AccuSine Power Correction System (PCS) Selection Program


AccuSine PCS is designed to correct for harmonics and poor displacement power factor. By completing the following information, this program will define the amount of corrective current to be provided by AccuSine PCS to meet the objective. 1. Review site carefully to determine all of the loads to which AccuSine PCS will be applied. AccuSine PCS is best applied to a common bus. Be sure to include all loads for proper evaluation. 2. Be sure there are no power factor capacitors downstream of the selected CT location Any and all capacitors downstream of the CTs must be removed or AccuSine PCS performance will be diminished greatly and/or resonance may occur. 3. Nonlinear loads with input EMI filters may interact with AccuSine PCS to prevent proper operation of AccuSine PCS Removal of these filters is best. However, if removal is not possible, insertion of a series line reactor in front of the EMI filter is required. 4. Use of series line reactors in front of all SCR type converters is best for optimum reduction in harmonics.In some cases line reactors may be required due to the design of the SCR converter. Consult Square D if questions arise. 5. PWM VFDs require either a 5% DC bus choke or a 3% input line reactor for optimum operation with AccuSine PCS. 6. If AccuSine PCS is on an electrical system that contains a combination of linear and nonlinear loads, all linear loads may be grouped as if they were one lo for the purposes of this selection program. 7. When TDD (total demand distortion of the current) is maintained below 5%, the upstream total harmonic voltage distortion [THD(V)] will not exceed 5% THD(V). 8. AccuSine PCS selection is based solely upon current requirements. Be sure to select the correct model that matches your system voltage. 9. Be sure to use harmonic distortion percentages based upon the fundamental current not total 'RMS' current.

Project Identification:
Company name: Address: City: Contact: Jason ADM Singapore Singapore St: Postal Code: Phone #: Fax #: e-mail ID: Job ID: Ref #: sess/dmd/acs-01 Completed by: dmd

Date: 5/18/2007

Comments:

Electrical System Data


This program requires no data entry for the "Electrical System Data." The program defaults to 480VAC and 5%TDD as the objective. A. Desired TDD level to be met: 5.0% (If you want the objective TDD to be selected according to IEEE 519-1992, Table 10.3 guidelines, leave "A" blank and enter the "Input Transformer Information" below.) Current Distortion Limits (120 to 69,000 V) Table 10.3 of IEEE 519-1992 TDD Isc/Iload < 20 20<50 50<100 100<1000 >1000 5% 8% 12% 15% 20%

Input Transformer Information


A1.a. KVA: A1.b. Impedance: A1. Short circuit current (SCC): A2. A3. B. 2,250.0 KVA 6.360% Impedance 51,062.8 SCA

799.8 amps Total demand load: Enter if known. Program will calculate demand load based upon loads defined below if not provided. 63.8 SCR (Isc/Iload) Short circuit current ratio (A1/A2): Electrical system voltage: If no value is entered for voltage, 480V is assumed. 400 V

AccuSine PCS Selection 060427.xls

Page 1 of 2

6/13/2007

Displacement power factor:


C1. C2. Known or calculated PF of the loads in question: 0.950

1.000 Objective displacement power factor: If no values are entered for PF, this program defaults to .95 for both entries.

Nonlinear Loads:
D. List all nonlinear loads applicable for each group to be evaluated. # does not require an entry if all nonlinear loads are 6-pulse and do not have dedicated tuned filters (5th harmonic trap filters). If a dedicated tuned filter is present enter '5' per line item. If the input rectifier is 12-pulse enter '12' per line item. If the input rectifier is 18-pulse enter '18' per line item. VFDs PWM VVI HP # Qty HP # Qty 1.01 6 2.01 6 2.95 6 5.36 6 10.1 6 14.7 6 40.2 6 49.6 6 60.3 6 DC Drives CSI HP # Qty HP UPS Inductive Diode Converter SCR Converter # Qty KVA # Qty KVA # Qty KVA 1 56.25 1 23.13 1 27.5 Other SCR converters Resistive Capacitive # Qty KVA # Qty KVA # 6 6 6

1 2 3 4 5 6 7 8 9 10 11 12

Qty 1 2 2 1 1 2 1 1 4

Are VFD loads centrifugal pump or fan loads? y (Program defaults to 'No'.) D.1 List the total KVA of installed UV equipment: Specify 6, 12, or 18 pulse or 5, if a 5th harmonic tuned filter is used:

Enter Y for yes, N for no.

KVA

Linear Loads:
E. Total Linear Loads Installed: Enter full load KVA capacity of linear loads. 112.25 KVA

AccuSine PCS Selection Results:


The following summary is the basis for the AccuSine PCS selection shown below. The electrical system voltage is All loads total All linear loads total The original displacement power factor is The objective displacement power factor is The TDD of the electrical system before AccuSine PCS is The objective TDD is The required rating of the AccuSine PCS system is 400 volts. 790.8 amps. 162.0 amps. 0.950 1.000 18.45% TDD. 5.00% TDD. 300.1 amperes of correction.

Electrical System Current Approximations System with System AccuSine without Operating AccuSine 743.7 Total rms current: 790.8 773.4 Fundamental current: 742.8 36.5 Harmonic current: 142.7 4.92% TDD: 18.45% 0.0 Reactive current: 267.9 Equivalent kVAR correction: 185.6

Amps Amps Amps Amps kVAR

AccuSine PCS Selection 060427.xls