Anda di halaman 1dari 44

Data Aire Mini Ceiling Systems

1, 1.5, 2, and 2.5 ton capacities

ISO 9001 Certified

Data Aire the pioneer and builder of the most complete line of precision cooling equipment Data Aires first precision cooling system was developed by data processing engineers who sought optimum environmental conditions for early computers. It was clear that people comfort air conditioning system were unable to meet the environmental requirements of computers and data processing equipment. Precision environmental control equipment with high sensible cooling ratios was a necessity. Problems with paper sticking , head crash, and static electricity were eliminated. Humidity fluctuation were controlled saving possible electrical and mechanical failures and more importantly Downtime. Data Aires innovative response to the challenge of eliminating problems within the computer room environment was the start of wide use precision cooling. As in the past, Data Aire is meeting todays challenge of not only the computer room but also the ever expanding telecommunications industry where precision cooling is vital to our everyday communications. Telecommunication equipment requires a controlled environment with clean and properly distributed air. As in the computer room, the environment must be precisely controlled 24 hour a day, 365 days a year. Data Aire produces solutions. We have offered environmental control solutions to meet specific needs in the smallest of places and in areas of thousands of square feet. We are prepared to assist you, your in-house engineering department, consulting engineer, or construction department in defining the proper solutions and bringing them to a predefined outcome. Data Aire is committed to being the supplier of choice for environmental process cooling with flexibility, reliability, and expertise required to meet our customers needs. To be successful, it is essential to be creative and use our resources to their fullest capabilities. The Data Aire goal is to benefit the employees, partners, and most of all our customers with honesty and integrity. Data Aire Delivers!

Mini Ceiling System


1, 1.5, 2, and 2.5 ton Air and Water Cooled and Chilled Water

TABLE OF CONTENTS

Design Features ................................................................................................. 6 Options ............................................................................................................. 8 Configuration Drawings Package Systems ............................................................................ 10 Split Systems .................................................................................. 12 Performance Data Air and Water Cooled ......................................................... 14 Electrical Data Air Cooled ..................................................................................... 17 Water Cooled ................................................................................. 19 Performance Data Chilled Water ...................................................................... 20 Electrical Data Chilled Water ............................................................................ 21 Dimensional and Component Drawings ............................................................. 22 Guide Specifications ......................................................................................... 38 Weights ........................................................................................................... 42

DATA AIRE, FOR ALL THE RIGHT REASONS!


PRECISION COOLING Computers, batteries, electronic and telephone equipment have special comfort requirements. These spaces require air which is clean with precisely controlled temperature and humidity. Data Aire Mini Ceiling SystemsTM are designed with this in mind. Building or "people comfort" systems simply are not designed to meet demands. PERFORMANCE, LOW COST Engineered and built by the people who introduced computer room air conditioning, the Mini Ceiling unit offers quality at a competitive price. Every Mini Ceiling System comes with Data Aire's commitment to excellence which began with our first air conditioner and has been tested and proven for more than forty years.

PEOPLE COMFORT Although "thru-the-wall" systems may help cool your staff, they still fall short where precision cooling is needed. Data Aire's Mini Ceiling Systems are the practical answer. It will keep your equipment on-line and will add to your personnel's comfort as well.

Units shown with optional side drain connections.

DATA AIRE DELIVERS


Data Aire's reputation for speedy delivery applies with special emphasis to the Mini Ceiling System. Units are shipped within a few days from receipt of order. Call your nearest Data Aire representative for details.

MINI CEILING SYSTEMSTM


1, 1.5, 2, and 2.5 ton capacities Air Cooled Water Cooled Chilled Water

ata Aire's Mini Ceiling Series is the perfect environmental control system for small computer centers, electronic, telephone, and battery rooms, or wherever spot cooling may be necessary and space is a problem. While vertical supply/return air units are designed to fit in a 2 ft x 4 ft standard T-bar ceiling grid space, horizontal units hang in the ceiling space with duct work connected to supply and return connections. The system offers an unsurpassed combination of features and options along with a high standard of performance. Mini Ceiling Systems are available as air cooled, water cooled, or chilled water systems with a variety of return and supply air arrangements. Air cooled can be specified as packaged indoor units or split systems with either remote outdoor condensers or condensing units.

CONTROLS

EVAPORATOR SECTION

Precise temperature regulation is provided by a built-in control system. All electrical components, including capacitors, contactors, relays, and control transformers are pre-wired and contained in an electrical box that is hinged and swings out for easy access and servicing. A factory installed microswitch will disable the unit prior to condensate pan overflow should the drain line become plugged with debris. Each unit is shipped with a thermostat and subbase as standard. A red indicator light is unit mounted to indicate a condensate problem. Units with the optional Mini Data Alarm ProcessorIITM have a high condensate water level alarm standard.

The evaporator coil contained in each unit is constructed with copper tubes and aluminum fins mounted in a stainless steel drain pan. The drain pan is made with a bottom drain connection and installed in a manner that provides a positive drain to prevent standing water in the condensate pan. The refrigeration circuit includes a scroll compressor with internal overload protection and crankcase heater. The circuit includes an expansion valve with an external equalizer, filter drier, sight-glass, and high and low pressure safety switches. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The blower assembly is a draw-through type with a centrifugal, forward curved, double width, double inlet blower configuration engineered for quiet, reliable operation. The belt driven variable pitch drive provides adjustable air flow capability to match the requirements of the controlled space. The draw-through design insures even distribution across the coil, low internal cabinet losses, and static sealing of the filter section. The motor has internal overload protection and is mounted on an adjustable slide base.

