MODEL SELECTIONS
Basic Model: PM210A Model Type Description Examples PM210A-STD-50Hz PM210A-STD-60Hz PM210A-100D-50Hz PM210A-200S-60Hz
PM210A-STD-yy Standard 5A model, direct input of up to 10A or use with external CTs. yy = 50 or 60 Hz PM210A-xx-yy Dedicated CT model, mA input, must always be used with the dedicated CT. xx = 30D, 75D, 100D, 50S, 100S, 200S yy = 50 or 60 Hz Warning: This model type is not to be used with standard 5A CTs.
Optional CT selection for PM210A-STD-yy. Donut type CT (solid core), rating 100A, ratio 100:1 CT-100A CT-200A
Description Donut type CT (solid core), rating 100A, ratio 100:1 Donut type CT (solid core), rating 200A, ratio 200:1
Dedicated CT selection for PM210A-xx-yy. PM210A-xx-yy xx selections 100D 200D 50S 100S 200S Description CT-100D, dedicated CT, 100A, donut type (solid core), 2000 turns CT-200D, dedicated CT, 200A, donut type (solid core), 2000 turns CT-50S, dedicated CT, 50A, split type, 3000 turns CT-100S, dedicated CT, 100A, split type, 3000 turns CT-200S, dedicated CT, 200A, split type, 3000 turns
INSTALLATION
Terminal Diagram
Panel Cut
Wiring Diagrams
IA+ IAIB+ IBIC+ ICVA VB VC N
A B C
SET UP
1. Enter the set up mode by pressing both the simultaneously, the display keys should be showing the
rmware version. The rmware version is read only and cannot be changed.
2. Press the
3. Press the
4. Press the
to move to the next digit. The PT can be set from 1.00 to 4.00, 100 or 200.
5. Press the
to move to the next digit. The CT ratio can be set from 1 to 1000. For the standard 5A model, set the CT ratio accordingly. Example 1: using a CT with ratio 100:5, set the CT ratio to 20. Example 2: using a CT with ratio 200:1, set the CT ratio to 200. Caution: For the dedicated CT model, the ratio has been factory set and should not be changed, changing this value may result in an incorrect or inaccurate reading.
6. Press the
model type of the PM210. Yes means that the meter is the standard 5A model, no means that the meter is the dedicated CT model. Caution: Do not change this value, this is factory set, changing this value may result in an incorrect or inaccurate reading.
7. Press the
type, 3 sets the meter to recognize the wiring as 3 phase 3 wire, 4 sets the meter to recognize the wiring as 3 phase 4 wire.
UNIT OPERATION
LED Display kWh Indicator Current Indicator
kVArh Indicator
Voltage Indicator
kW Indicator
PF Indicator
Display Indicators
Indicator Description Current: Amps, for each of 3 phases - IA, IB, IC Voltage: Volts, for each of 3 phases - VA, VB, VC Power: kW, total of all 3 phases Real Energy Consumption: kWh Apparent Power Consumption: kVArh Power Factor (PF) Rx Tx RS485 receive activity RS485 transmit activity
Key Operation
Key Combination
Function Regular Mode: Cycles between displayable values 1. Current - A phase 2. Current - B phase 3. Current - C phase 4. Voltage - A phase 5. Voltage - B phase 6. Voltage - C phase 7. kW 8. kWh 9. kVARh 10. PF Setting Mode: Save and move to the next parameter
1. 2. 3.
4. 100 and 200 5. 6.
Firmware version (read only) RS485 address - 0 to 99 Baud rate - 1200, 2400, 4800, 9600 PT ratio - 1.00 to 4.00 (0.01 resolution), CT ratio - 1 to 1000 (1 resolution)
5A - Yes (standard 5A) or No (dedicated CT) CAUTION: FACTORY USE ONLY, DO NOT CHANGE 7. Phase - 3 (3 phase 3 wire) or 4 (3 phase 4 wire)
Press together to enter or exit setting mode. During setting mode, increment digit. No function during regular mode. During setting mode of PT and CT, move to the next digit. No function during display mode.
