Anda di halaman 1dari 8

2001TR027 by Math Bollen 1

Algorithms for characterizing measured three-


phase unbalanced voltage dips
Math H.J. Bollen, Senior Member, IEEE

= algorithms are applied to a number of synthetic events to


Abstract— This paper addresses the problem of estimating the compare their performance. One of the algorithms is also
characteristics of three-phase unbalanced voltage dips from applied to a measured event to show some of the
measured phase voltages. This is important for obtaining statistics implementation problems. Finally a range of severe events is
on voltage dips and for obtaining information about the
underlying event (e.g. the fault type). Two different algorithms
used to explain the occurrence of erroneous estimates with the
are compared. The “six-phase algorithm” is computationally algorithm.
simple and easy to interpret. However large phase-angle jumps
lead to wrong estimations. The “symmetrical component II. CHARACTERIZATION
algorithm” gives a correct value in almost all cases. Exceptions
are events with very severe load influence on the voltages during A. The aim of Characterization
the fault. The latter algorithm is studied in more detail: through a
Voltage-dip characterization concerns the quantification of
measurement example and through a study of a range of synthetic
events. The conclusion is that both algorithms have their specific voltage-dip events through a limited number of parameters.
application areas. The forthcoming power-quality measurement standard IEC
Index Terms— electromagnetic compatibility (EMC), power 61000-4-30 uses two parameters: retained voltage and
quality, power quality monitoring, power system faults, voltage duration. The retained voltage is the lowest one-cycle rms
dips (sags). voltage; the duration is the length of time during which the rms
voltage is below a threshold [11]. This constitutes a loss of
I. INTRODUCTION
information for non-rectangular and multistage events but is an

V oltage dips due to non-symmetrical faults will affect


three-phase equipment in a different way than voltage
dips due to symmetrical faults. Therefore additional
appropriate approximation for most
measurements.
single-channel

Multi-channel measurements are characterized by the lowest


characterization effort is needed for these so-called three- retained voltage and the longest duration of all channels. This
phase unbalanced dips (i.e. voltage dips due to non- is only an appropriate approximation for balanced dips,
symmetrical faults). A number of proposals for their whereas the majority of dips are unbalanced. A somewhat
characterization were compared by [1]. Further contributions strange consequence of this is that the dip due to a single-
were made by [2][3][4][5]. Most of this work was directed phase fault in a resistance-grounded system will be quantified
towards obtaining dip characteristics from measurements, the same (or even more severe) as the dip due to a three-phase
without considering the basic circuit theory behind the fault. However a customer behind a Dy-transformer only
phenomenon. An alternative approach was followed in [6]: experiences a severe event in the second case. Some utilities
from analyzing basic fault types in idealized systems, a solve this by connecting their monitors phase-to-phase, but
classification in four dip types was proposed. Although the that will limit the amount of information to be obtained from
classification can be used for stochastic prediction and the monitors. To overcome this and similar problems an
equipment testing [7], it could not directly be used to classify improved dip characterization method has been proposed in
measured voltage dip events. The work presented in [8][9] [6], which will be summarized below.
generalizes the classification and proposes an algorithm for The aim of voltage-dip characterization is to present
extracting dip type and characteristics from measured voltage statistics in a simple way. These statistics can next be used in
waveforms; a simplified algorithm is presented in [10]. compatibility studies, to assess system performance, etc.
The aim of this paper is to find the limitations of these two Another aim is to extract information on the underlying
characterization methods. After a description of the event(s). The dip characterization proposed in [6] can be used
characterization method including a discussion on the need for to find out the type of fault and the voltage level at which the
characterization, two algorithms are described for extracting fault occurred. Such an algorithm can be used as part of an
characteristics from measured voltages. Next these two expert system for the automatic classification of power-quality
disturbances [12].
M. H. J. Bollen is with the Department of Electric Power Engineering, Voltage-dip statistics will typically be obtained at the lower
Chalmers University of Technology, Gothenburg, Sweden (e-mail: voltage levels, close to the end-users. Automatic analysis of
m.bollen@ieee.org).
2001TR027 by Math Bollen 2