CABINET Units are designed with a supply and return air plenum that fits in a 2 ft x 4 ft opening of a standard dropped ceiling grid. The field installed supply and return air plenum is constructed of aluminum and finished with offwhite textured paint. Both the supply and return air grilles are hinged for easy access when replacing filters. A 2 inch, 60% efficient filter (based on ASHRAE Std. 52.1-1992) is provided behind the return air grille. Mini Ceiling Systems are constructed with tubular steel frames for strength and service access. Removable panels of galvanized steel are lined with 1/2 inch thick, closed cell insulation for quiet and efficient operation.
6

SELF-CONTAINED UNITS Air Cooled - The cabinet houses the evaporator section, evaporator blower assembly, filter section (located in air distribution plenum), and the condenser coil. The condenser coil is constructed of copper tubes and aluminum fins. The condenser blower section is field installed. The condenser fan is double inlet, double width, with direct drive type two-speed motor that is controlled with a temperature operated switch. The condenser blower motor electrical connection is through a factory wired plug. Water Cooled - The cabinet houses the evaporator section, evaporator blower assembly, and filter section (located in air distribution plenum). In addition, a high efficiency coaxial condenser with head pressure activated 2-way water regulating valve is built into the refrigeration system and is contained in the evaporator section. The capillary tube connection from the water regulating valve to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Chilled Water - All components are housed within the cabinet. Chilled water units utilize an existing chilled water loop. Chilled water flow is controlled by a 2-way valve for accurate and economical temperature control and dehumidification. The maximum operating water pressure is 150 psi.

SPLIT SYSTEMS Air cooled systems are available with an outdoor condensing unit or remote air cooled condenser. Remote Outdoor Condensing Unit - The outdoor condensing unit contains the scroll compressor, sightglass, filter drier, high and low pressure safety switches, and condenser coil. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The condenser coil is constructed with copper tubes and aluminum fins. Air discharge is vertical. The condenser fan is variable speed for head pressure control down to -20 F. The capillary tube connection from the fan speed control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Field piping and wiring is required from the condensing unit to the indoor evaporator section. Remote Outdoor Air Cooled Condenser - Condensers are industrial duty design with galvanized corrosion resistant housing, aluminum finned/copper tube coils, coated fan guard, energy efficient, thermally protected motor, and variable fan speed control with an integral factory wired and tested control panel. The capillary tube connection from the fan speed control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Air discharge is vertical. Field piping and wiring is required from the condenser to the indoor compressor/evaporator section.

Unit Shown with Optional Side Drain Connections

Mini Ceiling Systems - OPTIONS


Mini Data Alarm Processor-II - The microprocessor based Mini Data Alarm Processor-II is wall mounted and has a single row, 16 character liquid crystal display (LCD) in clear vernacular format. The Mini Data Alarm Processor-II not only controls and monitors your room's temperature, humidity, air flow, and cleanliness, but also provides alarm history and an automatic self-test of the microprocessor system start-up. Multiple messages will be displayed by automatically scrolling from each message to the next. Multiple alarms will be displayed sequentially in order of occurrence. Operation - Unit on/off operation is controlled by a slide switch and push button control switches which allow menu selection for programming, operational information, diagnostics, and historical data. A password feature prevents unauthorized access. Menu programmed information for basic system operation and alarm parameters is nonvolatile. Programmable Functions/Monitoring - The user friendly switch permits step-by-step programming and display of the following functions: Temperature setpoint (60-80 F, 15.6-26.7 C) Temperature sensitivity (+1 to + 5 F or .5 to 2.7 C, in 0.1 increments) Humidity setpoint (30-70% RH) Humidity sensitivity (+1 to +15% RH in 0.1% increments) Temperature alarm points (50-90 F, 10-32.2 C) Humidity alarm points (10-90% RH) Unit start time delay Interstage time delay Password 1st level Password 2nd level Audio alarm level Restart mode Firestat trip temperature Local alarm function Normal functions are monitored and displayed on the LCD and include, in addition to the above set points, the following: Current temperature (F or C) Current humidity (% RH) Cooling Reheat Humidification Dehumidification Date and time

Alarms - Alarm conditions are monitored on the LCD and are enunciated by an audible alarm. The alarm silence button will quiet the audible alarm but the display will continue to indicate the alarm condition until the problem is corrected. The following alarms are standard: High temperature Low temperature High humidity Low humidity Compressor high pressure Compressor short cycle High condensate water Firestat tripped No air flow alarm Temperature sensor failure Humidity sensor failure

Historical Data - The current temperature and humidity, with minimum and maximum readings for the last 24 hours of operation can be recalled and displayed. Alarm history of the last five alarms is maintained in sequential order. Diagnostics - Automatic and manual diagnostics sequences simplify troubleshooting. Each Mini Data Alarm Processor-II is shipped with 25 feet of cable for field connection, (additional cable is available). Contact factory for cable lengths in excess of 75 feet. For full details on the Mini Data Alarm ProcessorII, see product brochure.

Site Monitoring
DARA-4 (Data Aire Relay Autochangeover) Controls up to four Mini Ceiling units using a dry set of relay contracts. The DARA-4 provides unit rotation, backup capacity and the ability to interface with most BMS systems. damper kit is field installed and consists of a 14" x 14" damper section and head pressure operator. The low ambient control damper allows unit to operate down to -30 F (-34.4 C). The capillary tube connection from the head pressure control to the refrigerant system is connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.