SPECIFICATIONS
Standard Type Electrical Phase/Wire Power Supply Power Consumption Rated Current Input Frequency Internal Measurement Phase Voltage Measured Current Cumulative Active Energy PF Communication Interface Bus Type Protocol Baud Rate Address Data Format Physical Operating Temperature 0 to 60C! RS485 Modbus/RTU 1200, 2400, 4800 or 9600 (default) settable via front panel or Modbus 0 to 99 8 / None / 1 80 to 350 Vac, resolution 0.1 V 8 mA to 5 A (resolution 1 mA) 50 mA to 100 A (resolution 1 mA) on CT primary 33w or 34w 110 or 220 Vac, 10% (on separate terminals) starting current 300 mA, working 35 mA at 110 V starting current 200 mA, working 20 mA at 220 V 5A (max 10A) depends on dedicated CT Dedicated CT Type
50 or 60 Hz - depending on model
450 gm
400 gm
Front Panel Interface Display LED Indicators Function Keys 6 digit 7 segment LED 8 - A, V, kW, kWh, kVArh, PF, Rx, TX 3 keys Up Arrow (increment digit) Right Arrow (select next digit) Page/Enter Modes Display Mode or Setting Mode
MODBUS REGISTERS
Real Time Data 1 (one word sized data)
Address Name Description 0000H 0001H 0002H V1 V2 V2 Phase R Voltage Phase S Volt Phase T Volt Words Format Min 1 1 1 1 1 1 1 1 1 1 1 1 1 1 F6 F6 F6 F6 F6 F6 F7 F7 F7 F8 F8 F8 F10 F9 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Max 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 65535 Default 0 0 0 0 0 0 0 0 0 0 0 0 0 0 Unit 0.1 0.1 0.1 0.1 0.1 0.1 0.001 0.001 0.001 0.001 0.001 0.001 0.1 0.01 Valid for 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W 3P4W/3P3W
0003H V12 Line R-S Volt 0004H V23 0005H V32 0006H 0007H 0008H 0009H 000AH 000BH 000CH 000DH 000EH 000FH I1 I2 I3 P Q S F PF Line S-T Volt Line T-R Volt Phase R Amp Phase S Amp Phase T Amp KW Total KVAR Total KVA Total Hz PF
reserved reserved
F12
999.9
0.1V
0016H V2 0017H 0018H V3 0019H 001AH V12 001BH 001CH V23 001DH 001EH V31 001FH 0020H I1 0021H 0022H I2 0023H 0024H I3 0025H 0026H P 0027H 0028H Q 0029H
Voltage Low Word Voltage High Word Voltage Low Word Voltage High Word Voltage Low Word Voltage High Word Voltage Low Word Voltage High Word Voltage Low Word Voltage High Word Current Low Word Current High Word Current Low Word Current High Word Current Low Word Current High Word Power Low Word Power High Word VAr Low Word Var High Word
F12
999.9
0.1V
3P4W/ 3P3W
F12
999.9
0.1V
3P4W/ 3P3W
F12
999.9
0.1V
3P4W/ 3P3W
F12
999.9
0.1V
3P4W/ 3P3W
F12
999.9
0.1V
3P4W/ 3P3W
F13
999.999
0.001A
3P4W/ 3P3W
F13
999.999
0.001A
3P4W/ 3P3W
F13
999.999
0.001A
3P4W/ 3P3W
F14
999999
1W
3P4W/ 3P3W
F14
999999
1VAR
3P4W/ 3P3W
002AH S 002BH 002CH F 002DH 002EH PF 002FH 0030H EP+ 0031H 0032H EQ+ 0033H
VA Low Word VA High Word Frequency Low Word Frequency High Word Power Factor Low Word Power Factor High Word kWh Low Word kWh High Word kVArh Low Word kVArh High Word
F14
999999
1VA
3P4W/ 3P3W
F16
999
0.1Hz
3P4W/ 3P3W
F15
999
0.001
3P4W/ 3P3W
F11
99999.99
0.01kWh
3P4W/ 3P3W
F11
99999.99
0.01kVArh
3P4W/ 3P3W
Energy Data