power-quality disturbances could find its application at any voltages Va, Vb, and Vc. The latter are obtained from the
voltage level. At higher voltage levels it could be part of measured voltage waveforms. Both characteristic voltage V
disturbance recorders of protection relays. and PN factor F are complex numbers. The absolute value and
the argument of the characteristic voltage are referred to as
B. Types of Three-Phase Unbalanced Dips
“magnitude” and “phase-angle jump” of the voltage dip,
Voltage dips are due to short circuits and earth faults, respectively. The magnitude (absolute value of the
transformer energizing and motor starting. By using the characteristic voltage) is a generalization for three-phase
voltage recovery and the voltage unbalance during the dip it is events of the retained voltage defined in IEC 61000-4-30.
possible to distinguish between these three types from voltage
recordings [12]. A further subdivision of voltage dips due to C. Relation with Fault Types
faults is proposed in [6][7]. The basic distinction is between The dip type depends on the fault type and the winding
types A, C and D: connection of the transformers between the fault and the
• type A is an equal drop in the three phases; measurement location [6]. The characteristic voltage is the
• type C is a drop in two phases; main characteristic describing the event. It is determined by
• type D is a large drop in one phase with a small drop in the positive-sequence source and feeder impedance for two-
the other two phases. phase and three-phase faults. For single-phase faults the zero-
For types C and D a further subdivision is needed to include sequence impedance also affects the characteristic voltage of
the symmetrical phase (the phase with the large voltage drop the dip [7].
for type D, the phase without voltage drop for type C). The The PN factor is a second characteristic. It is a measure of
resulting six types of three-phase unbalanced dips are shown in the unbalance of the event. The lower the magnitude of the PN
Fig.1. Type Db is a drop in phase b; type Cb a drop in phases a factor, the more balanced the dip; where the PN factor cannot
and c, etc. Alternatively, type Cb can be interpreted as a drop be smaller than the characteristic voltage (in absolute
in the ac voltage difference, etc. value)[8]. For single-phase and phase-to-phase faults the PN-
factor is close to 1 pu. The deviation from 1 pu is due to the
Ca Cb Cc load and will be discussed in more detail later. For two-phase-
to-ground faults in solidly-grounded systems, the PN factor is
less than 1 pu. The drop in PN factor is at most one third of the
drop in characteristic voltage. For three-phase faults the PN
factor is equal to the characteristic voltage.
The zero-sequence voltage V0 can be used as a third
Da Db Dc characteristic to completely describe the event. It gives
additional information for obtaining the location of the
underlying event, but the zero-sequence voltage rarely affects
the operation of equipment so that it is not needed for
statistics.
Fig. 1, Six types of three-phase unbalanced voltage dips: thin arrows indicate
normal voltages; thick arrows voltages during the event. III. THE TWO ALGORITHMS
The two parameters quantifying the dip are the A. The Symmetrical Component Algorithm
characteristic voltage V and the so-called PN factor F, both
The algorithm proposed in [8] determines the dip type from
complex numbers. The phase voltages as a function of these
the positive-sequence and negative-sequence voltages. From
two parameters are, for a type Ca dip:
(1), (2) and similar expressions for the other dip types in Fig.
Va = F 1, it can be concluded that the positive-sequence voltage (with
Vb = − 12 F − 12 jV 3 (1) reference to a-phase pre-fault voltage) is the same for all dip
types:
Vc = − F +
1 1
jV 3
2 2 V1 = 1
2
(F + V ) (3)
and for a type Da dip:
The negative-sequence voltage is the same in magnitude but
Va = V
different in argument:
Vb = − 12 V − 12 jF 3 (2)
Vc = − 12 V + 12 jF 3
The phasor diagrams in Fig. 1 are given for V=0.5 and F=1.
The aim of the two algorithms to be discussed below is to
obtain the dip type according to Fig.1, the characteristic
voltage V, and the PN factor F, from the complex phase
2001TR027 by Math Bollen 3