Unit Options
Remote Mounted Temperature and Humidity Sensors

Condensate Pumps Temperature and humidity sensors are provided in a wall mounted plastic case for remote sensing of temperature and humidity. Standard unit sensors are removed. Requires field wiring of (field provided) shielded cable. Remote temperature and humidity sensors option only available when used with the Mini Data Alarm Processor-II. Condensate pumps can be provided for field mounting or factory installed and wired. The pump body can be placed within the unit coil pan. Pump capacity is 60 GPH at 8 feet of head. Field installed condensate pumps require either separate 110 or 230 volt power source.

Steam Generator Humidifier The steam generator humidifier eliminates air contamination caused by mineral deposits. The totally selfcontained system includes a quick change, disposable cartridge, and automatic flush cycle. When steam generator humidifier option is selected, a Mini Data Alarm Processor-II is required.

Horizontal, Front, or Side Supply Air Units may be ordered with optional horizontal supply air configurations of front or either side. Optional supply air converts unit for ducted supply air connection.

Side Return Air Units may be ordered with optional side return consisting of a factory modified flanged for ducting return air. Optional side return air converts unit for ducted return air connection. An additional option provides ceiling mounted return air filter grille, ceiling mounted return air filter box with hinged grille, and filter for duct connection. Filter included with this option is a 20" x 20" x 4" deep, 60% efficient (based on ASHRAE Std. 52.11992) pleated filter.

Electric Reheat Low-watt density finned tubular sheathed coils are constructed of stainless steel and provide ample capacity to maintain room dry bulb conditions on a call for dehumidification. Low-watt density coils eliminate ionization associated with open wire electrical resistance heating. Electric reheat is available in 2, 4, or 5 kW capacities, shipped factory installed with high limit cutout.

Extended Compressor Warranty Low Ambient Control Damper A low ambient control damper is available for use with ducted outside condenser air. The low ambient control Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs.

CONFIGURATION VERSATILITY
Data Aire Mini Ceiling Systems allow for a wide variety of supply and return options capable of satisfying the most demanding installation requirements.

PACKAGED SYSTEMS
Standard Configuration - is provided with one ducted attachment, the condenser air out from the end of the unit with flange. Condenser air intake is supplied from the side and top. Evaporator return air is supplied from below and the evaporator supply air is returned to the space below.

Mini Ceiling Systems with non-ducted condenser supply air


Ducted alternate end supply air Ducted alternate rear air supply

Shown with option 260

Shown with option 262

Ducted alternate front air supply

Ducted alternate return air and alternate end supply air

Shown with option 261

Shown with options 260 and 263

10

PACKAGED SYSTEMS Mini Ceiling Systems with non-ducted condenser supply air
Ducted alternate return air and alternate rear supply air Ducted alternate return air and alternate front supply air

Shown with options 262 and 263

Shown with options 261 and

PACKAGED SYSTEMS Mini Ceiling Systems with flange for condenser supply air
Standard Configuration - has flange for condenser air intake and condenser discharge air. Evaporator return and supply air are from the space below.
Ducted condenser air intake

Ducted alternate end supply air

Ducted alternate return air and alternate front supply air

Shown with option 260

Shown with options 261 and 263

11

CONFIGURATION VERSATILITY

continued

PACKAGED SYSTEMS Ducted alternate return air and alternate rear supply air

continued

Ducted alternate return air and alternate end supply air

Shown with options 262 and 263

Shown with options 260 and 263

SPLIT SYSTEMS
Configuration of a split system is the same as the package system, except that you dont have to take into consideration the condenser supply and return air. Typical configuration is with the evaporator supply and return air from the space below, however all the following options are available to meet your requirements.
Standard configuration with standard supply air and standard return air

Ducted alternate end supply air

Ducted alternate front supply air

Shown with option 260

Shown with option 261

12

SPLIT SYSTEMS
Ducted alternate rear supply air and alternate return air

- continued

Ducted alternate end supply air and alternate return air

Shown with option 262 and 263

Shown with option 260 and 263

Ducted alternate front supply air and alternate return air

Ducted alternate end supply air and special return air

Shown with options 261 and 263

Shown with options 260 and special

Ducted alternate front supply air and alternate return air

Shown with options 262 and special

13

AIR, WATER or GLYCOL COOLED: Performance data


MODEL NUMBER CAPACITY in Btu/hr - Gross 80 DB/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible 16,300 12,400 14,900 12,100 14,500 12,900 14,100 11,800 13,800 12,600 20,400 16,000 18,800 15,800 18,300 17,900 17,900 15,400 17,400 16,400 25,800 21,300 23,700 20,900 24,200 22,800 22,700 20,500 22,000 21,800 32,200 26,000 29,300 25,300 28,800 27,200 28,100 24,800 27,500 26,500 DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5

* Insert: A - Air cooled W - Water cooled

EVAPORATOR BLOWER Airflow - CFM Standard motor - horsepower External Static Pressure (E.S.P.) - inches of W.G. 550 3/4 0.5 775 3/4 0.5 1000 3/4 0.5 1225 3/4 0.5

EVAPORATOR COIL Face area - sq ft Face velocity - fpm Rows of coil 2.4 208 3 2.4 328 3 2.4 424 4 2.4 519 4

CONDENSER COIL Face area - sq ft Face velocity - fpm Rows of coil

Air cooled indoor packaged units 2.4 500 4 2.4 500 4 2.4 500 6 2.4 500 6

CONDENSER BLOWER Standard airflow - CFM Standard motor - horsepower External Static Pressure (E.S.P.) - inches of W.G.

