Station Service Transformers Station service transformers are required to serve the auxiliary power requirements of the converter

station including the ac switchyard, converter building, dc switchyard, and ancillary buildings and equipment. Auxiliary power requirements include electrical loads such as building heating and cooling, process cooling systems, lighting, and various other support systems needed for station operation. Three three-phase, two-winding, 230 kV12.47 kV MVA (mega volt-amperes) station service transformers will be required, each containing approximately 35,000 litres of insulating oil. Instrument Transformers Instrument transformers measure currents (current transformers) and voltages (voltage transformers) on apparatus within the 230 kV ac switchyard. Signals from the instrument transformers are used for control, protection and monitoring purposes. The Keewatinoow ac switchyard will require approximately 70 single phase voltage transformers, each containing approximately 100 litres of insulating oil. The switchyard will also require approximately 126 single phase current transformers, each containing approximately 200 litres of insulating oil. ac Harmonic Filters Harmonic filters (see photo of existing ac harmonic filters at Dorsey Converter Station in Figure 3.5-3) are typically required due to the ac current harmonics generated in the process of converting ac power to dc power. These harmonics could be harmful to equipment connected to the ac system, including generators, if allowed to flow out of the converter station.

BIPOLE III PROJECT CHAPTER 3: PROJECT DESCRIPTION

3-72

Figure 3.5-3: ac Harmonic Filters at Dorsey Converter Station

Depending upon the conversion technology selected for Bipole III23, as well as the outcome of final design studies, Keewatinoow Station may require four three-phase ac harmonic filter banks, each of which may be comprised of up to three sub-banks. Operation of the sub-banks would be controlled using dedicated ac circuit breakers similar to those described in this section. Eight such ac circuit breakers would be required. The ac harmonic filter banks and sub-banks are typically comprised of a combination of capacitors, reactors, and resistors. Filter capacitors are generally filled with an insulating oil fluid. Approximately 1,100 capacitors, each containing approximately 16 litres of insulating fluid, will be required for each ac harmonic filter bank. Surge Arrestors Surge arrestors provide protection to ac switchyard components from abnormally high voltages induced from lightning. Surge arrestors are comprised of porcelain or composite materials, and are similar in appearance to insulators. Insulators Insulators are non-conducting posts (porcelain or composite) used to support energized equipment and hardware in the switchyard. Insulators are typically placed on the top of steel equipment support structures, but may also be placed directly on the equipment foundations. Control Buildings Two to four control buildings will be required for the Keewatinoow 230 kV ac switchyard to house the control, protection, and communications equipment necessary for its operation. Cables will connect the control buildings to the ac switchyard apparatus and to the remainder of the converter station. The control buildings typically contain battery banks to meet the power requirements for the electrical equipment installed within the building. Approximately 1,300 litres of battery acid will be contained

23

Line-commutated converter (LCC) technology utilizes thyristor based power electronic conversion equipment similar to that in the Manitoba Hydro Bipole I and Bipole II converter stations. Voltagesource converter (VSC) technology utilizes insulated gate bipolar transistor (IGBT) based power electronic conversion equipment. In addition to the valve group power electronic components, the different conversion technologies under consideration for Bipole III have different requirements for ac harmonic filters, the converter building, dc switchyard equipment, and synchronous condensers.

BIPOLE III PROJECT CHAPTER 3: PROJECT DESCRIPTION

3-74

within the batteries in each control building. The control buildings will also require heating and air handling equipment to control the building ambient temperature. Switchgear Buildings and Auxiliary Power Distribution Two switchgear buildings will be required within the ac switchyard. The buildings will house equipment for control of the 12.47 kV auxiliary power from the station service transformers to the converter station electric power loads. Each building will include approximately 15 circuit breakers and the control and protection electronics necessary for their proper operation. The buildings will require electric heat and air handling equipment. Power from the switchgear buildings to the converter station electric power loads will be distributed throughout the station by power cables to indoor and outdoor power centres. Each power centre will require two transformers approximately 2,500 kVA in size. Outdoor power centres may utilize oil-filled transformers, each containing approximately 2,200 litres of insulating oil. Indoor power centres, located within the converter building, typically utilize dry-type transformers which do not contain insulating oil. It is anticipated that four outdoor and four indoor power centres will be required for Keewatinoow Converter Station.

3.5.2.3

Converter Transformers
The 230 kV ac switchyard will be electrically connected to converter transformers, through which power is passed from the ac switchyard to the solid state power electronic valve groups within the converter building. The converter transformers provide an interface between the ac voltages in the ac switchyard and the dc voltages in the valve groups. Keewatinoow Converter Station will require up to fourteen converter transformers for the conversion of ac to dc power - three for each of the four valve groups, and two spares (for use during maintenance or outage). The final layout design of the converter transformers will depend on such factors as the HVdc system configuration, converter building size and layout, ac filtering and reactive power compensation requirements. In order to obtain a more compact station design and reduce the number of insulated high voltage wall bushings, converter transformers may be situated adjacent to the converter building with the valve group side connections protruding into the valve hall. This configuration reduces buswork requirements and improves protection of the valve group from lightning strikes. Alternatively, if the converter transformers are not situated

BIPOLE III PROJECT CHAPTER 3: PROJECT DESCRIPTION

3-75

adjacent to the converter building, approximately 48 wall bushings will be required in the converter building wall between the converter transformers and the valve halls. The principal components of individual converter transformers are the tank which includes the transformer core and copper windings, transformer bushings, and oil cooling radiators and fans. The converter transformers are filled with insulating oil for electrical insulation and heat transfer purposes. Insulating oil is circulated between the tank and the cooling radiators, where excess heat is transferred to the air. Each converter transformer (see photo of existing converter transformer at Dorsey Converter Station in Figure 3.5-4) will contain approximately 115,000 litres of insulating oil. Due to the volume of insulating oil in each transformer, the design will incorporate primary oil containment (see Section 3.5.2.1).

BIPOLE III PROJECT CHAPTER 3: PROJECT DESCRIPTION