V2 = 1
2
(F − V ) type C a arguments of the complex numbers V and F. The argument of
the characteristic voltage is the phase angle of the voltage that
V 2 = a (F − V )
1
2 type C b gives the lowest rms value: va-v0 for type Da, vb-vc for type Cc,
V 2 = 12 a 2 (F − V ) type C c etc. The argument of the PN factor is the phase angle of the
(4) voltage that gives the highest rms value.
V 2 = − 12 (F − V ) type D a
V 2 = − 12 a(F − V ) type D b IV. NUMERICAL EXAMPLES
V 2 = − 12 a 2 (F − V ) type D c To show the performance of the algorithms and their
limitations, the complex phase voltages are, for a number of
where a constitutes a rotation over 120°. If we assume that cases, calculated from given dip characteristics according to
F=1 the angle between the drop in positive-sequence positive (1) and (2). The two algorithms are next applied to the
and negative-sequence voltage is an integer multiple of 60°. complex phase voltages and the resulting characteristics
The angle obtained from a measurement can be used to obtain compared with the known input values.
the dip type:
1 ì V ü A. Single-phase fault
T= × arg í 2 ý (5)
60° î1 − V1 Consider a drop of voltage in phase a down to 50% of its
where T is rounded to the nearest integer: pre-event value. It is assumed that the voltage in b and c
T = 0  type Ca remains as before. According to the classification introduced
T = 1  type Dc before this is a dip of type Da with F=1, V=0.67, V0=-0.33.
T = 2  type Cb The results for the symmetrical component algorithm are
T = 3  type Da shown in the first column of Table 1. The remaining columns
T = 4  type Cc give the results for a voltage drop in one phase, including a
T = 5  type Db phase-angle jump of -20°, -30°, -40°. As the PN factor equals
Knowing the dip type, the other characteristics can be exactly one, the angle between drop in positive sequence and
obtained, e.g. from the sum and difference of positive and negative-sequence voltage is exactly 180°. The dip type is
negative-sequence voltage according to (3) and (4). obtained correctly and so are the other characteristics.
The phenomenon that the characteristic voltage is not
B. The six-phase algorithm exactly equal to the voltage in the faulted phase for single-
A simplified algorithm is described in [10]. After phase faults is described in [6].
subtraction of the zero-sequence voltage, the rms voltage is
TABLE I
obtained for the three phase voltages and the three phase-to- SYMMETRICAL COMPONENT ALGORITHM DURING SINGLE-PHASE FAULTS.
phase voltages: 50% 0° 50% -20° 50% -30° 50% -40°
{
V A = rms v a − 13 (v a + v b + v c ) } Va 0.50 0.47-0.17j 0.43-0.25j 0.38-0.32j
V B = rms{ v b − 13 (v a + v b + v c ) }
Vb -0.50-0.87j -0.50-0.87j -0.50-0.87j -0.50-0.87j
(6a)
Vc -0.50+0.87j -0.50+0.87j -0.50+0.87j -0.50+0.87j
VC = rms{ v c − 13 (v a + v b + v c ) } V0 -0.17 -0.18-0.06j -0.19-0.08j -0.21-0.11j
V1 0.83 0.82-0.06j 0.81-0.08j 0.79-0.11j
ì v − vb ü
V AB = rmsí a ý
V2 -0.17 -0.18-0.06j -0.19-0.08j -0.21-0.11j
î 3 angle 180° 180° 180° 180°
V 0.67 0.65-0.11j 0.62-0.17j 0.59-0.21j
ì v − vc ü
VBC = rmsí b ý (6b) |V| 0.67 0.66 0.64 0.63
î 3 F 1.00 1.00 1.00 1.00
ì v − va ü
VCA = rmsí c ý TABLE II
î 3 SIX-PHASE ALGORITHM DURING SINGLE-PHASE FAULTS
The dip parameters are obtained directly: the characteristic 50% 0° 50% -20° 50% -30° 50% -40°
voltage is the lowest of the six rms voltages, the PN factor the Type 3 (Da) 3 (Da) 3 (Da) 4 (Cc)
|V| 0.67 0.66 0.64 0.60
highest of the six. The dip type is determined from the voltage
|F| 1.00 1.00 1.00 1.02
according to (6) with the lowest rms value:
VA lowest  type Da
The same synthetic dips are also applied to the six-phase
VB lowest  type Db
algorithm. The results are shown in Table II. For moderate
VC lowest  type Dc
values of the phase-angle jump, also the six-phase algorithm
VAB lowest  type Cc
gives the correct type and characteristics. For a -40° phase-
VBC lowest  type Ca
angle jump the six-phase algorithm results in a type Cc instead
VCA lowest  type Cb
of Da. The rotation in the a-phase voltage is so large that the
The six-phase algorithm can also be used to obtain the
2001TR027 by Math Bollen 4