Air cooled indoor packaged units 1,200 1/2 0.5 1,200 1/2 0.5 1,200 1/2 0.5 1,200 1/2 0.5

CONDENSER DATA Type Water regulating valve Size - inches Maximum working pressure - PSI 14

Water cooled units Coaxial 2-way 3/8 150 Coaxial 2-way 3/8 150 Coaxial 2-way 3/4 150 Coaxial 2-way 3/4 150

AIR, WATER or GLYCOL COOLED: Performance data


MODEL NUMBER ENTERING WATER Using 65 F EWT Using 75 F EWT Using 85 F EWT With Fluid Cooler GPM PD in PSI GPM PD in PSI GPM PD in PSI GPM PD in PSI DAM*-01 Water cooled units 1.2 1.3 2.0 2.0 2.8 3.0 3.5 5.8 1.9 2.9 3.0 4.3 4.2 6.7 5.3 12.4 2.5 2.1 3.9 3.1 5.6 4.8 7.0 9.2 3.1 3.0 4.9 4.5 7.0 6.9 8.8 13.3 DAM*-1.5 DAM*-02 DAM*-2.5

COMPRESSOR DATA Type Quantity Cooling stages Refrigerant type Crankcase heater REHEAT SECTION Type - Electric Capacity- kW Btu/hr Capacity - kW Btu/hr Capacity- kW Btu/hr HUMIDIFIER SECTION Type - Steam Generator Capacity - lb/hr kW FILTER SECTION Type Quantity Size - inches Efficiency - percentage CONNECTION SIZES Condenser water - In/Out Condensate drain - fpt Humidifier CONNECTION SIZES With condensing unit: Liquid line - O.D. Copper Suction line - O.D. Copper With condenser: Liquid line - O.D. Copper Hot gas line - O.D. Copper 3/4 3/4 1/4 Air Cooled Split Systems 1/2 3/4 1/2 3/4 1/2 3/4 1/2 3/4 3/4 3/4 1/4 3/4 3/4 1/4 3/4 3/4 1/4 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 Scroll 1 1 R-22 Standard Optional 2 6,830 4 13,660 N/A 2 6,830 4 13,660 N/A 2 6,830 4 13,660 5 17,075 2 6,830 4 13,660 5 17,075 Scroll 1 1 R-22 Standard Scroll 1 1 R-22 Standard Scroll 1 1 R-22 Standard

Optional 5 1.7 5 1.7 5 1.7 5 1.7

1/2 1/2

1/2 1/2

1/2 1/2

1/2 1/2 15

AIR COOLED: Electrical data


ELECTRICAL SECTION AIR COOLED (Packaged Systems) MODEL NUMBER DAMA-01-P DAMA-1.5-P DAMA-02-P DAMA-2.5-P

Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 16/18/25 277 V FLA/MCA/MFS 16/18/25

16/18/25 16/18/25

18/21/30 17/19/25

21/25/35 19/22/30

Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 24/28/30 24/28/30 277 V FLA/MCA/MFS 22/25/30 22/25/30 Electrical data based on: 2 kW electric reheat -YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 26/30/35 26/30/35 277 V FLA/MCA/MFS 23/27/30 23/27/30 Electrical data based on: 4 kW electric reheat -YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 35/42/45 35/42/45 277 V FLA/MCA/MFS 30/36/40 30/36/40 Electrical data based on: 5 kW electric reheat -YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A Electrical data based on: 2 kW electric reheat -YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 26/30/35 26/30/35 277 V FLA/MCA/MFS 23/27/30 23/27/30 Electrical data based on: 4 kW electric reheat -YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 35/42/45 35/42/45 277 V FLA/MCA/MFS 30/36/40 30/36/40 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A

26/31/35 23/26/30

30/35/45 26/30/35

28/33/40 24/28/30

31/37/45 27/31/40

37/45/50 31/37/40

41/49/50 34/40/45

42/51/60 35/41/45

45/55/60 37/45/45

28/33/40 24/28/30

31/37/45 27/31/40

37/45/50 31/37/40

41/49/50 34/40/45

42/51/60 35/41/45

45/55/60 37/45/50

AIR COOLED (Split Systems with Outdoor Condensing Unit) MODEL NUMBER DAMA-01-AO DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO

Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS 5.3/6.6/15 5.3/6.6/15 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 4.3/5.4/15 4.3/5.4/15 ** Continued **

5.3/6.6/15 15/17/25 4.3/5.4/15

5.3/6.6/15 18/21/30 4.3/5.4/15

Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.

FLA - Full load amps MCA - Minimum circuit amps wire sizing ampsMFS - Maximum overcurrent protection device amp 16

AIR COOLED: Electrical data


AIR COOLED (Split Systems with Outdoor Condensing Unit) MODEL NUMBER DAMA-01-AO ** Continued ** DAMA-1.5-AO DAMA-02-AO DAMA-2.5-AO

Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 13/17/20 13/17/20 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 10/13/15 10/13/15 Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 15/19/20 15/19/20 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 12/14/15 12/14/15 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 25/31/35 25/31/35 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS N/A N/A Outdoor FLA/MCA/MFS N/A N/A 277 V Indoor FLA/MCA/MFS N/A N/A Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS 15/19/20 15/19/20 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 12/14/15 12/14/15 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS 25/31/35 25/31/35 Outdoor FLA/MCA/MFS 13/15/20 13/15/20 277 V Indoor FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS N/A N/A Outdoor FLA/MCA/MFS N/A N/A 277 V Indoor FLA/MCA/MFS N/A N/A

13/17/20 15/17/25 10/13/15

13/17/20 18/21/30 10/13/15

15/19/20 15/17/25 12/14/15

15/19/20 18/21/30 12/14/15

25/31/35 15/17/25 19/23/25

25/31/35 18/21/30 19/23/25

29/37/40 15/17/25 22/28/30

29/37/40 18/21/30 22/28/30

15/19/20 15/17/25 12/14/15

15/19/20 18/21/30 12/14/15

25/31/35 15/17/25 19/23/25

25/31/35 18/21/30 19/23/25

29/37/40 15/17/25 22/28/30

29/37/40 18/21/30 2/28/30

Note: Transformers are required to step from 277 volt to 208-230 volt on outdoor condensing units. 277 volt condensing units are not available.

