Project Identification:
Company name: Address: City: Contact: Jason ADM Singapore Singapore St: Postal Code: Phone #: Fax #: e-mail ID: Job ID: Ref #: sess/dmd/acs-01 Completed by: dmd
Date: 5/18/2007
Comments:
799.8 amps Total demand load: Enter if known. Program will calculate demand load based upon loads defined below if not provided. 63.8 SCR (Isc/Iload) Short circuit current ratio (A1/A2): Electrical system voltage: If no value is entered for voltage, 480V is assumed. 400 V
Page 1 of 2
6/13/2007
1.000 Objective displacement power factor: If no values are entered for PF, this program defaults to .95 for both entries.
Nonlinear Loads:
D. List all nonlinear loads applicable for each group to be evaluated. # does not require an entry if all nonlinear loads are 6-pulse and do not have dedicated tuned filters (5th harmonic trap filters). If a dedicated tuned filter is present enter '5' per line item. If the input rectifier is 12-pulse enter '12' per line item. If the input rectifier is 18-pulse enter '18' per line item. VFDs PWM VVI HP # Qty HP # Qty 1.01 6 2.01 6 2.95 6 5.36 6 10.1 6 14.7 6 40.2 6 49.6 6 60.3 6 DC Drives CSI HP # Qty HP UPS Inductive Diode Converter SCR Converter # Qty KVA # Qty KVA # Qty KVA 1 56.25 1 23.13 1 27.5 Other SCR converters Resistive Capacitive # Qty KVA # Qty KVA # 6 6 6
1 2 3 4 5 6 7 8 9 10 11 12
Qty 1 2 2 1 1 2 1 1 4
Are VFD loads centrifugal pump or fan loads? y (Program defaults to 'No'.) D.1 List the total KVA of installed UV equipment: Specify 6, 12, or 18 pulse or 5, if a 5th harmonic tuned filter is used:
KVA
Linear Loads:
E. Total Linear Loads Installed: Enter full load KVA capacity of linear loads. 112.25 KVA
Electrical System Current Approximations System with System AccuSine without Operating AccuSine 743.7 Total rms current: 790.8 773.4 Fundamental current: 742.8 36.5 Harmonic current: 142.7 4.92% TDD: 18.45% 0.0 Reactive current: 267.9 Equivalent kVAR correction: 185.6
Page 2 of 2