ab-phase difference becomes less in absolute value (after


removal of the zero-sequence component). TABLE IV
SYMMETRICAL COMPONENT ALGORITHM WITH ADDITIONAL DROP IN
VOLTAGE DUE TO LOAD EFFECTS
B. Phase-to-phase fault 50% 0° 50% -20° 50% -30° 50% -40°
The same testing has been done for drops in the voltage Va 0.85 0.85 0.85 0.85
between the phases b and c to 50%, thus representing a phase- Vb -0.43-0.37j -0.55-0.35j -0.61-0.32j -0.66-0.28j
to-phase fault at the same voltage level or a single-phase fault Vc -0.43+0.37j -0.30+0.35j -0.24+0.32j -0.19+0.28j
at another voltage level. For this the algorithm should result in V1 0.64 0.62-0.07j 0.61-0.11j 0.59-0.14j
a dip of type Ca with F=1 and V=0.5. The results for both V2 0.21 0.23+0.07j 0.24+0.11j 0.26+0.14j
algorithms are shown in Table III, where the bottom three angle 0° 6.9° 8.6° 9.18°
rows refer to the results of the six-phase algorithm. Again the V 0.43 0.40-0.15j 0.37-0.21j 0.33-0.27j
symmetrical component algorithm gives the correct result in F 0.85 0.85 0.85 0.85
all cases, whereas the six-phase algorithm gives a wrong dip
type and characteristics for large phase-angle jumps. D. Impact of load – phase shift
The change in load currents not only leads to a drop in the
TABLE III three voltages, it typically also causes a phase shift (rotation)
THE TWO ALGORITHMS DURING PHASE-TO-PHASE FAULTS of the three voltages. It is again assumed that the load effect is
50% 0° 50% -20° 50% -30° 50% -40° the same for the three phases: a drop of 15% and a rotation of
SYMMETRICAL-COMPONENT ALGORITHM -20°: thus F=0.85exp(-j20°). The results for this case are
Va 1.00 1.00 1.00 1.00 shown in Table V. It turns out that the symmetrical component
Vb -0.50-0.43j -0.65-0.41j -0.72-0.38j -0.78-0.33j algorithm gives an erroneous result for small phase-angle
Vc -0.50+0.43j -0.35+0.41j -0.28+0.38j -0.22+0.33j jumps in the voltage. The rotation in PN-factor severely affects
V1 0.75 0.73-0.09j 0.72-0.13j 0.69-0.16j the angles of (1-V1) and V2, leading to a wrong dip type. For
V2 0.25 0.27+0.09j 0.28+0.13j 0.31+0.16j larger phase-angle jumps the error in angle becomes less than
angle 0° 0° 0° 0° 30° so that the correct dip type results after rounding to the
V 0.50 0.47-0.17j 0.43-0.25j 0.38-0.32j nearest multiple of 60°.
F 1.00 1.00 1.00 1.00
The problem with the symmetrical component algorithm can
SIX-PHASE ALGORITHM be relatively easily solved. The dip type is determined in (5)
Type 0 (Ca) 0 (Ca) 1 (Dc) 1 (Dc)
by rounding off the angle. Modifying the rounding somewhat
|V| 0.50 0.50 0.47 0.40
will solve the problem: the range -50°, +10° becomes dip type
|F| 1.00 1.00 1.01 1.04
0, etc. The resulting equation, replacing (5) reads as:
C. Impact of load – drop in voltage ì V ü
argí 2 ý + 20°
Measurements [7][10][12] as well as simulations [7][9][13] T= î1 − V1 (7)
have shown that the voltages in the three phases drop by an 60°
equal factor due to the load. In terms of the classification where T is again rounded to the nearest integer. The results for
presented in Section II of the paper, the PN factor F drops to a this improved symmetrical component algorithm are shown in
value less than unity. Table VI.
This has been modeled for the phase-to-phase faults (type TABLE V
SYMMETRICAL COMPONENT ALGORITHM WITH ADDITIONAL VOLTAGE DROP
Ca dips) studied before. It is assumed that the voltage drops by AND ROTATION DUE TO LOAD EFFECTS
15% in all three phases due to the load. The input values of the 50% 0° 50% -20° 50% -30° 50% -40°
dip characteristics are Type=Da, V=0.43, F=0.85. The effect Va 0.80-0.29j 0.80-0.29j 0.80-0.29j 0.80-0.29j
of the phase-angle jump is a rotation in V but not in F. The Vb -0.53-0.20j -0.64-0.14j -0.68-0.09j -0.78-0.04j
results are shown in Table IV. As the PN-Factor is no longer Vc -0.27+0.49j -0.16+0.43j -0.12+0.38j -0.08+0.33j
equal to one, the angular difference between the drop in V1 0.60-0.22j 0.56-0.28j 0.54-0.31j 0.51-0.33j
positive-sequence and the negative-sequence voltage is no V2 0.20-0.07j 0.24-0.01j 0.26+0.02j 0.29+0.04j
longer exactly an integer multiple of 60°. But after rounding to angle -48.5° -34.9° -29.8° -26.2°
the nearest integer multiple of 60° the algorithm still gives in V 0.56-0.01j 0.45-0.07j 0.27-0.33j 0.21-0.37j
the correct results. F 0.64-0.53j 0.67-0.49j 0.80-0.29j 0.80-0.30j
As all three phases are affected in the same way, the six- Type 0 (Ca) 0 (Ca) 1 (Dc) 1 (Dc)
phase algorithm shows the same behavior as for unity PN- |V| 0.43 0.43 0.40 0.34
factor. |F| 0.85 0.85 0.86 0.89
2001TR027 by Math Bollen 5