FLA - Full load amps

MCA - Minimum circuit amps wire sizing amps

MFS - Maximum overcurrent protection device amps 17

AIR COOLED: Electrical data


AIR COOLED (Split Systems with Remote Air Cooled Condenser) MODEL NUMBER DAMA-01-CO DAMA-1.5-CO DAMA-02-CO DAMA-2.5-CO

Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS 14/16/20 14/16/20 Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277 V Indoor FLA/MCA/MFS 12/14/20 12/14/20 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 22/26/30 22/26/30 Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277 V Indoor FLA/MCA/MFS 18/22/25 18/22/25 Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 23/28/30 23/28/30 Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277 V Indoor FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS 33/40/45 33/40/45 Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277V Indoor FLA/MCA/MFS 26/32/35 26/32/35 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V Indoor FLA/MCA/MFS N/A N/A Outdoor FLA/MCA/MFS N/A N/A 277 V Indoor FLA/MCA/MFS N/A N/A Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS 23/28/30 23/28/30 Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277 V Indoor FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V 33/40/45 33/40/45 Indoor FLA/MCA/MFS Outdoor FLA/MCA/MFS 4.2/5.3/15 4.2/5.3/15 277 V Indoor FLA/MCA/MFS 26/32/35 26/32/35 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V Indoor FLA/MCA/MFS N/A N/A Outdoor FLA/MCA/MFS N/A N/A 277 V 18

16/18/25 4.2/5.3/15 13/15/20

19/22/35 4.2/5.3/15 16/19/30

24/28/35 4.2/5.3/15 19/23/30

27/32/40 4.2/5.3/15 22/26/35

25/30/35 4.2/5.3/15 20/24/30

28/34/45 4.2/5.3/15 23/28/35

35/42/45 4.3/5.3/15 27/33/35

38/46/50 4.2/5.3/15 30/37/40

40/48/50 4.2/5.3/15 31/38/40

43/52/60 4.2/5.3/15 34/41/45

25/30/35 4.2/5.3/15 20/24/30

28/34/45 422/5.3/15 23/28/35

35/42/45 4.2/5.3/15 27/33/35

38/46/50 4.2/5.3/15 30/37/40

40/48/50 4.2/5.3/15

43/52/60 4.2/5.3/15

WATER or GLYCOL COOLED: Electrical data


WATER COOLED (Packaged Systems) MODEL NUMBER DAMW-01 DAMW-1.5 14/16/20 12/14/20 DAMW-02 16/18/25 13/15/20 24/28/35 19/23/30 25/30/35 20/24/30 35/42/45 27/33/35 40/48/50 31/38/40 25/30/35 20/24/30 35/42/45 27/33/35 40/48/50 31/38/40 DAMW-2.5 19/22/35 16/19/30 27/32/40 22/26/35 28/34/45 23/28/35 38/46/50 30/37/40 43/52/60 34/41/45 28/34/40 23/28/35 38/46/50 30/37/40 43/52/60 34/41/45

Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 14/16/20 277 V FLA/MCA/MFS 12/14/20

Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 22/26/30 22/26/30 277 V FLA/MCA/MFS 18/22/25 18/22/25 Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 23/28/30 23/28/30 277 V FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 33/40/45 33/40/45 277 V FLA/MCA/MFS 26/32/35 26/32/35 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 23/28/30 23/28/30 277 V FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 33/40/45 33/40/45 277 V FLA/MCA/MFS 26/32/35 26/32/35 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A

COMPRESSORS and MOTORS (DX Units, Air Cooled, and Water Cooled)
MODEL NUMBER EVAPORATOR FAN MOTOR Standard motor - horsepower FLA at 208-230 V FLA at 277 V CONDENSER FAN MOTOR Standard motor - horsepower FLA at 208-230 V FLA at 277 V CONDENSER FAN MOTOR Standard motor - horsepower Motor FLA at 208-230 V COMPRESSOR Standard motor - horsepower FLA at 208-230 V FLA at 277 V FLA - Full load amps DAM*-01 DAM*-1.5 DAM*-02 DAM*-2.5

3/4 5.3 4.3

3/4 5.3 4.3

3/4 5.3 4.3 1/2 2.6 3.6

3/4 5.3 4.3 1/2 2.6 3.6 3/4 4.2 2.5 13.5 11.5

(Air Cooled Indoor Packaged Units) 1/2 1/2 2.6 2.6 3.6 3.6

(Air Cooled Split Systems - Condensing Units or Air Cooled Condensers) 3/4 3/4 3/4 4.2 4.2 4.2 1.5 8.3 7.7 1.5 8.3 7.7 2.0 10.3 8.7

MCA - Minimum circuit amps wire sizing amps MFS - Maximum overcurrent protection device amp 19

CHILLED WATER: Performance data


MODEL NUMBER CAPACITY in Btu/hr - Gross 80 DB/67 WB 50% RH 75 DB/62.5 WB 50% RH 75 DB/61 WB 45% RH 72 DB/60 WB 50% RH 72 DB/58.6 WB 45% RH Total Sensible Total Sensible Total Sensible Total Sensible Total Sensible 15,800 12,200 12,500 11,000 11,900 11,400 10,800 10,200 10,500 10,400 21,300 16,500 16,800 14,900 16,000 15,400 14,600 13,700 14,100 14,000 28,700 22,400 22,800 20,200 21,700 21,000 19,800 18,700 19,200 19,200 33,900 26,600 26,900 24,000 25,600 24,900 23,300 22,200 22,700 22,700 DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5

