
X Trip R Radius=|Zline |
Electric Power Systems - Olof Samuelsson 25
26
Distance protection
Series impedance ~ distance along line |Z|<0.8|Zline| equivalent to
Zero fault within 80% of line length The reach of the relay is 80%
G
Time Zone 3 Zone 2 Zone 1
Distance
Electric Power Systems - Olof Samuelsson 27 Electric Power Systems - Olof Samuelsson 28
G
Time
Distance Time
Generators
iin and iout of each winding
Ex
30
R S
R S
R S
R S
R S
S2 Load2 Load3
R opens
R opens S2 opens
32
R closes
System protection
Unit protection=Fault protection
Protects generator, line, transformer Weakens system when tripping CB
Summary
Short-circuit most common fault (lightning) Fuses and protection
Dependable = not miss a fault Selective = not overreact Many relay types One zone for each relay
Limiting blackout-area
Coordination, autoreclosing, autosectionalizing
Electric Power Systems - Olof Samuelsson 35