TABLE VI
IMPROVED SYMMETRICAL COMPONENT ALGORITHM WITH ADDITIONAL 1.5
VOLTAGE DROP AND ROTATION DUE TO LOAD EFFECTS
50% 0° 50% -20° 50% -30° 50% -40° 1
angle -28.5° -14.9° -9.8° -6.2°
V 0.40-0.15j 0.33-0.27j 0.27-0.33j 0.21-0.37j 0.5
F 0.80-0.29j 0.80-0.29j 0.80-0.29j 0.80-0.30j

Voltage [pi]
0
V. THE SIX-PHASE ALGORITHM
In the previous section, the six-phase algorithm has been -0.5
applied to a small number of synthetic dips with known
characteristics. This same process has been repeated for a -1
larger number of synthetic dips covering a wide range of
magnitude and phase angle of the characteristic voltage. (As -1.5
0 2 4 6 8 10 12 14 16
mentioned before, the PN-factor does not affect the Time [Cycles]
performance of the six-phase algorithm.) The results are Fig. 3. Example of a three-phase unbalanced dip.
presented graphically in Fig. 2. The black dots indicate the
combinations of magnitude and phase-angle (of the Applying the symmetrical component algorithm to these
characteristic voltage) for which the algorithm gives incorrect measurements will result in positive and negative-sequence
results. Also indicated in the figure, through the solid curves, voltage phasors V1 and V2, respectively. The symmetrical
is the range of magnitude and phase-angle jump that can be component voltages are calculated from the complex
expected. The upper and lower curves are for impedance fundamental phase voltages over a half cycle (10 ms) window.
angles +10° and -60°, respectively. The black dots are A sliding window is used to obtain the symmetrical component
generated by varying the impedance angle between -90° and voltages as a function of time. The angle between (1-V1) and
+90°. (See Appendix A for an explanation of the term V2 is used to determine the type of dip. This angle is shown in
“impedance angle”.) It follows from Fig. 2 that the six-phase Fig. 4 during the fault. The values of the angle before and after
algorithm gives incorrect results for events with a large the fault are ill-defined because the negative-sequence voltage
(negative) phase-angle jump and moderate drops in voltage. is very small. The half-cycle window used to extract the
symmetrical component voltages makes that it takes about one
half-cycle to obtain a value for the angle. Initially (shortly after
fault initiation) the angle is close to 240°: the “ideal value” for
a type Cc dip. But gradually the angle decreases. In this case,
the maximum deviation is about 25 degrees, just within the
error margin. A slightly larger deviation would have resulted
in the estimation of a type Da dip.
240