Note: Chilled Water capacity based on 45 F entering chilled water temperature. CHILLED WATER COIL Face are - sq ft Rows of coil Face velocity - fpm BLOWER SECTION Airflow - cfm Standard fan motor - hp External Static Pressure (E.S.P.) - inches of W.G. Number of fans CHILLED WATER REQUIRED Using 45 F EWT GPM PSI CHILLED WATER VALVE Valve body Valve size - inches REHEAT SECTION Electric kW Btu/hr kW Btu/hr kW Btu/hr HUMIDIFIER SECTION Steam generator Capacity - lbs/hr kW 2-WAY 3/4 (Optional) 2 6,825 4 13,650 N/A N/A (Optional) 5 1.7 5 1.7 5 1.7 5 1.7 2 6,825 4 13,650 N/A N/A 2 6,825 4 13,650 5 17,075 2 6,825 4 13,650 5 17,075 2-WAY 3/4 2-WAY 3/4 2-WAY 3/4 550 3/4 0.5 1 (Maximum 150 PSI) 3.0 2.4 4.5 5.3 6.0 7.7 7.5 10.5 775 3/4 0.5 1 1000 3/4 0.5 1 1225 3/4 0.5 1 2.4 3 208 2.4 3 328 2.4 4 424 2.4 4 519

20

CHILLED WATER: Performance data


MODEL NUMBER FILTER SECTION Type Quantity Size - inches Efficiency - percentage CONNECTION SIZES Chilled water in/out O.D. copper Condensate drain - FPT Humidifier ELECTRICAL SECTION Electrical data based on: electric reheat - NO, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 5.3/6.6/15 5.3/6.6/15 277 V FLA/MCA/MFS 4.3/5.4/15 4.3/5.4/15 Electrical data based on: electric reheat - NO, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 13/17/20 13/17/20 277 V FLA/MCA/MFS 10/13/15 10/13/15 Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 15/19/20 15/19/20 277 V FLA/MCA/MFS 12/14/15 12/14/15 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS 25/31/35 25/31/35 277 V FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - YES. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A Electrical data based on: 2 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 15/19/20 15/19/20 277V FLA/MCA/MFS 12/14/15 12/14/15 Electrical data based on: 4 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS 25/31/35 25/31/35 277 V FLA/MCA/MFS 19/23/25 19/23/25 Electrical data based on: 5 kW electric reheat - YES, steam generator humidifier - NO. 208-230 V FLA/MCA/MFS N/A N/A 277 V FLA/MCA/MFS N/A N/A 3/4 3/4 1/4 3/4 3/4 1/4 3/4 3/4 1/4 3/4 3/4 1/4 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 Pleated 1 20x20x2 60 DAMC-01 DAMC-1.5 DAMC-02 DAMC-2.5

5.3/6.6/15 4.3/5.4/15 13/17/20 10/13/15 15/19/20 12/14/15 25/31/35 19/23/25 29/37/40 22/28/30 15/19/20 12/14/15 25/31/35 19/23/25 29/37/40 22/28/30

5.3/6.6/15 4.3/5.4/15 13/17/20 10/13/15 15/19/ 20 12/14/15 25/31/35 19/23/25 29/37/40 22/28/30 15/19/20 12/14/15 25/31/35 19/23/25 29/37/40 22/28/30

BLOWER SECTION Standard motor - hp FLA at 208-230 V FLA at 277 V 3/4 5.3 4.3 3/4 5.3 4.3 3/4 5.3 4.3 3/4 5.3 4.3

FLA - Full load amps

MCA - Minimum circuit amps wire sizing amps

MFS - Maximum overcurrent protection device amp 21

Air Cooled Split with DARC Outdoor Condenser

DAMA-XXXX-CO

22

Air Cooled Split with DARC Outdoor Condenser

DAMA-XXXX-CO

23

Air Cooled Split with DRCU Outdoor Condensing Unit

DAMA-XXXX-AO

24

Air Cooled Split with DRCU Outdoor Condensing Unit

DAMA-XXXX-AO

25

Air Cooled Packaged

DAMA-XXXX-P

26

Air Cooled Packaged

DAMA-XXXX-P

27

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI

28

Air Cooled Split with Indoor Condenser DAMA-XXXX-CI

29

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI

230 W. BlueRidge Ave. Orange, CA 92865

30

Air Cooled Split with Indoor Condensing Unit DAMA-XXXX-AI

31

Water/Glycol Cooled DAMW-XXXX

32

Water/Glycol Cooled DAMW-XXXX

33

Chilled Water DAMC-XXXX

34

Chilled Water DAMC-XXXX

35

Condenser and Condensing Unit Dimensional Drawings

Condenser Unit

Condensing Unit

36

Return Air Filter Box

Typical Hanging Installation Detail


MINI CEILING SYSTEM TYPICAL HANGING INSTALLATION
5/8" Threaded Rod (4) Required

5/8" Flat Washer

See Mounting Detail

5/8" Nut

5/8" Jam Nut

MINI CEILING SYSTEM LOW AMBIENT DAMPER CONTROL PACKAGE (Optional)

All Mounting Hardware Field Provided Connect to Schrader Valve Fitting on Discharge Line

5 1/2" See Damper Detail Duct Work Supplied and Installed by Others 16" x 16" Ambient Controlled Damper Supplied by Data Aire (Shipped Loose)