Address Name Description Words Format 0040H EP+ 0041H 0042H Reserved 0043H 0044H EQ+ 0045H kVArh Low Word kVArh High Word kWh Low Word kWh High Word Min Max Default Unit Valid for 3P4W/ 3P3W
F11
99999.99
0.01KWH
F11
99999.99
0.01kVArH
3P4W/ 3P3W
F11
99999.99
0.01 kWh
3P4W only
F11
99999.99
0.01 kWh
3P4W only
F11
99999.99
0.01 kWh
3P4W only
F11
99999.99
F11
F11
F11
F11
0060H P1 0061H 0062H P2 0063H 0064H P3 0065H 0066H P 0067H 0068H Q1 0069H 006AH Q2 006BH 006CH Q3 006DH 006EH Q 006FH 0070H S1 0071H 0072H S2 0073H
Watt Low Word Watt High Word Watt Low Word Watt High Word Watt Low Word Watt High Word Watt Low Word Watt High Word VAr Low Word VAr High Word VAr Low Word VAr High Word VAr Low Word VAr High Word VAr Low Word VAr High Word VA Low Word VA High Word VA Low Word VA High Word
F14
999999
1W
3P4W only
F14
999999
1W
3P4W only
F14
999999
1W
3P4W only
F14
999999
1W
3P4W/3P3W
F14
999999
1 VAr
3P4W only
F14
999999
1 VAr
3P4W only
F14
999999
1 VAr
3P4W only
F14
999999
1 VAr
3P4W/3P3W
F14
999999
1 VA
3P4W only
F14
999999
1 VA
3P4W only
0074H S3 0075H 0076H S 0077H 0078H PF1 0079H 007AH PF2 007BH 007CH PF3 007DH 007EH PF 007FH
VA Low Word VA High Word VA Low Word VA High Word Power Factor Low Word Power Factor High Word Power Factor Low Word Power Factor High Word Power Factor Low Word Power Factor High Word Power Factor Low Word Power Factor High Word
F14
999999
1 VA
3P4W only
F14
999999
1 VA
3P4W/3P3W
F15
1000
0.001
3P4W only
F15
1000
0.001
3P4W only
F15
1000
0.001
3P4W only
F15
1000
0.001
3P4W/3P3W
Setup Data
Address 0080H 0081H 0082H 0083H 0084H 0085H 0086H Address Baud Rate PT CT RS-485 Address Baud Rate PT Rate CT Rate Name Wiring Description 3P3W or 3P4W Words 1 Reserved 1 1 1 1 F4 F5 F2 F3 0 0 1 1 99 3 200 1000 1 1 1 1 Format F1 Min 0 Max 1 Unit 1
0087H 0088H 0089H 008AH 008BH 008CH 008DH CT Fn Version Internal 5A CT or External DAE CT PM210 firmware version 1 1 F17 F18 0 1 1 Reserved
Format Types
Format No. F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11 Format Type Wiring table PT ratio CT ratio RS485 address Baud rate index Voltage Current Power (P, Q, S demand) PF Hz Energy (KWH, KVARH) Format Definition 1 = 3P3W; 0 = 3P4W PT = Data/100 CT = Data Data 0 = 1200, 1 = 2400, 2 = 4800, 3 = 9600 Voltage=Data/10 x PT ratio Current=Data/1000 x CT ratio Power = Data x PT ratio x CT ratio Positive : PF =Data/100 Freq = Data/10 Energy = {Word(h) x 65536 + word(L)} /100 When: 3P4W Voltage = {Word(h) x 65536 + word(L)}/10 x PT ratio When: 3P3W Voltage ={Word(h) x 65536 + word(L)}/10 When:3P4W Current = {Word(h) x 65536 + word(L)}/1000 x CT ratio When:3P3W Current = {Word(h) x 65536 + word(L)}/1000 When:3P4W Power = {Word(h) x 65536 + word(L)} x PT ratio x CT ratio When:3P3W Power = {Word(h) x 65536 + word(L)} Positive : PF = {Word(h) x 65536 + word(L)}/ 1000 Freq = {Word(h) x 65536 + word(L)}/10 0: Standard 5A 1: External Dedicated CT Ver = High byte*10+Low byte
F12
Voltage
F13
Current
F14
PF Hz CT Fn PM210 A Version
Note: 1. kk = value to write to Address 2. Baud Rate values: a. 00h ! 1200 bps b. 01h ! 2400 bps c. 02h ! 4800 bps d. 03h ! 9600 bps