230

220
Angle [Degrees]

210

200
Fig. 2. Whole-range testing of the six-phase algorithm: the black dots
indicate where the algorithm gives an incorrect result.
190

VI. CHARACTERISTICS VERSUS TIME


To show some of the potential problems when implementing 180
5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10
the symmetrical component algorithm, it is applied to the Time [Cycles]

three-phase unbalanced dip shown in Fig. 3. The voltages are Fig. 4. Angle between drop in positive-sequence voltage and negative-
measured in an 11-kV distribution system during a 132-kV sequence voltage for the dip shown in Fig. 3.
fault. The fault is cleared in about 5 cycles, after which the
voltage recovers. The slow but balanced recovery indicates the The resulting characteristics are shown in Fig. 5 and Fig. 6.
presence of large amounts of induction motor load.. Fig. 5 shows the magnitude of characteristic voltage and PN-
factor. Initially the PN-factor is close to unity, but decreases
2001TR027 by Math Bollen 6

during the event. Note that the PN-factor is continuous both at frequency will result in additional errors in the angle used for
fault initiation and at fault clearing. This behavior has been detecting the type of dip. An error of 0.1 Hz in frequency will
observed for all single-phase and phase-to-phase faults. The give in 10 cycles an error of 7.2° in phase angle for the phase
decay and recovery of the PN-factor can be explained from the voltages, leading to an error up to 14.4° in the angle used for
decay and recovery of the voltage source behind reactance in detecting the dip type.
the induction machine model. This also explains that the ratio
of characteristic voltage and PN-factor is constant during the
fault [9]. VII. THE PERFECT ALGORITHM
Fig. 6 shows the phase angle of the characteristic voltage To understand why there is no perfect algorithm to
and the PN-factor. The large transients in the angle at fault determine the dip characteristics, consider the following set of
initiation and fault clearing are artifacts due to the Fourier synthetic events:
transform method used to extract the phase-angle information. Dip Type = Ca
The figure shows that the angle of the PN-factor is zero at fault xe − j 60°
initiation and decreases to about -12° during the 5-cycle V= (8a)
1 + xe − j 60°
duration of the fault. Note that a 12° rotation in PN-factor (Fig.
− j 40°(1− V )
6) gives a 25° rotation in the angle used to detect the dip type F = (0.7 + 0.3V ) e (8b)
(Fig. 4). with 0<x<∞. The characteristic voltage is given for an
impedance angle of -60° (see Appendix A). For the PN-factor,
1
both magnitude and phase angle are assumed to depend
linearly on the magnitude of the characteristic voltage.
0.9
This represents dips with a large (characteristic) phase-angle
jump, a large drop in PN-factor, and a large phase shift in PN-
factor. The symmetrical component algorithm according to (5)
Magnitude [pu]

0.8
has been applied to these events. The resulting values are
0.7
shown in Fig. 7 and Fig. 8. For x<0.6 the algorithm results in
an incorrect dip type (Db in this case). The incorrect dip type
in turn results in incorrect values for characteristic voltage and
0.6
PN-factor.
The estimated magnitudes of characteristic voltage and PN-
0.5
factor are shown in Fig. 7; the phase angles in Fig. 8. In both
0 2 4 6 8 10
Time [Cycles]
12 14 16 cases the magnitude of the actual characteristic voltage is
given along the horizontal axis. For low values of the
Fig. 5. Absolute value of characteristic magnitude and PN-factor for the dip
shown in Fig. 3.
characteristic magnitude the algorithm results in significant
errors in both magnitude and phase angle, where the
10 magnitude of the PN-factor and the phase angle of the
characteristic voltage reach unrealistic values. The presence of
5
these unrealistic values can be used as an indication that the
0
algorithm has given an incorrect result.
Angle [Degrees]

-5
1

-10

0.8
-15
Estimated Magnitude

-20 0.6

-25
0 2 4 6 8 10 12 14 16 0.4
Time [Cycles]

Fig. 6. Phase angle of characteristic voltage (solid line) and PN-factor (dotted
0.2
line) for the dip shown in Fig. 3.