37

Mini Ceiling Systems Guide Specifications General


Provide and install an air conditioning system designed specifically for use in small computer/data processing areas, or controlled office environments, and shall be capable of cooling, humidifying, dehumidifying, and filtering air. Units shall be ETL or UL listed. The frame shall be constructed of 14 gauge welded tubular steel and be coated with a heavy corrosion inhibiting finish for long life. The side panels shall be of galvanized steel. The cabinet shall be insulated with one-half inch (1/2") thick, closed cell insulation. The plenum shall be of cold rolled steel and painted in a cloud white finish. The plenum (vertical unit only) shall be field mounted. The unit shall be serviceable through the removable side panels. The vertical air flow unit is to be ceiling mounted and sized to fit a standard 2 ft x 4 ft T-bar ceiling grid opening. The horizontal supply/return air unit is to be ceiling hung with duct work attached to supply and return openings. The total cooling capacity shall be ______ Btu/hr at ____ degree F DB and ____ degree F WB entering air temperature. The voltage shall be ___, 1 ph, 60 hz. Electrical - All electrical components including contactors, relays, control transformers, and capacitors shall be pre-wired. The control circuit voltage shall be 24 volts. A micro-switch shall disable the unit operation prior to condensate pan overflow should the drain line become plugged with debris. Filter - Provide a two (2") inch, 60% efficient (based on ASHRAE Std. 52.1-1992) disposable filter of twenty inches square (20" x 20"). The filter shall be located behind and accessible through the hinged return air grille. Air Cooled Self-Contained - The refrigeration system shall be self-contained, factory assembled, charged, and tested. No refrigerant piping shall be required. The unit shall contain an evaporator and condenser section. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with
38

capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive and variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. The field attached condenser section shall have a condenser coil constructed with copper tubes and aluminum fins and built into the refrigeration system. The condenser fan shall be double inlet, double width, direct drive type. The condenser blower motor electrical connection shall be through a factory wired plug. Air Cooled Split System (with outdoor condensing unit) - The refrigeration system shall be split consisting of an evaporator section and remote outdoor condensing unit. The evaporator and condensing unit shall be factory assembled and tested. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and low pressure safety switches. The high and low pressure safety switches are connected to the refrigerant system with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through type consisting of a double inlet, double width, centrifugal fan with belt drive and variable pitch sheave, and selfaligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel. The condensing unit shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated finish and contain a scroll type compressor with crankcase heater, filter drier, sightglass, and condenser coil. The coil shall be constructed with copper tubes and aluminum fins. The condenser fan motor shall be variable speed for head pressure control down to -20

GUIDE SPECIFICATIONS continued

degrees F. The capillary tube connection from the fan speed control to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. The condenser motor shall be direct drive with a propeller type fan. Air Cooled Split System (with outdoor condenser) The refrigeration system shall be split consisting of an evaporator section and remote outdoor condenser. The evaporator and condenser shall be factory assembled and tested. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel. The condenser section shall be a low profile, slow speed, direct drive propeller fan type. The condenser shall be constructed of heavy duty gauge corrosion resistant steel with a powder coated finish and contain a copper tube aluminum fin coil with vertical air discharge. The condenser shall have fan speed control with transducers to modulate the speed of the condenser fan and provide positive start-up and operation at ambient temperatures to -20 F. All controls including the fan speed control, shall be factory mounted in the air cooled condenser. Water Cooled Self-Contained - The refrigeration system shall be self-contained, factory assembled, charged and tested. No refrigerant piping connections shall be required. The unit shall contain an evaporator and condenser section. The evaporator section shall have a cooling coil constructed with copper tubes and aluminum fins. The single refrigeration circuit shall include the expansion valve with external equalizer, filter drier, and high and

low pressure safety switches. The scroll type compressor shall have internal overload protection. Units with capillary tube metering devices shall not be acceptable. The evaporator blower assembly shall be draw-through configuration consisting of a double inlet, double width, centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. A high efficiency coaxial water cooled condenser with head pressure activated water regulating valve built into the refrigeration system shall be provided. The capillary tube connection from the water regulating valve to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary. Maximum operating water pressure shall be 150 psi. Chilled Water - Provide a packaged system designed to utilize an existing chilled water loop. The unit shall be factory assembled, piped, wired, and tested. A chilled water coil consisting of copper tubes and aluminum fins shall be provided. The chilled water flow shall be controlled by a two-way valve for accurate and economical temperature control and dehumidification. The blower assembly shall be drawn through a configuration consisting of a double inlet, double width, direct drive centrifugal fan with belt drive, variable pitch sheave, and self-aligning ball bearings rated for an average life of 100,000 hours. The fan motor shall be ____ horsepower. Air delivery shall be a minimum of ____ cfm. The condensate drain pan shall be constructed of stainless steel and provide a positive drain to prevent standing water in the condensate pan. All components shall be housed within the same cabinet. Controls -The control system shall be electromechanical type, utilizing a 24 volt thermostat. A sub-base shall be provided for remote wall mounting of thermostat. The controls shall be accessible through the side panel of the unit and contained in a hinged electrical box that shall swing out for easy access and servicing. Removal of the unit from the ceiling space shall not be required for access.