As the symmetrical component algorithm uses complex 0


0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
phase voltages as its input, the system frequency must be Actual Characteristic Magnitude

known accurately. The discrete-Fourier transform algorithm Fig. 7. Estimated magnitude of characteristic voltage (solid line) and PN-
for extracting the complex phasors must be synchronized to factor (dashed line). The actual values are indicated through dotted lines.
the pre-fault voltage. Assuming exactly 50 Hz (60 Hz)
2001TR027 by Math Bollen 7

problems for large rotations in the PN-factor. It is however


0
unclear how often such large rotations occur in practice. But
-10 even when they occur, the initial value of the PN-factor (i.e.
-20 shortly after dip initiation) is always close to unity without any
-30 phase shift. Using the information that the dip type cannot
Estimated Phase Angle

suddenly change without a change in the phase voltages, can


-40
be used to accurately track the changes in the dip
-50
characteristics. More knowledge of the load effects on voltage
-60 dips is needed before this problem can be addressed further.
-70 For applying the symmetrical component algorithm it is
-80
essential that accurate values of complex positive-sequence
and negative-sequence voltage are obtained. They can be
-90
obtained by applying the Fourier transform on the phase
-100
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 voltage waveforms, or through a forward and a backward dq-
Actual Characteristic Magnitude
transform. With both methods is it important that the algorithm
Fig. 8. Estimated phase-angle of characteristic voltage (solid line) and PN- accurately tracks the system frequency. A small error in
factor (dashed line). The actual values are indicated through dotted lines.
frequency may result in an erroneous dip type.
In this paper, only single-phase and phase-to-phase faults
The “incorrect values” are mathematically speaking not
have been considered. Two-phase-to-ground faults already
incorrect. There are simply two combinations of dip type, F
give a non-unity PN-factor immediately after fault-initiation. A
and V, that result in the same phase voltages. For example the
large initial phase angle shift in the PN-factor may lead to
voltage dip, according to (8), with characteristic magnitude
errors in the classification in that case.
50% has the following phase voltages:
For extracting additional information on the underlying
Va = 0.85∠ − 20°
event of a voltage disturbance it is essential that the algorithm
Vb = 0.68∠ − 162° gives a correct result, and the symmetrical component
Vc = 0.53∠ + 107° algorithm should be used. To extract statistics on the supply
These phase voltages were generated from a type Ca dip performance erroneous results in a limited number of cases
with the following characteristics: may be acceptable. The simplicity of the six-phase algorithm is
V = 0.50∠ − 34° clearly an advantage for statistical studies when large numbers
of events need to be processed.
F = 0.85∠ − 20°
But exactly the same phase voltages are obtained for a type
IX. APPENDIX A
Db dip with characteristics:
V = 0.68∠ − 42° For faults on a given feeder the complex characteristic
voltage is found from the standard voltage divider equation:
F = 0.72∠ − 10°
z
The only way of distinguishing between them is by realising V= (A1)
that one of the solutions gives non-realistic values of the ZS + z
characteristics. Being able to make such a decision requires where the pre-event voltage is assumed to be 1pu, with Zs
knowledge of dip characteristics as they may occur in practice. the source impedance at the pcc, the distance between the
This calls for a further analysis of available monitoring data pcc and the fault, and z the feeder impedance per unit length.
and for detailed simulations of unbalanced faults in realistic Expression (A1) can be rearranged into:
systems. The effect of the load on the complex voltages plays λe jα
an important role in the dip characteristics so that special V= (A2)
1 + λe jα
emphasis has to be placed on the load model.
z
with λ = a measure for the “electrical distance” to the
VIII. CONCLUSIONS ZS
It is shown that both algorithms are capable of correctly ì lz ü
obtaining the dip characteristics for most three-phase fault, and α = arg í ý the angle between source impedance
unbalanced dips. However the six-phase algorithm results in î ZS
incorrect dip type and characteristics for shallow and moderate and feeder impedance. It easily follows from (A2) that
events with a large phase-angle jump. Voltage dips due to lim arg(V ) = α , so that α is the maximum phase-angle jump
V →0
faults on distribution cables could fall into this category. More
for faults on the given feeder. The angle between source and
statistical information on dip characteristics is needed to assess
feeder impedance (α) is referred to as the “impedance angle”.
the severity of this limitation.
It determines the relation between magnitude and phase-angle
The symmetrical component algorithm covers all
jump of a voltage dip. Expression (A2) is suitable for the
combinations of magnitude and phase angle jump, but shows
2001TR027 by Math Bollen 8

generation of synthetic voltage dips with realistic magnitude [8] L.D. Zhang, M.H.J. Bollen, Characteristic of voltage dips (sags) in
power systems, IEEE Transactions on Power Delivery, Vol. 15, no.2
and phase-angle jump combinations. (April 2000), pp.827-832.
The feeder impedance is normally more resistive than the [9] L.D. Zhang, Three-phase unbalance of voltage dips, Licentiate thesis,
source impedance, so that α is typically negative. Realistic Chalmers University of Technology, Gothenburg, Sweden, November
1999.
values for the impedance angle are between -10° and +10° for [10] M.H.J. Bollen, E. Styvaktakis, Characterization of three-phase
transmission system faults and between –60° and -10° for unbalanced dips (as easy as one two three?), IEEE Power Summer
distribution system faults. For faults on distribution cables Meeting 16-20 July, 2000, Seattle, WA, USA, pp.899-904, Vol.2.
[11] IEC 61000-4-30, Power quality measurement methods, CDV 2001.
values between –40° and -60° have been found. [12] E. Styvaktakis, M.H.J. Bollen, Y.H. Gu, Expert system for classification
and analysis of power system events, IEEE Transactions on Power
X. REFERENCES Delivery, in print.
[13] G. Yalcinkaya, M.H.J. Bollen, P.A. Crossley, Characterisation of
[1] G. Desquilbet, C. Foucher, P. Fauquembergue, Statistical analysis of voltage sags in industrial distribution systems, IEEE Transactions on
voltage dips, PQA-94 Amsterdam. Industry Applications, Vol.34, no.4, July 1998, p.682-688.
[2] J.C. Smith, J. Lamoree, P. Vinett, T. Duffy, M. Klein, The impact of
voltage sags on industrial plants, Int. Conf. on Power Quality: End-use
Applications and perspectives (PQA-91), pp.171-178. XI. BIOGRAPHY
[3] M.F. McGranaghan, D.R. Mueller, M.J. Samotyj, Voltage sags in Math Bollen (M’94, SM’96) is professor in
industrial power systems, IEEE Transactions on Industry Applications, electric power systems in the department of
Vol.29, no.2, pp.397-403, Mar/Apr 1993. electric power engineering at Chalmers University
[4] L. Conrad, K. Little, C. Grigg, Predicting and preventing problems of Technology, Gothenburg, Sweden. He received
associated with remote fault-clearing voltage dips, IEEE Transactions his MSc and BSc from Eindhoven University of
on Industry Applications, Vol.27, no.1, Jan. 1991, p.167-172. Technology in 1985 and 1989, respectively.
[5] D.O. Koval, M.B. Hughes, Canadian national power quality survey: Before joining Chalmers in 1996 he was post-doc
frequency of industrial and commercial voltage sags, IEEE Transactions at Eindhoven University of Technology and
on Industry Applications, Vol.33, no.3, pp.622-627, May/June 1997. lecturer at UMIST, Manchester, UK. Math Bollen
[6] M.H.J. Bollen, Characterization of voltage sags experienced by leads a team of researchers on power quality,
three-phase adjustable-speed drives, IEEE Transactions on Power reliability and power-electronic applications to
Delivery, Vol.12, no.4, pp.1666-1671, October 1997. power systems. His own contribution to research consists of the development
[7] M.H.J. Bollen, Understanding power quality problems – voltage sags of methods for voltage dip analysis, which resulted in a text book on power
and interruptions. New York, IEEE Press, 1999. quality. Math is active in IEEE and CIGRE working groups on voltage dip
analysis and statistics

Anda mungkin juga menyukai