39

OPTIONS

Unit Control
Mini Data Alarm Processor-II - The control system shall be furnished with the microprocessor based Mini Data Alarm Processor-II. The panel shall include unit switching functions and display normal functions, malfunctions, and service diagnostics on a one row, 16 character liquid crystal display (LCD) in clear vernacular format. The panel shall automatically display temperature and humidity along with all operational and alarm messages. The panel shall recall and display the high and low temperature and the high and low humidity for the last 24 hours, date and time, reheat, humidification, dehumidification, and chilled water operation (as applicable). Programming shall have a two level password security to prevent unauthorized access. Programming shall be accomplished entirely from the microprocessor. Programmable functions shall be entered on nonvolatile EEPROM to insure program retention should power fail. Multiple messages shall be displayed by automatically scrolling from each message to the next. Alarm conditions, in addition to being displayed, shall enunciate an audible alarm with variable output. Additional test or service terminals shall not be required for any functions. An alarm condition shall continue to be displayed until the malfunction is corrected. Multiple alarms shall be displayed sequentially in order of occurrence and only those alarms which have not been acknowledged shall continue to sound an audible alarm. The Mini Data Alarm Processor-II shall perform an automatic self-test on system start-up. A user accessible diagnostic program shall aid in system component trouble shooting by displaying on the unit LCD screen output relay number, terminal plug and pin number for each controlled item. The following functions shall be programmable: Temperature setpoint (60-80 F, 15.6-26.7 C), Temperature sensitivity (1-5 F, .5-2.7 C in 0.1 increments), Humidity setpoint (30-70% RH), Humidity sensitivity (1-15% RH in 0.1% increments), Temperature alarm points, Humidity alarm points, Unit start time delay,
40

Interstage time relay, Password 1st level, Password 2nd level, Audio alarm level, Restart mode, Firestat trip temperature, Local alarm function The following normal functions shall be monitored and displayed: Current temperature (F or C), Current humidity (% RH), Cooling, Reheat, Humidification, Dehumidification, Date and time The following alarm functions shall be monitored and displayed when they occur, in addition to enunciating an audible alarm: High temperature, Low temperature, High humidity, Low humidity, Compressor high pressure, High condensate water, Firestat tripped, No air flow, Compressor short cycle, Temperature sensor error, Humidity Sensor error The following switching and control functions shall be included: System On/Off switch, Menu selection button for: Programming operational information, Diagnostics, Historical data, and Alarm silence/program set button

Site Monitoring
DARA-4 (Data Aire Relay Autochangeover) Controls up to four Mini Ceiling units using a dry set of relay contracts. The DARA-4 provides unit rotation, backup capacity and the ability to interface with most BMS systems.

Unit Options
HUMIDIFIER Provide a steam generator type humidifier. The steam humidifier shall be of the self-contained cylinder type with electronic controls. The humidifier shall discharge pure steam with no material dust carry-over, and shall have self-regulating flush cycle. Cylinders shall be disposable not requiring cleaning or maintenance. Humidifier rate shall automatically adapt, both in frequency and duration, to variations in the incoming water. The humidifier capacity shall be 5 pounds per hour with power consumption of 1.7 kW. (Note: When specifying the steam generator type humidifier, a Mini Data Alarm Processor-II is required.) REHEAT Provide electric reheat. The electrical heating element shall be of the finned tube resistant type and constructed of stainless steel with high limit cutout. The capacity shall be ____ kW, _____ Btu/hr. CONDENSATE PUMP A condensate pump shall be provided with the unit and shall have a capacity of 60 GPH at 8 feet of head. The pump shall be shipped loose for field mounting and installation. It is also available installed and wired from the factory. The pump voltage shall be ___. LOW AMBIENT CONTROL DAMPER Provide a low ambient control damper for ducting of outside condenser air. The low ambient control damper shall consist of a 14" x 14" damper section with headpressure operator. The control shall enable the unit to operate down to -30 F ambient. The capillary tube connection from the head pressure control to the refrigerant system shall be connected with a Schrader fitting that allows replacement without affecting the refrigerant charge, making recovery unnecessary.

HORIZONTAL SUPPLY AND RETURN AIR Supply and return air shall be horizontal for ducted connection. Refer to the project drawings. FRONT SUPPLY AIR Supply air shall be through the front of the unit for ducted connection. The unit shall be provided with a flange connection. Refer to the project drawings. SIDE SUPPLY AIR Supply air shall be through the side of the unit for ducted connection. The unit shall be provided with a flange connection. Refer to the project drawings. SIDE RETURN AIR Return air shall be through the side of the unit for ducted connection. The return air shall be through a factory provided ceiling mounted return air grille. The ceiling mounted return air grille shall be hinged for easy access and shall contain a 60% efficient (based on ASHRAE Std. 52.1-1992) 20" x 20" x 4" pleated filter. Refer to the project drawings. EXTENDED COMPRESSOR WARRANTY Extended compressor warranties are available from Data Aire. Contact your local representative for one that best suites your needs.

41

Weights - lbs
1.0 Packaged Systems Air Cooled Water Cooled Chilled Water Split Systems* Air Cooled - AO Air Cooled - CO 425 350 300 Operational 1.5 2.0 425 350 300 425 350 300 2.5 425 350 300 1.0 450 375 325 Shipping 1.5 2.0 450 375 325 450 375 325 2.5 450 375 325

280/300 325/260

280/300 280/300 325/260 325/260

280/300 325/260

305/340 305/340 350/300 350/300

305/340 305/340 350/300 350/300

* Weights provided are for the evaporator section (inside-first number) and condensing or condenser section (outside-second number). Each section shipped separately. Weights shown are for standard units.

42

43

230 W. BlueRidge Avenue Orange CA 92865 800-347-2473


www.dataaire.com e-mail: sales@dataaire.com
A Member of the CS Group of Companies 2003 Data Aire Inc. Data Aire, Inc. reserves the right to make design changes for the purposes of product improvement, or to withdraw any design without notice.

DAMCS-0605

Anda mungkin juga menyukai